Set Appliance State:
Gas Off
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Attach pressure gauge to the inlet pressure test point
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Monitor the gas inlet pressure as boiler carries out its ignition sequence.
Inlet pressure should remain above 17mb NG, 25mb LPG throughout and during the sparking stage there should be a noticeable dip in pressure (indicating the gas valve has opened).
Note:
When pressure gauge is removed the pressure test point should be tightened and checked for gas tightness.
Inlet pressure should remain above 17mb NG, 25mb LPG throughout and during the sparking stage there should be a noticeable dip in pressure (indicating the gas valve has opened).
Note:
When pressure gauge is removed the pressure test point should be tightened and checked for gas tightness.