Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
S-PLAN FAULT FINDING GUIDE
GLOBALLY REPLACED
SPLAN FF
Z DUMMY TO CLOSE
SPLAN NO POWER TO PUMP - HOT WATER
FAULT IN WIRING TO PUMP
NO SUPPLY TO HOT WATER VALVE
240V NO SUPPLY TO GREY
NO SUPPLY TO GRAY - HEATING
240V NO SUPPLY TO GREY
SPLAN NO POWER TO PUMP - HEATING
FAULT IN WIRING TO PUMP
ON WITH NO DEMAND
FROST THERMOSTAT
MAINS TO HW BROWN WIRE
S PLAN WIRING FAULT
HW TO HOT
CYLINDER THERMOSTAT POSITION
MAINS FUSE
3 AMP MAIN FUSE
WIRING CENTRE TO TIMER FAULT
240V MAINS SUPPLY - TO TIMER
TIMER FAULTY 2
Z DUMMY TO CLOSE
NO VOLTAGE TO ROOM STAT WITH TIMER LINKED FOR ALL OFF
S-PLAN WIRING FAULT
TIMER FAULTY 1
Z DUMMY TO CLOSE
NO VOLTAGE TO CYL STAT WITH TIMER LINKED FOR ALL OFF
S-PLAN WIRING FAULT
NO CH AND HW
240V NO SUPPLY TO GREY
NO HOT WATER HEAT OK
SYNCHRON MOTOR
NO HEAT HW OK
SYNCHRON MOTOR
JAMMED - NO HW
SYNCHRON MOTOR
JAMMED - NO HEATING
SYNCHRON MOTOR
SPLAN NO HEATING - HOT WATER
SYNCHRON MOTOR
SPLAN NO HEATING
SYNCHRON MOTOR
SPLAN NO HEATING 2
TIMER
NO HOT WATER
TIMER
HEATING OK NO HOT WATER
MICROSWITCH
HOT WATER OK NO HEATING
MICROSWITCH
STUCK ON NO DEMAND - HEATING
MICROSWITCH
STUCK ON NO DEMAND - HEATING - NO PERM
MICROSWITCH
STUCK ON WITH NO DEMAND - HOT WATER - HAS PERM
MICROSWITCH
S-PLAN NOT HOT WATER
CYLINDER THERMOSTAT
SPLAN NO HEATING
ROOM THERMOSTAT
BODY PASSING ON HOT WATER
ZONE VALVE BODY
BODY PASSING ON HEATING
ZONE VALVE BODY
HEATING WITH NO DEMAND
TIMER
SPLAN NO HEATING
ZONE VALVE BODY
HEAD JAMMED - HEATING
HEATING ZONE VALVE ACTUATOR
WATER OK NO HEATING - ROOM STAT LINKED
S-PLAN WIRING FAULT
HEATING OK NO WATER - CYL STAT LINKED OUT
S-PLAN WIRING FAULT
SPLAN NO HEATING
TIMER
SHORT ON WIRE FROM SROST STAT
S-PLAN WIRING FAULT
SYNCHRON MOTOR AND ROOM STAT
SYNCHRON MOTOR AND ROOM THERMOSTAT
HOT WATER OK NO HEATING - POWER ON BROWN
ZONE VALVE BODY
HOT WATER OK NO HEAT - BODY STUCK 2
ZONE VALVE BODY
HOT WATER OK NO HEAT - NON RMV HEAD 2
ZONE VALVE JAMMED
HEATING NON REMOVE HEAD - ON WITH NO DEMAND
ZONE VALVE JAMMED
HEATING OK NO HOT WATER - NON RMV VALV1
ZONE VALVE BODY
HEATING OK NO HOT WATER - NON RMV VALV1
ZONE VALVE JAMMED
SYNCHRON MOTOR AND CYL STAT
SYNCHRON MOTOR AND CYLINDER THERMOSTAT
HEATING OK NO HOT WATER - NON RMV VALV2
ZONE VALVE BODY
HEAD JAMMED HOT WATER
HOT WATER ZONE VALVE ACTUATOR
BODY STUCK HOT WATER
ZONE VALVE BODY
HW NON REMOVE HEAD - ON WITH NO DEMAND
ZONE VALVE JAMMED
HOT WATER WITH NO DEMAND
TIMER
HOT WATER TO HOT
CYLINDER THERMOSTAT
NEITHER DEMAND WORKING
POWER SUPPLY (EXTERNAL)
NO HEAT OR HOT WATER
TIMER
NO HEAT OR HOT WATER
S-PLAN WIRING FAULT - TIMER TO WIRING CENTRE
ALL OFF
ROOM THERMOSTAT
ALL OFF - ROOM STAT LINKED
S-PLAN WIRING FAULT
SYNCRON AND ROOM STAT FOR ALL OFF
SYNCHRON MOTOR AND ROOM THERMOSTAT
ALL OFF - BODY STUCK 2
ZONE VALVE BODY
ALL OFF - BODY STUCK2
ZONE VALVE JAMMED
ALL OFF
CYLINDER THERMOSTAT
ALL OFF - CYL STAT LINKED OUT
S-PLAN WIRING FAULT
SYNCHRON MOTOR AND CYL STAT FOR ALL OFF
