XSol Diagnostic System

Interactive Test Sequence Navigator

Welcome to the XSol Diagnostic System

This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.

Start Diagnostic Sequence

or choose a specific test below:

WORCESTER 24 CDI BF

GLOBALLY REPLACED

Next: &20, *

RE-IGNITE DELAY

BOILER ON/OFF SWITCH ON

Next: &nff, !f125

OVERRUN OPERATION

BOILER ON/OFF SWITCH ON

Next: &1, !f124

FLUE

Next: &2, !f92

CH MODULATION

{ISOLATEMAINSPOWER}<

Next: &3, f121

EXCESSIVE SYSTEM PRESSURE RISE

BOILER ON/OFF SWITCH ON
CH TEMPERATURE SELECTOR TO MAXIMUM
ROOM THERMOSTAT (IF FITTED) CALLING

Next: &170, !f120

DHW MODULATION

{ISOLATEMAINSPOWER}<

Next: &5, f111

GAS VALVE SOUNDNESS

Next: &149, !f96

AUTOMATIC FROST PROTECTION

CH TEMPERATURE SELECTOR TO OFF
DHW TEMPERATURE SELECTOR TO MINIMUM
BOILER ON/OFF SWITCH ON

Next: &9, f93

CH BURNER IGNITES

{ISOLATEMAINSPOWER}<

Next: &10, ?82, ?84

DHW HIGH FLAME

{ISOLATEMAINSPOWER}<

Next: &11, f397

DHW LOW FLAME

{ISOLATEMAINSPOWER}<

Next: &12, f450

DHW BURNER IGNITES

{ISOLATEMAINSPOWER}<

Next: &138, ?51, ?53, ?55, ?57

DHW PUMP RUNS

Next: &15, f33

DHW DEMAND

{ISOLATEMAINSPOWER}
REMOVE PLASTIC COVER FROM DIVERTER VALVE MICROSWITCH

Next: &16, f30

DHW FLOW RATE

Next: &17, f429

SYSTEM CHECKS

{ISOLATEMAINSPOWER}

Next: &351, !f22

WORCESTER 24 CDI BF

{ISOLATEMAINSPOWER}<

Next: &19, !f21

DHW OPERATION

DHW TEMPERATURE SELECTOR TO MAXIMUM

Next: &7, ?150, ?154, ?199, ?367

CENTRAL HEATING OPERATION

BOILER ON/OFF SWITCH ON
ROOM THERMOSTAT (IF FITTED) CALLING

Next: &4, ?171, ?173, ?385

FAIL POINT A

OUTSIDE MODEL

Next: &nff, f210

FAIL POINT B

OUTSIDE MODEL

Next: &nff, f216

FAIL POINT C

OUTSIDE MODEL

Next: &nff, f222

FAIL POINT D

OUTSIDE MODEL

Next: &nff, f226

FAIL POINT E

OUTSIDE MODEL

Next: &nff, f234

FAIL POINT F

OUTSIDE MODEL

Next: &nff, f248

FAIL POINT G

OUTSIDE MODEL

Next: &nff, f254

FAIL POINT H - LINK TO DHW BURNER IGNITES

OUTSIDE MODEL

Next: &nff, !f295

FAIL POINT I

OUTSIDE MODEL

Next: &nff, f297

FAIL POINT J

OUTSIDE MODEL

Next: &nff, f355

FAIL POINT K

OUTSIDE MODEL

Next: &nff, f348

TYPE OF DIAGNOSTIC PROCEDURE

PLEASE SELECT FROM O

Next: &353, !f352

FAULT CODES

Next: &18, !f354

FUSE INVESTIGATION TREE

OUTSIDE MODEL

Next: &nff, f481

DHW MODULATION

THERMISTOR SENSOR

Next: End

EXPANSION VESSEL

EXPANSION VESSEL

Next: End

CH MODULATION

PRIMARY SENSOR

Next: End

OVERRUN OPERATION

PCB - BOSCH HEATRONIC

Next: End

RE-IGNITION DELAY

PCB - BOSCH HEATRONIC

Next: End

NO GAS PRESSURE, NO SPARKING PRESENT

DIVERTER VALVE SWITCH ASSEMBLY

Next: End

NO GAS PRESSURE, NO SPARKING PRESENT

THERMISTOR SENSOR

Next: End

NO GAS PRESSURE, NO SPARKING PRESENT

PRIMARY SENSOR

Next: End

10K RESISTOR

HARNESS - MAIN

Next: End

DHW BURNER IGNITES

PCB - BOSCH HEATRONIC

Next: End

