VIESSMANN VITODENS 100 24KW SYSTEM
WARNING - IMPORTA
OBSERVATION APPLIANCE SELF CHECK
ENSURE NO DEMANDS
TYPE OF DIAGNOSTIC PROCEDURE
PLEASE SELECT FROM O
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO GAS INLET PRESSURE TEST POINT
CH OPERATION
CH TEMPERATURE CONTROL TURNED TO MAX
DISPLAY FAULT CODE 30 / 38
OK TO BE BLANK
DISPLAY FAULT CODE E5
OK TO BE BLANK
DISPLAY FAULT CODE B1 / B5 / F0
OK TO BE BLANK
DISPLAY FAULT CODE F2
OK TO BE BLANK
DISPLAY FAULT CODE F3
OK TO BE BLANK
DISPLAY FAULT CODE F8
OK TO BE BLANK
DISPLAY FAULT CODE F9 / FA
OK TO BE BLANK
DISPLAY FAULT CODE FD
OK TO BE BLANK
FUSE FURTHER INVESTIGATION
NOT USED
OBSERVATION FAN RUNS CH DEMAND
ENSURE APPLIANCE IS COOL
CH TEMPERATURE CONTROL TURNED TO MAX
HOT WATER OPERATION
HW DEMAND
OBSERVATION BURNER IGNITION & ESTABLISH
CH TEMPERATURE CONTROL TURNED TO MAX
DISPLAY FAULT CODE 0B
OK TO BE BLANK
DISPLAY FAULT CODE OC / E4
OK TO BE BLANK
DISPLAY FAULT CODE E6
OK TO BE BLANK
DISPLAY FAULT CODE F5
OK TO BE BLANK
DISPLAY FAULT CODE F7
OK TO BE BLANK
DISPLAY FAULT CODE 58
OK TO BE BLANK
OBSERVATION PUMP OVERRUN
CH TEMPERATURE CONTROL TURNED TO MAX
OBSERVATION PUMP RUNS
CH TEMPERATURE CONTROL TURNED TO MAX
FAULT CODE E5
ELECTRODE - IGNITING
FAULT CODE E5
CONTROL UNIT (PCB)
FAULT CODE F2 2
CONTROL UNIT (PCB)
FAULT CODE FD FF 2
ELECTRODE - IGNITING
FAULT CODE F3
CONTROL UNIT (PCB)
FAULT CODE FD FF
ELECTRODE - IGNITING
FAULT CODE FD FF
CONTROL UNIT (PCB)
FAULT CODE F2 2
THERMOCOUPLE
FAULT CODE 2
Z REDIRECT
EXCESSIVE PRESSURE RISE
EXPANSION VESSEL
APPLIANCE TO TEMP RADS COOL
SYSTEM PRESSURE
APPLIANCE TO TEMP RADS COOL
GAS COCK - HEATING WATER
BURNER BAFFLES OR NOISY
CONDENSATE PIPEWORK
BURNER BAFFLES OR NOISY
GAS INLET PRESSURE
BURNER DOES NOT IGNITE 2
CONDENSATE PIPEWORK
BURNER DOES NOT ESTABLISH
GAS INLET PRESSURE
BURNER DOES NOT IGNITE 3
GAS TRAIN
SERVICE MODE 2
Z REDIRECT
BOILER TEMP LOW RADS COOL
SENSOR - TEMPERATURE
APPLIANCE FAILS TO REACH SET TEMP
SYSTEM PRESSURE
APPLIANCE FAILS TO REACH SET TEMP
GAS INLET PRESSURE
APPLIANCE FAILS TO REACH SET TEMP
CONTROL KNOB
BLANK DISPLAY
FUSE (PCB FUSE)
BLANK DISPLAY
FUSE (FUSED SPUR)
NO VOLTAGE TO PRESSURE SENSOR
CONTROL UNIT (PCB)
ERROR CODE F7
HARNESS - CABLE X9
BURNER IGNITES BUT BAFFLES / NOISY
TOP - VENTURI - TYPE 002
FAULT CODE F2 3
CONTROL UNIT (PCB)
NO VOLTAGE SENT TO PRESSURE SENSOR
CONTROL UNIT (PCB)
ERROR CODE E6
HARNESS - CABLE X9
ERROR CODE E6
SYSTEM PRESSURE
FAULT CODE F2
SENSOR - TEMPERATURE
FAULT CODE 58
DIP SWITCH
LOW PRESSURE
SYSTEM PRESSURE
RESTRICTED / BLOCKED
TOP - VENTURI - TYPE 002
FUSE FURTHER INVESTIGATION
GAS TRAIN
FAN DOES NOT RUN
HARNESS - CABLE X8
NO PUMP OVERRUN
CONTROL UNIT (PCB)
BURNER DOES NOT IGNITE
CONDENSATE PIPEWORK
BURNER DOES NOT IGNITE
TOP - VENTURI - TYPE 002
BURNER DOES NOT IGNITE 1
ELECTRODE - IGNITING
CASE REMOVAL
Z REDIRECT
BURNER DOES NOT ESTABLISH 2
ELECTRODE - IGNITING
BURNER IGNITES BUT DOES NOT ESTABLISH
TRANSFORMER - IGNITION C/W IONISATION CONNECTING CABLE
IGNITES BUT DOES NOT ESTABLISH
SPARK GENERATOR - ZIG 2/12
NO CH
CLOCK / TIMESWITCH - MECHANICAL
FAULT CODE F2
GAS COCK - HEATING WATER
FAN DOES NOT RUN
SENSOR - TEMPERATURE
FAN DOES NOT RUN
SWITCH - PRESSURE
DOES NOT IGNITE
TRANSFORMER - IGNITION C/W IONISATION CONNECTING CABLE
BURNER DOES NOT IGNITE 4
ELECTRODE - IGNITING
PUMP RUNS CONTINUALLY
DIP SWITCH
ON WITH NO DEMAND
CLOCK / TIMESWITCH - MECHANICAL
SELF CHECK
SENSOR - TEMPERATURE
BURNER DOES NOT IGNITE 1
TOP - VENTURI - TYPE 002
UNABLE TO RESET SERVICE MODE
CONTROL UNIT (PCB)
UNABLE TO RESET PUMP PURGE MODE
CONTROL UNIT (PCB)
