Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
WORCESTER 24I RSF
WARNING - IMPORTA
RE-IGNITE DELAY
SELECTOR SWITCH TO CH - MID POSITION
OVERRUN OPERATION
SELECTOR SWITCH TO CH - MAX POSITION
CH MODULATION
ATTACH A U-GAUGE TO
CH OPERATION
ATTACH A U-GAUGE TO
DHW MODULATION
ATTACH A U-GAUGE TO THE GAS VALVE BURNER PRESSURE TEST POINT
CH BURNER IGNITES
SELECTOR SWITCH TO CH - MAX POSITION
BURNER ESTABLISHES AT MINIMUM PRESSURE
ATTACH A U-GAUGE TO
DHW BURNER IGNITES
SELECTOR SWITCH IN DHW POSITION
DHW SPARKING
REMOVE INNER CASING COVER
SELECTOR SWITCH IN DHW POSITION
DHW FAN RUNS
SELECTOR SWITCH IN DHW POSITION
CH DEMAND PUMP RUN
SELECTOR SWITCH TO CH
ENSURE PUMP IS AT MAX SPEED SETTING
WORCESTER 24I RSF
G.C. NUMBER 47 311 3
TYPE OF DIAGNOSTIC MODEL
PLEASE SELECT FROM O
FUSE INVESTIGATION TREE
OUTSIDE MODEL
ELECTRICAL SAFETY CHECKS
ELECTRICAL SAFETY CHECKS
CH BURNER IGNITES
EXT CONTROLS - PROGRAMMER
CH BURNER IGNITES
EXT CONTROLS - ROOM THERMOSTAT
AUTO FROST PROTECTION
THERMISTOR / SENSOR - ELMWOOD
DHW OPERATION
FAN ASSEMBLY
DHW OPERATION
FLUE
DHW OPERATION
MAIN BURNER INJECTOR
DHW MODULATION
THERMISTOR / SENSOR - ELMWOOD
CH OPERATION
PIPE ASSEMBLY - BY - PASS
CH OPERATION
THERMISTOR / SENSOR - ELMWOOD
SYSTEM PRESSURE RISE
EXPANSION VESSEL
OVERRUN OPERATION
THERMISTOR / SENSOR - ELMWOOD
RE-IGNITE DELAY
PCB
CH DEMAND PUMP RUN
EXT CONTROLS - PROGRAMMER
BURNER ESTABLISHES AT MINIMUM PRESSURENR
INLET PRESSURE
DHW SPARKING6666123
AIR PRESSURE TUBES
AIR CHECK123
KIT - SWITCH AIR PRESSURE
DHW SPARKING6666123
PROBE - AIR PRESSURE SENSING - FIRST PRESS
BROKEN - TURNED OFF
KNOB - CONTROL - AZTEC TOOLING & MOULDING
FAN DOES NOT RUN
KIT - SWITCH AIR PRESSURE
CH BURNER IGNITES
KNOB - CONTROL - AZTEC TOOLING & MOULDING
CH MODULATION
THERMISTOR / SENSOR - ELMWOOD
FLUE123
FLUE
DHW SPARKING9992222
SAFETY TEMPERATURE LIMITER
AIR CHECKNSP
KIT - SWITCH AIR PRESSURE
DHW SPARKING9992222NSP
SPARK ELECTRODE ASSEMBLY
OVERHEAT THERMOSTAT (RESISTANCE)9992222NSP
HARNESS ASSEMBLY - IGNITION
DHW SPARKING6666NSP
AIR PRESSURE TUBES
DHW SPARKING6666NSP
PROBE - AIR PRESSURE SENSING - FIRST PRESS
FLUENSP
FLUE
OVERHEAT INVESTIGATION
SYSTEM PRESSURE
DHW SPARKING - WILL NOT RESET
