Set Appliance State:

CH Demand
Isolate Mains Power to appliance as per TOPs P4
Boiler ON/OFF switch ON
Room thermostat (if fitted) calling
Attach temperature clamps to flow and return pipes
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Allow boiler to ignite and reach a reasonable flow temperature, e.g. 55°C.
Measure the differential across the flow and return pipe.
Expect approximately 18°C or less.
Notes:
To reduce the time for the test the heating load can be reduced by turning off some radiators.
Differential may be higher at initial system start-up.