BURNER NOT ESTABLISHING

GAS INLET PRESSURE

Next: End

MINIMUM GAS PRESSURE

GAS VALVE - MULTIFUNCTION - DUNGS

Next: End

CH NOISY

PUMP C/W LEAD - CIRCULATING - GRUNDFOS

Next: End

BOILER NOISY

PRIMARY SENSOR

Next: End

CH OP NOISY

HEAT EXCHANGER - GAS TO WATER - INTER ALBION

Next: End

RADS DO NOT HEAT

ISOLATING VALVE 22MM

Next: End

RADS DO NOT HEAT

PUMP C/W LEAD - CIRCULATING - GRUNDFOS

Next: End

CH RADS COLD

DIVERTER VALVE ASSEMBLY - INTER ALBION

Next: End

DHW NOISY

HEAT EXCHANGER - GAS TO WATER - INTER ALBION

Next: End

DHW NOISY

PUMP C/W LEAD - CIRCULATING - GRUNDFOS

Next: End

DHW NOISY

THERMISTOR SENSOR

Next: End

DHW RUNS HOT AND COLD DHW MODULATION

THERMISTOR SENSOR

Next: End

DHW HOT AND COLD

HEAT EXCHANGER - GAS TO WATER - INTER ALBION

Next: End

DHW COOL RADS COOL

PUMP C/W LEAD - CIRCULATING - GRUNDFOS

Next: End

ELECTRICAL CHECKS

ELECTRICAL CHECKS

Next: End

FAIL POINT A

FUSE 2 AMP

Next: End

FAIL POINT A

Next: End

FAIL POINT B

FUSE 1.25 AMP

Next: End

SYSTEM CHECKS

SYSTEM CHECKS

Next: End

FAIL POINT B

TRANSFORMER - JUNKER

Next: End

FAIL POINT C

PCB - BOSCH HEATRONIC

Next: End

FAIL POINT D

Next: End

FAIL POINT D - NEON FAULTY

PCB - BOSCH HEATRONIC

Next: End

FAIL POINT E

KIT - DIAPHRAGM - REPLACEMENT

Next: End

FAIL POINT E

DIVERTER VALVE SWITCH ASSEMBLY

Next: End

FAIL POINT E - NEON FAULTY

PCB - BOSCH HEATRONIC

Next: End

FAIL POINT F

FROST PROTECTION

Next: End

FAIL POINT F

PRIMARY SENSOR (AUTO FROST)

Next: End

FAIL POINT G - NO POWER TO PUMP

PCB - BOSCH HEATRONIC

Next: End

FAIL POINT G - RUNNING SLOW

PUMP C/W LEAD - CIRCULATING - GRUNDFOS

Next: End

FAIL POINT G

GAS INLET PRESSURE

Next: End

FAIL POINT G - BOSCH GV

GAS VALVE - MULTIFUNCTION - DUNGS

Next: End

FAIL POINT G - DUNGS GV

GAS VALVE - MULTIFUNCTION - DUNGS

Next: End

FAIL POINT G

PCB ADJUSTMENT

Next: End

FAIL POINT G

HEAT EXCHANGER - GAS TO WATER - INTER ALBION

Next: End

FAIL POINT G

PLATE HEAT EXCHANGER - INTER ALBION

Next: End

FAIL POINT G

PRIMARY SENSOR

Next: End

FAIL POINT G - NO PUMP OVERRUN

PCB - BOSCH HEATRONIC

Next: End

FAIL POINT H

Z REDIRECT

Next: End

DIVERTER VALVE (DIAPHRAGM)

KIT - DIAPHRAGM - REPLACEMENT

Next: End

FAIL POINT K

Z REDIRECT

Next: End

TYPE OF DIAGNOSTIC PROCEDURE

Z REDIRECT

Next: End

FAULT CODES

Z REDIRECT

Next: End

FAIL POINT J10K RESISTOR

HARNESS - MAIN

Next: End

DHW COOL

PUMP C/W LEAD - CIRCULATING - GRUNDFOS

Next: End

DHW TOO COOL

HEAT EXCHANGER - GAS TO WATER - INTER ALBION

Next: End

DHW COOL RADS COOL

THERMISTOR SENSOR

Next: End

DHW COOL RADS COOL

PRIMARY SENSOR

Next: End

CH OPERATION SHUTTING DOWN EARLY

PRIMARY SENSOR

Next: End

DHW HIGH FLAME

GAS INLET PRESSURE

Next: End

DHW HIGH FLAME RESISTANCE

GAS VALVE - MULTIFUNCTION - DUNGS

Next: End

PCB (24 VOLT SUPPLY)

