Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
4126721 FERROLI MAXIMA 35 S
GLOBALLY REPLACED
F1 - NO BURNER IGNITION (DUMMY, GO TO BURNER IGNITES)
OUTSIDE MODEL
F3 - 100°C SAFETY THERMOSTAT TRIPS
OUTSIDE MODEL
F5 - FAN FAULT
OUTSIDE MODEL
F10 TO F22, F25, F35, F36 PCB INTERNAL FAULTS
OUTSIDE MODEL
F26 - NO FLAME AFTER THE IGNITION PHASE (5 TIMES IN 4 MIN) (DUMMY, GO TO BURNER IGNITES)
OUTSIDE MODEL
F30, F31 - CH FLOW SENSOR FAULT
OUTSIDE MODEL
F34 - SUPPLY VOLTAGE UNDER 190V OR OVER 250V
OUTSIDE MODEL
F37 - INCORRECT SYSTEM WATER PRESSURE (TOO LOW)
OUTSIDE MODEL
F40 - INCORRECT SYSTEM WATER PRESSURE (TOO HIGH)
OUTSIDE MODEL
F45, F46 - FLUE SENSOR FAULT
OUTSIDE MODEL
F43, F44 - RETURN SENSOR FAULT
OUTSIDE MODEL
F23 - NOT APPLICABLE TO UK MARKETS
OUTSIDE MODEL
FUSE INVESTIGATION TREE - MAINS
OUTSIDE MODEL
OBSERVATION DISPLAY OPERATES
{ONOFFSWITCHON}
TYPE OF DIAGNOSTIC PROCEDURE
PLEASE SELECT FROM O
00 AND SPANNER SYMBOL
OUTSIDE MODEL
OBSERVATION BOILER SELF CHECK
ENSURE POWER IS TURN
FUSE INVESTIGATION TREE - DISPLAY
OUTSIDE MODEL
WEAK SPARK POOR IGNITION
PCB - MAIN
POOR IGNTION
PARAMETERS IGNITION FAN SPEED
EXPLOSIVE IGNITION
ELECTRODE IGNITION
EXPLOSIVE IGNITION
IGNITION ELECTRODE INTERNAL
FAULT CODES 3
Z REDIRECT
F30 F31
SENSOR - FLOW RETURN
F43 F44
SENSOR - FLOW RETURN
OPERATION CH
EXPANSION VESSEL - 10 LITRE
F23 - WONT GO INTO UK MARKET
PCB - MAIN
OBSERVATION FAN
SET - CONTROL
OBSERVATION FAN RUNS - FLOW
SENSOR - FLOW RETURN
OBSERVATION FAN RUNS - RETURN
SENSOR - FLOW RETURN
OBSERVATION FAN RUNS
SENSOR - FLUE
OBSERVATION PUMP RUNS - RELAY
HARNESS
DAMAGED CAUSING BAFFLING
BURNER - CERAMIC
RESTRICTING HEAT EX CAUSING BAFFLING
INSULATION - COMBUSTION CHAMBER
RESTRICTED OR BLOCKED BAFFLING
HEAT EXCHANGER
OBSERVATION PUMP RUNS - DEMAND RECOGNISED
PCB - MAIN
OBSERVATION BURNER IGNITES AND ESTABLISHES - IGNITES BUT BAFFLES
AIR IMPULSE TUBE
OBSERVATION PUMP RUNS - PUMP
HARNESS
INFORMATION HOW TO ADJUST MAX CH TEMPERATURE
Z REDIRECT
F3
SET - CONTROL
F3 - NO POWER TO PUMP
PCB - MAIN
F3 OBSERVATION PUMP RUNS - PUMP
HARNESS
F9
PCB - MAIN
OBSERVATION PUMP RUNS
TERMINAL BLOCK LINK
OPERATION CH - UP TO TEMP RADS COOL
ISOLATION VALVES
OPERATION CH - UP TO TEMP RADS COOL
PUMP ASSEMBLY - CH
OPERATION CH - UP TO TEMP RADS COOL
VALVE- BYPASS
OPERATION CH - UP TO TEMP RADS COOL
VALVE - NON RETURN
OPERATION CH - NOISY
SET - CONTROL
OPERATION CH - TOO COOL
GAS INLET PRESSURE
OPERATION CH - TOO COOL
INJECTOR
OPERATION CH - TOO COOL
NOZZLE AIR GAS MIXING CHAMBER
OPERATION CH - TOO COOL
BURNER - CERAMIC
OPERATION CH - TOO COOL
HEAT EXCHANGER
OPERATION CH - TOO COOL - LPG
GAS INLET PRESSURE