SAFETY TEMPERATURE LIMITER
TYPE OF DIAGNOSTIC PROCEDURE
Z REDIRECT
RUNNING SLOW - OVERHEAT INVESTIGATION
PUMP AND HARNESS ASSEMBLY
GAS VALVE & HARNESS ASSEMBLY
GAS VALVE
OVERHEAT INVESTIGATION
PIPE ASSEMBLY - BY - PASS
OVERHEAT INVESTIGATION CH SENSOR
THERMISTOR / SENSOR - ELMWOOD
DHW MAXIMUM GAS PRESSURE
INLET PRESSURE
CH DEMAND PUMP RUNS
FUSE MAINS
CH DEMAND PUMP RUN
KIT - FUSE 1.25A & 2A 20MM
DHW FLOW RATE
FILTER GAUZE - EXPAMET
CH DEMAND PUMP RUN
FUSE 2A 20MM - SLOW BLOW
FUSE INVESTIGATION
PUMP AND HARNESS ASSEMBLY
FUSE INVESTIGATION
FAN ASSEMBLY
FUSE INVESTIGATION GV1/2
GAS VALVE
FUSE INVESTIGATION GV3
GAS VALVE
CH OPERATION - TURNED LOW
KNOB - CONTROL - AZTEC TOOLING & MOULDING
CH MODULATION - NOT TURNING DOWN
KNOB - CONTROL - AZTEC TOOLING & MOULDING
DHW MAX GAS PRESSURE - MODUREG
GAS VALVE
DHW MODULATION MECHANICAL
GAS VALVE
GAS VALVE 1 2 VOLTAGE
GAS VALVE
DHW FAN RUNS
AIR PRESSURE TUBES
DHW TOO HOT
THERMISTOR / SENSOR - ELMWOOD
DHW MAX PRESSURE
THERMISTOR / SENSOR - ELMWOOD
DHW MAX PRESSURE
FLOW SWITCH ASSEMBLY - ALCO /63/64
BURNER DOES NOT IGNITE
BURNER ASSEMBLY
CH DEMAND PUMP RUN
THERMISTOR / SENSOR - ELMWOOD
DHW FAN RUNS
PROBE - AIR PRESSURE SENSING - FIRST PRESS
CH DEMAND PUMP RUN
THERMISTOR / SENSOR - ELMWOOD
DHW FAN RUNS
THERMISTOR / SENSOR - ELMWOOD
DHW FAN RUNS
THERMISTOR / SENSOR - ELMWOOD
CH BURNER IGNITES
THERMISTOR / SENSOR - ELMWOOD
CH DEMAND PUMP RUN
FLOW SWITCH ASSEMBLY - ALCO /63/64
DHW FAN RUNS
FLOW SWITCH ASSEMBLY - ALCO /63/64
BURNER DOES NOT CROSSLIGHT
BURNER ASSEMBLY
MINIMUM BURNER PRESSURE INCORRECT
INLET PRESSURE
FAN RUNS SLOW
PCB
DHW FLOW RATE
FLOW REGULATOR
GAS VALVE 1 2 RESISTANCE
GAS VALVE
DHW BURNER IGNITES
INLET PRESSURE
DHW BURNER IGNITES
SPARK ELECTRODE ASSEMBLY
BURNER ESTABLISHES AT MINIMUM PRESSURE (FAIL)
PROBE - FLAME SENSOR C/W LEAD
HEAT EXCHANGER NOISY (KETTLES) DURING DHW OPERATION
HEAT EXCHANGER - GAS TO WATER - PRB 20/501
DHW OPERATION
PCB
DHW OPERATION
HEAT EXCHANGER - GAS TO WATER - PRB 20/501
DHW MODULATION
GAS VALVE
DHW MODULATION
PCB
CH OPERATION
HEAT EXCHANGER - GAS TO WATER - PRB 20/501
CH OPERATION
PCB
OVERRUN OPERATON
PCB
BURNER ESTABLISHES AT MINIMUM PRESSURE (PASS)
