Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
KESTON CELSIUS 25
WARNING - IMPORTA
KESTON CELSIUS 25
{ISOLATEMAINSPOWER}<
SPARKING PRESENT (DHW DEMAND)
ENSURE DHW IS CALLING FOR HEAT
BURNER IGNITION
ENSURE THAT DHW IS CALLING FOR HEAT
BURNER ESTABLISHES
ENSURE THAT DHW IS CALLING FOR HEAT
CH DEMAND
ENSURE ALL HEATING CONTROLS ARE CALLING
SAFETY NOTICE - ELECTRICAL ISOLATION
A NUMBER OF KESTO
FAN RUNS
ENSURE THAT DHW IS CALLING FOR HEAT
PUMP RUNS
ENSURE DHW IS CALLING FOR HEAT
FAULT
ELECTRICAL SAFETY CHECKS
GAS VALVE FUNCTION
PCB DBI
FAULT 1
GAS INLET PRESSURE
MECHANICAL 1
GAS VALVE
FAULT 1
IGNITION/FLAME SENSE ELECTRODE
FAULT LT
IGNITION/ LEAD
FAULT 2
SENSOR FLOW CALIBRATION
FAULT 2
SENSOR RETURN CALIBRATION
FAULT 3
LINK OUT CONTROLS
EXPANSION VESSEL
EXPANSION VESSEL
FAULT 2
PUMP
FAULT 3
SENSOR FLOW CALIBRATION
FAULT 3
SENSOR RETURN CALIBRATION
FAULT 3
PUMP
FAULT 399
SENSOR FLOW CALIBRATION
FAULT 399
SENSOR RETURN CALIBRATION
FAULT 3
GAS INLET PRESSURE
FAULT 2
FLUE
FAULT 2
IGNITION/FLAME SENSE ELECTRODE
FAULT 2
GAS INLET PRESSURE
FAULT 1
CONDENSATE TRAP
FAULT 1
FLUE
FAULT 2
BURNER
BLOCKED 2
AIR PRESSURE TUBE
IGNITION FUNCTION
CONTROL PCB
FAULT HT
IGNITION/ LEAD
NO APSIGNITION FUNCTION
CONTROL PCB
NO APSFAULT HT
IGNITION/ LEAD
ELECTRICAL ISOLATION
SAFETY NOTICE
RECHARGE
SYSTEM CHARGE PRESSURE
OC
SYSTEM PRESSURE SWITCH
TX SU
CONTROL PCB
BLOWN
FUSE THERMAL
OC
SENSOR FLUE TEMPERATURE
OC
SENSOR FLOW OVERHEAT
FASCIA PCB SU 1
CONTROL PCB
ON OFF SWITCH 1
FACIA PCB
WORN
EARTH LEAD
DAMAGED
EARTH LEAD
FAULTY
EARTH LEAD
WORN
PUMP HARNESS
SHORTING
GAS VALVE HARNESS
BLOWING FUSE
FAN HARNESS
BLOWING FUSES
TRANSFORMER HARNESS
SHORT TO EARTH
SENSOR HARNESS
BLOWING FUSE
SENSOR HARNESS
WORN
SENSOR HARNESS
BLOWN
FUSE F1
PUMP (RUNS)
FUSE F1
BLOWN
FUSE F2
BLOWN
FUSE MAIN 3A
NO APSBLOWN
FUSE F3 DBI
BLOWN
FUSE F3 DBI
WORN DAMAGED
FAN HARNESS
EXTERNAL CONTROL FUNCTION 2
CONTROL PCB
FAULT 1
SENSOR FLOW CALIBRATION
FAULT 1
SENSOR RETURN CALIBRATION
FASCIA PCB SU
CONTROL PCB
ON OFF SWITCH 2
FACIA PCB
DEMAND CALIBRATION 1
CONTROL PCB
DEMAND CALIBRATION 2
CONTROL PCB
DEMAND CALIBRATION 299
CONTROL PCB
FAULT FAULT 1
HEAT EXCHANGER
MECHANICAL 2
GAS VALVE
FAULT 2
FAN ASSEMBLY
NO BURNER IGNITION
CONDENSATE TRAP
BURNER NOT ESTABLISHING
CONDENSATE TRAP
FLAME SENSE FUNCTION
PCB DBI
FAILED OC
AIR PRESSURE SWITCH
NO SPARK
CONDENSATE TRAP
NO APSNO SPARK
CONDENSATE TRAP
FAULT 1
PUMP
FAULT 1
TRANSFORMER
INPUT FROM FASCIA FUNCTION 1
CONTROL PCB
FAULT 1
LINK OUT CONTROLS
EXTERNAL CONTROL FUNCTION 1
CONTROL PCB
NO APSIGNITION FUNCTION
PCB DBI
IGNITION FUNCTION
PCB DBI
FAULT 1
BURNER
BLOWING FUSE
PUMP
SHORTING
GAS VALVE
BLOWING FUSE
FAN ASSEMBLY
BLOWING FUSE
TRANSFORMER
SHORT TO EARTH
SENSOR FLUE TEMPERATURE
SHORT TO EARTH
SENSOR FLOW OVERHEAT
SHORTING
SYSTEM PRESSURE SWITCH
BLANK FOR FUSE F1 INVESTIGATION
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR FUSE F1 INVESTIGATION 2
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR FUSE INVESTIGATION F2
