Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to DC Volts Set meter to measure DC Volts
Gain access to display PCB
Ensure power has been off to boiler for at least 10 seconds (or it will not carry out self-check)
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow fan to run for self-check.
Measure the voltage between pin 2 (purple) and pin 5 (white) at X5 on the display PCB.
Voltage should be approximately 6V DC.
Note:
Fan purge runs for approximately 90 seconds, repeat test as required
(turning power off for at least 10 seconds to allow fan purge)