Set Appliance State:

CH Demand
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Allow burner to ignite and boiler to run with a CH demand for 1 minute.
Remove CH demand.
Monitor the pump and fan after the demand has ceased.
The fan should overrun for approximately 15 seconds.
The pump should overrun as per parameter 5 (default 7 minutes).
CLICK HERE FOR INSTRUCTIONS ON CHECKING PARAMETER
Do the over runs behave as described above?