OPERATION CH - TOO COOL OPERATION CH - NOISYOPERATION CH - UP TO TEMP RADS COOL - LPG
VALVE - NON RETURN
OPERATION CH - TOO COOL - LPG
INJECTOR
OPERATION CH - TOO COOL - LPG
NOZZLE AIR GAS MIXING CHAMBER
OPERATION CH - TOO COOL - LPG
BURNER - CERAMIC
OPERATION CH - TOO COOL - LPG
HEAT EXCHANGER
F3
PARAMETERS CH OUTPUT
RESISTANCE HIGH OR POOR CONDITION 2
LEAD IGNITION W/O PLUG
NOT SPARKING 2
ELECTRODE IGNITION
NOT SPARKING
IGNITION LEAD END DAMAGED
RESISTANCE HIGH OR POOR CONDITION
LEAD IGNITION W/O PLUG
NOT SPARKING
IGNITION CAP
NOT SPARKING
ELECTRODE IGNITION
LOW CAUSING NO RECTIFICATION
GAS INLET PRESSURE
LOW CAUSING BAFFLING
GAS INLET PRESSURE
BLOCKED CAUSING BAFFLING
CONDENSATE TRAP
RESTRICTED OR BLOCKED
UNIT - CONDENSE COLLECTION
INFORMATION CASE REMOVAL
Z REDIRECT
RESTRICTED OR BLOCKED 2
NOZZLE AIR GAS MIXING CHAMBER
BLOCKED CAUSING HIGH FAN PRESSURE
CONDENSATE TRAP
RESTRICTED HIGH FAN PRESSURE
UNIT - CONDENSE COLLECTION
RESTRICTED CAUSING HIGH FAN PRESSURE
BURNER - CERAMIC
ONLY PARTIALLY OPENING GAS VALVE
AIR IMPULSE TUBE
ONLY PARTIALLY OPENING GAS VALVE
CONDENSATE TRAP
ONLY PARTIALLY OPENING GAS VALVE
UNIT - CONDENSE COLLECTION
SHORTING
PUMP ASSEMBLY - CH
NOT LIGHTING
ELECTRODE IGNITION
PARTIAL RESTRICTION
INJECTOR
RESTRICTED OR BLOCKED
NOZZLE AIR GAS MIXING CHAMBER
NOT LIGHTING
IGNITION ELECTRODE INTERNAL
CAUSING NO IGNITION
BURNER - CERAMIC
BLOCKED STOPPING IGNITION
INJECTOR
FUSE INVESTIGATION
VALVE C/W WASHERS - GAS
SPLIT NOT OPENING GAS VALVE
AIR IMPULSE TUBE
NOT RECTIFYING
RECTIFICATION LEAD
NOT RECTIFYING
ELECTRODE - FLAME SENSING
OBSERVATION DISPLAY ILLUMINATES - BOILER FIRES AFTER SELF CHECK
FROST PROTECTION
OBSERVATION DISPLAY ILLUMINATES - BOILER FIRES AFTER SELF CHECK - FLOW
SENSOR - FLOW RETURN
FAULT CODES 2
Z REDIRECT
OBSERVATION DISPLAY ILLUMINATES
FUSE (MAINS)
OBSERVATION DISPLAY ILLUMINATES
FUSE (TERMINAL BLOCK) F2A
OBSERVATION DISPLAY ILLUMINATES
SET - CONTROL
NO SPARK
PCB - MAIN
OBSERVATION FAN AND PUMP OVERRUN
PCB - MAIN
OBSERVATION CH MODULATION
SENSOR - FLOW RETURN
F2
RECTIFICATION LEAD
F2
ELECTRODE - FLAME SENSING
F3 - STUCK OPEN CIRCUIT
THERMOSTAT 100DEG C - OVERHEAT CUT-OFF
F9
PCB - MAIN (FITMENT)
F9
VALVE C/W WASHERS - GAS
F10 TO F22 F25 F35 F36
PCB - MAIN
F45 F46
SENSOR - FLUE
F41 F47 NO VOLTAGE TO PRESSURE SENSOR
PCB - MAIN
F41 F47
HARNESS
F40
SENSOR - LOW WATER PRESSURE (BLOCKAGE)
F37
SENSOR - LOW WATER PRESSURE (BLOCKAGE)
F40
EXPANSION VESSEL - 10 LITRE
F23
SENSOR - LOW WATER PRESSURE (BLOCKAGE)
OBSERVATION DISPLAY ILLUMINATES
FUSE (DISPLAY PCB) 3.15A
FUSE INVESTIGATION
TRANSFORMER
OBSERVATION DISPLAY ILLUMINATES
TRANSFORMER
FAN DC SECTION SHORTING
HARNESS
