BIASI ADVANCE 25/30/35 C
GLOBALLY REPLACED
OBSERVATION BOILER INITIALISATION
BOILER IN CH AND DHW MODE, NO DEMANDS
TYPE OF DIAGNOSTIC PROCEDURE
PLEASE SELECT FROM O
OBSERVATION DHW DEMAND RECOGNISED
FLOW RATE SET TO 3 LITRES A MIN
BOILER DHW THERMOSTAT SET TO MAX
OBSERVATION FAN RUNS
BOILER DHW THERMOSTAT SET TO MAX
OBSERVATION BURNER IGNITES AND ESTABLISHES
BOILER DHW THERMOSTAT SET TO MAX
PERFORMANCE ANALYSIS
BOILER IN SERVICE MODE
OPERATION DHW
BOILER DHW SETTING TO MAX
REFIT DIVERTER VALVE MOTOR
OBSERVATION CH DEMAND RECOGNISED
USER CONTROL SET TO
OBSERVATION PREHEAT OPERATION
BOILER DHW THERMOSTAT SET TO MAX
OBSERVATION ANTI CYCLE DELAY
BOILER CH THERMOSTAT SET TO 50°C
PRESSURE GAS INLET PRIMARY TEST
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
REMOVE THE DIVERTER VALVE MOTOR
OPERATION CH
BOILER CH THERMOSTAT SET TO MAX
IMPORTANT NOTES FOR THIS APPLIANCE PLEASE READ THOROUGHLY
THIS APPLIANCE INCOR
HEADER FOR FUSE FURTHER INVESTIGATION
INTENTIONALLY BLANK HEADER FOR FUSE INVESTIGATION
HEADER FOR E04
INTENTIONALLY BLANK FAULT CODE HEADER
HEADER FOR E05
INTENTIONALLY BLANK FAULT CODE HEADER
HEADER FOR E06 AND E12
INTENTIONALLY BLANK FAULT CODE HEADER
HEADER FOR E07
INTENTIONALLY BLANK FAULT CODE HEADER
HEADER FOR E08
INTENTIONALLY BLANK FAULT CODE HEADER
HEADER FOR E09
INTENTIONALLY BLANK FAULT CODE HEADER
HEADER FOR E10
INTENTIONALLY BLANK FAULT CODE HEADER
HEADER FOR OVERHEAT INVESTIGATION E02, E13, E14, L01
INTENTIONALLY BLANK FAULT CODE HEADER
HEADER FOR E69
INTENTIONALLY BLANK FAULT CODE HEADER
HEADER FOR E19
INTENTIONALLY BLANK FAULT CODE HEADER
HEADER FOR E99
INTENTIONALLY BLANK FAULT CODE HEADER
SERVICE MODE INFORMATION PAGE
THE 🔧 SYMBOL
HEADER FOR E25 AND E11
BLANK
E10 FAULT CODE
FLUE TEMPERATURE PROBE NTC - SAFETY THERMAL FUSE (THERMISTOR COMPONENT)
E10 FAULT CODE
MANIFOLD - AIR
E10 FAULT CODE
AIR BOX ASSEMBLY
E10 FAULT CODE
CONDENSATE TRAP OR PIPEWORK
DIVERTER VALVE SECTION BLOWING FUSES
CABLE - 230V ELECTRICITY SUPPLY
BLOWING FUSES FAN SECTION
CABLE - 230V ELECTRICITY SUPPLY
BLANK FOR COMBUSTION MODE PAGE
Z DIRECTION CHOICE OR CONTINUE
IGNITES BUT DOES NOT ESTABLISH
CONDENSATE TRAP OR PIPEWORK
OVERPRESSURING ON CH
VESSEL - EXPANSION
OPEN CIRCUIT
THERMOSTAT 105 DEG C OVERHEAT
NOT SUPPLYING POWER TO DIVERTER FOR DHW FOR OVERHEAT
MAIN ELECTRONIC CONTROL - IGNITION PCB
POWER TO DIVTERTER VALVE DHW FOR OVERHEAT
CABLE - 230V ELECTRICITY SUPPLY
OVERHEAT INVESTIGATION
PROBE SPRING MOUNTING TEMPERATURE - FLOW
PUMP NOT RUNNING
CABLE - 230V ELECTRICITY SUPPLY
BOILER TO TEMP RADS COLD
TAP 3/4 IN - CH
BLANK FOR FAULT CODES 2
Z DIRECTION CHOICE OR CONTINUE
WEAK NOISY CH
PUMP
BLANK FOR SERVICE INDICATOR
Z DIRECTION CHOICE OR CONTINUE
DHW TOO COOL
FLUE TEMPERATURE PROBE NTC - SAFETY THERMAL FUSE (THERMISTOR COMPONENT)
DHW HOT AND COLD
FLUE TEMPERATURE PROBE NTC - SAFETY THERMAL FUSE (THERMISTOR COMPONENT)
HOLDING FAN OFF
TEMPERATURE PROBE - OUTLET
MAINS FUSE
FUSE MAINS
PUMP NOT RUNNING OVERHEAT
CABLE - 230V ELECTRICITY SUPPLY
PUMP OVERRUN FOR OVERHEATING
MAIN ELECTRONIC CONTROL - IGNITION PCB
OVERHEATING
KIT - BY-PASS
NO POWER TO PUMP
MAIN ELECTRONIC CONTROL - IGNITION PCB
NO POWER TO PUMP OVERHEAT
MAIN ELECTRONIC CONTROL - IGNITION PCB
E10 FAULT CODE
BURNER
E10 FAULT CODE
FLUE
FUSE F1 MAIN PCB
FUSE F1 MAIN PCB
BAFFLING
CONDENSATE TRAP OR PIPEWORK
BAFFLING
MANIFOLD - AIR
IGNITES BUT BAFFLES
AIR BOX ASSEMBLY
BAFFLING
BURNER
BAFFLING
CONDENSING HEAT EXCHANGER
NOT ESTABLISHING
AIR BOX ASSEMBLY
NOT RECTIFYING
BURNER
NOT ESTABLISHING
ELECTRODE DETECTION AND BURNER GAP
TO FLOW TURBINE
SENSORS - CABLE
NO POWER TO DISPLAY
WIRING - PCB - MAIN ELECTRONIC CONTROL TO - PCB (DISPLAY)
E09 FAULT CODE
FLUE TEMPERATURE PROBE NTC - SAFETY THERMAL FUSE (FUSE PART)
BLOWING FUSES - PUMP
CABLE - 230V ELECTRICITY SUPPLY
NOT TRANSMITTING CH DEMAND
CABLE - 230V ELECTRICITY SUPPLY
POWER NOT GETTING TO TERMINAL STRIP FROM DISPLAY
CABLE - 230V ELECTRICITY SUPPLY
NOT RECOGNISING CH DEMAND
