XSol Diagnostic System

Interactive Test Sequence Navigator

Welcome to the XSol Diagnostic System

This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.

Start Diagnostic Sequence

or choose a specific test below:

VOKERA 20 / 80 R.S. FLOWMATIC.

GC NUMBER 47 094 07<

Next: &18, *

HOT WATER

DHW THERMOSTAT TO MAX
MODE SELECTOR SWITCH TO SUMMER
HOT WATER TAP ON

Next: &nff, ?98, ?100

DHW MODULATION

{ISOLATEMAINSPOWER}<

Next: &1, f95

DHW HIGH FLAME

{ISOLATEMAINSPOWER}<

Next: &2, f92

DHW FAN HIGH SPEED

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO SUMMER
TURN HOT WATER TAP ON

Next: &3, f89

HW DEMAND

{ISOLATEMAINSPOWER}

Next: &4, f84

PUMP OVERRUN

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO CONSTANT

Next: &5, !f83

CENTRAL HEATING

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO CONSTANT
HEATING THERMOSTAT TO MAX

Next: &6, ?79, ?81

CH MODULATION

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO CONSTANT
HEATING THERMOSTAT TO MAX

Next: &7, f76

CH LOW FLAME

{ISOLATEMAINSPOWER}<

Next: &8, f71

CH HIGH FLAME

{ISOLATEMAINSPOWER}<

Next: &9, ?49, ?51

CH FAN HIGH SPEED

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO CONSTANT

Next: &10, f370

SLOW FAN

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO SUMMER

Next: &11, f19

PILOT FLAME FAILURE

{ISOLATEMAINSPOWER}

Next: &12, !f18

PILOT ESTABLISHED

{ISOLATEMAINSPOWER}

Next: &13, f13

IGNITE PILOT

{ISOLATEMAINSPOWER}

Next: &14, f10

SYSTEM CHECKS.

{ISOLATEMAINSPOWER}

Next: &115, !f2

VOKERA 20 / 80 R.S. FLOWMATIC

{ISOLATEMAINSPOWER}<

Next: &17, !f1

ELECTRODE SPARKING

{ISOLATEMAINSPOWER}

Next: &15, f116

ELECTRICAL SAFETY CHECKS

ELECTRICAL SAFETY CHECKS

Next: End

PILOT BURNER ASSEMBLY

PILOT BURNER ASSEMBLY

Next: End

PIEZO SPARK UNIT EARTH

EARTH FOR PIEZO IGNITER

Next: End

ELECTRODE LEAD

SPARK ELECTRODE LEAD

Next: End

THERMOCOUPLE

THERMOCOUPLE

Next: End

HIGH LIMIT THERMOSTAT

HIGH LIMIT THERMOSTAT

Next: End

PILOT FLAME FAILURE

GAS VALVE

Next: End

SYSTEM CHECKS

SYSTEM CHECKS

Next: End

MAINS POWER SUPPLY

Next: End

ON / OFF SWITCH

ON / OFF SWITCH

Next: End

NO HIGH FLAME

PRINTED CIRCUIT BOARD

Next: End

FLOW SWITCH SPINDLE

FLOW SWITCH SPINDLE

Next: End

SAFETY THERMOSTAT

SAFETY THERMOSTAT

Next: End

GAS VALVE COIL

GAS VALVE COIL/SOLENOID

Next: End

CH HIGH FLAME

AIR TUBE

Next: End

NO FLAME

VENTURI

Next: End

CH HIGH FLAME

FAN (CONDITION)

Next: End

FAN SPEED RESISTOR (560 OHM)

SLOW FAN SPEED RESISTOR (560 OHM)

Next: End

CH HIGH FLAME

FLUE

Next: End

NO POWER

PRINTED CIRCUIT BOARD

Next: End

SLOW FAN

FLOW SWITCH MICROSWITCH

Next: End

HEATING CONTROL SWITCH

HEATING CONTROL SWITCH

Next: End

BOILER THERMOSTAT

BOILER THERMOSTAT

Next: End

DC POWER SUPPLY

PRINTED CIRCUIT BOARD

Next: End

CH RELAY 1 NORMALLY OPEN VOLTAGE

PRINTED CIRCUIT BOARD

Next: End

NO POWER TO PUMP

PRINTED CIRCUIT BOARD

Next: End

LOW FLAME

BOILER THERMOSTAT

Next: End

DOMESTIC HOT WATER MICROSWITCH

DOMESTIC HOT WATER MICROSWITCH

Next: End

MODULATION COIL

GAS VALVE MODULATION COIL

Next: End

CH MODULATION

VENTURI

Next: End

PUMP OVVERRUN

BOILER THERMOSTAT

Next: End

FILTER (COLD WATER INLET)