OPERATION CH - TOO COOL
PUMP ASSEMBLY - CH
OPERATION CH - NOISYOPERATION CH - UP TO TEMP RADS COOL
PUMP ASSEMBLY - CH
OPERATION CH - NOISYOPERATION CH - UP TO TEMP RADS COOL
VALVE- BYPASS
OPERATION CH - NOISYOPERATION CH - UP TO TEMP RADS COOL
VALVE - NON RETURN
OPERATION CH - TOO COOL
PARAMETERS CH OUTPUT
OPERATION CH - TOO COOL
SET - CONTROL
RESTRICTED OR BLOCKED CAUING POOR FLUE GAS READINGS 3
NOZZLE AIR GAS MIXING CHAMBER
DAMAGED CAUSING FLUE GAS FAIL 3
BURNER - CERAMIC
RESTRICTING HEAT EX CAUSING POOR FLUE GAS READINGS3
INSULATION - COMBUSTION CHAMBER
RESTRICTED OR BLOCKED CAUSING POOR FLUE GAS READINGS 2
HEAT EXCHANGER
FLUE GAS ANALYSIS
GAS INLET PRESSURE
OPERATION CH - TOO COOL - FLOW
SENSOR - FLOW RETURN
OPERATION CH - TOO COOL - RETURN
SENSOR - FLOW RETURN
OPERATION CH - TOO COOL
SENSOR - FLUE
OPERATION CH - NOISY
PARAMETERS CH OUTPUT
00 AND SPANNER SYMBOL - MAIN PCB
HARNESS
F5 - NO PERM VOLTAGE TO FAN
PCB - CPD3 1 DISPLAY
F5 - NO DEMAND VOLTAGE TO FAN
PCB - CPD3 1 DISPLAY
F5 NO FAN
HARNESS
F5 FAN RUNS
HARNESS
F26
Z REDIRECT
F3
ISOLATION VALVES
F3
PUMP ASSEMBLY - CH
TYPE OF DIAGNOSTIC PROCEDURE
Z REDIRECT
F3
SENSOR - FLUE
F3 - RETURN
SENSOR - FLOW RETURN
F3 - FLOW
SENSOR - FLOW RETURN
F3
VALVE- BYPASS
F3
FILTER
F3
VALVE - NON RETURN
OVERHEATING AFTER DEMAND
PCB - MAIN
00 AND SPANNER SYMBOL
HARNESS
F1
Z REDIRECT
OBSERVATION BURNER IGNITES AND ESTABLISHES - EXPLOSIVE IGNITION
GAS INLET PRESSURE
OBSERVATION BURNER IGNITES AND ESTABLISHES - EXPLOSIVE IGNITION
NOZZLE AIR GAS MIXING CHAMBER
OBSERVATION BURNER IGNITES AND ESTABLISHES - EXPLOSIVE IGNITION
BURNER - CERAMIC
OBSERVATION BURNER IGNITES AND ESTABLISHES - EXPLOSIVE IGNITION
INSULATION - COMBUSTION CHAMBER
WRONG MIX EXPLOSIVE IGNITION
VALVE C/W WASHERS - GAS
FAULT CODES 1
Z REDIRECT
F30 F31
HARNESS
F43 F44
HARNESS
OPERATION CH
EXPANSION VESSEL PIPE
F23
PCB SETTING - UK MARKET
OBSERVATION FAN RUNS - POTENTIOMETER FAULT
PCB - CPD3 1 DISPLAY
OBSERVATION FAN RUNS - IGNORING SENSORS
PCB - MAIN
WRONG MIX BAFFLING
VALVE C/W WASHERS - GAS
OBSERVATION PUMP RUNS
PUMP ASSEMBLY - CH
F3 - TEMPERATURE SETTING
PCB - CPD3 1 DISPLAY
F3
NO FAULT FOUND OVERHEAT
F3 - NOT RUNNING
PUMP ASSEMBLY - CH
F9
Z REDIRECT
OPERATION CH - TOO COOL
PCB - MAIN
OPERATION CH - UP TO TEMP RADS COOL
GAUGE - PRESSURE
OBSERVATION PUMP RUNS - IGNORING DEMAND
PCB - CPD3 1 DISPLAY
OPERATION CH
SYSTEM PRESSURE LOW
DC SECTION SHORTING - DISPLAY
FAN ASSEMBLY
FUSE INVESTIGATION - DISPLAY
PCB DISPLAY - FUSE
OPERATION CH - NOISY
PCB - CPD3 1 DISPLAY
OBSERVATION PUMP RUNS
RELAY
OPERATION CH - TOO COOL - GAS RATE WRONG
PCB - MAIN
OPERATION CH - TOO COOL - LPG
PCB - MAIN
NOT SPARKING 2