CABLE - DUMMY JUMPER / CLOCK
NOT TRANSMITTING CH DEMAND 2
CABLE - 230V ELECTRICITY SUPPLY
POWER NOT GETTING TO TERMINAL STRIP FROM DISPLAY 2
CABLE - 230V ELECTRICITY SUPPLY
NOT RECOGNISING CH DEMAND 2
CABLE - DUMMY JUMPER / CLOCK
FROM INCOMING TERMINAL TO MAIN PCB
CABLE - 230V ELECTRICITY SUPPLY
NOT TRANSMITTING CH DEMAND 3
CABLE - 230V ELECTRICITY SUPPLY
POWER NOT GETTING TO TERMINAL STRIP FROM DISPLAY 3
CABLE - 230V ELECTRICITY SUPPLY
NOT RECOGNISING CH DEMAND 3
CABLE - DUMMY JUMPER / CLOCK
NOT TRANSMITTING CH DEMAND 4
CABLE - 230V ELECTRICITY SUPPLY
POWER NOT GETTING TO TERMINAL STRIP FROM DISPLAY 4
CABLE - 230V ELECTRICITY SUPPLY
NOT RECOGNISING CH DEMAND 4
CABLE - DUMMY JUMPER / CLOCK
NOT TRANSMITTING CH DEMAND 5
CABLE - 230V ELECTRICITY SUPPLY
POWER NOT GETTING TO TERMINAL STRIP FROM DISPLAY 5
CABLE - 230V ELECTRICITY SUPPLY
NOT RECOGNISING CH DEMAND 5
CABLE - DUMMY JUMPER / CLOCK
TAP OPEN OR DHW DRAW OFF OPEN
TAP OPEN OR DHW DRAW OFF OPEN
FIRING NO DEMAND
FLOW SWITCH - MAGNETIC (FLOW TURBINE)
DEMAND WHEN SHOULDNT BE
SWITCH - FLOW - DHW
FOR FROST PROTECTION
PROBE SPRING MOUNTING TEMPERATURE - FLOW
POSSIBLY FAULTY
FROST THERMOSTAT
FIRING WITH NO CH DEMAND
MAIN ELECTRONIC CONTROL - IGNITION PCB
DHW COOL RADS COOL
EXTERNAL MIXING
NOT SENSING PRESSURE
SWITCH - PRESSURE - PRIMARY CIRCUIT
E04 FAULT CODE
SENSORS - CABLE
NOT FULLY OPEN
TAP 1/2 IN - DHW
DHW FLOW RATE
WATER SUPPLY
FAULT CODE 020
WATER INGRESS
E25 AND E11 - INCORRECTLY READING FAULT
MAIN ELECTRONIC CONTROL - IGNITION PCB
E25 AND E11 - SENDING VOLTAGE TO GAS VALVE AFTER DEMAND
MAIN ELECTRONIC CONTROL - IGNITION PCB
BLOWING FUSES GAS VALVE SECTION
CABLE - 230V ELECTRICITY SUPPLY
INCORRECT FAN PRESSURE
CONDENSATE TRAP OR PIPEWORK
TO GAS VALVE
CABLE - 230V ELECTRICITY SUPPLY
GAS VALVE NOT OPENING
COIL UNIT - GAS VALVE SIT
NO DROP
FLUE
PRESSURES CORRECT BUT NOT LIGHTING
ELECTRODE - IGNITION
INCORRECT FAN PRESSURE
MANIFOLD - AIR
NOT IGNITING
AIR BOX ASSEMBLY
BLANK FOR CASE OFF
Z DIRECTION CHOICE OR CONTINUE
INCORRECT FAN PRESSURE
CONDENSING HEAT EXCHANGER
NOT IGNITING
ELECTRODE - IGNITION AND BURNER GAP
PERFORMANCE TEST FAIL
MANIFOLD - AIR
PERFORMANCE TEST FAIL
AIR BOX ASSEMBLY
PERFORMANCE TEST FAIL
BURNER
PERFORMANCE TEST FAIL
CONDENSING HEAT EXCHANGER
FUSE F2 MAIN PCB
FUSE F2 MAIN PCB
UNABLE TO ADJUST TO CORRECT SETTINGS
GAS VALVE
IGNITES BUT BAFFLES OUT
GAS RESTRICTOR
NO IGNITION - NO DROP
GAS RESTRICTOR
NO IGNITION WITH DROP
GAS RESTRICTOR
FAN SUPPLY E05 FAULT CODE
CABLE - 230V ELECTRICITY SUPPLY
DC FAN SECTION E05 FAULT CODE
SENSORS - CABLE
DC FAN SECTION RUNNING CONTINUALLY 3 E05 FAULT CODE
SENSORS - CABLE
NO PERMANENT DC TO FAN E05 FAULT CODE
MAIN ELECTRONIC CONTROL - IGNITION PCB
E05 FAN RUNNING WITH DEMAND
SENSORS - CABLE
E08
PCB - OUTDOOR PARAMETER
E08
OUTDOOR SENSOR
KEEPING BOILER TEMP TOO LOW - NO SENSOR
MAIN ELECTRONIC CONTROL - IGNITION PCB
KEEPING BOILER TEMP TOO LOWE08
OUTDOOR SENSOR
BAFFLING AT IGNITION
FLUE
PERFORMANCE ANALYSIS
GAS RESTRICTOR
BLANK FOR TYPE OF DIAGNOSTICS
Z DIRECTION CHOICE OR CONTINUE
NO PERMANENT VOLTAGE TO FLOW TURBINE
MAIN ELECTRONIC CONTROL - IGNITION PCB
TO FLOW TURBINE NOT RECOGNISING DEMAND
SENSORS - CABLE
NOT SPINNING FREELY
FLOW SWITCH - MAGNETIC (FLOW TURBINE)
HOLDING FAN OFF
PROBE SPRING MOUNTING TEMPERATURE - FLOW
IGNITION ELECTRODE AND LEAD
ELECTRODE - IGNITION
RECTIFICATION LEAD
SENSORS - CABLE
NOT RECTIFYING
ELECTRODE DETECTION
IGNITES BUT DOES NOT ESTABLISH
GAS INLET PRESSURE
IGNITES BUT BAFFLES OUT
GAS INLET PRESSURE
NOT SUPPLYING POWER TO DIVERTER FOR DHW
MAIN ELECTRONIC CONTROL - IGNITION PCB
POWER TO DIVTERTER VALVE DHW
CABLE - 230V ELECTRICITY SUPPLY
DHW TOO HOT
TEMPERATURE PROBE - OUTLET
DHW TOO COOL
TEMPERATURE PROBE - OUTLET
DHW TOO COOL
PROBE SPRING MOUNTING TEMPERATURE - FLOW
WEAK CAUSING NOISY
PUMP
DHW TOO COOL DHW HOT AND COLD
TEMPERATURE PROBE - OUTLET
DHW HOT AND COLD
PROBE SPRING MOUNTING TEMPERATURE - FLOW
NOT PREHEATING PROPERLY