FAN DOES NOT RUN
TOP - VENTURI - TYPE 002
FAN DOES NOT RUN
SWITCH - PRESSURE TUBE
FAN DOES NOT RUN
SYSTEM PRESSURE
FAULT CODE F2
SYSTEM PRESSURE
FAULT CODE F5
SWITCH - PRESSURE
ERROR CODE F5
HARNESS - CABLE X8
FAULT CODE F5
SWITCH - PRESSURE TUBE
FAULT CODE F5
GAS TRAIN
FAULT CODE F5
FLUE
FAULT CODE F5
TOP - VENTURI - TYPE 002
FAULT CODE F5
HEAT EXCHANGER
APS FAULT CODE F5
SWITCH - PRESSURE
MOISTURE / BLOCKAGE
SWITCH - PRESSURE TUBE
BURNER DOES NOT IGNITE 1
CONTROL UNIT (PCB)
FAN DOES NOT RUN
CABLE - CONNECTING - STEP MOTOR
FAN DOES NOT RUN
PUMP
FAULT CODE OB
SYSTEM PRESSURE
ERROR CODE OB
CONTROL UNIT (PCB)
FAULT CODE OB
PUMP
FAULT CODE OB
HARNESS - CABLE X8
FAULT CODE 0B
GAS COCK - HEATING WATER
NO VOLTAGE TO GAS VALVE
SWITCH - PRESSURE
OPEN CIRRCUIT NO POWER TO GAS VALVE
HARNESS - CABLE X8
BURNER DOES NOT IGNITE
GAS TRAIN / CONTROL UNIT (PCB)
BURNER DOES NOT IGNITE
SWITCH - PRESSURE TUBE
BURNER DOES NOT IGNITE 4
GAS TRAIN
BURNER DOES NOT IGNITE 2
TOP - VENTURI - TYPE 002
BURNER DOES NOT IGNITE 1
HEAT EXCHANGER
FAULT CODE 0B
CABLE - CONNECTING - STEP MOTOR
NO HW
CONTROL UNIT (PCB)
STUCK IN HEATING
MOTOR - STEP
HW OP
CONTROL UNIT (PCB)
HW OP
CABLE - CONNECTING - STEP MOTOR
FAN DOES NOT RUN 1
CONTROL UNIT (PCB)
FAN DOES NOT RUN
SWITCH - FLOW
FAN DOES NOT RUN 1 FAN DOES NOT RUN
MOTOR - STEP
FAULT CODE 0B
CONTROL UNIT (PCB)
FAULT CODE OB
SWITCH - FLOW
FAULT CODE 0B
MOTOR - STEP
NO POWER TO PUMP
CONTROL UNIT (PCB)
PUMP NOT RUNNING
HARNESS PUMP
STEPPER
CABLE - CONNECTING - STEP MOTOR
NOT OPERATING FOR CH
CONTROL UNIT (PCB)
WINDINGS OK BUT NO MOVEMENT
MOTOR - STEP
APPLIANCES REACHES TEMP RADS COOL
VALVE - BYPASS / OVERFLOW
FAULT CODE OB
RETEST APPLIANCE
SELF CHECK 2
CONTROL UNIT (PCB)
NOT RECOGNISING CH DEMAND
CONTROL UNIT (PCB)
ON WITH NO DEMAND
DIGITAL PROGRAMMER
NOT RECOGNISING DEMAND
DIGITAL PROGRAMMER
GAS INLET DHW DEMAMD
GAS INLET PRESSURE
FAULT CODE 30
SENSOR - TEMPERATURE
FAULT CODE 30
CONTROL UNIT (PCB)
FAULT CODE F0
CONTROL UNIT (PCB)
FAULT CODE F2
PUMP
FAULT CODE F8
GAS TRAIN
FAULT CODE F8
ELECTRODE - IGNITING
FAULT CODE F8
CONTROL UNIT (PCB)
FAULT CODE F9 FA FC 2
CONTROL UNIT (PCB)
FAULT CODE FD FF
EMC FIELD
FUSE FURTHER INVESTIGATION
FAN - RADIAL
FAULT CODE F9
HARNESS - CABLE - FAN
FAULT CODE F9 FA FC
HARNESS - CABLE X8
FAULT CODE F9
CONTROL UNIT (PCB)
TYPE OF DIAGNOSTIC PROCEDURE
Z REDIRECT
FAULT CODE E5
FAULT CODE RESET - RETEST APPLIANCE OPERATION
FAULT CODE F2 2
PUMP
FAULT CODE F2
HARNESS PUMP
FAULT CODE F3
FAULT CODE RESET - RETEST APPLIANCE OPERATION
FAULT CODE FD FF
FAULT CODE RESET - RETEST APPLIANCE OPERATION
FUSE FURTHER INVESTIGATION
HARNESS PUMP
FAULT CODE F2 4
CONTROL UNIT (PCB)
FAULT CODE F2
HARNESS - CABLE X8
FAULT CODE
Z REDIRECT
NO DISPLAY
CONTROL UNIT (PCB)
BLOCKED CAUSING PRESSURE RISE
HOSE - EXPANSION VESSEL
BURNER BAFFLES OR NOISY
SIPHON
BURNER BAFFLES OR NOISY
GAS TRAIN
BURNER BAFFLES OR NOISY
BURNER GAUZE ASSEMBLY
BURNER BAFFLES OR NOISY
HEAT EXCHANGER
BURNER DOES NOT IGNITE 2
SIPHON
BURNER DOES NOT IGNITE
GAS INLET PRESSURE
BURNER DOES NOT IGNITE
CABLE - CONNECTING - GAS VALVE
BOILER TEMP LOW RADS COOL
CONTROL UNIT (PCB)
SERVICE MODE
Z REDIRECT
BOILER TEMP LOW RADS COOL
BURNER GAUZE ASSEMBLY
BOILER TEMP LOW RADS COOL
HEAT EXCHANGER
FUSE FURTHER INVESTIGATION
Z REDIRECT
FUSE FURTHER INVESTIGATION 1
Z REDIRECT
ERROR CODE F7
CONTROL UNIT (PCB)
FAULT CODE F7
SENSOR - WATER PRESSURE
BLOCKED / RESTRICTED
SENSOR - WATER PRESSURE
BLOCKED
BLOCK - HYDRAULIC
ERROR CODE F7
SENSOR - WATER PRESSURE
FAULT CODE F2
THERMOCOUPLE
FAULT CODE F2
CONTROL UNIT (PCB)
FAULT CODE F2
FAULT CODE F2 - OVERHEAT