SYNCHRON MOTOR AND CYLINDER THERMOSTAT
ALL OFF - BODY STUCK 1
ZONE VALVE BODY
ALL OFF - BODY STUCK1
ZONE VALVE JAMMED
CH AND HW
FAULT IN WIRING TO PUMP
NO HOT WATER MOTOR OK
S PLAN WIRING FAULT
NO HEAT HW OK
S PLAN WIRING FAULT
HEATING OK NO HOT WATER - NON RMV VALV2
ZONE VALVE JAMMED
HOT WATER OK NO HEATING - NON REMV HEAD
ZONE VALVE JAMMED
HEAD JAMMED HOT WATER 2
HOT WATER ZONE VALVE ACTUATOR
HEAD JAMMED - HEATING 2
HEATING ZONE VALVE ACTUATOR
NO VOLTAGE TO CYL STAT WITH TIMER LINKED
S-PLAN WIRING FAULT
HEAT OK - NO HW
TIMER AND SYNCHRON MOTOR
NO VOLTAGE TO ROOM STAT WITH TIMER LINKED
S-PLAN WIRING FAULT
HW OK - NO HEATING
TIMER AND SYNCHRON MOTOR
HEAT OK - NO HW
TIMER & ZONE VALVE BODY
HEAT OK - NO HW
TIMER & ZONE VALVE JAMMED
HOT WATER OK NO HEAT
TIMER & ZONE VALVE JAMMED
HOT WATER OK NO HEAT
TIMER & ZONE VALVE BODY
STUCK ON WITH NO DEMAND
BOILER
MICROSWITCH FAULTY - HOT WATER
HOT WATER ZONE VALVE ACTUATOR
MICROSWITCH FAULTY - HEATING
HEATING ZONE VALVE ACTUATOR
MICROSWITCH STUCK ON WITH NO DEMAND
HEATING ZONE VALVE ACTUATOR
MICROSWITCH STUCK - HOT WATER ON WITH NO DEMAND
HOT WATER ZONE VALVE ACTUATOR
MICROSWITCH STUCK - HOT WATER ON WITH NO DEMAND 2
HOT WATER ZONE VALVE ACTUATOR
VOLTAGE STILL NOT PRESENT AT BROWN WIRE
CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT
VOLTAGE OK BUT VALVE NOT MOVING
CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT
VOLTAGE OK BUT VALVE NOT MOVING
CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT
VOLTAGE STILL NOT PRESENT AT BROWN WIRE
CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT
HEAD SPRINGS BACK WHEN REMOVED
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS)
VALVE HEAD IS NOT REMOVEABLE
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS)
VALVE SPINDLE IS STUCK
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
HEAD OF THE VALVE IS NOT REMOVEABLE
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
VALVE SPINDLE IS STUCK
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
HEAD OF THE VALVE IS NOT REMOVEABLE
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
VALVE SPINDLE IS STUCK
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
HEAD OF THE VALVE IS NOT REMOVEABLE
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
VALVE SPINDLE IS STUCK
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
HEAD OF THE VALVE IS NOT REMOVEABLE
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
HOT WATER VALVE IS NOT CLOSED WITH NO HW DEMAND
CHARACTERISTIC TEST FROM IS HOT WATER COMMING ON ALL TIME OR ONLY WITH HEATING DEMAND
HOT WATER VALVE CLOSED AND CYLINDER CIRCS REMAIN COOL WITH CH DEMAND
CHARACTERISTIC TEST FROM IS HOT WATER COMMING ON ALL TIME OR ONLY WITH HEATING DEMAND
HEAD SPRINGS BACK WHEN REMOVED
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS)
VALVE HEAD IS NOT REMOVEABLE
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS)
NEITHER VALVE OPENS
CHARACTERISTIC TEST FROM LINK OUT TIMER - BOTH