MAIN ELECTRONIC CONTROL - IGNITION PCB
OVERRUNS NOT WORKING
MAIN ELECTRONIC CONTROL - IGNITION PCB
ANTI CYCLE DELAY
MAIN ELECTRONIC CONTROL - IGNITION PCB
UNSATISFACTORY AT MAXIMUM LOAD
GAS INLET PRESSURE
NOT SENDING POWER TO DIVERTER ON CH
MAIN ELECTRONIC CONTROL - IGNITION PCB
POWER TO DIVERTER VALVE CH
CABLE - 230V ELECTRICITY SUPPLY
NOT OPENING TO RADS
KIT - DIVERTER VALVE
OPEN WHEN SHOLDNT BE CAUSING RADS NOT TO HEAT
KIT - BY-PASS
KEEPING BOILER TEMP TOO LOW
PROBE SPRING MOUNTING TEMPERATURE - FLOW
BOILER NOISY ON CH
TAP 3/4 IN - CH
NOISY BOILER ON CH
KIT - BY-PASS
FOR SAFETY WARNING
Z DIRECTION CHOICE OR CONTINUE
BLOWING FUSES
COIL UNIT - GAS VALVE SIT
E06 FAULT CODE
PROBE SPRING MOUNTING TEMPERATURE - FLOW
E07 FAULT CODE
TEMPERATURE PROBE - OUTLET
E09 FAULT CODE
FLUE TEMPERATURE PROBE NTC - SAFETY THERMAL FUSE (THERMISTOR COMPONENT)
E69 FAULT CODE
MAIN ELECTRONIC CONTROL - IGNITION PCB
E19 FAULT CODE
MAIN ELECTRONIC CONTROL - IGNITION PCB
BLANK FOR BOILER CONFIGURATION
Z DIRECTION CHOICE OR CONTINUE
E10 FAULT CODE
MAIN ELECTRONIC CONTROL - IGNITION PCB
FUSE BLOWN
MAIN ELECTRONIC CONTROL - IGNITION PCB - FUSE INVESTIGATION
BLOWING FUSES
ACTUATOR DIVERTER VALVE
BLOWING FUSES
FAN
BLOCKED
PIPE - CONNECTION EXPANSION VESSEL
NOT RESETTING FROM OVERHEAT
MAIN ELECTRONIC CONTROL - IGNITION PCB
OVERHEAT STAT SECTION
SENSORS - CABLE
NOT MOVING TO DHW POSITION FOR OVERHEAT
ACTUATOR DIVERTER VALVE
BLANK FOR FAULT CODES
Z DIRECTION CHOICE OR CONTINUE
FAULTY WINDINGS
PUMP
DHW TOO COOL
MAIN ELECTRONIC CONTROL - IGNITION PCB
RESTRICTED OR BLOCKED LOW DHW TEMP
HEAT EXCHANGER DHW
RESTRICTED CAUSING POOR DHW
CONDENSING HEAT EXCHANGER
DHW TOO COOL DHW HOT AND COLD
MAIN ELECTRONIC CONTROL - IGNITION PCB
RESTRICTED OR BLOCKED DHW HOT AND COLD
HEAT EXCHANGER DHW
DHW HOT AND COLD
CONDENSING HEAT EXCHANGER
E06 AND E12 FAULT CODE
MAIN ELECTRONIC CONTROL - IGNITION PCB
BLANK FOR MAINS FUSE FURTHER INVESTIGATION
Z DIRECTION CHOICE OR CONTINUE
RESTRICTED OR BLOCKED LOW DHW TEMPOVERHEAT INVESTIGATION
HEAT EXCHANGER DHW
RESTRICTED CAUSING POOR DHWOVERHEAT INVESTIGATION
CONDENSING HEAT EXCHANGER
BLANK FOR OVERHEAT SECTION
Z DIRECTION CHOICE OR CONTINUE
OUT OF CALIBRATION
THERMOSTAT 105 DEG C OVERHEAT
NOT SHUTTING DOWN AT TEMP
MAIN ELECTRONIC CONTROL - IGNITION PCB
BLANK FOR FUSE F1 MAIN PCB INVESTIGATION
Z DIRECTION CHOICE OR CONTINUE
E10 FAULT CODE
CONDENSING HEAT EXCHANGER
ADJUSTED INCORRECTLY BAFFLING
GAS VALVE
NOT RECOGNISING RECTIFICATION
MAIN ELECTRONIC CONTROL - IGNITION PCB
MAKING DISPLAY BLANK
SWITCH - FLOW - DHW
PCB DISPLAY
CONTROL PANEL ELECTRONIC PCB
PCB MAIN
MAIN ELECTRONIC CONTROL - IGNITION PCB
E09 FAULT CODE
SENSORS - CABLE
BLOWING FUSES
PUMP
NO POWER TO CH CIRCUIT
MAIN ELECTRONIC CONTROL - IGNITION PCB
NOT RECOGNISING CH DEMAND
MAIN ELECTRONIC CONTROL - IGNITION PCB
NOT SENDING CH DEMAND TO MAIN PCB
CONTROL PANEL ELECTRONIC PCB
NOT SENDING TIMER DEMAND TO MAIN PCB
CONTROL PANEL ELECTRONIC PCB
NO POWER TO CH CIRCUIT 2
MAIN ELECTRONIC CONTROL - IGNITION PCB
NOT RECOGNISING CH DEMAND 2
MAIN ELECTRONIC CONTROL - IGNITION PCB
NOT SENDING CH DEMAND TO MAIN PCB 2
CONTROL PANEL ELECTRONIC PCB
NOT SENDING TIMER DEMAND TO MAIN PCB 2
CONTROL PANEL ELECTRONIC PCB
NO POWER TO CH CIRCUIT 3
MAIN ELECTRONIC CONTROL - IGNITION PCB
NOT RECOGNISING CH DEMAND 3
MAIN ELECTRONIC CONTROL - IGNITION PCB
NOT SENDING CH DEMAND TO MAIN PCB 3
CONTROL PANEL ELECTRONIC PCB
NOT SENDING TIMER DEMAND TO MAIN PCB 3
CONTROL PANEL ELECTRONIC PCB
NO POWER TO CH CIRCUIT 4
MAIN ELECTRONIC CONTROL - IGNITION PCB
NOT RECOGNISING CH DEMAND 4
MAIN ELECTRONIC CONTROL - IGNITION PCB
NOT SENDING CH DEMAND TO MAIN PCB 4
CONTROL PANEL ELECTRONIC PCB
NOT SENDING TIMER DEMAND TO MAIN PCB 4
CONTROL PANEL ELECTRONIC PCB
NO POWER TO CH CIRCUIT 5
MAIN ELECTRONIC CONTROL - IGNITION PCB
NOT RECOGNISING CH DEMAND 5
MAIN ELECTRONIC CONTROL - IGNITION PCB
NOT SENDING CH DEMAND TO MAIN PCB 5
CONTROL PANEL ELECTRONIC PCB
NOT SENDING TIMER DEMAND TO MAIN PCB 5