IGNITION ELECTRODE INTERNAL
NOT SPARKING
IGNITION ELECTRODE INTERNAL
DROPPING AWAY COMPLETELY
GAS INLET PRESSURE
CLOGGED SCROLL
FAN ASSEMBLY
RESTRICTED HIGH PRESSURE
HEAT EXCHANGER
PUMP SECTION SHORTING
HARNESS
WRONG MIX NOT IGNITING
VALVE C/W WASHERS - GAS
OBSERVATION BURNER IGNITION AND ESTABLISH - SPARKING NO IGNITION - DROP SEEN
VALVE C/W WASHERS - GAS
NOT RECTIFYING
PCB - MAIN
OBSERVATION DISPLAY ILLUMINATES - BOILER FIRES AFTER SELF CHECK - STUCK IN FROST
PCB - CPD3 1 DISPLAY
PCB TAKING OUT FUSES
PCB - FUSE
OBSERVATION DISPLAY ILLUMINATES - MAINS FUSE
Z REDIRECT
OBSERVATION DISPLAY ILLUMINATES - PCB FUSE
Z REDIRECT
OBSERVATION CH MODULATION
PCB - MAIN
F2
Z REDIRECT
F2
PCB - MAIN
F3 - STUCK IN FAULT
PCB - MAIN
F3 - OVERHEAT
HARNESS
F10 TO F22 F25 F36 F36
Z REDIRECT
F30 F31
PCB - MAIN
F43 F44
PCB - MAIN
F45 F46
PCB - MAIN
F45 F46
HARNESS
F41 F47
PCB - MAIN
F41 F47
SENSOR - LOW WATER PRESSURE
F37
GAUGE - PRESSURE
F37
SYSTEM PRESSURE LOW
F37 - IGNORING PRESSURE SENSOR
PCB - MAIN
F40
GAUGE - PRESSURE
F40
SYSTEM PRESSURE (TOO HIGH)
F40 - STUCK IN FAULT
PCB - MAIN
F40
SENSOR - LOW WATER PRESSURE
F37
SENSOR - LOW WATER PRESSURE
F40
F40 NO FAULT FOUND
F23
GAUGE - PRESSURE
F23
SYSTEM PRESSURE LOW
F23
PCB - MAIN
F23
SENSOR - LOW WATER PRESSURE
OBSERVATION DISPLAY ILLUMINATES - NO DISPLAY
PCB - CPD3 1 DISPLAY
OBSERVATION DISPLAY ILLUMINATES - BOILER FIRES AFTER SELF CHECK - FIRING NO DEMAND
PCB - CPD3 1 DISPLAY
FUSE INVESTIGATION - TRANSFORMER
HARNESS
DC SECTION SHORTING
FAN ASSEMBLY
OPERATION CH - NOISYOPERATION CH - UP TO TEMP RADS COOL
GAUGE - PRESSURE
OPERATION CH - NOISYOPERATION CH
SYSTEM PRESSURE LOW
OPERATION CH - NOISY
HEAT EXCHANGER
OPERATION CH - TOO COOL
PCB - CPD3 1 DISPLAY
CAUSING POOR EMISSIONS OR BURNER DROP OUT 3
GAS VALVE ADJUSTMENT
00 AND SPANNER SYMBOL
PCB - MAIN
F5 NO FAN
FAN ASSEMBLY
F5
PCB - MAIN
F5 FAN RUNS
FAN ASSEMBLY
F3
GAUGE - PRESSURE
F3
SYSTEM PRESSURE LOW
F3
SYSTEM RESTRICTION OR BLOCKAGE
F3 - TRIPPING EARLY
THERMOSTAT 100DEG C - OVERHEAT CUT-OFF
HOT SPOTS CAUSING OVERHEAT
HEAT EXCHANGER
F34
PCB - MAIN
OBSERVATION BURNER IGNITES AND ESTABLISHES - EXPLOSIVE IGNITION
GAS VALVE ADJUSTMENT
NO INFORMATION AND SPANNER FLASHING ON DISPLAY
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
BOILER REACHES TEMPERATURE, RADIATORS DO NOT HEAT OR ONLY GET WARM
CHARACTERISTIC TEST FROM OPERATION CH
PRESSURE OK BUT GAUGE DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM PRESSURE SYSTEM
SPARKING OCCURS BUT BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
BURNER IGNITES BUT THEN BAFFLES OR DROPS OUT
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