PCB - BOSCH HEATRONIC

Next: End

DHW BURNER IGNITES

GAS INLET PRESSURE

Next: End

DHW FLOW ADJUSTER

DHW FLOW ADJUSTER

Next: End

TRANSFORMER

TRANSFORMER - JUNKER

Next: End

DHW INLET FILTER

FILTER STAINLESS STEEL

Next: End

FLOW RESTRICTOR

FLOW REGULATOR

Next: End

DHW FLOW RATE

MAINS WATER SUPPLY

Next: End

DHW BURNER ESTABLISHES - LEAD DAMAGED

PROBE - FLAME SENSOR C/W LEAD

Next: End

FLAME SENSE ELECTRODE

HARNESS MAIN

Next: End

DHW LOW FLAME

GAS INLET PRESSURE

Next: End

DHW LOW FLAME - BOSCH GV

GAS VALVE - MULTIFUNCTION - DUNGS

Next: End

DHW LOW FLAME - DUNGS GV

GAS VALVE - MULTIFUNCTION - DUNGS

Next: End

HIGH FLAME - BOSCH GV

GAS VALVE - MULTIFUNCTION - DUNGS

Next: End

HIGH FLAME - DUNGS GV

GAS VALVE - MULTIFUNCTION - DUNGS

Next: End

DHW PUMP RUNS

FUSE 1.25 AMP

Next: End

DHW PUMP RUNS

FUSE 2 AMP

Next: End

DHW PUMP RUNS

MAINS FUSE

Next: End

DIVERTER VALVE MICROSWITCH

DIVERTER VALVE SWITCH ASSEMBLY

Next: End

FUSE INVESTIGATION

PUMP C/W LEAD - CIRCULATING - GRUNDFOS

Next: End

FUSE INVESTIGATION - MAIN

GAS VALVE - MULTIFUNCTION - DUNGS

Next: End

FUSE INVESTIGATION - MODUREG

GAS VALVE - MULTIFUNCTION - DUNGS

Next: End

FAIL POINT I

PRIMARY SENSOR

Next: End

FAIL POINT I

THERMISTOR SENSOR

Next: End

FAULT CODE G

THERMOSTAT - OVERHEAT - ELMWOOD

Next: End

PCB (IGNITION TRANSFORMER)

PCB - BOSCH HEATRONIC

Next: End

SPARK ELECTRODES

SPARK ELECTRODE ASSEMBLY

Next: End

DHW BURNER IGNITES

SPARK ELECTRODE ASSEMBLY

Next: End

OVERHEAT THERMOSTAT

THERMOSTAT - OVERHEAT - ELMWOOD

Next: End

GAS VALVE (SOLENOIDS)

GAS VALVE - MULTIFUNCTION - DUNGS

Next: End

PRIMARY SENSOR

PRIMARY SENSOR

Next: End

FLUE

FLUE

Next: End

PRIMARY SENSOR (AUTO FROST)

PRIMARY SENSOR (AUTO FROST)

Next: End

GAS VALVE SOUNDNESS

GAS VALVE - MULTIFUNCTION - DUNGS

Next: End

DHW MODULATION

PCB - BOSCH HEATRONIC

Next: End

CH MODULATION

PCB - BOSCH HEATRONIC

Next: End

PCB (LOCKOUT RESET STATUS)

PCB (LOCKOUT RESET STATUS)

Next: End

DIVERTER VALVE

DIVERTER VALVE ASSEMBLY - INTER ALBION

Next: End

CH OP NOISY

Next: End

RADS DO NOT HEAT

Next: End

DHW OPERATION NOISY

PLATE HEAT EXCHANGER - INTER ALBION

Next: End

DHW RUNS HOT AND COLDDHW MODULATION

PCB - BOSCH HEATRONIC

Next: End

DHW OPERATION HOT AND COLD

PLATE HEAT EXCHANGER - INTER ALBION

Next: End

FAIL POINT A

PCB - BOSCH HEATRONIC

Next: End

FAIL POINT B

PCB - BOSCH HEATRONIC

Next: End

FAIL POINT C

Z REDIRECT

Next: End

FAIL POINT D - IGNORING CH DEMAND

PCB - BOSCH HEATRONIC

Next: End

FAIL POINT D

Z REDIRECT

Next: End

FAIL POINT E

DIVERTER VALVE (SPINDLE)