FAULT CODE E4
CONTROL UNIT (PCB)
ERROR CODE E6
CONTROL UNIT (PCB)
ERROR CODE E6
SENSOR - WATER PRESSURE
RESTRICTED / BLOCKED
SENSOR - WATER PRESSURE
RESTRICTED
BLOCK - HYDRAULIC
FAULT CODE 58
CONTROL UNIT (PCB)
SYSTEM PRESSURE FURTHER INVESTIGATION
Z REDIRECT
NOT REGISTERING PRESSURE
SENSOR - WATER PRESSURE
RESTRICTED OR BLOCKED
SENSOR - WATER PRESSURE
RESTRICTED OR BLOCKED
BLOCK - HYDRAULIC
POOR OUTPUT
MIXTURE DAMPER
BOILER TEMP LOW RADS COOL
FAN - RADIAL
BOILER TEMP LOW RADS COOL 2
CONTROL UNIT (PCB)
FUSE FURTHER INVESTIGATION 2
CABLE - CONNECTING - GAS VALVE
FUSE FURTHER INVESTIGATION
CONTROL UNIT - FUSE BLOWN
BURNER DOES NOT IGNITE
SIPHON
BURNER DOES NOT IGNITE
GAS TRAIN
BURNER DOES NOT IGNITE
BURNER GAUZE ASSEMBLY
BURNER DOES NOT IGNITE
HEAT EXCHANGER
BURNER DOES NOT IGNITE
ELECTRODE - IGNITING
BURNER DOES NOT ESTABLISH
CONTROL UNIT (PCB)
BURNER DOES NOT ESTABLISH
BURNER GAUZE ASSEMBLY
BURNER DOES NOT ESTABLISH
HEAT EXCHANGER
BURNER DOES NOT IGNITE 3
ELECTRODE - IGNITING
NO CH
CONTROL UNIT (PCB)
OVERHEAT 1
VALVE - BYPASS / OVERFLOW
OVERHEAT F2
VALVE - BYPASS / OVERFLOW
FAN DOES NOT RUN 2
CONTROL UNIT (PCB)
FAN NOT RUNNING
HARNESS - CABLE X8
DOES NOT IGNITE
SPARK GENERATOR - ZIG 2/12
FAULT CODE F2
SYSTEM BLOCKAGE
BOILER FIRES NO DEMAND
CONTROL UNIT (PCB)
BOILER SELF CHECK
FROST PROTECTION NORMAL OPERATION
SELF CHECK
CONTROL UNIT (PCB)
STICKING
MIXTURE DAMPER
CONTAMINATED
FAN - RADIAL
BURNER DOES NOT IGNITE 2
GAS TRAIN
BURNER DOES NOT IGNITE 2
BURNER GAUZE ASSEMBLY
BURNER DOES NOT IGNITE 2
HEAT EXCHANGER
SELF CHECK
SERVICE MODE
SELF CHECK
PUMP PURGE
MOISTURE / BLOCKAGE IN OUT TEST POINT
GAS TRAIN
FLOW SWITCH NOT MAKING
SENSOR - WATER PRESSURE
BLOCKED / RESTRICTED FLOW SWITCH NOT MAKING
SENSOR - WATER PRESSURE
BLOCKED / RESTRICTED FLOW SWITCH NOT MAKING
BLOCK - HYDRAULIC
FAULT CODE F2
SENSOR - WATER PRESSURE
BLOCKED / RESTRICTED FAULT CODE F2
SENSOR - WATER PRESSURE
BLOCKED FAULT CODE F2
BLOCK - HYDRAULIC
FAULT CODE F5
MIXTURE DAMPER
ERROR CODE F5
FAN - RADIAL
APS FAULT CODE F5
CONTROL UNIT (PCB)
APS FAULT CODE F5
HARNESS - CABLE X8
MOISTURE / RESTRICTION IN OUT TEST POINT
GAS TRAIN
HW OPERATION
CONTROL UNIT (PCB)
FAN DOES NOT RUN
CONTROL UNIT (PCB)
FAN DOES NOT RUN
MOTOR - STEP
FAULT CODE OB
SENSOR - WATER PRESSURE
BLOCKED / RESTRICTED FAULT CODE OB
SENSOR - WATER PRESSURE
BLOCKED FAULT CODE OB
BLOCK - HYDRAULIC
ERROR CODE OB
PUMP
FAULT CODE OB
HARNESS PUMP
FAULT CODE OB
VALVE - BYPASS / OVERFLOW
FAULT CODE 0B
VALVE - BYPASS / OVERFLOW
FAULT CODE OB FAN DOES NOT RUN
VALVE - BYPASS / OVERFLOW
FAULT CODE 0B FAN DOES NOT RUN
VALVE - BYPASS / OVERFLOW
BLOCKING VOLTAGE TO GAS VALVE
SPARK GENERATOR - ZIG 2/12
BURNER DOES NOT IGNITE
CABLE - CONNECTING - GAS VALVE / CONTROL UNIT (PCB)
BURNER DOES NOT IGNITE
MIXTURE DAMPER
BURNER DOES NOT IGNITE
FAN - RADIAL
BURNER DOES NOT IGNITE
CONTROL UNIT (PCB)
ERROR COD OB
CONTROL UNIT (PCB)
ERROR CODE 0B
MOTOR - STEP
NO HW OP
MOTOR - STEP
BLOCKED HOSES / HEAT EX / PIPES FAN DOES NOT RUN
CIRCULATION ISSUE (APPLIANCE)
BLOCKED HOSES / HEAT EX / PIPES
CIRCULATION ISSUE (APPLIANCE)
PUMP NOT RUNNING
PUMP
NO PERMANENT VOLTAGE TO STEPPER
CONTROL UNIT (PCB)
WINDINGS GONE
MOTOR - STEP
APPLIANCE TO TEMP RADS COOL
SYSTEM BLOCKAGE
FAULT CODE OB
CONTROL UNIT (PCB)
ON WITH NO DEMAND
CONTROL UNIT (PCB)
NOT RECOGNISING HTG DEMAND
CONTROL UNIT (PCB)
FAULT CODE 30
HARNESS - CABLE X8
FAULT CODE 30
FAULT CODE RESET - RETEST APPLIANCE OPERATION
FAULT CODE F0
FAULT CODE RESET - RETEST APPLIANCE OPERATION
FAULT CODE F8
FAULT CODE RESET - RETEST APPLIANCE OPERATION
FAULT CODE F8 2