FILTER (COLD WATER INLET)

Next: End

DIVERTER VALVE DIAPHRAGM

DOMESTIC HOT WATER DIAPHRAGM

Next: End

DHW FAN HIGH SPEED (FAIL)

DOMESTIC HOT WATER MICROSWITCH

Next: End

DOMESTIC HOT WATER THERMOSTAT

DOMESTIC HOT WATER THERMOSTAT

Next: End

DHW MODULATION

DOMESTIC HOT WATER THERMOSTAT

Next: End

DIVERTER VALVE

THREE PORT DIVERTER VALVE

Next: End

CH MODULATION

BOILER THERMOSTAT

Next: End

PIEZO IGNITOR

PIEZO SPARK UNIT

Next: End

IGNITE PILOT

GAS VALVE

Next: End

SPARK ELECTRODE

SPARK ELECTRODE

Next: End

HW DEMAND

PRINTED CIRCUIT BOARD

Next: End

PILOT ESTABLISHED

GAS VALVE

Next: End

SLOW FAN

PRINTED CIRCUIT BOARD

Next: End

BURNER

BURNER

Next: End

NO FLAME

GAS VALVE

Next: End

NO FLAME

AIR PRESSURE SWITCH

Next: End

FLUE VENTURI

VENTURI

Next: End

NOT LIGHTING

GAS VALVE

Next: End

FAN

FAN

Next: End

ROOM THERMOSTAT CONNECTIONS

ROOM THERMOSTAT CONNECTIONS

Next: End

AIR PRESSURE SWITCH

AIR PRESSURE SWITCH

Next: End

CH RELAY 1 NORMALLY OPEN VOLTAGE

FLOW SWITCH MICROSWITCH

Next: End

PUMP

PUMP

Next: End

SPLIT

DIAPHRAGM CH FLOW SWITCH

Next: End

LOW FLAME

PRINTED CIRCUIT BOARD

Next: End

CH LOW FLAME

GAS VALVE

Next: End

PRIMARY HEAT EXCHANGER

PRIMARY HEAT EXCHANGER

Next: End

SYSTEM FAULT

Next: End

DIVERTER VALVE SPINDLE

DIVERTER VALVE SPINDLE

Next: End

DHW HIGH FLAME

DOMESTIC HOT WATER MICROSWITCH

Next: End

DHW MODULATION

DOMESTIC HOT WATER MICROSWITCH

Next: End

SECONDARY HEAT EXCHANGER

SECONDARY HEAT EXCHANGER

Next: End

HOT RADIATORS

CHARACTERISTIC TEST FROM HOT WATER.

Next: !p101

LOW FLAME

CHARACTERISTIC TEST FROM CH HIGH FLAME.

Next: p50

NO FLAME

CHARACTERISTIC TEST FROM CH HIGH FLAME.

Next: p52

NOISILY

CHARACTERISTIC TEST FROM CENTRAL HEATING.

Next: !p80

QUIETLY

CHARACTERISTIC TEST FROM CENTRAL HEATING.

Next: !p82

COLD RADIATORS

CHARACTERISTIC TEST FROM HOT WATER.

Next: !p99

PILOT INJECTOR BLOCKED

{ISOLATEMAINSPOWER}

Next: !p12, !f11

PIEZO EARTH CHECK

{ISOLATEMAINSPOWER}

Next: p117, !f118

ELECTRODE LEAD/ ELECTRODE

{ISOLATEMAINSPOWER}

Next: !p121, !f122

THERMOCOUPLE VOLTAGE

{ISOLATEMAINSPOWER}

Next: p15, !f14

RELAY 1 NORMALLY CLOSED CHECK

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO SUMMER

Next: p21, f20

MAINS POWER SUPPLY

ON/OFF SWITCH IN OFF POSITION

Next: p23, !f22

VOLTAGE AIR PRESSURE SWITCH COMMON

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO CONSTANT

Next: p273, !f248

GAS VALVE SOLENOID RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT AND REMOVE WIRES FROM SOLENOID BEFORE TESTING.