Next: End

FAIL POINT E

PCB - BOSCH HEATRONIC

Next: End

FAIL POINT E

Z REDIRECT

Next: End

FAIL POINT F

PCB - BOSCH HEATRONIC

Next: End

FAIL POINT G

PRESSURE GAUGE

Next: End

FAIL POINT G

SYSTEM PRESSURE

Next: End

FAIL POINT G - NOT RUNNING

PUMP C/W LEAD - CIRCULATING - GRUNDFOS

Next: End

FAIL POINT G - BOSCH GV

GAS VALVE ADJUSTMENT

Next: End

FAIL POINT G - DUNGS GV

GAS VALVE ADJUSTMENT

Next: End

FAIL POINT G

Next: End

FAIL POINT G

THERMOSTAT - OVERHEAT - ELMWOOD

Next: End

FAIL POINT G - NOT SHUTTING DOWN

PCB - BOSCH HEATRONIC

Next: End

NO FAULT FOUND

OVERHEAT

Next: End

FAIL POINT I

PCB - BOSCH HEATRONIC

Next: End

DIVERTER VALVE (SPINDLE)

DIVERTER VALVE (SPINDLE)

Next: End

FAIL POINT K

PCB - BOSCH HEATRONIC

Next: End

FAIL POINT J

PCB - BOSCH HEATRONIC

Next: End

DHW COOL RADIATORS COOL

PLATE HEAT EXCHANGER - INTER ALBION

Next: End

DHW TOO COOL

PCB - BOSCH HEATRONIC

Next: End

DHW TOO COOL RADS COLD

INJECTOR NO7 4.5MM - MAIN BURNER - NG

Next: End

DHW TOO COOL RADS COLD

BURNER - AEROMATIC

Next: End

CH OPERATION SHUTTING DOWN EARLY

PCB - BOSCH HEATRONIC

Next: End

GAS VALVE

GAS VALVE - MULTIFUNCTION - DUNGS

Next: End

CH BURNER IGNITES

PCB - BOSCH HEATRONIC

Next: End

SECONDARY HEAT EXCHANGER (SCALED)

PLATE HEAT EXCHANGER - INTER ALBION

Next: End

DHW BURNER ESTABLISHED (FLAME SENSE)

PCB - BOSCH HEATRONIC

Next: End

PCB

PCB - BOSCH HEATRONIC

Next: End

DHW LOW FLAME - BOSCH GV

GAS VALVE ADJUSTMENT

Next: End

DHW LOW FLAME - DUNGS GV

GAS VALVE ADJUSTMENT

Next: End

HIGH FLAMED - BOSCH GV

GAS VALVE ADJUSTMENT

Next: End

HIGH FLAMED - DUNGS GV

GAS VALVE ADJUSTMENT

Next: End

DHW PUMP RUNS - F2

Z REDIRECT

Next: End

PUMP

PUMP C/W LEAD - CIRCULATING - GRUNDFOS

Next: End

DHW PUMP RUNS - F1

Z REDIRECT

Next: End

ON / OFF SWITCH

PCB - BOSCH HEATRONIC

Next: End

DHW PUMP RUNS

Next: End

DHW PUMP RUNS - MAINS

Z REDIRECT

Next: End

PCB

PCB - BOSCH HEATRONIC

Next: End

FUSE INVESTIGATION

PCB - FUSE INVESTIGATION

Next: End

FAIL POINT I - PRIMARY SENSOR

HARNESS MAIN

Next: End

FAIL POINT I - DHW SENSOR

HARNESS MAIN

Next: End

SPARK ELECTRODE LEADS

HARNESS ASSEMBLY - IGNITION

Next: End

BURNER INJECTOR

INJECTOR NO7 4.5MM - MAIN BURNER - NG

Next: End

CH BURNER IGNITES

DIVERTER VALVE SWITCH ASSEMBLY

Next: End

PCB (AUTO FROST SENSOR)