Z DIRECTION CHOICE OR CONTINUE
MAINS FUSE 3 AMP
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR FUSE F3 DBI
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR FUSE INVESTIGATION F3 DBI
Z DIRECTION CHOICE OR CONTINUE
BLOWN
FUSE
OPEN CIRCUIT
FAN ASSEMBLY
FAULT 2
LINK OUT CONTROLS
INPUT FROM FASCIA FUNCTION 2
CONTROL PCB
FAULT 1
FAN ASSEMBLY
Boiler reaches temperature but system is cool
CHARACTERISTIC TEST FROM CH OPERATION
Boiler does not reach temperature
CHARACTERISTIC TEST FROM CH OPERATION
Boiler noisy
CHARACTERISTIC TEST FROM CH OPERATION
27/11/2017 14:40:46 1709_1_50_1 09/01/2018 08:44:08
30/11/2017 09:21:03
BLOWING FUSES
PCBS
GAS VALVE VOLTAGE
ENSURE DHW IS CALLING FOR HEAT
SPARK ELECTRODE GAP
{ISOLATEMAINSPOWER}
FAN VOLTS
{ISOLATEMAINSPOWER}<
FLOW SENSOR RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE RED AND GREEN LEADS FROM THE FLOW TEMPERATURE SENSOR
FLOW SENSOR RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE RED AND GREEN LEADS FROM THE FLOW TEMPERATURE SENSOR
SPARK ELECTRODE AND LEAD CONDITION
{ISOLATEMAINSPOWER}
GAS INLET PRESSURE
{ISOLATEMAINSPOWER}<
AIR PRESSURE SWITCH TUBES
{ISOLATEMAINSPOWER}
SPARK ELECTRODE AND LEAD CONDITION
{ISOLATEMAINSPOWER}
PCB DBI VOLTAGE INPUT
{ISOLATEMAINSPOWER}
ENSURE DHW IS CALLING FOR HEAT
GAIN ACCESS TO PCB
SPARK ELECTRODE AND LEAD CONDITION
{ISOLATEMAINSPOWER}
PUMP VOLTS
{ISOLATEMAINSPOWER}
GAIN ACCESS TO PCB
EXTERNAL CONTROLS INPUT
{ISOLATEMAINSPOWER}
GAIN ACCESS TO TERMINAL STRIP
MAINS POWER SUPPLY
{ISOLATEMAINSPOWER}
GAIN ACCESS TO TERMINAL STRIP
MAINS POWER SUPPLY FUSE RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE FUSE LOCATED IN FUSED SPUR
RESISTANCE PUMP AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE CONNECTOR CN11 FROM THE PCB
RESISTANCE PUMP HARNESS
{ISOLATEMAINSPOWER}<
RESISTANCE GAS VALVE HARNESS
{ISOLATEMAINSPOWER}
REMOVE CONNECTOR CN1 FROM THE DBI PCB.
REMOVE CONNECTOR FROM GAS VALVE.
RESISTANCE FAN HARNESS DC
{ISOLATEMAINSPOWER}
REMOVE CONNECTOR CN4 FROM THE PCB.
REMOVE CONNECTOR FROM THE FAN.
RESISTANCE TRANSFORMER HARNESS DC SIDE
{ISOLATEMAINSPOWER}<
RESISTANCE SENSOR FLUE HARNESS
{ISOLATEMAINSPOWER}
REMOVE CONNECTOR CN9 FROM PCB.
REMOVE BOTH WIRES FROM THE FLUE STAT.
RESISTANCE SENSOR FLOW OVERHEAT HARNESS
{ISOLATEMAINSPOWER}
REMOVE CONNECTOR CN9 FROM PCB
REMOVE WIRES FROM FLOW OVERHEAT STAT.
RESISTANCE SYSTEM PRESSURE SWITCH HARNESS
{ISOLATEMAINSPOWER}<
FURTHER INVESTIGATION FUSE F1
THE INFORMATION PROV
FURTHER INVESTIGATION FUSE F1
THE INFORMATION PROV
FURTHER INVESTIGATION FUSE F2
THE INFORMATION PROV
FURTHER INVESTIGATION MAIN FUSE 3AMP
THE INFORMATION PROV
FURTHER INVESTIGATION FUSE F3 DBI
THE INFORMATION PROV
FURTHER INVESTIGATION FUSE F3 DBI
THE INFORMATION PROV
RESISTANCE FAN COIL
{ISOLATEMAINSPOWER}
REMOVE CONNECTOR CN4 FROM PCB.
RESISTANCE FAN HARNESS DC
{ISOLATEMAINSPOWER}
REMOVE CONNECTOR CN4 FROM THE PCB.
REMOVE CONNECTOR FROM THE FAN.