CONTROL PANEL ELECTRONIC PCB
FIRING WITH NO DEMAND
MAIN ELECTRONIC CONTROL - IGNITION PCB
CORRECTLY ACTIVATED
FROST PROTECTION
INCORRECTLY ACTIVATING FROST PROTECTION
MAIN ELECTRONIC CONTROL - IGNITION PCB
FIRING NO FROST PROTECTION DEMAND
MAIN ELECTRONIC CONTROL - IGNITION PCB
E04 FAULT CODE
MAIN ELECTRONIC CONTROL - IGNITION PCB
LOW FLOW RATE
HEAT EXCHANGER DHW
RESTRICTING FLOW
LIMITER - FLOW 10 LITRES/MIN
RESTRICTED OR BLOCKED
FLOW SWITCH - MAGNETIC (FILTER)
RESTRICTED BLOCKED OR JAMMED
FLOW SWITCH - MAGNETIC (FLOW TURBINE)
E25 AND E11 - STUCK IN FAULT
MAIN ELECTRONIC CONTROL - IGNITION PCB
E25 AND E11
ELECTRODE DETECTION
E25 AND E11 - READING FLAME AFTER CUTOFF
MAIN ELECTRONIC CONTROL - IGNITION PCB
E25 AND E11 - NOT SHUTTING
GAS VALVE
SPARKS BUT DOES NOT IGNITE
GAS INLET PRESSURE
NO POWER TO GAS VALVE
MAIN ELECTRONIC CONTROL - IGNITION PCB
NOT LIGHTING WRONG MIX
GAS VALVE
BLANK FOR FUSE F2 MAIN PCB INVESTIGATION
Z DIRECTION CHOICE OR CONTINUE
FAILING PERFORMANCE TEST
COMBUSTION ADJUSTMENT
MECHANICALLY FAILED
GAS VALVE
E05 NOT RUNNING
FAN
NO AC POWER TO FAN E05 FAULT CODE
MAIN ELECTRONIC CONTROL - IGNITION PCB
NO DC DEMAND E05 FAULT CODE
MAIN ELECTRONIC CONTROL - IGNITION PCB
FAN RUNNING CONTINUOUSLY 2 E05 FAULT CODE
MAIN ELECTRONIC CONTROL - IGNITION PCB
E05 FAN RUNNING WITH DEMAND
MAIN ELECTRONIC CONTROL - IGNITION PCB
E04
PRESSURE GAUGE
E04
SYSTEM PRESSURE
NOISH CH
SYSTEM PRESSURE
NOISY CH
PRESSURE GAUGE
NOISY KETTLING ON DHW
SYSTEM PRESSURE
NOISY DHW
PRESSURE GAUGE
OVERHEAT INVESTIGATION
SYSTEM PRESSURE
OVERHEAT
PRESSURE GAUGE
E08 - NO SENSOR
MAIN ELECTRONIC CONTROL - IGNITION PCB
E08 - WITH SENSOR
MAIN ELECTRONIC CONTROL - IGNITION PCB
E08
SENSORS - CABLE
KEEPING BOILER TEMP TOO LOW - WITH SENSOR
MAIN ELECTRONIC CONTROL - IGNITION PCB
HOLDING FAN OFF
MAIN ELECTRONIC CONTROL - IGNITION PCB
E05 - NEUTRAL FAULT
MAIN ELECTRONIC CONTROL - IGNITION PCB
NOT RECOGNISING DHW DEMAND
MAIN ELECTRONIC CONTROL - IGNITION PCB
NOT RECOGNISING DEMAND
SWITCH - FLOW - DHW
NOT SPARKING
MAIN ELECTRONIC CONTROL - IGNITION PCB
PASSING TO RADS ON HW
KIT - DIVERTER VALVE
NOT MOVING TO DHW POSITION
ACTUATOR DIVERTER VALVE
DHW TOO HOT
MAIN ELECTRONIC CONTROL - IGNITION PCB
BOILER NOISY
HEAT EXCHANGER DHW
NOISY ON DHW
CONDENSING HEAT EXCHANGER
NO GOING TO CH POSITION
ACTUATOR DIVERTER VALVE
ALLOWING BOILER TO GET TOO HOT
MAIN ELECTRONIC CONTROL - IGNITION PCB
RESTRICTED BLOCKED CAUSING CH NOISE
CONDENSING HEAT EXCHANGER
E06 FAULT CODE
SENSORS - CABLE
E07 FAULT CODE
MAIN ELECTRONIC CONTROL - IGNITION PCB
E07 FAULT CODE
SENSORS - CABLE
E09 FAULT CODE
MAIN ELECTRONIC CONTROL - IGNITION PCB
BLANK FOR CONFIGURATION 2
Z DIRECTION CHOICE OR CONTINUE
SYSTEM PRESSURE RISES EXCESSIVELY
CHARACTERISTIC TEST FROM OPERATION CH
BOILER FIRES WITH NO DEMAND OR PUMP RUNNING CONTINUOUSLY
CHARACTERISTIC TEST FROM OBSERVATION BOILER INITIALISATION
FAULT CODE SHOWN
CHARACTERISTIC TEST FROM OBSERVATION BOILER INITIALISATION
DISPLAY ILLUMINATED WITH NO FAULT CODE SHOWING BUT FAN DOES NOT RUN
CHARACTERISTIC TEST FROM OBSERVATION BOILER INITIALISATION
DISPLAY DOES NOT ILLUMINATE
CHARACTERISTIC TEST FROM OBSERVATION BOILER INITIALISATION
DIFFERENTIAL STILL EXCESSIVE
CHARACTERISTIC TEST FROM DIFFERENTIAL TEMPERATURE PRIMARY HEAT EXCHANGER
BOILER DOES NOT RESPOND TO CENTRAL HEATING DEMAND
CHARACTERISTIC TEST FROM DIFFERENTIAL TEMPERATURE PRIMARY HEAT EXCHANGER
DIFFERENTIAL STILL EXCESSIVE
CHARACTERISTIC TEST FROM DIFFERENTIAL TEMPERATURE PRIMARY HEAT EXCHANGER
BOILER DOES NOT RESPOND TO CENTRAL HEATING DEMAND
CHARACTERISTIC TEST FROM DIFFERENTIAL TEMPERATURE PRIMARY HEAT EXCHANGER
DIFFERENTIAL STILL EXCESSIVE
CHARACTERISTIC TEST FROM DIFFERENTIAL TEMPERATURE PRIMARY HEAT EXCHANGER
BOILER DOES NOT RESPOND TO CENTRAL HEATING DEMAND
CHARACTERISTIC TEST FROM DIFFERENTIAL TEMPERATURE PRIMARY HEAT EXCHANGER
BOILER OVERHEATS BEFORE 90 DEGREES
CHARACTERISTIC TEST FROM OBSERVATION DOES OVERHEAT OCCUR AT MAX TEMP?