PROBE - FLAME SENSOR C/W LEAD
DHW QUIET OPERATION, RADIATORS COLD
HEAT EXCHANGER - GAS TO WATER - PRB 20/501
HEAT EXCHANGER (SECONDARY COIL)
HEAT EXCHANGER - GAS TO WATER - PRB 20/501
CH DEMAND PUMP RUN
EXT CONTROLS - ROOM THERMOSTAT
CH DEMAND PUMP RUN
PUMP AND HARNESS ASSEMBLY
CH MODULATION
PCB
SPARKING ELECTRODES123
FAN ASSEMBLY
SPARKING ELECTRODESNSP
FAN ASSEMBLY
OVERHEAT INVESTIGATION
HEAT EXCHANGER - GAS TO WATER - PRB 20/501
TRIPPING EARLY - OVERHEAT INVESTIGATION
SAFETY TEMPERATURE LIMITER
NO FAULT FOUND
OVERHEAT
FAN DOES NOT RUN
FAN ASSEMBLY
MAINS FUSE
Z REDIRECT
FUSE F2
Z REDIRECT
FUSE F1
Z REDIRECT
FUSE INVESTIGATION
NO FAULT FUSE INVESTIGATION
NOT RUNNING - OVERHEAT INVESTIGATION
PUMP AND HARNESS ASSEMBLY
DHW BURNER IGNITES
GAS VALVE ADJUSTMENT
DHW TOO HOT
GAS VALVE
DHW TOO HOT
PCB
DHW MAX PRESSURE
GAS VALVE ADJUSTMENT
DHW BURNER IGNITES
MAIN BURNER INJECTOR
PUMP DOES NOT RUN
HARNESS MAIN
PUMP DOES NOT RUN 2
HARNESS MAIN
FAN DOES NOT RUN
HARNESS MAIN
FAN DOES NOT RUN 2
HARNESS MAIN
CH BURNER IGNITES
HARNESS MAIN
DHW FAN RUNS
KIT - SWITCH AIR PRESSURE
CH DEMAND PUMP RUN
HARNESS MAIN
DHW FAN RUNS
HARNESS MAIN
BURNER DOES NOT CROSSLIGHT
MAIN BURNER INJECTOR
BURNER ESTABLISHES AT MIN PRESSURE
GAS VALVE ADJUSTMENT
FAN DOES NOT RUN
PCB
FAN RUNS SLOW
FAN ASSEMBLY
BURNER BAFFLES OUT DURING FULL DEMAND
CHARACTERISTIC TEST FROM DHW OPERATION
HEAT EXCHANGER NOISY (KETTLES) DURING DHW OPERATION
CHARACTERISTIC TEST FROM DHW OPERATION
DHW TOO COOL-RADIATORS REMAIN COOL WITH NO HEAT DEMAND-BOILER QUIET
CHARACTERISTIC TEST FROM DHW OPERATION
DHW QUIET OPERATION, BUT PUMP RUNS AND RADIATORS HEAT
CHARACTERISTIC TEST FROM DHW OPERATION
RADIATORS HEAT UP BUT HEAT EXCHANGER NOISY (KETTLES)
CHARACTERISTIC TEST FROM CH OPERATION
SYSTEM DOES NOT HEAT, BUT BOILER REACHES TEMPERATURE
CHARACTERISTIC TEST FROM CH OPERATION
BURNER PRESSURE DOESN'T RAMP UP, RADIATORS AND BOILER STAY COOL
CHARACTERISTIC TEST FROM CH OPERATION
BURNER IGNITES,SPARK STOPS,BURNER SHUTS DOWN, SEQUENCE RESTARTS
CHARACTERISTIC TEST FROM BURNER ESTABLISHES AT MINIMUM PRESSURE
FAN DOES NOT RUN
CHARACTERISTIC TEST FROM DHW FAN RUNS
FAN RUNS SLOW
CHARACTERISTIC TEST FROM DHW FAN RUNS