HEATING VALVE OPENS BUT HOT WATER VALVE REMAINS CLOSED
CHARACTERISTIC TEST FROM LINK OUT TIMER - BOTH
HOT WATER VALVE OPENS BUT HEATING REMAINS CLOSED
CHARACTERISTIC TEST FROM LINK OUT TIMER - BOTH
VOLTAGE OK BUT VALVE NOT MOVING
CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT
VOLTAGE STILL NOT PRESENT AT BROWN WIRE
CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT
VALVE SPINDLE IS STUCK
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
HEAD OF THE VALVE IS NOT REMOVEABLE
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
VOLTAGE OK BUT VALVE NOT MOVING
CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT
VOLTAGE STILL NOT PRESENT AT BROWN WIRE
CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT
VALVE SPINDLE IS STUCK
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
HEAD OF THE VALVE IS NOT REMOVEABLE
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
VOLTAGE STILL NOT PRESENT AT BROWN WIRE
CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT
VOLTAGE OK BUT VALVE NOT MOVING
CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT
VALVE SPINDLE IS STUCK
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
HEAD OF THE VALVE IS NOT REMOVEABLE
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
VOLTAGE OK BUT VALVE NOT MOVING
CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT
VOLTAGE STILL NOT PRESENT AT BROWN WIRE
CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT
VALVE SPINDLE IS STUCK
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
HEAD OF THE VALVE IS NOT REMOVEABLE
CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE
14/12/2020 09:59:14 2011_1_50_1 04/01/2021 14:12:40
14/12/2020 16:41:14
HOT WATER ZONE VALVE OPERATION
LOCATE AND IDENTIFY
VOLTAGE ON BROWN WIRE
IDENTIFY THE HOT WATER ZONE VALVE ELECTRICAL LEAD AND TERMINAL CONNECTIONS USED
VOLTAGE CYLINDER THERMOSTAT COMMON
SET THE CYLINDER THERMOSTAT TO ITS MAXIMUM POSITION
REMOVE COVER FROM CYLINDER THERMOSTAT
VOLTAGE ON GREY WIRE
LOCATE THE GREY WIRES IN THE WIRING CENTRE
VOLTAGE TO PUMP
REMOVE COVER FROM THE PUMP WIRING BOX.
HEATING ZONE VALVE OPERATION
LOCATE AND IDENTIFY
VOLTAGE ON GREY WIRE
LOCATE THE GREY WIRES IN THE WIRING CENTRE
VOLTAGE TO PUMP
REMOVE COVER FROM THE PUMP WIRING BOX.
VOLTAGE ON BROWN WIRE
IDENTIFY THE HEATING ZONE VALVE ELECTRICAL LEAD AND TERMINAL CONNECTIONS USED
VOLTAGE ROOM THERMOSTAT COMMON
REMOVE COVER FROM THE ROOM THERMOSTAT
FROST THERMOSTAT CHECK
{ALLDEMANDOFF}
AS
DISCONNECT HEATING VALVE ORANGE
DISCONNECT AND MAKE SAFE THE ORANGE WIRE FROM THE HEATING ZONE VALVE IN THE WIRING CENTRE
LINK OUT TIMER - HOT WATER
REMOVE THE PROGRAMME
LINK OUT TIMER - HEATING
REMOVE THE PROGRAMME
OBSERVATION ZONE VALVES-NO CH AND HW OPERATION
LOCATE AND IDENTIFY
MAINS POWER INTO SYSTEM
GAIN ACCESS TO THE MAINS INPUT CONNECTIONS IN THE WIRING CENTER
IDENTIFY THE MAIN LIVE TERMINAL
RESISTANCE 3AMP FUSE
REMOVE FUSE FROM FUSED SPUR
VOLTAGE TO PUMP - CH AND HW
REMOVE COVER FROM THE PUMP WIRING BOX.