BOILER CONTINUES TO HEAT PAST 90 DEGREES
CHARACTERISTIC TEST FROM OBSERVATION DOES OVERHEAT OCCUR AT MAX TEMP?
VOLTAGE IS NOT PRESENT ON PIN 5 (BUT PRESENT ON PIN 9)
CHARACTERISTIC TEST FROM VOLTAGE DISPLAY PCB TO MAIN PCB (CH DEMAND)
VOLTAGE IS NOT PRESENT ON PIN 9
CHARACTERISTIC TEST FROM VOLTAGE DISPLAY PCB TO MAIN PCB (CH DEMAND)
VOLTAGE IS NOT PRESENT ON PIN 5 (BUT PRESENT ON PIN 9)
CHARACTERISTIC TEST FROM VOLTAGE DISPLAY PCB TO MAIN PCB (CH DEMAND)
VOLTAGE IS NOT PRESENT ON PIN 9
CHARACTERISTIC TEST FROM VOLTAGE DISPLAY PCB TO MAIN PCB (CH DEMAND)
VOLTAGE IS NOT PRESENT ON PIN 5 (BUT PRESENT ON PIN 9)
CHARACTERISTIC TEST FROM VOLTAGE DISPLAY PCB TO MAIN PCB (CH DEMAND)
VOLTAGE IS NOT PRESENT ON PIN 9
CHARACTERISTIC TEST FROM VOLTAGE DISPLAY PCB TO MAIN PCB (CH DEMAND)
VOLTAGE IS NOT PRESENT ON PIN 5 (BUT PRESENT ON PIN 9)
CHARACTERISTIC TEST FROM VOLTAGE DISPLAY PCB TO MAIN PCB (CH DEMAND)
VOLTAGE IS NOT PRESENT ON PIN 9
CHARACTERISTIC TEST FROM VOLTAGE DISPLAY PCB TO MAIN PCB (CH DEMAND)
VOLTAGE IS NOT PRESENT ON PIN 5 (BUT PRESENT ON PIN 9)
CHARACTERISTIC TEST FROM VOLTAGE DISPLAY PCB TO MAIN PCB (CH DEMAND)
VOLTAGE IS NOT PRESENT ON PIN 9
CHARACTERISTIC TEST FROM VOLTAGE DISPLAY PCB TO MAIN PCB (CH DEMAND)
AF SHOWING ON DISPLAY
CHARACTERISTIC TEST FROM OBSERVATION WHAT IS SHOWING ON DISPLAY
bP SHOWING ON DISPLAY
CHARACTERISTIC TEST FROM OBSERVATION WHAT IS SHOWING ON DISPLAY
DHW DEMAND SHOWING ON DISPLAY
CHARACTERISTIC TEST FROM OBSERVATION WHAT IS SHOWING ON DISPLAY
FLOW LIMITER RESTRICTED OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION TURBINE, FILTER AND FLOW LIMITER
FILTER RESTRICTED OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION TURBINE, FILTER AND FLOW LIMITER
TURBINE RESTRICTED, BLOCKED OR JAMMED
CHARACTERISTIC TEST FROM INSPECTION TURBINE, FILTER AND FLOW LIMITER
PUMP AND FAN RUN BUT SPARKING DOES NOT OCCUR THEN FAULT REAPPEARS
CHARACTERISTIC TEST FROM OBSERVATION BOILER RESET - FALSE FLAME
FAULT CODE REAPPEARS WITHOUT PUMP OR FAN RUNNING
CHARACTERISTIC TEST FROM OBSERVATION BOILER RESET - FALSE FLAME
GAS INLET PRESSURE UNSATISFACTORY
CHARACTERISTIC TEST FROM PRESSURE GAS INLET AND DROP
GAS INLET PRESSURE DOES NOT DIP DURING SPARKING
CHARACTERISTIC TEST FROM PRESSURE GAS INLET AND DROP
PRESSURE LOW OR AIR IN SYSTEM
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND AIR
PRESSURE OK BUT DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND AIR
PRESSURE LOW OR AIR IN SYSTEM
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND AIR
PRESSURE OK BUT DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND AIR
PRESSURE LOW OR AIR IN SYSTEM
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND AIR
PRESSURE OK BUT DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND AIR
FAN RUNS CONTINUOUSLY
CHARACTERISTIC TEST FROM OBSERVATION BOILER INITIALISATION
PRESSURE LOW OR AIR IN SYSTEM
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND AIR
PRESSURE OK BUT DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND AIR
SPARKING DOES NOT OCCUR
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
SPARKING OCCURS BUT BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
BURNER IGNITES BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
BURNER IGNITES BUT BAFFLES OUT
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
DHW TOO HOT
CHARACTERISTIC TEST FROM OPERATION DHW
DHW TOO COOL RADS REMAIN COOL WITH NO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION DHW
DHW TOO COOL AND RADS BEGIN TO HEAT WITH NO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION DHW
BOILER NOISY (KETTLING)
CHARACTERISTIC TEST FROM OPERATION DHW
DHW RUNS HOT AND COLD
CHARACTERISTIC TEST FROM OPERATION DHW
BOILER STILL NOISY
CHARACTERISTIC TEST FROM OBSERVATION OPERATION CH (NOISY)
BOILER DOES NOT RESPOND TO CH DEMAND
CHARACTERISTIC TEST FROM OBSERVATION OPERATION CH (NOISY)
BOILER UP TO TEMP RADS COLD
CHARACTERISTIC TEST FROM OPERATION CH
BOILER AND SYSTEM TEMPERATURE LOW
CHARACTERISTIC TEST FROM OPERATION CH
BOILER NOISY
CHARACTERISTIC TEST FROM OPERATION CH
DIFFERENTIAL INCORRECT OR LOCAL NOISE
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER FOR CH NOISY
DIFFERENTIAL OK SYSTEM NOISE
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER FOR CH NOISY
11/09/2019 09:39:48 1907_3_50_1 07/10/2019 10:56:11
12/09/2019 09:17:24
RESISTANCE THERMISTOR FLUE
DISCONNECT PLUG FOR THERMAL FUSE / FLUE THERMISTOR
INSPECTION AIR INTAKE TUBE
REMOVE AIR INTAKE TUBE
RESISTANCE HARNESS DIVERTER VALVE
REMOVE CONNECTOR CN4 FROM THE MAIN PCB
REMOVE THE CONNECTOR FROM THE DIVERTER VALVE
OBSERVATION RESET APPLIANCE - OVERHEAT
ALLOW APPLIANCE TO COOL
RESISTANCE OVERHEAT THERMOSTAT AND HARNESS
REMOVE CONNECTOR CN6 FROM THE MAIN PCB
RESISTANCE OVERHEAT THERMOSTAT
