Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Remove bottom facia panel
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Measure the voltage across the connection RL on connector block X2 and the neutral (marked N) on connector block X1.
Both connector blocks are situated at the bottom L/H side of the PCB.
Note:
If no room thermostat is fitted a link will be present between "Rl" and "RL".
Both connector blocks are situated at the bottom L/H side of the PCB.
Note:
If no room thermostat is fitted a link will be present between "Rl" and "RL".

Isolate as per TOPs P4
and refit as necessary