GAS TRAIN
FAULT CDOE F8
FAULT CODE RESET - RETEST APPLIANCE OPERATION
FAULT CODE F9 FA FC
FAN - RADIAL
FUSE FURTHER INVESTIGATION
HARNESS - CABLE - FAN
HW DEMAND NOT RECOGNISED
CHARACTERISTIC TEST FROM HOT WATER OPERATION
HW OPERATION UNSATISFACTORY
CHARACTERISTIC TEST FROM HOT WATER OPERATION
EXCESSIVE SYSTEM PRESSURE RISE
CHARACTERISTIC TEST FROM CH OPERATION
BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH
BURNER IGNITES BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH
BURNER IGNITES BUT BAFFLES OR IS NOISY
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH
BURNER RESTRICTED AND / OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
HEAT EXCHANGER FLUEWAYS RESTRICTED AND / OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
NO PRESSURE DROP OBSERVED
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
PRESSURE DROPS BELOW AN ACCEPTABLE MIMIMUM LEVEL
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
HOW TO SET APPLIANCE TO 100% OUTPUT
CHARACTERISTIC TEST FROM BOILER OUTPUT
BURNER RESTRICTED AND / OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
HEAT EXCHANGER FLUEWAYS RESTRICTED AND / OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
WATER PRESSURE SENSOR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION LOW PRESSURE SENSOR AND PUMP MANIFOLD
PUMP MANIFOLD BLOCKED
CHARACTERISTIC TEST FROM INSPECTION LOW PRESSURE SENSOR AND PUMP MANIFOLD
APPLIANCE GOES TO FAULT CODE F2 BEFORE MAXIMUM FLOW TEMPERATURE REACHED
CHARACTERISTIC TEST FROM OBSERVATION CH - OVERHEAT OCCUR
TEMPERATURE EXCEEDS MAXIMUM FLOW TEMPERATURE 80°C AND CONTINUES TO FIRE
CHARACTERISTIC TEST FROM OBSERVATION CH - OVERHEAT OCCUR
WATER PRESSURE SENSOR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION LOW PRESSURE SENSOR AND PUMP MANIFOLD
PUMP MANIFOLD BLOCKED
CHARACTERISTIC TEST FROM INSPECTION LOW PRESSURE SENSOR AND PUMP MANIFOLD
LOW SYSTEM PRESSURE DISPLAYED
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
WATER PRESSURE SENSOR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION LOW PRESSURE SENSOR AND PUMP MANIFOLD
PUMP MANIFOLD BLOCKED
CHARACTERISTIC TEST FROM INSPECTION LOW PRESSURE SENSOR AND PUMP MANIFOLD
MIXTURE DAMPER STICKING / NOT FUNCTIONING CORRECTLY
CHARACTERISTIC TEST FROM INSPECTION FAN AND DAMPER
FAN IMPELLORS CONTAMINATED AND / OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION FAN AND DAMPER
CH DEMAND NOT RECOGNISED
CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS CH DEMAND
CH DEMAND RECOGNISED BUT FAN DOES NOT RUN
CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS CH DEMAND
BURNER RESTRICTED AND / OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
HEAT EXCHANGER FLUEWAYS RESTRICTED AND / OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
ELECTRODE GAP TO BURNER SURFACE INCORRECT
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS / ELECTRODE
BURNER RESTRICTED AND / OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
HEAT EXCHANGER FLUEWAYS RESTRICTED AND / OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
ELECTRODE GAP TO BURNER SURFACE INCORRECT
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS / ELECTRODE
INTERNAL BYPASS IN POOR CONDITION AND / OR NOT OPERATING CORRECTLY
CHARACTERISTIC TEST FROM INSPECTION HOSE AND INTERNAL BYPASS
BYPASS PIPE BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION HOSE AND INTERNAL BYPASS
SERV DISPLAYED
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
MIXTURE DAMPER STICKING / NOT FUNCTIONING CORRECTLY
CHARACTERISTIC TEST FROM INSPECTION FAN AND DAMPER