VOLTAGE ON ORANGE WIRE - NO CH AND HW
LOCATE THE ORANGE WIRES IN THE WIRING CENTRE
RESISTANCE SYNCHRON MOTOR
REMOVE THE COVER FROM THE VALVE
REMOVE THE SYNCHRON MOTOR FROM THE VALVE
RESISTANCE SYNCHRON MOTOR
REMOVE THE COVER FROM THE VALVE
REMOVE THE SYNCHRON MOTOR FROM THE VALVE
REMOVE TIMER
{ALLDEMANDOFF}
RE
RESISTANCE END FEED MICROSWITCH - HEATING
NOTE: THIS TE
RESISTANCE END FEED MICROSWITCH - HOT WATER
NOTE: THIS TE
RESISTANCE END FEED MICROSWITCH - HOT WATER
NOTE: THIS TE
VOLTAGE ON ORANGE WIRE
LOCATE THE ORANGE WIRES IN THE WIRING CENTRE
LINK OUT CYLINDER THERMOSTAT
PLACE A LINK BETWEEN
PUMP RUNNING - HOT WATER
IF POSSIBLE REMOVE T
VOLTAGE ON ORANGE WIRE
LOCATE THE ORANGE WIRES IN THE WIRING CENTRE
PUMP RUNNING - NO HEATING
IF POSSIBLE REMOVE T
LINK OUT ROOM THERMOSTAT
PLACE A WIRE LINK BE
REMOVE TIMER
{ALLDEMANDOFF}
RE
INSPECTION CYLINDER THERMOSTAT
LOCATE CYLINDER THERMOSTAT
ISOLATE POWER AND LOOK FOR VALVE SPRING BACK
{ALLDEMANDOFF}
HOT WATER RESPONDS TO TIMER
{ALLDEMANDOFF}
RE
PUMP RUNNING - NO CH AND HW
IF POSSIBLE REMOVE T
MAINS SUPPLY TO TIMER
REMOVE THE PROGRAMMER FROM ITS BACKPLATE.
LINK OUT TIMER
REMOVE THE PROGRAMME
VOLTAGE ROOM THERMOSTAT COMMON
REMOVE COVER FROM THE ROOM THERMOSTAT
LINK OUT ROOM THERMOSTAT
PLACE A WIRE LINK BE
VOLTAGE CYLINDER THERMOSTAT COMMON
SET THE CYLINDER THERMOSTAT TO ITS MAXIMUM POSITION
REMOVE COVER FROM CYLINDER THERMOSTAT
LINK OUT CYLINDER THERMOSTAT
PLACE A LINK BETWEEN
RESISTANCE BROWN WIRE TO BLUE - HW
IDENTIFY THE HOT WATER ZONE VALVE ELECTRICAL LEAD AND TERMINAL CONNECTIONS USED
RESISTANCE BROWN WIRE TO BLUE - HEATING
IDENTIFY THE HEATING ZONE VALVE ELECTRICAL LEAD AND TERMINAL CONNECTIONS USED
MECHANICAL CHECK SYNCHRON MOTOR
REMOVE THE COVER FROM THE VALVE
REMOVE THE SYNCHRON MOTOR FROM THE VALVE
MECHANICAL CHECK SYNCHRON MOTOR
REMOVE THE COVER FROM THE VALVE
REMOVE THE SYNCHRON MOTOR FROM THE VALVE
MECHANICAL CHECK SYNCHRON MOTOR
REMOVE THE COVER FROM THE VALVE
REMOVE THE SYNCHRON MOTOR FROM THE VALVE
MECHANICAL CHECK SYNCHRON MOTOR
REMOVE THE COVER FROM THE VALVE
REMOVE THE SYNCHRON MOTOR FROM THE VALVE
VOLTAGE ON BROWN WIRE
IDENTIFY THE HEATING ZONE VALVE ELECTRICAL LEAD AND TERMINAL CONNECTIONS USED
VOLTAGE ON BROWN WIRE
IDENTIFY THE HOT WATER ZONE VALVE ELECTRICAL LEAD AND TERMINAL CONNECTIONS USED
DISCONNECT HOT WATER VALVE ORANGE - DOES DEMAND STOP
DISCONNECT AND MAKE SAFE THE ORANGE WIRE FROM THE HOT WATER ZONE VALVE IN THE WIRING CENTRE
RESISTANCE END FEED MICROSWITCH - HOT WATER
NOTE: THIS TE
RESISTANCE END FEED MICROSWITCH - HEATING
NOTE: THIS TE
System Information
- Total Tests: 217
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control