BURNER IGNITES SMOOTHLY BUT FAILS TO ESTABLISH (SPARKING CONTINUES)
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
NO SPARKING OBSERVED
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
BURNER IGNITES BUT LIGHTS WITH EXPLOSIVE IGNITION
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
INLET PRESSURE SATISFACTORY BUT DOES NOT DIP DURING SPARKING
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
INLET PRESSURE DROPS AWAY
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
FAN PRESSURE EXCESSIVELY LOW (E G 6MB)
CHARACTERISTIC TEST FROM PRESSURE FAN
FAN PRESSURE EXCESSIVELY HIGH (E G 12MB OR GREATER)
CHARACTERISTIC TEST FROM PRESSURE FAN
AFTER SELF CHECK PUMP RUNS CONTINUALLY OR BOILER ATTEMPTS TO FIRE
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
FAULT CODE SHOWN
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
EXCESSIVE SYSTEM PRESSURE RISE
CHARACTERISTIC TEST FROM OPERATION CH
BOILER AND RADIATORS REMAIN COOL - INSUFFICIENT BOILER OUTPUT
CHARACTERISTIC TEST FROM OPERATION CH
BOILER DOES NOT RESPOND TO DHW DEMAND
CHARACTERISTIC TEST FROM OPERATION DHW
BOILER RESPONDS TO DHW DEMAND BUT OPERATION UNSATISFACTORY
CHARACTERISTIC TEST FROM OPERATION DHW
PRESSURE OK BUT GAUGE DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM PRESSURE SYSTEM
PRESSURE OK BUT GAUGE DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM PRESSURE SYSTEM
SYSTEM PRESSURE TOO HIGH
CHARACTERISTIC TEST FROM PRESSURE SYSTEM (TOO HIGH)
PRESSURE OK BUT GAUGE DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM PRESSURE SYSTEM
BOILER NOISY
CHARACTERISTIC TEST FROM OPERATION CH
PRESSURE OK BUT GAUGE DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM PRESSURE SYSTEM
PRESSURE OK BUT GAUGE DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM PRESSURE SYSTEM
OVERHEAT REOCCURS BEFORE REACHING TEMPERATURE
CHARACTERISTIC TEST FROM OBSERVATION PRIMARY HEAT EXCHANGER TEMPERATURE - OVERHEAT
TEMPERATURE EXCEEDS 90 DEGREES WHEN DEMAND TURNED OFF
CHARACTERISTIC TEST FROM OBSERVATION PRIMARY HEAT EXCHANGER TEMPERATURE - OVERHEAT
27/02/2019 15:17:59 1901_2_50_1 01/04/2019 14:05:21
28/02/2019 10:19:15
VOLTAGE EXTERNAL CONTROLS DEMAND INTO TERMINAL BLOCK
GAIN ACCESS TO MAINS TERMINAL BLOCK
VOLTAGE PUMP AT PCB
GAIN ACCESS TO MAIN PCB WIRING
RESISTANCE FAN AND HARNESS AND TO EARTH
REMOVE CONNECTOR X5 FROM THE DISPLAY PCB
RESISTANCE HARNESS FAN AND TO EARTH
DISCONNECT PLUG FROM FAN
RESISTANCE IGNITION LEAD (MODIFIED)
REMOVE THE IGNITION LEAD FROM THE MAIN PCB AND FROM THE SPARK ELECTRODE
RESISTANCE PUMP AND HARNESS AND TO EARTH
REMOVE CONNECTOR X1 FROM THE MAIN PCB
RESISTANCE PUMP AND TO EARTH