FAN IMPELLORS CONTAMINATED AND / OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION FAN AND DAMPER
BURNER RESTRICTED AND / OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
HEAT EXCHANGER FLUEWAYS RESTRICTED AND / OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
WATER PRESSURE SENSOR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION LOW PRESSURE SENSOR AND PUMP MANIFOLD
PUMP MANIFOLD BLOCKED
CHARACTERISTIC TEST FROM INSPECTION LOW PRESSURE SENSOR AND PUMP MANIFOLD
WATER PRESSURE SENSOR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION LOW PRESSURE SENSOR AND PUMP MANIFOLD
PUMP MANIFOLD BLOCKED
CHARACTERISTIC TEST FROM INSPECTION LOW PRESSURE SENSOR AND PUMP MANIFOLD
MIXTURE DAMPER STICKING / NOT FUNCTIONING CORRECTLY
CHARACTERISTIC TEST FROM INSPECTION FAN AND DAMPER
FAN IMPELLORS CONTAMINATED AND / OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION FAN AND DAMPER
VOLTAGE MISSING FROM PIN 2 OR 5
CHARACTERISTIC TEST FROM VOLTAGE DC STEPPER MOTOR PERMANENT AT PCB
VOLTAGE PRESENT ON PIN 2 AND 5 BUT ABSENT FROM ONE OR MORE OTHER PINS
CHARACTERISTIC TEST FROM VOLTAGE DC STEPPER MOTOR PERMANENT AT PCB
VOLTAGE MISSING FROM PIN 2 OR 5
CHARACTERISTIC TEST FROM VOLTAGE DC STEPPER MOTOR PERMANENT AT PCB
WATER PRESSURE SENSOR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION LOW PRESSURE SENSOR AND PUMP MANIFOLD
PUMP MANIFOLD BLOCKED
CHARACTERISTIC TEST FROM INSPECTION LOW PRESSURE SENSOR AND PUMP MANIFOLD
BYPASS BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM VOLTAGE DC STEPPER MOTOR PERMANENT AT PCB
INTERNAL BYPASS IN POOR CONDITION AND / OR NOT OPERATING CORRECTLY
CHARACTERISTIC TEST FROM INSPECTION HOSE AND INTERNAL BYPASS
BYPASS BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM VOLTAGE DC STEPPER MOTOR PERMANENT AT PCB
INTERNAL BYPASS IN POOR CONDITION AND / OR NOT OPERATING CORRECTLY
CHARACTERISTIC TEST FROM INSPECTION HOSE AND INTERNAL BYPASS
MIXTURE DAMPER STICKING / NOT FUNCTIONING CORRECTLY
CHARACTERISTIC TEST FROM INSPECTION FAN AND DAMPER
FAN IMPELLORS CONTAMINATED AND / OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION FAN AND DAMPER
VOLTAGE PRESENT ON PIN 2 AND 5 BUT ABSENT FROM ONE OR MORE PINS
CHARACTERISTIC TEST FROM VOLTAGE DC STEPPER MOTOR PERMANENT AT PCB
VOLTAGE MISSING FROM PIN 2 OR 5
CHARACTERISTIC TEST FROM VOLTAGE DC STEPPER MOTOR PERMANENT AT PCB
VOLTAGE PRESENT ON PIN 2 AND 5 BUT ABSENT FROM ONE OR MORE OTHER PINS
CHARACTERISTIC TEST FROM VOLTAGE DC STEPPER MOTOR PERMANENT AT PCB
VOLTAGE MISSING FROM PIN 2 OR 5
CHARACTERISTIC TEST FROM VOLTAGE DC STEPPER MOTOR PERMANENT AT PCB
VOLTAGE PRESENT ON PIN 2 AND 5 BUT ABSENT FROM ONE OR MORE OTHER PINS
CHARACTERISTIC TEST FROM VOLTAGE DC STEPPER MOTOR PERMANENT AT PCB
APPLIANCE REACHES TEMPERATURE BUT RADIATORS REMAIN COOL OR DO NOT HEAT
CHARACTERISTIC TEST FROM CH OPERATION
APPLIANCE AND RADIATORS FAIL TO REACH SET TEMPERATURE
CHARACTERISTIC TEST FROM CH OPERATION
PUMP RUNS CONTINUOUSLY OR APPLIANCE ATTEMPTS TO FIRE AFTER SELF CHECK COMPLETE
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
FAULT CODE DISPLAYED
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
DELAY IN RETURNING TO STANDING PRESSURE
CHARACTERISTIC TEST FROM PRESSURE STANDING RETURN
APPLIANCE DOES NOT RESET - FAULT CODE REMAINS THE SAME
CHARACTERISTIC TEST FROM PRESSURE STANDING RETURN
DISPLAY DOES NOT OPERATE CORRECTLY
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
25/02/2020 09:01:43 2002_1_50_1 12/03/2020 13:56:34
25/02/2020 09:59:26
VOLTAGE AT PUMP
CH TEMPERATURE CONTR
VOLTAGE PUMP AT PCB
{GAINPCBACS}
