Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
DHW Demand
Attach temperature clamps to flow and return pipes underneath boiler as close to isolation valves as possible
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Skip self-check as necessary.
Set boiler into service mode (hold + and - buttons until display changes - approx. 3 seconds).
Allow boiler to run for approximately 2 minutes or until return pipe begins to heat.
Measure the temperature differential between the flow and return pipes.
The differential should be approximately 25°C or less.
Note:
Temperature differential may be higher on initial start-up.
Set boiler into service mode (hold + and - buttons until display changes - approx. 3 seconds).
Allow boiler to run for approximately 2 minutes or until return pipe begins to heat.
Measure the temperature differential between the flow and return pipes.
The differential should be approximately 25°C or less.
Note:
Temperature differential may be higher on initial start-up.