PCB - BOSCH HEATRONIC

Next: End

DHW NOISY

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p187

TEMPERATURE RISE BELOW SPECIFICATION, RADIATORS WARM

CHARACTERISTIC TEST FROM DHW OPERATION

Next: !p155

BOILER REACHES TEMPERATURE, RADS DO NOT HEAT

CHARACTERISTIC TEST FROM CH OPERATION

Next: p172

BOILER NOISY

CHARACTERISTIC TEST FROM CH OPERATION

Next: p174

DHW RUNS HOT AND COLD

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p200

PRESSURE READS CORRECTLY BUT DOES NOT INCREASE

CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM

Next: !p257

SYSTEM PRESSURE LOW

CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM

Next: !p259

RETURNS TO OVERHEAT FAULT CODE BEFORE 82°C

CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER UP TO TEMPERATURE

Next: !p287

FLOW TEMPERATURE ABOVE 82°C AND BOILER DOES NOT SHUT DOWN

CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER UP TO TEMPERATURE

Next: p289

DHW TOO COOL, RADIATORS COLD

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p368

BURNER INJECTOR BLOCKED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION BURNER AND INJECTOR

Next: !p382

BURNER BLOCKED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION BURNER AND INJECTOR

Next: !p384

SYSTEM BEGINS TO HEAT BUT BOILER SHUTS DOWN BEFORE REACHING TEMPERATURE

CHARACTERISTIC TEST FROM CH OPERATION

Next: p386

GAS PRESSURE PRESENT, NO SPARKING

CHARACTERISTIC TEST FROM DHW BURNER IGNITES

Next: p52

GAS PRESSURE AND SPARKING PRESENT BUT NO IGNITION

CHARACTERISTIC TEST FROM DHW BURNER IGNITES

Next: p54

NO GAS PRESSURE, NO SPARKING PRESENT

CHARACTERISTIC TEST FROM DHW BURNER IGNITES

Next: p56

SPARKING BUT NO GAS PRESSURE

CHARACTERISTIC TEST FROM DHW BURNER IGNITES

Next: p58

BURNER IGNITES AT HIGH FLAME

CHARACTERISTIC TEST FROM CH BURNER IGNITES

Next: !p83

BURNER DOES NOT IGNITE OR IGNITES BUT DOES NOT RAMP UP

CHARACTERISTIC TEST FROM CH BURNER IGNITES

Next: p85

DHW SENSOR MODULATION RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT YELLOW WIRES FROM DHW SENSOR

Next: !p113, !f112

PRIMARY SENSOR (CH MODULATION)

{ISOLATEMAINSPOWER}
REMOVE RED WIRES FROM CH SENSOR

Next: !p123, !f122

PRESSURE GAS INLET

{ISOLATEMAINSPOWER}<

Next: p140, !f141

DHW SENSOR MODULATION RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT YELLOW WIRES FROM DHW SENSOR

Next: !p204, !f205

FUSE F1 (2 AMP) (FAULT CODE)

{ISOLATEMAINSPOWER}
REMOVE FUSE F1 FROM PCB

Next: p211, !f212

FUSE F2 (1.25 AMP) (FAULT CODE)

{ISOLATEMAINSPOWER}
REMOVE FUSE F2 FROM PCB

Next: p217, !f218

INFORMATION FAIL POINT C

Next: !p223, !f224

ROOM THERMOSTAT/EXTERNAL CONTROLS RESISTANCE

{ISOLATEMAINSPOWER}
ROOM THERMOSTAT (IF FITTED) CALLING

Next: !p229, !f230

DHW DEMAND

{ISOLATEMAINSPOWER}
REMOVE PLASTIC COVER FROM DIVERTER VALVE MICROSWITCH

Next: p237, f238

DIVERTER VALVE DIAPHRAGM

{ISOLATEMAINSPOWER}
WATER OFF
DRAIN AND DISCHARGE BOILER

Next: !p239, !f240

TEMPERATURE AMBIENT

{ISOLATEMAINSPOWER}

Next: p249, !f250

INSPECTION PRESSURE SYSTEM

Next: p509, ?256, ?258

PUMP VOLTAGE

Next: !p262, !f263

PRESSURE GAS INLET

{ISOLATEMAINSPOWER}<

Next: p268, !f269

ADJUSTMENT PRESSURE MAX AND MIN (BOSCH)