REMOVE PLUG FROM THE PUMP
VOLTAGE MAINS IN AFTER FUSE
GAIN ACCESS TO MAINS TERMINAL BLOCK
VOLTAGE MAINS IN BEFORE FUSE
GAIN ACCESS TO MAINS TERMINAL BLOCK
RESISTANCE MAINS FUSE
REMOVE FUSE FROM FUSED SPUR
RESISTANCE HARNESS FAN AND TO EARTH
DISCONNECT PLUG FROM FAN
RESISTANCE TRANSFORMER AND HARNESS
GAIN ACCESS TO DISPL
RESISTANCE TRANSFORMER
DISCONNECT INLINE CONNECTOR AT TRANSFORMER
RESISTANCE FLOW THERMISTOR AND HARNESS
REMOVE CONNECTOR X12 FROM THE MAIN PCB
RESISTANCE RECTIFICATION LEAD
REMOVE THE CONNECTOR
RESISTANCE OVERHEAT STAT AND HARNESS
GAIN ACCESS TO MAIN PCB
DISCONNECT CONNECTOR X12 FROM THE MAIN PCB
RESISTANCE OVERHEAT STAT
DISCONNECT WIRES FRO
RESISTANCE FLOW THERMISTOR AND HARNESS
REMOVE CONNECTOR X12 FROM THE MAIN PCB
RESISTANCE FLOW THERMISTOR
REMOVE THE TWO SPADE
RESISTANCE RETURN THERMISTOR AND HARNESS
GAIN ACCESS TO MAIN PCB
DISCONNECT CONNECTOR X12 FROM THE MAIN PCB
RESISTANCE RETURN THERMISTOR
REMOVE THE TWO SPADE
RESISTANCE FLUE THERMISTOR AND HARNESS
REMOVE CONNECTORS X11 AND X12 FROM THE MAIN PCB
RESISTANCE FLUE THERMISTOR
REMOVE THE TWO SPADE CONNECTORS FROM THE FLUE THERMISTOR
VOLTAGE PRESSURE SENSOR (PRESSURE)
GAIN ACCESS TO DISPLAY PCB
VOLTAGE PRESSURE SENSOR (PRESSURE)
GAIN ACCESS TO DISPLAY PCB
INSPECTION PRESSURE SENSOR BLOCKAGE
DRAIN BOILER PRIMARY CIRCUIT
REMOVE PRESSURE SENSOR FROM APPLIANCE
INSPECTION PRESSURE SENSOR BLOCKAGE
DRAIN BOILER PRIMARY CIRCUIT
REMOVE PRESSURE SENSOR FROM APPLIANCE
INSPECTION PRESSURE SENSOR BLOCKAGE
DRAIN BOILER PRIMARY CIRCUIT
REMOVE PRESSURE SENSOR FROM APPLIANCE
VOLTAGE EXTERNAL CONTROLS INTO TERMINAL BLOCK (NO DEMAND)
GAIN ACCESS TO MAINS TERMINAL BLOCK
ENSURE NO DEMANDS
RESISTANCE TRANSFORMER AND TO EARTH
DISCONNECT INLINE CONNECTOR AT TRANSFORMER
PRESSURE GAS INLET (OPERATION)
ATTACH U GAUGE TO INLET PRESSURE TEST POINT
VOLTAGE FAN PERMANENT
GAIN ACCESS TO DISPLAY PCB
RESISTANCE HARNESS FAN
DISCONNECT PLUG FROM FAN
RESISTANCE HARNESS X1 (DISPLAY PCB)
GAIN ACCESS TO BOTH PCBS
DISCONNECT X1 FROM THE DISPLAY PCB AND X11 FROM THE MAIN PCB
VOLTAGE MAINS IN (FAULT CODE)
GAIN ACCESS TO MAINS TERMINAL BLOCK
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
INSPECTION ELECTRODE INTERNAL
REMOVE BURNER ASSEMBLY
PRESSURE EXPANSION VESSEL
DRAIN BOILER PRIMARY CIRCUIT
RESISTANCE HARNESS X1 (DISPLAY PCB)
GAIN ACCESS TO BOTH PCBS
DISCONNECT X1 FROM THE DISPLAY PCB AND X11 FROM THE MAIN PCB
RESISTANCE HARNESS X1 (MAIN PCB)
REMOVE CONNECTOR X1 FROM THE MAIN PCB
DISCONNECT INLINE CONNECTOR RUNNING TO THE MAIN PCB
RESISTANCE FLOW THERMISTOR
REMOVE THE TWO SPADE
RESISTANCE RETURN THERMISTOR
REMOVE THE TWO SPADE
RESISTANCE FLUE THERMISTOR