Next: !p271, !f272

VOLTAGE AIR PRESSURE SWITCH COMMON

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO CONSTANT

Next: !p285, !f286

CH - AIR PRESSURE SWITCH NORMALLY CLOSED

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO CONSTANT

Next: p371, f372

ROOM THERMOSTAT/LINK VOLTAGE

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO CONSTANT

Next: p373, f374

SELECTOR SWITCH IN CONSTANT POSITION

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO CONSTANT
HEATING THERMOSTAT TO MAX

Next: !p375, !f376

CH PUMP RUNS

Next: !p392, f388

VOLTAGE CH PUMP

Next: !p389, !f391

AIR PRESSURE SWITCH NORMALLY OPEN VOLTAGE

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO CONSTANT

Next: !p291, f284

DHW MICROSWITCH NORMALLY CLOSED CHECK

{ISOLATEMAINSPOWER}
ON/OFF SWITCH IN OFF POSITION

Next: p73, !f72

BLOCKED VENTURI

{ISOLATEMAINSPOWER}

Next: !p103, !f77

DHW FILTER

{ISOLATEMAINSPOWER}

Next: p86, !f85

RESISTANCE DHW MICROSWITCHES

{ISOLATEMAINSPOWER}

Next: !p123, !f90

DHW THERMOSTAT RESISTANCE (COLD)

{ISOLATEMAINSPOWER}

Next: !p94, !f93

DHW THERMOSTAT RESISTANCE (MODULATING)

{ISOLATEMAINSPOWER}
ENSURE THAT THE BOILER IS AT ITS FULL OPERATING TEMPERATURE

Next: !p97, !f96

ELECTRODE LEAD AND ELECTRODE

{ISOLATEMAINSPOWER}

Next: !p119, f120

HIGH LIMIT THERMOSTAT CONTINUITY

{ISOLATEMAINSPOWER}

Next: !p17, !f16

FLOW SWITCH SPINDLE

{ISOLATEMAINSPOWER}
REMOVE PLASTIC COVER FROM FLOWSWITCH

Next: p27, !f26

ON/OFF SWITCH OPERATION

ON/OFF SWITCH IN ON POSITION

Next: !p25, !f24

SAFETY THERMOSTAT RESISTANCE

{ISOLATEMAINSPOWER}

Next: p267, !f268

BURNER PRESSURE

{ISOLATEMAINSPOWER}<

Next: !p269, f270

FAN SPEED (560 OHM) RESISTOR

{ISOLATEMAINSPOWER}

Next: p29, !f28

APS TUBES

{ISOLATEMAINSPOWER}

Next: p274, !f275

BLOCKED VENTURI

{ISOLATEMAINSPOWER}

Next: p276, !f277

FAN CONDITION

{ISOLATEMAINSPOWER}
REMOVE FAN ASSEMBLY

Next: p278, !f279

BLOCKED FLUE.

Next: !p280, !f281

SLOW FAN VOLTAGE

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO SUMMER

Next: !p31, !f30

CH FLOW SWITCH MICROSWITCH

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO CONSTANT

Next: p379, f387

BOILER THERMOSTAT 2ND. STAGE

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO CONSTANT

Next: !p377, !f378

DC POWER SUPPLY

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO CONSTANT
HEATING THERMOSTAT TO MAX

Next: p383, !f384

CH RELAY 1 NORMALLY OPEN VOLTAGE

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO CONSTANT
HEATING THERMOSTAT TO MAX

Next: !p385, !f386

MODUREG SOLENOID SLUG FAILURE

{ISOLATEMAINSPOWER}<

Next: p54, f53

AIR PRESSURE SWITCH NORMALLY OPEN VOLTAGE

ON/OFF SWITCH IN ON POSITION
MODE SELECTOR SWITCH TO CONSTANT

Next: p266, f238

BOILER THERMOSTAT (COLD) RESISTANCE

{ISOLATEMAINSPOWER}
ENSURE THAT THE BOILER IS NOT AT ITS FULL OPERATING TEMPERATURE

Next: !p58, !f57

MODULATION COIL RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT WIRES FROM THE MODULATION COIL

Next: !p75, !f74

DIVERTER VALVE DIAPHRAGM.

{ISOLATEMAINSPOWER}

Next: !p88, !f87

System Information

  • Total Tests: 132
  • Sequence Logic: Decoded from encrypted .seq file
  • Navigation: Dynamic based on pass/fail results
  • Source: 4731307 GW SWIFTFLOW 100 SIT Control