{ISOLATEMAINSPOWER}<

Next: !p272, !f273

DIFFERENTIAL PLATE HEAT EX

{ISOLATEMAINSPOWER}
ATTACH TEMPERATURE CLAMPS TO PRIMARY FLOW AND RETURN AS INDICATED

Next: !p280, !f281

RESISTANCE PRIMARY SENSOR AT PCB (FAULT CODE)

{ISOLATEMAINSPOWER}
DISCONNECT PLUG CONNECTOR (MARKED ST16) FROM PCB

Next: p298, f503

DIVERTER VALVE DIAPHRAGM

{ISOLATEMAINSPOWER}
WATER OFF
DRAIN AND DISCHARGE BOILER

Next: !p32, !f31

ON/OFF SWITCH VOLTAGE (OUTPUT)

BOILER ON/OFF SWITCH ON

Next: p35, f469

INFORMATION FAIL POINT K

{ISOLATEMAINSPOWER}<

Next: !p349, !f350

10K RESISTOR FAULT CODE

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR MARKED ST16 FROM PCB

Next: !p366, !f357

DIFFERENTIAL PRIMARY HEAT EXCHANGER

{ISOLATEMAINSPOWER}
ATTACH TEMPERATURE CLAMPS TO PRIMARY FLOW AND RETURN AS INDICATED

Next: !p373, !f374

PRESSURE GAS INLET

{ISOLATEMAINSPOWER}<

Next: p409, !f408

FUSE F2 (1.25 AMP)

{ISOLATEMAINSPOWER}
REMOVE FUSE F2 FROM PCB

Next: p43, f466

PRESSURE GAS INLET

{ISOLATEMAINSPOWER}<

Next: p451, !f452

ADJUSTMENT PRESSURE MAX AND MIN (BOSCH)

{ISOLATEMAINSPOWER}<

Next: !p455, !f456

DIVERTER VALVE MICROSWITCH RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT PLUG CONNECTOR (MARKED ST16) FROM PCB

Next: !p49, !f48

ADJUSTMENT PRESSURE MAX AND MIN (BOSCH)

{ISOLATEMAINSPOWER}<

Next: !p462, !f463

FUSE FURTHER INVESTIGATION

Next: !p467, !f468

FUSE F1 (2 AMP)

{ISOLATEMAINSPOWER}
REMOVE FUSE F1 FROM PCB

Next: p470, f471

FUSE FURTHER INVESTIGATION

Next: !p472, !f473

RESISTANCE MAINS FUSE

{ISOLATEMAINSPOWER}
REMOVE THE FUSE FROM THE FUSED SPUR

Next: !p476, f477

FUSE FURTHER INVESTIGATION

Next: !p478, !f479

RESISTANCE PUMP AND HARNESS (FUSE INVESTIGATION)

{ISOLATEMAINSPOWER}
DISCONNECT PLUG ST15 FROM THE PCB

Next: p498, !f483

PRIMARY SENSOR FAULT CODE

{ISOLATEMAINSPOWER}
REMOVE RED WIRES FROM CH TEMPERATURE SENSOR

Next: !p504, !f505

DHW SENSOR (CALLING)

{ISOLATEMAINSPOWER}
DISCONNECT YELLOW WIRES FROM DHW SENSOR
ENSURE DHW IS COOL

Next: !p507, !f508

PRIMARY SENSOR (AUTO FROST)

{ISOLATEMAINSPOWER}
DISCONNECT RED LEADS FROM SENSOR

Next: !p95, !f94

10K RESISTOR

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR MARKED ST16 FROM PCB

Next: p129, !f136

PRIMARY SENSOR (CH CALLING)

{ISOLATEMAINSPOWER}
REMOVE RED WIRES FROM CH TEMPERATURE SENSOR

Next: p130, !f135

DHW SENSOR (CALLING)

{ISOLATEMAINSPOWER}
DISCONNECT YELLOW WIRES FROM DHW SENSOR
ENSURE DHW IS COOL

Next: p131, !f134

DIVERTER VALVE MICROSWITCH (RESISTANCE)