REMOVE THE CONNECTORS (BLACK WIRES) FROM THE OVERHEAT THERMOSTAT
VOLTAGE TO DIVERTER VALVE (DHW)
{GAINPCBACS}
DIFFERENTIAL TEMPERATURE PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE P
RESISTANCE FUSE MAINS
REMOVE THE MAINS FUSE FROM ITS HOLDER
DIFFERENTIAL TEMPERATURE PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE P
DIFFERENTIAL TEMPERATURE PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE P
RESISTANCE HARNESS FLOW TURBINE
REMOVE CONNECTOR CN12 FROM THE MAIN PCB
REMOVE THE CONNECTOR FROM THE FLOW TURBINE ASSEMBLY
RESISTANCE HARNESS FLAT DISPLAY PCB
DISCONNECT CONNECTOR CN8 FROM THE MAIN PCB
DISCONNECT CONNECTOR CN2 FROM THE DISPLAY PCB
RESISTANCE HARNESS MAIN PCB TO DISPLAY PCB (MAINS)
REMOVE CONNECTOR CN15 FROM THE MAIN PCB
REMOVE CONNECTOR CN4 FROM THE DISPLAY PCB
RESISTANCE HARNESS MAIN PCB TO DISPLAY PCB (MAINS)
REMOVE CONNECTOR CN15 FROM THE MAIN PCB
REMOVE CONNECTOR CN4 FROM THE DISPLAY PCB
RESISTANCE HARNESS MAIN PCB TO DISPLAY PCB (MAINS)
REMOVE CONNECTOR CN15 FROM THE MAIN PCB
REMOVE CONNECTOR CN4 FROM THE DISPLAY PCB
RESISTANCE HARNESS MAIN PCB TO DISPLAY PCB (MAINS)
REMOVE CONNECTOR CN15 FROM THE MAIN PCB
REMOVE CONNECTOR CN4 FROM THE DISPLAY PCB
VOLTAGE EXTERNAL CONTROLS RECEIVE AT DISPLAY PCB
GAIN ACCESS TO DISPLAY PCB CONNECTIONS
RESISTANCE HARNESS MAIN PCB TO DISPLAY PCB (MAINS)
REMOVE CONNECTOR CN15 FROM THE MAIN PCB
REMOVE CONNECTOR CN4 FROM THE DISPLAY PCB
RESISTANCE THERMISTOR FLOW
REMOVE CONNECTOR FROM FLOW THERMISTOR
OBSERVATION BOILER RESET - FALSE FLAME
ALLOW APPLIANCE TO COOL
RESISTANCE HARNESS GAS VALVE
REMOVE CONNECTOR CN2 FROM THE MAIN PCB
REMOVE THE GAS VALVE CONNECTOR
INSPECTION AIR INTAKE TUBE
REMOVE AIR INTAKE TUBE
VOLTAGE AC FAN AT FAN
NO DEMANDS
RESISTANCE HARNESS FAN AC
REMOVE CONNECTOR CN2 FROM THE MAIN PCB
REMOVE THE AC FAN CONNECTOR (3 WIRE) FROM THE FAN
RESISTANCE HARNESS FAN DC
REMOVE CONNECTOR CN5 FROM THE MAIN PCB
REMOVE THE FAN DC CONNECTOR (4 WIRE) FROM THE FAN
RESISTANCE OUTDOOR SENSOR
GAIN ACCESS TO MAIN
VOLTAGE FLOW TURBINE DEMAND
{GAINPCBACS}
EASE CONNECTOR SLIGHTLY OFF THE PCB TO EXPOSE TEST POINT
VOLTAGE FLOW TURBINE PERMANENT
{GAINPCBACS}
RESISTANCE THERMISTOR FLOW
REMOVE CONNECTOR FROM FLOW THERMISTOR
VOLTAGE TO DIVERTER VALVE (DHW)
{GAINPCBACS}
VOLTAGE TO DIVERTER VALVE (CH)
{GAINPCBACS}
RESISTANCE PUMP AND HARNESS FOR FUSE INVESTIGATION
REMOVE CONNECTOR CN2 FROM THE INTERFACE PCB
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR CN2 FROM THE MAIN PCB
REMOVE THE CONNECTION FROM THE PUMP ASSEMBLY
RESISTANCE HARNESS FAN AC
REMOVE CONNECTOR CN2 FROM THE MAIN PCB
REMOVE THE AC FAN CONNECTOR (3 WIRE) FROM THE FAN
OBSERVATION SYSTEM PRESSURE AND AIR
NO DEMANDS
RESISTANCE THERMISTOR FLOW AND HARNESS
REMOVE CONNECTOR CN6 FROM THE MAIN PCB
RESISTANCE THERMISTOR FLOW
REMOVE CONNECTOR FROM FLOW THERMISTOR
RESISTANCE THERMISTOR DHW AND HARNESS
REMOVE CONNECTOR CN12 FROM THE MAIN PCB
RESISTANCE THERMISTOR DHW
REMOVE CONNECTOR FROM DHW THERMISTOR
RESISTANCE THERMISTOR FLUE, THERMAL FUSE AND HARNESS
REMOVE CONNECTOR CN11 FROM THE MAIN PCB
RESISTANCE THERMISTOR FLUE
DISCONNECT PLUG FOR THERMAL FUSE / FLUE THERMISTOR
RESISTANCE HARNESS FAN DC
REMOVE CONNECTOR CN5 FROM THE MAIN PCB
REMOVE THE FAN DC CONNECTOR (4 WIRE) FROM THE FAN
INSPECTION AIR BOX ASSEMBLY
REMOVE THE AIR TUBE FROM THE AIR BOX'S AIR INTAKE
RESISTANCE DIVERTER VALVE MOTOR AND HARNESS
REMOVE CONNECTOR CN4 FROM THE MAIN PCB
PRESSURE EXPANSION VESSEL
RELEASE PRIMARY HEATING CIRCUIT PRESSURE
OBSERVATION DIVERTER VALVE MOTOR SPINDLE DHW
REMOVE THE DIVERTER VALVE HEAD FROM THE DIVERTER VALVE BODY
RESISTANCE HARNESS DIVERTER VALVE
REMOVE CONNECTOR CN4 FROM THE MAIN PCB
REMOVE THE CONNECTOR FROM THE DIVERTER VALVE
RESISTANCE THERMISTOR FLOW
REMOVE CONNECTOR FROM FLOW THERMISTOR
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR CN2 FROM THE MAIN PCB
REMOVE THE CONNECTION FROM THE PUMP ASSEMBLY
OBSERVATION SYSTEM PRESSURE AND AIR
NO DEMANDS
OBSERVATION SYSTEM PRESSURE AND AIR
NO DEMANDS
RESISTANCE THERMISTOR FLUE
DISCONNECT PLUG FOR THERMAL FUSE / FLUE THERMISTOR
DIFFERENTIAL TEMPERATURE DHW HEAT EXCHANGER
ATTACH TEMPERATURE P
VOLTAGE MAINS POWER
{GAINPCBACS}
RESISTANCE THERMISTOR FLUE
DISCONNECT PLUG FOR THERMAL FUSE / FLUE THERMISTOR
DIFFERENTIAL TEMPERATURE DHW HEAT EXCHANGER
ATTACH TEMPERATURE P
RESISTANCE THERMISTOR DHW
REMOVE CONNECTOR FROM DHW THERMISTOR
OBSERVATION SYSTEM PRESSURE AND AIR
NO DEMANDS
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR CN2 FROM THE MAIN PCB
REMOVE THE CONNECTION FROM THE PUMP ASSEMBLY
INSPECTION BYPASS INTERNAL
BOILER PRIMARY CIRCU
RESISTANCE FUSE F1 MAIN PCB
REMOVE FUSE F1 FROM THE MAIN PCB
DIFFERENTIAL TEMPERATURE DHW FOR OVERHEAT INVESTIGATION
ATTACH TEMPERATURE P
OBSERVATION DOES OVERHEAT OCCUR AT MAX TEMP?
