Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
CARADON IDEAL MINI C24
WARNING - IMPORTA
CH OPERATION
ENSURE DHW TAP IS TURNED OFF
CH TEMPERATURE SELECTOR TO MAXIMUM
DHW MODULATION
SELECTOR SWITCH TO H
DHW OPERATION
SELECTOR SWITCH TO HOT WATER
DHW TEMPERATURE SELECTOR TO MAXIMUM
SYSTEM PRESSURE RISE
SELECTOR SWITCH TO HEATING
CH TEMPERATURE SELECTOR TO MAXIMUM
BURNER IGNITES (CH)
SELECTOR SWITCH TO HEATING
CH TEMPERATURE SELECTOR TO MAXIMUM
BURNER IGNITES (DHW)
SELECTOR SWITCH TO H
SPARKING (DHW)
SELECTOR SWITCH TO HOT WATER
DHW TEMPERATURE SELECTOR TO MAXIMUM
FAN RUNS (DHW)
SELECTOR SWITCH TO HOT WATER
DHW TEMPERATURE SELECTOR TO MAXIMUM
CARADON IDEAL MINI C24 (2 PCB VERSION)
G.C.NUMBER 47 348 18
CH MODULATION
SELECTOR SWITCH TO H
PUMP RUNS (DHW)
SELECTOR SWITCH TO HOT WATER
DHW TEMPERATURE SELECTOR TO MAXIMUM
ANTI-CYCLE DELAY
SELECTOR SWITCH TO HEATING
CH TEMPERATURE SELECTOR TO MAXIMUM
ELECTRICAL SAFETY CHECKS
ELECTRICAL SAFETY CHECKS
BURNER IGNITES PRESSURE LOW
CH SENSOR
BURNER IGNITES BUT DOES NOT ESTABLISH
CABLE - FLAME SENSE ELECTRODE
BURNER IGNITES BUT DOES NOT ESTABLISH
FLAME SENSE ELECTRODE
HEAT EXCHANGER NOISY
PRIMARY HEAT EXCHANGER
HEAT EXCHANGER NOISY
PUMP
DHW COOL RADIATORS COOL
INJECTORS
DHW COOL RADIATORS HOT
MAIN PCB
BOILER TO TEMPERATURE RADIATORS COLD
MAIN PCB
RADIATORS COOL BOILER COOL
CH SENSOR
DHW COOL RADIATORS COOL
DHW SENSOR
CH NOISY DHW OK
BYPASS
DHW FLOW RATE
COMBINED FILTER/RESTRICTOR
SPARKING
AIR PRESSURE SWITCH TUBES
SPARKING
VENTURI
SPARKING
FLUE
DHW FAN RUNS
DHW SENSOR
DHW FAN RUNS
FUSE - IGNITION PCB
RADIATORS DO NOT HEAT, BOILER NOISY
MAIN PCB
SPARKING PRESENT NO GAS PRESSURE
GAS INLET PRESSURE
DHW MODULATION
DHW SENSOR
FAULTY
HARNESS (GAS VALVE)
FAULTY
HARNESS CH FLOW SWITCH, TEMPERATURE PROBE AND MODULATOR
ANTI-CYCLE DELAY
MAIN PCB
BOILER TO TEMPERATURE RADIATORS COLD
DIVERTER VALVE MANIFOLD
CH MODULATION
CH SENSOR
DHW FAN RUNS
AIR PRESSURE SWITCH TUBES
BOILER TO TEMPERATURE RADIATORS COLD
RETURN MANIFOLD
DUMMY
DUMMY
DHW FAN RUNS
VENTURI
DHW FAN RUNS
CH FLOW SWITCH MICROSWITCH
RADIATORS DO NOT HEAT, BOILER NOISY
BYPASS - EXTERNAL
BURNER IGNITES
HARNESS CH FLOW SWITCH, TEMPERATURE PROBE AND MODULATOR
ELECTRICAL
GAS VALVE
DHW MODULATION
HARNESS CH FLOW SWITCH, TEMPERATURE PROBE AND MODULATOR
CH OPERATION
DHW FLOW SWITCH
LOCKOUT DOES NOT RESET
MAIN PCB
FAULTY
HARNESS (PCB1 TO PCB2 SHORT)
DHW FAN RUNS
SYSTEM PRESSURE
DHW FAN RUNS
CH FLOW SWITCH DIAPHRAGM
DHW SENSOR
DHW SENSOR
HARNESS TO GV (MODULATION)
HARNESS CH FLOW SWITCH, TEMPERATURE PROBE AND MODULATOR
SPARKING
SPARK LEADS
OPERATIONAL SEQUENCE
SYSTEM CHECKS
CH IGNITES
CH SENSOR
DHW PUMP RUNS
FUSE - MAIN PCB
NOT SPARKING
SPARK ELECTRODE ASSEMBLY
DHW PUMP RUNS
DHW FLOW SWITCH
SYSTEM PRESSURE RISE
EXPANSION VESSEL
BURNER IGNITES PRESSURE LOW
GAS INLET PRESSURE
BURNER IGNITES PRESSURE LOW
DHW SENSOR
