Set Appliance State:
Mains Power Off
CH Demand
Locate and identify the heating zone valve.
Ensure the room thermostat is turned to its max position.
Ensure the room thermostat is turned to its max position.
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Inspect the Indicator lever on the side of the valve, at rest with no demand the lever should be in the A position.
Once a demand is placed the valve should open moving the lever to the B position.
Does the valve operate as described?
Once a demand is placed the valve should open moving the lever to the B position.
Does the valve operate as described?