BOILER CH THERMOSTAT SET TO MAX
ATTACH TEMPERATURE PROBES AS PER THE RED ARROWS
RESISTANCE FUSE F2 MAIN PCB
REMOVE FUSE F2 FROM THE MAIN PCB
INSPECTION BURNER
REMOVE THE FAN & BUR
INSPECTION AIR INTAKE TUBE
REMOVE AIR INTAKE TUBE
INSPECTION AIR BOX ASSEMBLY
REMOVE THE AIR TUBE FROM THE AIR BOX'S AIR INTAKE
INSPECTION BURNER
REMOVE THE FAN & BUR
INSPECTION FLUEWAYS
REMOVE FAN AND BURNER ASSEMBLY
INSPECTION AIR BOX ASSEMBLY
REMOVE THE AIR TUBE FROM THE AIR BOX'S AIR INTAKE
INSPECTION BURNER
REMOVE THE FAN & BUR
INSPECTION FLAME RECTIFICATION ELECTRODE AND BURNER GAP
REMOVE COMBUSTION DOOR ASSEMBLY COMPLETE WITH BURNER
OBSERVATION FLOW TURBINE DISCONNECTION
REMOVE CONNECTOR CN12 FROM THE PCB AND MAKE SAFE
NO DEMANDS
VOLTAGE DISPLAY PCB AT HARNESS
UNCLIP DISPLAY PCB AND WEDGE IN POSITION AS SHOWN
NO DEMANDS
VOLTAGE EXTERNAL CONTROLS RECEIVE AT DISPLAY PCB
GAIN ACCESS TO DISPLAY PCB CONNECTIONS
VOLTAGE DISPLAY PCB TO MAIN PCB (CH DEMAND)
UNCLIP AND FLIP DISPLAY PCB OVER THEN SECURE IT IN PLACE WITH A SCREW AS SHOWN
RESISTANCE HARNESS DISPLAY PCB TO TERMINAL STRIP
REMOVE CONNECTOR CN5 FROM THE DISPLAY PCB
RESISTANCE HARNESS CLOCK / LINK
DISCONNECT CN1 FROM THE DISPLAY PCB
RESISTANCE HARNESS MAINS INTO PCB
REMOVE CONNECTOR CN1 FROM THE MAIN PCB
VOLTAGE EXTERNAL CONTROLS RECEIVE AT DISPLAY PCB
GAIN ACCESS TO DISPLAY PCB CONNECTIONS
VOLTAGE DISPLAY PCB TO MAIN PCB (CH DEMAND)
UNCLIP AND FLIP DISPLAY PCB OVER THEN SECURE IT IN PLACE WITH A SCREW AS SHOWN
RESISTANCE HARNESS DISPLAY PCB TO TERMINAL STRIP
REMOVE CONNECTOR CN5 FROM THE DISPLAY PCB
RESISTANCE HARNESS CLOCK / LINK
DISCONNECT CN1 FROM THE DISPLAY PCB
VOLTAGE EXTERNAL CONTROLS RECEIVE AT DISPLAY PCB
GAIN ACCESS TO DISPLAY PCB CONNECTIONS
VOLTAGE DISPLAY PCB TO MAIN PCB (CH DEMAND)
UNCLIP AND FLIP DISPLAY PCB OVER THEN SECURE IT IN PLACE WITH A SCREW AS SHOWN
RESISTANCE HARNESS DISPLAY PCB TO TERMINAL STRIP
REMOVE CONNECTOR CN5 FROM THE DISPLAY PCB
RESISTANCE HARNESS CLOCK / LINK
DISCONNECT CN1 FROM THE DISPLAY PCB
VOLTAGE EXTERNAL CONTROLS RECEIVE AT DISPLAY PCB
GAIN ACCESS TO DISPLAY PCB CONNECTIONS
VOLTAGE DISPLAY PCB TO MAIN PCB (CH DEMAND)
UNCLIP AND FLIP DISPLAY PCB OVER THEN SECURE IT IN PLACE WITH A SCREW AS SHOWN
RESISTANCE HARNESS DISPLAY PCB TO TERMINAL STRIP
REMOVE CONNECTOR CN5 FROM THE DISPLAY PCB
RESISTANCE HARNESS CLOCK / LINK
DISCONNECT CN1 FROM THE DISPLAY PCB
VOLTAGE DISPLAY PCB TO MAIN PCB (CH DEMAND)
UNCLIP AND FLIP DISPLAY PCB OVER THEN SECURE IT IN PLACE WITH A SCREW AS SHOWN
RESISTANCE HARNESS DISPLAY PCB TO TERMINAL STRIP
REMOVE CONNECTOR CN5 FROM THE DISPLAY PCB
RESISTANCE HARNESS CLOCK / LINK
DISCONNECT CN1 FROM THE DISPLAY PCB
VOLTAGE EXTERNAL CONTROLS AT TERMINAL STRIP FIRING WITH NO DEMAND
GAIN ACCESS TO THE APPLIANCE TERMINAL STRIP
NO DEMANDS
VOLTAGE FROST THERMOSTAT
GAIN ACCESS TO THE APPLIANCE TERMINAL STRIP
NO DEMANDS
OBSERVATION ISOLATE DHW
TURN DHW ISOLATION OFF
OBSERVATION REMOVE FLOW SENSOR ASSEMBLY
REMOVE THE FLOW SENS
OBSERVATION REMOVE FLOW SENSOR CONNECTOR
NO DEMANDS
REMOVE THE CONNECTOR FROM THE FLOW SENSOR
ASSEMBLY AND MAKE SAFE
RESISTANCE PRESSURE SWITCH
DISCONNECT LEADS FROM WATER PRESSURE SWITCH
RESISTANCE HARNESS PRESSURE SWITCH
REMOVE CONNECTOR CN10 FROM THE PCB
REMOVE WIRES FROM PRESSURE SWITCH
INSPECTION TURBINE, FILTER AND FLOW LIMITER
ISOLATE THE COLD MAI
OBSERVATION FLAME SHUT OFF DELAY
ENSURE NO CH DEMAND
INSPECTION PCB AND CONNECTIONS
{GAINPCBACS}
OBSERVATION DISCONNECT RECTIFICATION LEAD
DISCONNECT RECTIFICATION LEAD FROM INLINE CONNECTOR AND MAKE SAFE