{ISOLATEMAINSPOWER}
DISCONNECT PLUG CONNECTOR (MARKED ST16) FROM PCB

Next: !p132, !f133

PRESSURE GAS IGNITION

{ISOLATEMAINSPOWER}<

Next: p445, !f143

INSPECTION ISOLATION VALVES FLOW AND RETURN

{ISOLATEMAINSPOWER}

Next: p181, !f182

PUMP LIMPET TEST

Next: p175, !f176

RESISTANCE PRIMARY SENSOR

{ISOLATEMAINSPOWER}
REMOVE YELLOW WIRES FROM DHW SENSOR

Next: p177, !f178

TEMPERATURE DIFFERENTIAL CH

{ISOLATEMAINSPOWER}<

Next: !p179, !f180

PUMP LIMPET TEST

Next: p183, !f184

CH DIVERTER CHECK

ENSURE SECONDARY HEA

Next: !p185, !f186

PUMP LIMPET TEST

Next: p194, !f193

CENTRAL HEATING OPERATION

BOILER ON/OFF SWITCH ON
ROOM THERMOSTAT (IF FITTED) CALLING

Next: !p191, !f192

RESISTANCE DHW SENSOR

{ISOLATEMAINSPOWER}
REMOVE YELLOW WIRES FROM DHW SENSOR

Next: p190, !f198

PUMP LIMPET TEST

Next: p201, !f208

DHW MODULATION

{ISOLATEMAINSPOWER}<

Next: p202, f203

TEMPERATURE DIFFERENTIAL CH

{ISOLATEMAINSPOWER}<

Next: !p206, !f207

MAINS POWER

BOILER ON/OFF SWITCH ON

Next: !p213, !f214

TRANSFORMER RESISTANCE

{ISOLATEMAINSPOWER}<

Next: !p219, !f220

INFORMATION FAIL POINT D

Next: !p231, !f232

INFORMATION FAIL POINT E

Next: !p245, !f246

DIVERTER VALVE MICROSWITCH RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT PLUG CONNECTOR (MARKED ST16) FROM PCB

Next: !p241, !f242

PRIMARY SENSOR (CH HIGH FLAME)

{ISOLATEMAINSPOWER}
REMOVE RED WIRES FROM CH SENSOR

Next: !p251, !f252

DHW PUMP RUNS

Next: p260, f261

PUMP LIMPET TEST

Next: p264, !f265

PRESSURE BURNER MAX AND MIN

{ISOLATEMAINSPOWER}<

Next: p266, f267

PRESSURE BURNER CH MODE

{ISOLATEMAINSPOWER}<

Next: p276, !f277

OBSERVATION GAS VALVE TYPE

THE GAS VALVE WILL N

Next: p270, f271

ADJUSTMENT PRESSURE MAX AND MIN (DUNGS)

{ISOLATEMAINSPOWER}<

Next: !p274, !f275

DIFFERENTIAL PRIMARY HEAT EXCHANGER

{ISOLATEMAINSPOWER}
ATTACH TEMPERATURE CLAMPS TO PRIMARY FLOW AND RETURN AS INDICATED

Next: p278, f279

DIFFERENTIAL PLATE HEAT EX

{ISOLATEMAINSPOWER}
ATTACH TEMPERATURE CLAMPS TO PRIMARY FLOW AND RETURN AS INDICATED

Next: p282, !f283

OBSERVATION RUN BOILER UP TO TEMPERATURE

{ISOLATEMAINSPOWER}<

Next: p284, ?286, ?288

OVERRUN OPERATION

BOILER ON/OFF SWITCH ON

Next: !p292, !f293

PRIMARY SENSOR (CH HIGH FLAME)

{ISOLATEMAINSPOWER}
REMOVE RED WIRES FROM CH SENSOR

Next: !p290, !f291

RESISTANCE DHW SENSOR AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT PLUG CONNECTOR (MARKED ST16) FROM PCB

Next: !p302, f506

TRANSFORMER VOLTAGE (OUTPUT)

BOILER ON/OFF SWITCH ON

Next: p41, f40

PUMP LIMPET TEST

Next: p369, !f370

DIFFERENTIAL PLATE HEAT EX

{ISOLATEMAINSPOWER}
ATTACH TEMPERATURE CLAMPS TO PRIMARY FLOW AND RETURN AS INDICATED

Next: p371, f372

RESISTANCE DHW SENSOR

{ISOLATEMAINSPOWER}
REMOVE YELLOW WIRES FROM DHW SENSOR

Next: p375, !f376

PRIMARY SENSOR (CH HIGH FLAME)

{ISOLATEMAINSPOWER}
REMOVE RED WIRES FROM CH SENSOR

Next: p377, !f378

INSPECTION BURNER AND INJECTOR

{ISOLATEMAINSPOWER}
REMOVE THE BURNER ASSEMBLY FROM THE BOILER

Next: !p379, ?381, ?383

PRIMARY SENSOR (CH HIGH FLAME)