BURNER IGNITES THEN BAFFLES OUT
PRIMARY HEAT EXCHANGER - FLUEWAYS
BURNER IGNITES PRESSURE LOW
GAS VALVE
HEAT EXCHANGER NOISY
SECONDARY HEAT EXCHANGER
DHW COOL RADIATORS COOL
SECONDARY HEAT EXCHANGER
DHW COOL RADIATORS HOT
DIVERTER VALVE MANIFOLD
DHW COOL RADIATORS HOT
DIVERTER VALVE MOTOR
DHW MODULATION
GAS VALVE
CH NOISY DHW NOISY
BYPASS
RADIATORS COOL BOILER COOL
MAIN PCB
BOILER TO TEMPERATURE RADIATORS COLD
DIVERTER VALVE MOTOR
CH MODULATION
MAIN PCB
DHW FLOW RATE
SECONDARY HEAT EXCHANGER
DHW FAN RUNS
FAN
SPARKING
AIR PRESSURE SWITCH
DHW PUMP RUNS
PUMP
BURNER IGNITES
OVERHEAT THERMOSTAT
FLAME SENSE
IGNITION PCB
MECHANICAL
GAS VALVE
SPARKING PRESENT, NO GAS PRESSURE 1
IGNITION PCB
DHW FAN RUNS
AIR PRESSURE SWITCH
BURNER IGNITES PRESSURE LOW
MAIN PCB
DHW MODULATION
IGNITION PCB
DHW MODULATION
MAIN PCB
DHW FAN RUNS
IGNITION PCB
FAN RUNS
MAIN PCB
DHW FAN RUNS
DIVERTER VALVE MANIFOLD
GAS VALVE
GAS VALVE
DHW TOO HOT
MAIN PCB
BURNER IGNITES PRESSURE LOW
IGNITION PCB
DHW PUMP RUNS 2
MAIN PCB
SPARKING
IGNITION PCB
DHW PUMP RUNS
MAIN PCB
Heat exchanger noisy
CHARACTERISTIC TEST FROM DHW OPERATION
DHW COOL, RADIATORS COOL
CHARACTERISTIC TEST FROM DHW OPERATION
DHW COOL, RADIATORS HOT
CHARACTERISTIC TEST FROM DHW OPERATION
BOILER TO TEMPERATURE, RADIATORS COLD
CHARACTERISTIC TEST FROM CH OPERATION
CH NOISY, DHW OK
CHARACTERISTIC TEST FROM CH OPERATION
CH NOISY, DHW NOISY
CHARACTERISTIC TEST FROM CH OPERATION
RADIATORS COOL, BOILER COOL
CHARACTERISTIC TEST FROM CH OPERATION
RADIATORS DO NOT HEAT, BOILER NOISY
CHARACTERISTIC TEST FROM CH OPERATION
DHW TOO HOT
CHARACTERISTIC TEST FROM DHW OPERATION
BURNER IGNITES, PRESSURE LOW
CHARACTERISTIC TEST FROM BURNER IGNITES (DHW)
BURNER IGNITES THEN BAFFLES OUT
CHARACTERISTIC TEST FROM BURNER IGNITES (DHW)
BURNER IGNITES BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM BURNER IGNITES (DHW)
SPARKING PRESENT, NO GAS PRESSURE
CHARACTERISTIC TEST FROM BURNER IGNITES (DHW)
SPARKING AND GAS PRESSURE PRESENT BUT NO IGNITION
CHARACTERISTIC TEST FROM BURNER IGNITES (DHW)
31-01-2014 10:57:04 1403_1_35_3 19/03/2014 12:56:29
31/01/2014 11:37:09
DHW MODULATION VOLTS
SELECTOR SWITCH TO H
DIVERTER VALVE VOLTAGE
SELECTOR SWITCH TO HOT WATER
DHW TEMPERATURE SELECTOR TO MAXIMUM
CH SENSOR RESISTANCE
REMOVE THE GREEN PLUG FROM THE SENSOR
DHW FLOW SWITCH
REMOVE THE DHW FLOW SWITCH FROM THE RETURN MANIFOLD
CH SENSOR RESISTANCE
REMOVE THE GREEN PLUG FROM THE SENSOR
DHW FILTER/RESTRICTOR
ISOLATE BOILER AND DRAIN DHW
REMOVE DHW FLOW SWITCH
AIR PRESSURE SWITCH AIR DETECT
SELECTOR SWITCH TO H
PUMP VOLTAGE
{USEINSMAT}
SELECTOR SWITCH TO HOT WATER
DHW TEMPERATURE SELECTOR TO MAXIMUM
IGNITION PCB FUSE RESISTANCE
REMOVE THE FUSE FROM IGNITION PCB
PUMP VOLTAGE
{USEINSMAT}
SELECTOR SWITCH TO HEATING
CH TEMPERATURE SELECTOR TO MAXIMUM
GAS VALVE (VOLTAGE)
SELECTOR SWITCH TO HOT WATER
