Set Appliance State:

Set Multimeter to Resistance Set meter to measure resistance
Isolate Mains Power to appliance as per TOPs P4
Remove red and green leads from the flow temperature sensor

Measurement:

Measure the resistance across the exposed terminals of the sensor.
The resistance measured will depend upon the boiler temperature, the higher the temperature the lower the resistance.
The resistance should conform to the table below.
Temperature °CResistance in kOhms
25-359.5-6.1
35-456.1-3.9
45-553.9-2.7
55-652.7-1.9
65-751.9-1.4
75-801.4-1.2