EXTERNAL CONTROLS OUTPUT
{ISOLATEMAINSPOWER}
GAIN ACCESS TO TERMINAL STRIP
EXTERNAL CONTROLS INPUT
{ISOLATEMAINSPOWER}
GAIN ACCESS TO TERMINAL STRIP
GAS INLET PRESSURE
{ISOLATEMAINSPOWER}<
GAS VALVE OPENS
ENSURE DHW IS CALLING FOR HEAT
ELECTRODE LEAD
{ISOLATEMAINSPOWER}
REMOVE THE ELECTRODE LEAD
RETURN SENSOR RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE BLUE AND BLACK LEADS FROM THE RETURN SENSOR
FLOW SENSOR RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE RED AND GREEN LEADS FROM THE FLOW TEMPERATURE SENSOR
RETURN SENSOR RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE BLUE AND BLACK LEADS FROM THE RETURN SENSOR
RETURN SENSOR RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE BLUE AND BLACK LEADS FROM THE RETURN SENSOR
FAN PRESSURE
{ISOLATEMAINSPOWER}<
GAS INLET PRESSURE
{ISOLATEMAINSPOWER}<
REMOVE LEAD FROM CONDENSE
{ISOLATEMAINSPOWER}<
REMOVE LEAD FROM CONDENSE 3
{ISOLATEMAINSPOWER}
REMOVE YELLOW WIRE FROM THE CONDENSE TRAP AND MAKE SAFE
BURNER
{ISOLATEMAINSPOWER}
AIR PRESSURE SWITCH PROVING
{ISOLATEMAINSPOWER}<
PCB DBI VOLTAGE INPUT
{ISOLATEMAINSPOWER}
ENSURE DHW IS CALLING FOR HEAT
GAIN ACCESS TO PCB
FUSE DBI RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE FUSE FROM THE DBI PCB
REMOVE LEAD FROM CONDENSE 2
{ISOLATEMAINSPOWER}<
FUSE DBI RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE FUSE FROM THE DBI PCB
REMOVE LEAD FROM CONDENSE 2
{ISOLATEMAINSPOWER}<
EXTERNAL CONTROLS OUTPUT
{ISOLATEMAINSPOWER}
GAIN ACCESS TO TERMINAL STRIP
SYSTEM PRESSURE SWITCH RESISTANCE
{ISOLATEMAINSPOWER}
DISCONNECT BLUE AND YELLOW LEADS FROM THE SYSTEM PRESSURE SWITCH
THERMAL FUSE
{ISOLATEMAINSPOWER}
REMOVE FUSE FROM THE TERMINAL STRIP ON THE TRANSFORMER
MAIN FUSE RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE FUSE F1 FROM CONTROL BOARD
FUSE F2 RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE FUSE F2 FROM CONTROL BOARD
SENSOR FLUE TEMPERATURE RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE GREEN AND YELLOW LEADS FROM THE FLUE TEMPERATURE SENSOR
SENSOR FLOW OVERHEAT RESISTANCE
{ISOLATEMAINSPOWER}
DISCONNECT RED AND BLACK LEADS FROM THE FLOW OVERHEAT SENSOR
FACIA PCB VOLTS INPUT
{ISOLATEMAINSPOWER}
GAIN ACCESS TO PCB
ON/OFF SWITCH OUTPUT
{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR MARKED CN3 DISPLAY FROM
THE MAIN PCB
MAIN FUSE RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE FUSE F1 FROM CONTROL BOARD
INSPECTION ELECTRODE EARTH LEAD
{ISOLATEMAINSPOWER}
INSPECTION ELECTRODE EARTH LEAD
{ISOLATEMAINSPOWER}
INSPECTION ELECTRODE EARTH LEAD
{ISOLATEMAINSPOWER}
RESISTANCE GAS VALVE AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE CONNECTOR CN1 FROM DBI PCB
RESISTANCE FAN AND HARNESS DC FUSE INVESTIGATION
{ISOLATEMAINSPOWER}
REMOVE CONNECTOR CN4 FROM PCB
RESISTANCE TRANSFORMER AND HARNESS DC SIDE
{ISOLATEMAINSPOWER}
REMOVE CONNECTOR CN5 FROM PCB.
RESISTANCE SENSOR FLUE AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE CONNECTOR CN9 FROM PCB.
RESISTANCE SENSOR FLOW OVERHEAT AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE CONNECTOR CN9 FROM THE PCB.
RESISTANCE SYSTEM PRESSURE SWITCH AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE CONNECTOR CN9 FROM THE PCB
FAN VOLTS
{ISOLATEMAINSPOWER}<
FLOW SENSOR RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE RED AND GREEN LEADS FROM THE FLOW TEMPERATURE SENSOR
RETURN SENSOR RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE BLUE AND BLACK LEADS FROM THE RETURN SENSOR
FACIA PCB VOLTS INPUT
{ISOLATEMAINSPOWER}
GAIN ACCESS TO PCB
ON/OFF SWITCH OUTPUT
{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR MARKED CN3 DISPLAY FROM
THE MAIN PCB
System Information
- Total Tests: 207
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control