RESISTANCE HARNESS GAS VALVE
REMOVE CONNECTOR CN2 FROM THE MAIN PCB
REMOVE THE GAS VALVE CONNECTOR
PRESSURE GAS INLET AND DROP
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
RESISTANCE GAS VALVE SOLENOID
REMOVE THE CONNECTOR FROM THE GAS VALVE
INSPECTION IGNITION ELECTRODE AND LEAD
REMOVE THE IGNITION ELECTRODE AND LEAD ASSEMBLY
INSPECTION AIR INTAKE TUBE
REMOVE AIR INTAKE TUBE
INSPECTION AIR BOX ASSEMBLY
REMOVE THE AIR TUBE FROM THE AIR BOX'S AIR INTAKE
INSPECTION BURNER
REMOVE THE FAN & BUR
INSPECTION FLUEWAYS
REMOVE FAN AND BURNER ASSEMBLY
INSPECTION IGNITION ELECTRODE AND BURNER GAP
REMOVE FAN AND BURNER ASSEMBLY
INSPECTION AIR BOX ASSEMBLY
REMOVE THE AIR TUBE FROM THE AIR BOX'S AIR INTAKE
INSPECTION BURNER
REMOVE THE FAN & BUR
INSPECTION FLUEWAYS
REMOVE FAN AND BURNER ASSEMBLY
OBSERVATION CAN COMBUSTION BE ADJUSTED
BOILER IN SERVICE MODE
INSPECTION GAS RESTRICTOR
UNDO NUT AT TOP OF GAS VALVE
INSPECTION GAS RESTRICTOR
UNDO NUT AT TOP OF GAS VALVE
INSPECTION GAS RESTRICTOR
UNDO NUT AT TOP OF GAS VALVE
OBSERVATION DISCONNECT FAN (DC)
UNPLUG 4 WIRE CONNECTOR FROM FAN
VOLTAGE DC DEMAND AT FAN
RECONNECT 4 WIRE CONNECTOR AT FAN IF YOU HAVE NOT ALREADY DONE SO
NO DEMANDS
RESISTANCE HARNESS FAN DC
REMOVE CONNECTOR CN5 FROM THE MAIN PCB
REMOVE THE FAN DC CONNECTOR (4 WIRE) FROM THE FAN
VOLTAGE DC FAN PERMANENT AT FAN
NO DEMANDS
RESISTANCE OUTDOOR SENSOR AND HARNESS
REMOVE CONNECTOR CN12 FROM THE MAIN PCB
RESISTANCE OUTDOOR SENSOR AND HARNESS
REMOVE CONNECTOR CN12 FROM THE MAIN PCB
INSPECTION GAS RESTRICTOR
UNDO NUT AT TOP OF GAS VALVE
RESISTANCE HARNESS FLOW TURBINE
REMOVE CONNECTOR CN12 FROM THE MAIN PCB
REMOVE THE CONNECTOR FROM THE FLOW TURBINE ASSEMBLY
INSPECTION FLOW TURBINE
ISOLATE COLD MAINS TO APPLIANCE AND DRAIN AND DISCHARGE DHW CIRCUIT
INSPECTION IGNITION ELECTRODE AND LEAD
REMOVE THE IGNITION ELECTRODE AND LEAD ASSEMBLY
INSPECTION RECTIFICATION ELECTRODE AND LEAD
REMOVE THE RECTIFICA
RESISTANCE HARNESS RECTIFICATION
REMOVE CONNECTOR T2 FROM THE MAIN PCB
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
RESISTANCE THERMISTOR DHW
REMOVE CONNECTOR FROM DHW THERMISTOR
RESISTANCE THERMISTOR DHW
REMOVE CONNECTOR FROM DHW THERMISTOR
OBSERVATION DIVERTER VALVE MOTOR SPINDLE DHW
REMOVE THE DIVERTER VALVE HEAD FROM THE DIVERTER VALVE BODY
OBSERVATION OPERATION CH (NOISY)
BOILER CH THERMOSTAT SET TO MAX
INTERNAL TIMER TURNED ON / SET TO ON PERIOD (IF FITTED)
RESISTANCE HARNESS DIVERTER VALVE
REMOVE CONNECTOR CN4 FROM THE MAIN PCB
REMOVE THE CONNECTOR FROM THE DIVERTER VALVE
RESISTANCE THERMISTOR FLOW
REMOVE CONNECTOR FROM FLOW THERMISTOR
RESISTANCE THERMISTOR DHW
REMOVE CONNECTOR FROM DHW THERMISTOR
RESISTANCE THERMISTOR FLOW
REMOVE CONNECTOR FROM FLOW THERMISTOR
OBSERVATION DIVERTER VALVE MOTOR SPINDLE CH
REMOVE THE DIVERTER VALVE HEAD FROM THE DIVERTER VALVE BODY
INSPECTION DIVERTER VALVE BODY
REMOVE DIVERTER VALVE MOTOR FROM THE DIVERTER VALVE BODY
RESISTANCE HARNESS DIVERTER VALVE
REMOVE CONNECTOR CN4 FROM THE MAIN PCB
REMOVE THE CONNECTOR FROM THE DIVERTER VALVE
INSPECTION BYPASS INTERNAL
BOILER PRIMARY CIRCU
RESISTANCE THERMISTOR FLOW
REMOVE CONNECTOR FROM FLOW THERMISTOR
INSPECTION BYPASS INTERNAL
BOILER PRIMARY CIRCU
DIFFERENTIAL PRIMARY HEAT EXCHANGER FOR CH NOISY
BOILER CH THERMOSTAT
RESISTANCE GAS VALVE FOR FUSE INVESTIGATION
REMOVE THE CONNECTOR FROM THE GAS VALVE
RESISTANCE FAN AND HARNESS FOR FUSE INVESTIGATION
REMOVE CONNECTOR CN2 FROM THE MAIN PCB
RESISTANCE THERMAL FUSE
DISCONNECT PLUG FOR THERMAL FUSE / FLUE THERMISTOR