OVERHEAT TRIPS BEFORE 82°C
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER UP TO TEMPERATURE
FLOW TEMPERATURE ABOVE 82°C AND BOILER DOES NOT SHUT DOWN
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER UP TO TEMPERATURE
DHW TOO HOT
CHARACTERISTIC TEST FROM DHW OPERATION
MINIMUM BURNER PRESSURE CORRECT BUT DOES NOT FULLY CROSSLIGHT
CHARACTERISTIC TEST FROM BURNER ESTABLISHES AT MINIMUM PRESSURE
BURNER FULLY CROSSLIGHTS, SPARK DOESN'T STOP, BOILER LOCKS OUT
CHARACTERISTIC TEST FROM BURNER ESTABLISHES AT MINIMUM PRESSURE
MINIMUM BURNER PRESSURE INCORRECT
CHARACTERISTIC TEST FROM BURNER ESTABLISHES AT MINIMUM PRESSURE
01/12/2020 11:57:57 2012_1_50_1 04/01/2021 12:16:23
16/12/2020 13:33:58
MAINS POWER SUPPLY
REMOVE BOTTOM FACIA PANEL
EXTERNAL CONTROLS - ROOM THERMOSTAT (INPUT)
REMOVE BOTTOM FACIA PANEL
EXTERNAL CONTROLS - PROGRAMMER (INPUT)
REMOVE BOTTOM FACIA PANEL
CH THERMISTOR SENSOR
REMOVE THE RED LEADS FROM CH THERMISTOR
DHW MODULATION VOLTAGE
SET DHW FLOW RATE AT TAP TO APPROXIMATELY 5 L/MIN
AND ALLOW DHW TO RUN COLD
DHW THERMISTOR SENSOR
REMOVE THE YELLOW LE
CH THERMISTOR SENSOR
REMOVE THE RED LEADS FROM CH THERMISTOR
AIR PRESSURE SWITCH DROPPING OUT
DISCONNECT THE GREEN WIRE (NORMALLY OPEN CONNECTION) FROM THE AIR PRESSURE SWITCH AND MAKE SAFE
FUSE F2 (1.25 AMP)
REMOVE BOTTOM FACIA
INSPECTION CONTROL KNOB ON POTENTIOMETER
REMOVE CONTROL KNOB FROM THE FRONT OF THE BOILER
OVERHEAT THERMOSTAT (RESISTANCE)
DISCONNECT ONE OF THE ORANGE WIRES ON THE OVERHEAT THERMOSTAT
AIR PRESSURE SWITCH (AIR CHECK)
REMOVE THE AIR PRESSURE SWITCH FROM THE BOILER
(MAKE A NOTE OF THE CONNECTIONS)
DHW GAUZE FILTER
TURN OFF DHW INLET VALVE AND DRAIN DOWN THE DHW CIRCUIT
PUMP VOLTAGE
SELECTOR SWITCH TO CH
REMOVE BOTTOM FACIA PANEL
BY-PASS PIPE
TURN CH FLOW AND RETURN ISOLATING VALVES OFF
DRAIN AND DISCHARGE BOILER
GAS PRESSURE (INLET)
ATTACH A U-GAUGE TO THE GAS VALVE INLET PRESSURE TEST POINT
DHW FLOW SWITCH & HARNESS
REMOVE CONNECTOR X6 FROM THE PCB
DHW THERMISTOR SENSOR
REMOVE THE YELLOW LE
RESISTANCE FUSE (MAINS)
REMOVE THE FUSE FROM THE FUSED SPUR
RESISTANCE PUMP
REMOVE BOTTOM FACIA PANEL
DISCONNECT CONNECTOR X3 FROM THE PCB MARKED PUMP