DHW TEMPERATURE SELECTOR TO MAXIMUM
GAS VALVE VOLTAGE
{USEINSMAT}
SELECTOR SWITCH TO HOT WATER
DHW TEMPERATURE SELECTOR TO MAXIMUM
AIR PRESSURE SWITCH RESISTANCE
DISCONNECT ONE OF THE WIRES FROM THE AIR PRESSURE SWITCH
MAIN PCB TO IGNITION PCB CONTINUITY
REMOVE CONNECTOR J7 (BLACK) FROM MAIN PCB
MAIN PCB TO IGNITION PCB CONTINUITY
REMOVE CONNECTOR J7 (BLACK) FROM MAIN PCB
GAS VALVE MODULATION HARNESS
REMOVE CONNECTOR J7 (BLACK) FROM MAIN PCB
PCB VOLTAGE (J1)
{USEINSMAT}
SELECTOR SWITCH TO HOT WATER
DHW TEMPERATURE SELECTOR TO MAXIMUM
MAINS POWER IN
{USEINSMAT}
CH SENSOR RESISTANCE
REMOVE THE GREEN PLUG FROM THE SENSOR
CH SENSOR RESISTANCE
REMOVE THE GREEN PLUG FROM THE SENSOR
DIVERTER VALVE HEAD OPERATION
SELECTOR SWITCH TO HEATING
CH TEMPERATURE SELECTOR TO MAXIMUM
REMOVE THE DIVERTER VALVE HEAD
CH OPERATION
ENSURE DHW TAP IS TURNED OFF
CH TEMPERATURE SELECTOR TO MAXIMUM
CH SENSOR RESISTANCE
REMOVE THE GREEN PLUG FROM THE SENSOR
DIVERTER VALVE HEAD OPERATION
SELECTOR SWITCH TO HEATING
CH TEMPERATURE SELECTOR TO MAXIMUM
REMOVE THE DIVERTER VALVE HEAD
BYPASS
DRAIN AND DISCHARGE BOILER
CH SENSOR RESISTANCE
REMOVE THE GREEN PLUG FROM THE SENSOR
CH OPERATION
SELECTOR SWITCH TO HEATING
CH TEMPERATURE SELECTOR TO MAXIMUM
DIVERTER VALVE VOLTS (CH)
SELECTOR SWITCH TO HEATING
CH TEMPERATURE SELECTOR TO MAXIMUM
FAN VOLTS
{USEINSMAT}
SELECTOR SWITCH TO HOT WATER
VENTURI
REMOVE THE FAN ASSEMBLY FROM THE BOILER.
OVERHEAT THERMOSTAT RESISTANCE
REMOVE THE WIRES FROM THE OVERHEAT THERMOSTAT
RESISTANCE DHW SENSOR
REMOVE CONNECTOR J6 FROM MAIN PCB
CH FLOW SWITCH SPINDLE
SELECTOR SWITCH TO HOT WATER
DHW TEMPERATURE SELECTOR TO MAXIMUM
GAS INLET PRESSURE
SELECTOR SWITCH TO H
GAS VALVE RESISTANCE
REMOVE THE CONNECTOR FROM THE MAIN GAS VALVE
GAS VALVE MODULATION HARNESS
REMOVE CONNECTOR J7 (BLACK) FROM MAIN PCB
VENTURI
REMOVE THE FAN ASSEMBLY FROM THE BOILER.
CH FLOW SWITCH MICRO SWITCH
REMOVE CONNECTOR J7 (BLACK) FROM THE MAIN PCB
EXTERNAL CONTROLS (INPUT)
SELECTOR SWITCH TO H
EXTERNAL CONTROLS OUTPUT
ENSURE THERE IS A DEMAND ON THE EXTERNAL CONTROLS
DHW FLOW SWITCH
{USEINSMAT}
SELECTOR SWITCH TO HOT WATER
DHW TEMPERATURE SELECTOR TO MAXIMUM
HARNESS MAIN PCB TO IGNITION PCB VOLTAGE
{USEINSMAT}
SELEC
C.H FLOW SWITCH DIAPHRAGM
BOILER DISCHARGED AND DRAINED
DHW MODULATION VOLTS
SELECTOR SWITCH TO H
CH SENSOR RESISTANCE
REMOVE THE GREEN PLUG FROM THE SENSOR
DHW FLOW SWITCH VOLTAGE
{USEINSMAT}
SELECTOR SWITCH TO HOT WATER
DHW TEMPERATURE SELECTOR TO MAXIMUM
MAINS POWER FUSE ON PCB
REMOVE THE FUSE FROM MAIN PCB
SPARK ELECTRODE CONDITION
REMOVE THE SPARK ELECTRODE FROM THE BOILER.
DHW MODULATION PRESSURE
SET FLOW RATE AT HOT
GAS INLET PRESSURE
SELECTOR SWITCH TO H
CH SENSOR RESISTANCE
REMOVE THE GREEN PLUG FROM THE SENSOR
System Information
- Total Tests: 198
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control