{ISOLATEMAINSPOWER}
REMOVE RED WIRES FROM CH SENSOR

Next: !p387, !f388

FULL VOLTAGE MODULATING SOLENOID

{ISOLATEMAINSPOWER}<

Next: p459, !f417

RESISTANCE GAS VALVE MODULATING SOLENOID

{ISOLATEMAINSPOWER}
DISCONNECT PLUG CONNECTOR (MARKED ST16) FROM PCB

Next: p403, !f415

PUMP VOLTAGE

Next: !p47, f46

PRESSURE GAS INLET

{ISOLATEMAINSPOWER}<

Next: !p424, !f425

ROOM THERMOSTAT/EXTERNAL CONTROLS RESISTANCE

{ISOLATEMAINSPOWER}
ROOM THERMOSTAT (IF FITTED) CALLING

Next: !p427, !f428

TRANSFORMER RESISTANCE

{ISOLATEMAINSPOWER}<

Next: !p45, !f44

DHW FLOW RATE ADJUSTER

{ISOLATEMAINSPOWER}

Next: p438, !f439

DHW INLET FILTER

{ISOLATEMAINSPOWER}
WATER OFF
BOILER DRAINED AND DISCHARGED

Next: p440, !f441

FLOW RESTRICTOR

{ISOLATEMAINSPOWER}
WATER OFF
BOILER DRAINED AND DISCHARGED

Next: !p442, !f443

RESISTANCE FLAME SENSE ELECTRODE

{ISOLATEMAINSPOWER}

Next: p446, !f447

RESISTANCE FLAME SENSE LEAD

{ISOLATEMAINSPOWER}<

Next: !p448, !f449

OBSERVATION GAS VALVE TYPE

THE GAS VALVE WILL N

Next: p453, f454

ADJUSTMENT PRESSURE MAX AND MIN (DUNGS)

{ISOLATEMAINSPOWER}<

Next: !p457, !f458

OBSERVATION GAS VALVE TYPE

THE GAS VALVE WILL N

Next: p460, f461

ADJUSTMENT PRESSURE MAX AND MIN (DUNGS)

{ISOLATEMAINSPOWER}<

Next: !p464, !f465

MAINS POWER

BOILER ON/OFF SWITCH ON

Next: !p474, f475

MAIN GAS VALVE SOLENOID RESISTANCE (FUSE INVESTIGATION)

{ISOLATEMAINSPOWER}
DISCONNECT PLUG CONNECTOR (MARKED ST16) FROM PCB

Next: p499, !f500

RESISTANCE GAS VALVE MODULATING SOLENOID (FUSE INVESTIGATION)

{ISOLATEMAINSPOWER}
DISCONNECT PLUG CONNECTOR (MARKED ST16) FROM PCB

Next: !p501, !f502

OVERHEAT THERMOSTAT RESISTANCE - FAULT CODE

{ISOLATEMAINSPOWER}
DISCONNECT ORANGE WIRES FROM OVERHEAT THERMOSTAT
ENSURE BOILER IS COOL

Next: p255, !f545

IGNITION TRANSFORMER (OPERATION)

{ISOLATEMAINSPOWER}
DISCONNECT ELECTRODE LEADS FROM ELECTRODES AND MAKE SAFE

Next: p60, !f59

SPARK ELECTRODES

{ISOLATEMAINSPOWER}

Next: !p64, !f63

OVERHEAT THERMOSTAT RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT ORANGE WIRES FROM OVERHEAT THERMOSTAT

Next: p128, !f65

MAIN GAS VALVE SOLENOID RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT PLUG CONNECTOR (MARKED ST16) FROM PCB

Next: p68, !f67

SPARK ELECTRODES

{ISOLATEMAINSPOWER}

Next: !p62, !f61

MAIN GAS VALVE VOLTAGE

{ISOLATEMAINSPOWER}<

Next: p423, !f137

PRIMARY SENSOR (CH HIGH FLAME)

{ISOLATEMAINSPOWER}
REMOVE RED WIRES FROM CH SENSOR

Next: p426, !f86

System Information

  • Total Tests: 318
  • Sequence Logic: Decoded from encrypted .seq file
  • Navigation: Dynamic based on pass/fail results
  • Source: 4731307 GW SWIFTFLOW 100 SIT Control