CH TEMPERATURE CONTROL SET TO MAX
REMOVE CONNECTOR 20 FROM THE PCB AND MAKE SAFE
INSPECTION ELECTRODE
REMOVE ELECTRODE ASSEMBLY FROM THE BURNER DOOR
DISCONNECT LEAD FROM THE SPARK GENERATOR
RESISTANCE TEMPERATURE LIMITER AND HARNESS
ENSURE APPLIANCE IS COOL
REMOVE CONNECTOR X8 FROM THE PCB
RESISTANCE TEMPERATURE LIMITER
REMOVE 1 X SPADE CONNECTOR FROM THE TEMPERATURE LIMITER
RESISTANCE FUSE (FUSED SPUR)
REMOVE FUSE FROM FUSED SPUR
RESISTANCE GAS VALVE
REMOVE ELECTRICAL CONNECTOR FROM GAS VALVE
VOLTAGE SOCKET AND SEE
{GAINPCBACS}
VOLTAGE LOW PRESSURE SENSOR - RETURN
{GAINPCBACS}
INSPECTION WATER PRESSURE SENSOR AND PUMP MANIFOLD
APPLIANCE DRAINED AND DISCHARGED
REMOVE THE WATER PRESSURE SENSOR FROM THE PUMP MANIFOLD
INSPECTION DIP SWITCHES
GAIN ACCESS TO THE DISPLAY PCB
RELEASE THE 2 CLIPS ON THE FACIA AND LOWER THE PANEL
INSPECTION WATER PRESSURE SENSOR AND PUMP MANIFOLD
APPLIANCE DRAINED AND DISCHARGED
REMOVE THE WATER PRESSURE SENSOR FROM THE PUMP MANIFOLD
RESISTANCE GAS VALVE - FUSE INVESTIGATION
REMOVE ELECTRICAL CONNECTOR FROM GAS VALVE
RESISTANCE APS (REST POSITION)
REMOVE THE LEADS FROM THE APS
RESISTANCE APS WITH TUBE DISCONNECTED
REMOVE THE LEADS FROM THE APS
DISCONNECT THE TUBE FROM THE APS
VOLTAGE SPARK GENERATOR AT PCB
{GAINPCBACS}
CH T
DISCONNECT EXTERNAL CONTROLS
REMOVE CONNECTOR 56 FROM THE PCB AND MAKE SAFE
ENSURE NO DEMANDS
RESISTANCE FLOW TEMPERATURE SENSOR
REMOVE CONNECTORS FROM THE FLOW SENSOR
INSPECTION WATER PRESSURE SENSOR AND PUMP MANIFOLD
APPLIANCE DRAINED AND DISCHARGED
REMOVE THE WATER PRESSURE SENSOR FROM THE PUMP MANIFOLD
INSPECTION WATER PRESSURE SENSOR AND PUMP MANIFOLD
APPLIANCE DRAINED AND DISCHARGED
REMOVE THE WATER PRESSURE SENSOR FROM THE PUMP MANIFOLD
RESISTANCE APS AND HARNESS (REST POSITION)
REMOVE CONNECTOR X8 FROM THE PCB
RESISTANCE APS (REST POSITION)
REMOVE THE LEADS FROM THE APS
RESISTANCE APS WITH TUBE DISCONNECTED
REMOVE THE LEADS FROM THE APS
DISCONNECT THE TUBE FROM THE APS
RESISTANCE FLOW SWITCH (0B FAULT CODE)
CH TEMPERATURE CONTROL TURNED TO MAX
DISCONNECT INLINE CONNECTOR TO FLOW SWITCH
INSPECTION WATER PRESSURE SENSOR AND PUMP MANIFOLD
APPLIANCE DRAINED AND DISCHARGED
REMOVE THE WATER PRESSURE SENSOR FROM THE PUMP MANIFOLD
VOLTAGE AT PUMP
CH TEMPERATURE CONTR
VOLTAGE PUMP AT PCB
{GAINPCBACS}
CH TEMPERATURE CONTROL SET TO MAX
REMOVE CONNECTOR 20 FROM THE PCB AND MAKE SAFE
VOLTAGE GAS VALVE AT PCB - SPARK GENERATOR DISCONNECTED
{GAINPCBACS}
CH T
AIR PRESSURE SWITCH PROVING
DISCONNECT LEADS FRO
RESISTANCE GAS VALVE
REMOVE ELECTRICAL CONNECTOR FROM GAS VALVE
VOLTAGE PUMP AT PCB
{GAINPCBACS}
CH TEMPERATURE CONTROL SET TO MAX
REMOVE CONNECTOR 20 FROM THE PCB AND MAKE SAFE
VOLTAGE DIGITAL PROGRAMMER - NO DEMAND
GAIN ACCESS TO THE D
VOLTAGE DIGITAL PROGRAMMER - CH DEMAND
GAIN ACCESS TO THE D
RESISTANCE FLOW TEMPERATURE SENSOR & HARNESS
REMOVE CONNECTOR X8 FROM THE PCB
RESISTANCE FLOW TEMPERATURE SENSOR
REMOVE CONNECTORS FROM THE FLOW SENSOR
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESET APPLIANCE - FAULT CODE F2
ENSURE NO DEMANDS ARE PRESENT
ENSURE BOILER IS COOL
VOLTAGE FAN ASSEMBLY (MAINS VOLTAGE)
{GAINPCBACS}
REMOVE CONNECTOR 100 FROM THE PCB AND MAKE SAFE
RESISTANCE FAN AND HARNESS - FUSE INVESTIGATION
REMOVE CONNECTOR 100 FROM THE PCB
RESISTANCE FAN - FUSE INVESTIGATION
REMOVE MAINS VOLTAGE CONNECTOR FROM THE FAN ASSEMBLY
RESISTANCE PUMP - FUSE INVESTIGATION
REMOVE WIRING CONNECTIONS AT PUMP
INSPECTION ELECTRODE
REMOVE ELECTRODE ASSEMBLY FROM THE BURNER DOOR
DISCONNECT LEAD FROM THE SPARK GENERATOR
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
