Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
IMI RANGE POWERMAX 135
G.C. NUMBER 41 389 0
CENTRAL HEATING.
BOILER THERMAL STORE
DOMESTIC HOT WATER TEMPERATURE
BOILER THERMAL STORE
HOT WATER FLOW RATE.
{ISOLATEMAINSPOWER}
TURN HOT WATER TAP ON.
PUMP RUNS.
BOILER THERMAL STORE
CENTRAL HEATING DEMAND.
MODELS WITH PROGRAMM
GREEN NEON OFF (BOILER UP TO TEMPERATURE).
BOILER THERMAL STORE
SUSTAINED GREEN NEON.
BOILER THERMAL STORE
AIR DETECTED.
BOILER THERMAL STORE
FAN RUNS.
BOILER THERMAL STORE
FULL SEQUENCE IGNITION BOX SUPPLY.
BOILER THERMAL STORE
ORANGE NEON ILLUMINATED
APPLIANCE SWITCHED O
FROST THERMOSTAT (IF FITTED).
{ISOLATEMAINSPOWER}<
COLD START THERMOSTAT (NORMALLY CLOSED).
{ISOLATEMAINSPOWER}<
SYSTEM CHECKS.
{ISOLATEMAINSPOWER}
IMI RANGE POWERMAX 135
G.C. NUMBER 41 389 0
CH TIMER ABSENT
ROOM THERMOSTAT
CH TIMER PRESENT
APPLIANCE SWITCH
CH TIMER PRESENT
ROOM THERMOSTAT
PUMP RUNS
COLD START THERMOSTAT
DHW FLOW RATE TOO LOW
DHW FILTER
DHW FLOW RATE TOO LOW
FLOW RESTRICTOR
DOMESTIC HOT WATER TEMPERATURE
BLENDER VALVE
ELECTRICAL SAFETY CHECKS
ELECTRICAL SAFETY CHECKS
SYSTEM CHECK
SYSTEM CHECK
COLD START THERMOSTAT
COLD START THERMOSTAT
FROST THERMOSTAT (IF FITTED)
FROST THERMOSTAT
EMC FILTER ABSENT
3A FUSE (FUSE SPUR)
EMC FILTER ABSENT
9 WAY CONNECTOR BLOCK
EMC FILTER PRESENT
3A FUSE (FUSE SPUR)
EMC FILTER PRESENT
EMC FILTER
EMC FILTER PRESENT
9 WAY CONNECTOR BLOCK
LIMIT THERMOSTAT ABSENT
APPLIANCE SWITCH
LIMIT THERMOSTAT ABSENT
BOILER THERMOSTAT
LIMIT THERMOSTAT PRESENT
APPLIANCE SWITCH
LIMIT THERMOSTAT PRESENT
BOILER THERMOSTAT
2A FULL SEQUENCE IGNITION BOX FUSE
2A FULL SEQUENCE IGNITION BOX FUSE
FAN RUNS
AIR PRESSURE SWITCH TUBES
FAN RUNS
CAPACITOR
AIR DETECTED
AIR PRESSURE SWITCH TUBES
AIR DETECTED
FLUE ASSEMBLY.
BURNER PRESSURE
EV 1 AND EV 2 SOLENOIDS
BURNER PRESSURE
FULL SEQUENCE IGNITION BOX
SUSTAINED GREEN NEON
ELECTRODE LEAD
SUSTAINED GREEN NEON
SPARK ELECTRODE
SUSTAINED GREEN NEON
INJECTOR ASSEMBLY
SUSTAINED GREEN NEON
BURNER
SUSTAINED GREEN NEON
GAS SUPPLY
SUSTAINED GREEN NEON
9 WAY CONNECTOR BLOCK
GREEN NEON OFF (BOILER UP TO TEMPERATURE)
BOILER THERMOSTAT
C/H TIMER ABSENT
C/H SWITCH
CH TIMER ABSENT
9 WAY CONNECTOR BLOCK
CH TIMER PRESENT
PROGRAMMER
CH TIMER PRESENT
9 WAY CONNECTOR BLOCK
PUMPS
PUMP
DHW FLOW RATE TOO HIGH
FLOW RESTRICTOR
DHW FLOW RATE TOO LOW
SECONDARY HEAT EXCHANGER (SCALED)
EMC FILTER ABSENT
MAINS SUPPLY
EMC FILTER ABSENT
ORANGE NEON (ELECTRICAL SUPPLY ON)
EMC FILTER PRESENT
MAINS SUPPLY
EMC FILTER PRESENT
ORANGE NEON (ELECTRICAL SUPPLY ON)
LIMIT THERMOSTAT ABSENT
9 WAY CONNECTOR BLOCK
LIMIT THERMOSTAT PRESENT
9 WAY CONNECTOR BLOCK
HIGH-LIMIT THERMOSTAT
HIGH-LIMIT THERMOSTAT
FAN RUNS
FULL SEQUENCE IGNITION BOX
FAN RUNS
AIR PRESSURE SWITCH
FAN RUNS
FAN
AIR DETECTED
AIR PRESSURE SWITCH
BURNER PRESSURE
GAS VALVE ASSEMBLY
SUSTAINED GREEN NEON
FULL SEQUENCE IGNITION BOX
SUSTAINED GREEN NEON
GREEN NEON (BURNER ON)
DHW FLOW RATE TOO LOW
CHARACTERISTIC TEST FROM HOT WATER FLOW RATE
DHW FLOW RATE TOO HIGH
CHARACTERISTIC TEST FROM HOT WATER FLOW RATE
NEON NOT ILLUMINATED, EMC FILTER NOT FITTED
CHARACTERISTIC TEST FROM ORANGE NEON ILLUMINATED
NEON NOT ILLUMINATED, EMC FILTER FITTED
CHARACTERISTIC TEST FROM ORANGE NEON ILLUMINATED
MAINS VOLTAGE ABSENT, LIMIT THERMOSTAT NOT FITTED
CHARACTERISTIC TEST FROM FULL SEQUENCE IGNITION BOX SUPPLY
MAINS VOLTAGE ABSENT, LIMIT THERMOSTAT FITTED
CHARACTERISTIC TEST FROM FULL SEQUENCE IGNITION BOX SUPPLY
CH TIMER ABSENT
CHARACTERISTIC TEST FROM CENTRAL HEATING DEMAND
CH TIMER PRESENT
CHARACTERISTIC TEST FROM CENTRAL HEATING DEMAND
18/01/2018 13:13:45 1801_1_50_1 06/03/2018 13:16:20
02/02/2018 14:20:11
SELECTOR SWITCH (TIMED) OPERATION.