DHW THERMISTOR SENSOR
REMOVE THE YELLOW LE
DHW THERMISTOR SENSOR
REMOVE THE YELLOW LE
CH THERMISTOR SENSOR
REMOVE THE RED LEADS FROM CH THERMISTOR
DHW THERMISTOR SENSOR
REMOVE THE YELLOW LE
CH THERMISTOR SENSOR
REMOVE THE RED LEADS FROM CH THERMISTOR
CH THERMISTOR SENSOR
REMOVE THE RED LEADS FROM CH THERMISTOR
DHW FLOW SWITCH
DISCONNECT THE TWO B
DHW FLOW SWITCH
DISCONNECT THE TWO B
BURNER PRESSURE IGNITION
SELECTOR SWITCH IN DHW POSITION
ATTACH A U-GAUGE TO THE GAS VALVE BURNER PRESSURE TEST POINT
GAS VALVE 1 & 2 RESISTANCE
REMOVE LOWER FACIA PANEL
DISCONNECT THE CONNECTOR X5 ON THE PCB (MARKED GV)
EXTERNAL CONTROLS - ROOM THERMOSTAT (OUTPUT)
REMOVE BOTTOM FACIA PANEL
EXTERNAL CONTROLS - PROGRAMMER (INPUT)
REMOVE BOTTOM FACIA PANEL
PUMP VOLTAGE
SELECTOR SWITCH TO CH
REMOVE BOTTOM FACIA PANEL
EXTERNAL CONTROLS - ROOM THERMOSTAT (OUTPUT)
REMOVE BOTTOM FACIA PANEL
EXTERNAL CONTROL - PROGRAMMER (OUTPUT)
REMOVE LOWER FACIA PANEL
EXTERNAL CONTROL - PROGRAMMER (OUTPUT)
REMOVE LOWER FACIA PANEL
CH THERMISTOR SENSOR & HARNESS
REMOVE CONNECTOR X6 FROM THE PCB
BURNER INJECTOR
REMOVE COMBUSTION CHAMBER COVER
REMOVE BURNER TO GAIN ACCESS TO BURNER INJECTOR
FUSE F1 (2 AMP)
REMOVE BOTTOM FACIA
BY-PASS PIPE
TURN CH FLOW AND RETURN ISOLATING VALVES OFF
DRAIN AND DISCHARGE BOILER
CH THERMISTOR SENSOR
REMOVE THE RED LEADS FROM CH THERMISTOR
EXTERNAL CONTROLS - ROOM THERMOSTAT (INPUT)
REMOVE BOTTOM FACIA PANEL
GAS PRESSURE (INLET)
ATTACH A U-GAUGE TO THE GAS VALVE INLET PRESSURE TEST POINT
GAS VALVE VOLTAGE
SELECTOR SWITCH IN DHW POSITION
AIR PRESSURE SWITCH (AIR CHECK)
REMOVE THE AIR PRESSURE SWITCH FROM THE BOILER
(MAKE A NOTE OF THE CONNECTIONS)
FLOW SENSOR (VENTURI)
REMOVE SILICONE RUBBER TUBES FROM THE VENTURI
INSPECTION CONTROL KNOB ON POTENTIOMETER
REMOVE CONTROL KNOB FROM THE FRONT OF THE BOILER
AIR PRESSURE SWITCH RESISTANCE (N/O)
DISCONNECT THE BROWN WIRE FROM THE AIR PRESSURE SWITCH COMMON TERMINAL
INSPECTION CONTROL KNOB ON POTENTIOMETER
REMOVE CONTROL KNOB FROM THE FRONT OF THE BOILER
CH THERMISTOR SENSOR
REMOVE THE RED LEADS FROM CH THERMISTOR
OVERHEAT FURTHER INVESTIGATION
RESET THE OVERHEAT THERMOSTAT BY PUSHING IN THE BUTTON UNDERNEATH THE BOILER.