INSPECTION ELECTRODE
REMOVE ELECTRODE ASSEMBLY FROM THE BURNER DOOR
DISCONNECT LEAD FROM THE SPARK GENERATOR
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESISTANCE FUSE PCB
REMOVE THE FUSE FROM THE PCB
INSPECTION EXPANSION VESSEL PRESSURE
GAIN ACCESS TO THE EXPANSION VESSEL
APPLIANCE DRAINED AND DISCHARGED
INSPECTION CONDENSATE SYPHON
GAIN ACCESS TO CONDENSATE SYPHON
INSPECTION CONDENSATE SYPHON
GAIN ACCESS TO CONDENSATE SYPHON
INSPECTION CONDENSATE SYPHON
GAIN ACCESS TO CONDENSATE SYPHON
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO GAS INLET PRESSURE TEST POINT
INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
REMOVE BURNER MODULE UNIT ASSEMBLY
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO GAS INLET PRESSURE TEST POINT
INSPECTION ELECTRODE
REMOVE ELECTRODE ASSEMBLY FROM THE BURNER DOOR
DISCONNECT LEAD FROM THE SPARK GENERATOR
OBSERVATION SPARKING OCCURS
DISCONNECT THE IGNIT
PRESSURE GAS INLET DROP
ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE INLET TEST POINT
RESISTANCE GAS VALVE AND HARNESS
REMOVE CONNECTOR 35 FROM THE PCB
APPLIANCE OUTPUT
SET APPLIANCE TO 100% OUTPUT
INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
REMOVE BURNER MODULE UNIT ASSEMBLY
INSPECTION CH CONTROL SPINDLE
GAIN ACCESS TO THE DISPLAY PCB
RELEASE THE 2 CLIPS ON THE FACIA AND LOWER THE PANEL
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO GAS INLET PRESSURE TEST POINT
RESISTANCE LOW PRESSURE SENSOR HARNESS
REMOVE CONNECTOR FROM THE LOW WATER PRESSURE SENSOR
OBSERVATION CH - OVERHEAT OCCUR
CH TEMPERATURE CONTROL TURNED TO MAX
OBSERVATION PUMP OVERRUN FOR OVERHEAT
CH TEMPERATURE CONTROL TURNED TO MAX
VOLTAGE LOW PRESSURE SENSOR - RETURN
{GAINPCBACS}
RESISTANCE LOW PRESSURE SENSOR HARNESS
REMOVE CONNECTOR FROM THE LOW WATER PRESSURE SENSOR
INSPECTION WATER PRESSURE SENSOR AND PUMP MANIFOLD
APPLIANCE DRAINED AND DISCHARGED
REMOVE THE WATER PRESSURE SENSOR FROM THE PUMP MANIFOLD
TEMPERATURE DIFFERENTIAL CH
CH TEMPERATURE CONTROL SET TO MAX
ATTACH TEMPERATURE CLAMPS TO THE FLOW AND RETURN PIPES
SYSTEM PRESSURE FURTHER INVESTIGATION
THE SYSTEM PRESSURE
INSPECTION FAN AND DAMPER
REMOVE BURNER MODULE ASSEMBLY AND SEPARATE FAN SECTION FROM BURNER DOOR ARM
BYPASS EXTERNAL CONTROLS
CH TEMPERATURE CONTR
RESISTANCE INTERNAL CLOCK / TIMESWITCH
GAIN ACCESS TO THE D
RESISTANCE FLOW SWITCH
CH TEMPERATURE CONTROL TURNED TO MAX
DISCONNECT INLINE CONNECTOR TO FLOW SWITCH
RESISTANCE FLOW SWITCH HARNESS
DISCONNECT INLINE CONNECTOR TO FLOW SWITCH
RESISTANCE FLOW TEMPERATURE SENSOR
REMOVE CONNECTORS FROM THE FLOW SENSOR
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
CH TEMPERATURE CONTROL SET TO MAX
REMOVE CONNECTOR 35 FROM THE PCB AND MAKE SAFE
INSPECTION ELECTRODE
REMOVE ELECTRODE ASSEMBLY FROM THE BURNER DOOR
DISCONNECT LEAD FROM THE SPARK GENERATOR
INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS / ELECTRODE
REMOVE BURNER MODULE UNIT ASSEMBLY
RESISTANCE SPARK GENERATOR
REMOVE THE LEADS FROM THE SPARK GENERATOR
INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS / ELECTRODE
REMOVE BURNER MODULE UNIT ASSEMBLY
RESISTANCE HARNESS SPARK GENERATOR
REMOVE CONNECTOR 54/11 FROM THE PCB
INSPECTION HOSE AND INTERNAL BYPASS
APPLIANCE DRAINED AND DISCHARGED
RESISTANCE APS AND HARNESS (REST POSITION)
REMOVE CONNECTOR X8 FROM THE PCB
INSPECTION APS TUBE
REMOVE APS TUBE
RESISTANCE HARNESS SPARK GENERATOR
REMOVE CONNECTOR 54/11 FROM THE PCB
INSPECTION ELECTRODE
REMOVE ELECTRODE ASSEMBLY FROM THE BURNER DOOR
DISCONNECT LEAD FROM THE SPARK GENERATOR
INSPECTION DIP SWITCHES
GAIN ACCESS TO THE DISPLAY PCB