SELECTOR SWITCH TO T
PUMP SUPPLY VOLTAGE.
BOILER THERMAL STORE
3 AMP FUSE - MAINS SUPPLY.
{ISOLATEMAINSPOWER}
MAINS POWER AT APPLIANCE FUSED SPUR OFF.
REMOVE THE EXTERNAL 3 AMP FUSE.
3 AMP FUSE - MAINS SUPPLY.
{ISOLATEMAINSPOWER}
MAINS POWER AT APPLIANCE FUSED SPUR OFF.
REMOVE THE EXTERNAL 3 AMP FUSE.
SELECTOR SWITCH (CONTINUOUS) OUTPUT VOLTAGE.
MODELS WITH PROGRAMM
FAN SUPPLY OUTPUT.
BOILER THERMAL STORE
FULL SEQUENCE IGNITION BOX - INTERNAL 2 AMP FUSE.
{ISOLATEMAINSPOWER}<
AIR PRESSURE SWITCH TUBES.
{ISOLATEMAINSPOWER}
ENSURE APPLIANCE IS SWITCHED OFF.
AIR PRESSURE SWITCH TUBES.
{ISOLATEMAINSPOWER}
ENSURE APPLIANCE IS SWITCHED OFF.
BURNER PRESSURE.
{ISOLATEMAINSPOWER}<
EV1 & EV2 SOLENOID RESISTANCE.
{ISOLATEMAINSPOWER}<
ELECTRODE LEAD.
{ISOLATEMAINSPOWER}
ROOM THERMOSTAT/LINK.
{ISOLATEMAINSPOWER}<
ROOM THERMOSTAT/LINK.
{ISOLATEMAINSPOWER}<
DHW FILTER.
{ISOLATEMAINSPOWER}
DHW COLD WATER INLET OFF.
DHW FLOW RESTRICTOR.
{ISOLATEMAINSPOWER}
DHW COLD WATER INLET OFF.
SELECTOR SWITCH SUPPLY.
{ISOLATEMAINSPOWER}<
EMC FILTER.
{ISOLATEMAINSPOWER}
ENSURE APPLIANCE OFF AND 3A EXTERNAL FUSE IS REMOVED
SELECTOR SWITCH SUPPLY.
{ISOLATEMAINSPOWER}<
SELECTOR SWITCH (CONTINUOUS) OUTPUT VOLTAGE.
MODELS WITH PROGRAMM
BOILER THERMOSTAT INPUT VOLTAGE.
SELECTOR SWITCH TO CONSTANT.
HEATING SWITCH TO ON.
BOILER THERMOSTAT (COLD).
{ISOLATEMAINSPOWER}<
BOILER THERMOSTAT (COLD).
{ISOLATEMAINSPOWER}<
FAN VOLTAGE.
BOILER THERMAL STORE
FAN CAPACITOR VOLTAGE.
BOILER THERMAL STORE
FULL SEQUENCE IGNITION BOX (FLAME SENSE OUTPUT).
BOILER THERMAL STORE
SOLENOID SUPPLY.
ENSURE THERMAL STORE
GREEN NEON VOLTAGE.
BOILER THERMAL STORE
SPARK ELECTRODE.
{ISOLATEMAINSPOWER}<
INJECTOR ASSEMBLY.
{ISOLATEMAINSPOWER}
REMOVE AND INSPECT THE INJECTOR ASSEMBLY.
BURNER
{ISOLATEMAINSPOWER}<
GAS SUPPLY.
{ISOLATEMAINSPOWER}
C/H - TIMER; ROCKER SWITCH OUTPUT.
MODELS WITH PROGRAMM
C/H - TIMER; ROCKER SWITCH OUTPUT.
MODELS WITH PROGRAMM
System Information
- Total Tests: 119
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control