AIR PRESSURE SWITCH TESTING KIT (AIR CHECK)
REMOVE PLUS AND MINU
SPARK ELECTRODES
REMOVE INNER CASING PANEL
PCB IGNITION RELAY OPERATION
REMOVE LOWER FACIA PANEL
SELECTOR SWITCH IN DHW POSITION
SPARK ELECTRODE LEADS
REMOVE THE ELECTRODE LEADS
FLOW SENSOR (VENTURI)
REMOVE SILICONE RUBBER TUBES FROM THE VENTURI
CH DEMAND PUMP RUN
SELECTOR SWITCH TO CH
ENSURE PUMP IS AT MAX SPEED SETTING
FAN VOLTAGE
SELECTOR SWITCH IN DHW POSITION
PRESSURE MINIMUM ON CH
ATTACH A U-GAUGE TO
CH OPERATION (OVERHEAT)
ENSURE ALL RADIATORS ARE TURNED ON
SELECTOR SWITCH TO CH - MAX POSITION
OBSERVATION RUN BOILER UP TO TEMPERATURE
ATTACH TEMPERATURE PROBE TO THE FLOW PIPE NEAR TO THE FLOW THERMISTOR
CH TEMPERATURE SET TO MAX
OVERRUN OPERATION
SELECTOR SWITCH TO CH - MAX POSITION
FAN VOLTAGE
SELECTOR SWITCH IN DHW POSITION
CH THERMISTOR SENSOR
REMOVE THE RED LEADS FROM CH THERMISTOR
GAS VALVE 3 (RESISTANCE)
REMOVE ONE OF THE BLUE WIRES ATTACHED TO THE MODULATING SOLENOID
DHW FLOW SWITCH
DISCONNECT THE TWO B
RESISTANCE FAN
REMOVE BOTTOM FACIA PANEL
DISCONNECT CONNECTOR X4 FROM THE PCB MARKED FAN
GAS VALVE 1 & 2 RESISTANCE
REMOVE LOWER FACIA PANEL
DISCONNECT THE CONNECTOR X5 ON THE PCB (MARKED GV)
GAS VALVE 3 (RESISTANCE)
REMOVE ONE OF THE BLUE WIRES ATTACHED TO THE MODULATING SOLENOID
AIR PRESSURE SWITCH RESISTANCE (N/C)
DISCONNECT THE BROWN WIRE FROM THE AIR PRESSURE SWITCH COMMON TERMINAL
DHW FLOW SWITCH & HARNESS
REMOVE CONNECTOR X6 FROM THE PCB
DHW THERMISTOR SENSOR & HARNESS
REMOVE CONNECTOR X6
CH THERMISTOR SENSOR & HARNESS
REMOVE CONNECTOR X6 FROM THE PCB
INSPECTION CONTROL KNOB ON POTENTIOMETER
REMOVE CONTROL KNOB FROM THE FRONT OF THE BOILER
ADJUSTMENT GAS VALVE
ATTEMPT TO ADJUST TH
DHW THERMISTOR SENSOR & HARNESS
REMOVE CONNECTOR X6
ADJUSTMENT GAS VALVE
ATTEMPT TO ADJUST TH
DHW MODULATION VOLTAGE
SET DHW FLOW RATE AT TAP TO APPROXIMATELY 5 L/MIN
AND ALLOW DHW TO RUN COLD
FLOW SENSOR (VENTURI)
REMOVE SILICONE RUBBER TUBES FROM THE VENTURI
GAS PRESSURE (INLET)
ATTACH A U-GAUGE TO THE GAS VALVE INLET PRESSURE TEST POINT
ADJUSTMENT GAS VALVE
ATTEMPT TO ADJUST TH
CH THERMISTOR SENSOR & HARNESS
REMOVE CONNECTOR X6 FROM THE PCB
DHW FLOW RESTRICTOR
TURN OFF DHW INLET VALVE AND DRAIN DOWN THE DHW CIRCUIT.
GAS VALVE 1 & 2 VOLTAGE
SELECTOR SWITCH IN DHW POSITION
GAS PRESSURE (INLET)
ATTACH A U-GAUGE TO THE GAS VALVE INLET PRESSURE TEST POINT
FLAME SENSE (OUTPUT)
DISCONNECT FLAME SEN
System Information
- Total Tests: 276
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control