RELEASE THE 2 CLIPS ON THE FACIA AND LOWER THE PANEL
OBSERVATION FLOW TEMPERATURE DISPLAYED (FROST PROTECTION)
ENSURE NO DEMANDS
TEMPERATURE FLOW PIPE (FROST PROTECTION)
ATTACH A TEMPERATURE CLAMP TO THE FLOW PIPE
RESISTANCE INTERNAL CLOCK / TIMESWITCH
GAIN ACCESS TO THE D
INSPECTION FAN AND DAMPER
REMOVE BURNER MODULE ASSEMBLY AND SEPARATE FAN SECTION FROM BURNER DOOR ARM
INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
REMOVE BURNER MODULE UNIT ASSEMBLY
AIR PRESSURE SWITCH PROVING
DISCONNECT LEADS FRO
RESISTANCE APS HARNESS
REMOVE CONNECTOR X8 FROM THE PCB
INSPECTION APS TUBE
REMOVE APS TUBE
INSPECTION GAS VALVE
REMOVE THE APS TUBE FROM THE GAS VALVE TEST POINT (OUT)
INSPECTION FAN AND DAMPER
REMOVE BURNER MODULE ASSEMBLY AND SEPARATE FAN SECTION FROM BURNER DOOR ARM
INSPECTION HEAT EXCHANGER FLUEWAYS
THE BURNER MODULE ASSEMBLY SHOULD ALREADY BE REMOVED FROM THE PREVIOUS TEST
INSPECTION APS TUBE
REMOVE APS TUBE
VOLTAGE DC STEPPER MOTOR PERMANENT AT PCB
{GAINPCBACS}
VOLTAGE DC STEPPER MOTOR PERMANENT AT PCB
{GAINPCBACS}
RESISTANCE HARNESS STEPPER MOTOR
REMOVE THE CONNECTOR FROM THE STEPPER MOTOR
RESISTANCE FLOW SWITCH HARNESS
DISCONNECT INLINE CONNECTOR TO FLOW SWITCH
OBSERVATION PUMP RUNS
CH TEMPERATURE CONTROL TURNED TO MAX
VOLTAGE DC STEPPER MOTOR PERMANENT AT PCB
{GAINPCBACS}
INSPECTION HOSE AND INTERNAL BYPASS
APPLIANCE DRAINED AND DISCHARGED
OBSERVATION DIVERTER MOVEMENT
APPLIANCE DRAINED AN
INSPECTION HOSE AND INTERNAL BYPASS
APPLIANCE DRAINED AND DISCHARGED
OBSERVATION DIVERTER MOVEMENT
APPLIANCE DRAINED AN
RESISTANCE APS HARNESS
REMOVE CONNECTOR X8 FROM THE PCB
RESISTANCE GAS VALVE AND HARNESS
REMOVE CONNECTOR 35 FROM THE PCB
INSPECTION APS TUBE
REMOVE APS TUBE
INSPECTION GAS VALVE
REMOVE THE APS TUBE FROM THE GAS VALVE TEST POINT (OUT)
INSPECTION FAN AND DAMPER
REMOVE BURNER MODULE ASSEMBLY AND SEPARATE FAN SECTION FROM BURNER DOOR ARM
INSPECTION HEAT EXCHANGER FLUEWAYS
THE BURNER MODULE ASSEMBLY SHOULD ALREADY BE REMOVED FROM THE PREVIOUS TEST
RESISTANCE HARNESS STEPPER MOTOR
REMOVE THE CONNECTOR FROM THE STEPPER MOTOR
VOLTAGE LS
{GAINPCBACS}
HW DEMAND
OBSERVATION DIVERTER MOVEMENT
APPLIANCE DRAINED AN
RESISTANCE HARNESS STEPPER MOTOR
REMOVE THE CONNECTOR FROM THE STEPPER MOTOR
RESISTANCE FLOW SWITCH MANUALLY MADE
APPLIANCE DRAINED AN
RESISTANCE FLOW SWITCH MANUALLY MADE
APPLIANCE DRAINED AN
VOLTAGE AT PUMP
CH TEMPERATURE CONTR
VOLTAGE DC STEPPER MOTOR PERMANENT AT PCB
{GAINPCBACS}
RESISTANCE HARNESS STEPPER MOTOR
REMOVE THE CONNECTOR FROM THE STEPPER MOTOR
OBSERVATION DIVERTER MOVEMENT
APPLIANCE DRAINED AN
INSPECTION INTERNAL BYPASS
APPLIANCE DRAINED AN
RESISTANCE FLOW TEMPERATURE SENSOR
REMOVE CONNECTORS FROM THE FLOW SENSOR
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
OBSERVATION PUMP RUNS
CH TEMPERATURE CONTROL TURNED TO MAX
RESISTANCE FLOW TEMPERATURE SENSOR
REMOVE CONNECTORS FROM THE FLOW SENSOR
PRESSURE STANDING RETURN
ATTACH PRESSURE GAUG
INSPECTION ELECTRODE
REMOVE ELECTRODE ASSEMBLY FROM THE BURNER DOOR
DISCONNECT LEAD FROM THE SPARK GENERATOR
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
VOLTAGE FAN CONTROL
REMOVE 1 X CONNECTOR
RESISTANCE FAN CONTROL HARNESS
REMOVE FAN CONTROL CONNECTOR FROM FAN ASSEMBLY
RESISTANCE POWER CABLE FAN ASSEMBLY
REMOVE CONNECTOR 100 FROM THE PCB
DISCONNECT THE FAN POWER CONNECTOR FROM THE FAN ASSEMBLY
RESISTANCE PUMP AND HARNESS - FUSE INVESTIGATION
REMOVE CONNECTOR 20 FROM THE PCB
RESISTANCE GAS VALVE AND HARNESS - FUSE INVESTIGATION
REMOVE CONNECTOR 35 FROM THE PCB
VOLTAGE MAINS POWER INPUT AT PCB
{GAINPCBACS}