REMOVE THE TWO SPADE CONNECTORS FROM THE FLUE THERMISTOR
RESISTANCE HARNESS RELAY - LOW VOLTAGE
DISCONNECT X2 FROM THE PCB
FOR EASIER ACCESS UNCLIP RELAY AND POSITION AS SHOWN
VOLTAGE PUMP AT PCB
GAIN ACCESS TO MAIN PCB WIRING
INSPECTION BURNER
REMOVE BURNER
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR X1 FROM THE MAIN PCB
REMOVE THE ELECTRICAL PLUG FROM THE PUMP
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR X1 FROM THE MAIN PCB
REMOVE THE ELECTRICAL PLUG FROM THE PUMP
VOLTAGE EXTERNAL CONTROLS DEMAND INTO PCB
GAIN ACCESS TO DISPLAY PCB
INSPECTION FILTER
BOILER DRAINED AND DISCHARGED
REMOVE THE FILTER FITTED IN THE CENTRAL HEATING RETURN VALVE
INSPECTION NON-RETURN VALVE
BOILER DRAINED AND DISCHARGED
INSPECTION FILTER
BOILER DRAINED AND DISCHARGED
REMOVE THE FILTER FITTED IN THE CENTRAL HEATING RETURN VALVE
INSPECTION NON-RETURN VALVE
BOILER DRAINED AND DISCHARGED
RESISTANCE HARNESS RELAY - MAINS VOLTAGE
FOR EASIER ACCESS UNCLIP RELAY AND POSITION AS SHOWN
PRESSURE GAS INLET (OPERATION)
ATTACH U GAUGE TO INLET PRESSURE TEST POINT
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE FAN FROM
INSPECTION BURNER
REMOVE BURNER
PRESSURE GAS INLET (OPERATION)
ATTACH U GAUGE TO INLET PRESSURE TEST POINT
INSPECTION FILTER
BOILER DRAINED AND DISCHARGED
REMOVE THE FILTER FITTED IN THE CENTRAL HEATING RETURN VALVE
INSPECTION NON-RETURN VALVE
BOILER DRAINED AND DISCHARGED
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE FAN FROM
INSPECTION BURNER
REMOVE BURNER
PRESSURE GAS INLET DROP
ATTACH U GAUGE TO INLET PRESSURE TEST POINT
PRESSURE GAS INLET
ATTACH U GAUGE TO INLET PRESSURE TEST POINT
PRESSURE GAS INLET
ATTACH U GAUGE TO INLET PRESSURE TEST POINT
OBSERVATION SPARKING FROM PCB
{ONOFFSWITCHON}
D
INSPECTION IGNITION LEAD END
REMOVE THE CAP FROM THE SPARK ELECTRODE
UNSCREW IT ANTICLOCKWISE FROM THE IGNITION LEAD
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
RESISTANCE IGNITION LEAD
REMOVE THE IGNITION LEAD FROM THE MAIN PCB
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
INSPECTION SUMP
REMOVE CONDENSATE TR
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE FAN FROM
PRESSURE FAN
REMOVE THE AIR IMPUL
RESISTANCE GAS VALVE AND TO EARTH
REMOVE MAIN PCB FROM GAS VALVE
INSPECTION SUMP
REMOVE CONDENSATE TR
INSPECTION BURNER
REMOVE BURNER
INSPECTION SUMP
REMOVE CONDENSATE TR
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE FAN FROM
INSPECTION ELECTRODE INTERNAL
REMOVE BURNER ASSEMBLY
INSPECTION BURNER
REMOVE BURNER
RESISTANCE TRANSFORMER AND HARNESS AND TO EARTH
GAIN ACCESS TO DISPL
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
RESISTANCE RECTIFICATION LEAD
