Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Gain access to display PCB
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Measure the DC voltage between pin 4 (yellow) and pin 5 (green) at connector X7 on the display PCB.
Voltages depend on system pressure (refer to the manual pressure gauge) and should conform approximately to the table below:
Voltages depend on system pressure (refer to the manual pressure gauge) and should conform approximately to the table below:
| Pressure (bar) | DC Volts |
| 0.5 | 0.6 |
| 1 | 0.9 |
| 1.5 | 1.1 |
| 2 | 1.4 |
| 2.5 | 1.6 |

Isolate as per TOPs P4
and refit as necessary