Set Appliance State:
CH Demand
CH temperature control turned to MAX
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow the burner to ignite and run with a CH demand for 1 minute.
Remove the CH demand.
Does the pump continue to run for approximately 12 minutes ?
PUMP OVERRUN OPERATES AS ABOVE
PUMP OVERRUN DOES NOT OPERATE AS ABOVE
Remove the CH demand.
Does the pump continue to run for approximately 12 minutes ?
PUMP OVERRUN OPERATES AS ABOVE
PUMP OVERRUN DOES NOT OPERATE AS ABOVE