REMOVE THE CONNECTOR
INSPECTION RECTIFICATION ELECTRODE
REMOVE RECTIFICATION ELECTRODE
RESISTANCE FAN AND HARNESS AND TO EARTH
REMOVE CONNECTOR X5 FROM THE DISPLAY PCB
TEMPERATURE AMBIENT
REMOVE COMBUSTION CHAMBER IF YOU HAVE NOT ALREADY DONE SO
RESISTANCE FLOW THERMISTOR
REMOVE THE TWO SPADE
FAULT CODES
THIS APPLIANCE INCORPORATES FAULT CODE HISTORY CLICK HERE FOR INSTRUCTIONS
VOLTAGE TRANSFORMER INTO PCB
GAIN ACCESS TO DISPLAY PCB
RESISTANCE ON/OFF SWITCH
ON/OFF SWITCH SET TO ON (BUTTON PUSHED IN)
INSPECTION RECTIFICATION ELECTRODE
REMOVE RECTIFICATION ELECTRODE
RESISTANCE GAS VALVE AND TO EARTH
REMOVE MAIN PCB FROM GAS VALVE
RESISTANCE HARNESS PRESSURE SENSOR
DISCONNECT X7 FROM THE DISPLAY PCB
REMOVE THE CONNECTOR FROM THE LOW PRESSURE SENSOR
VOLTAGE PRESSURE SENSOR (PRESSURE)
GAIN ACCESS TO DISPLAY PCB
OBSERVATION SYSTEM PRESSURE RISE (F40)
BOILER CH THERMOSTAT TO MAX
VOLTAGE PRESSURE SENSOR (PRESSURE)
GAIN ACCESS TO DISPLAY PCB
RESISTANCE DISPLAY PCB FUSE
REMOVE FUSE FROM DISPLAY PCB
VOLTAGE EXTERNAL CONTROLS INTO PCB (NO DEMAND)
ENSURE NO DEMANDS
INSPECTION FILTER
BOILER DRAINED AND DISCHARGED
REMOVE THE FILTER FITTED IN THE CENTRAL HEATING RETURN VALVE
INSPECTION NON-RETURN VALVE
BOILER DRAINED AND DISCHARGED
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE FAN FROM
INSPECTION BURNER
REMOVE BURNER
RESISTANCE FLOW THERMISTOR
REMOVE THE TWO SPADE
RESISTANCE RETURN THERMISTOR
REMOVE THE TWO SPADE
RESISTANCE FLUE THERMISTOR
REMOVE THE TWO SPADE CONNECTORS FROM THE FLUE THERMISTOR
RESISTANCE HARNESS X1 (MAIN PCB)
REMOVE CONNECTOR X1 FROM THE MAIN PCB
DISCONNECT INLINE CONNECTOR RUNNING TO THE MAIN PCB
VOLTAGE FAN DEMAND
GAIN ACCESS TO DISPLAY PCB
DISCONNECT X1 FROM THE DISPLAY PCB
RESISTANCE HARNESS FAN
DISCONNECT PLUG FROM FAN
VOLTAGE FAN HALL SENSOR
GAIN ACCESS TO DISPL
RESISTANCE FLOW THERMISTOR
REMOVE THE TWO SPADE
RESISTANCE RETURN THERMISTOR
REMOVE THE TWO SPADE
RESISTANCE FLUE THERMISTOR
REMOVE THE TWO SPADE CONNECTORS FROM THE FLUE THERMISTOR
TEMPERATURE DIFFERENTIAL CH
ATTACH TEMPERATURE C
INSPECTION FILTER
BOILER DRAINED AND DISCHARGED
REMOVE THE FILTER FITTED IN THE CENTRAL HEATING RETURN VALVE
INSPECTION NON-RETURN VALVE
BOILER DRAINED AND DISCHARGED
OBSERVATION PRIMARY HEAT EXCHANGER TEMPERATURE - OVERHEAT
CH TEMPERATURE CONTROL KNOB SET TO MAX
PRESSURE GAS INLET (OPERATION)
ATTACH U GAUGE TO INLET PRESSURE TEST POINT
OBSERVATION SPARKING FROM PCB
{ONOFFSWITCHON}
D
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE FAN FROM
INSPECTION BURNER
REMOVE BURNER
System Information
- Total Tests: 523
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control