WICKES COMBI 102 FROM SNO AC100000131

WARNING - IMPORTA

Next: &2, *

WICKES COMBI 102 FROM SNO AC100000131

GC NUMBER 47-333-18

Next: &801, !f4

OBSERVATION PUMP RUNS

SET FLOW RATE TO 2.8

Next: &118, f15

OBSERVATION FAN RUNS

GAIN ACCESS TO COMBU

Next: &206, ?733, ?735

OBSERVATION DHW FLOW RATE

Next: &14, f186

OBSERVATION BURNER IGNITION

REFIT COMBUSTION CHA

Next: &316, ?208, ?210, ?212, ?551

OBSERVATION BOILER RESPONDS TO CH DEMAND

CH TEMPERATURE SET TO MAX
SELECTOR SWITCH IN HEATING & HOT WATER POSITION

Next: &467, f441

OPERATION DHW

SELECTOR SWITCH IN HOT WATER POSITION
DHW TEMPERATURE SET TO MAX

Next: &701, ?470, ?472, ?474, ?476

OPERATION CH

CH TEMPERATURE CONTROL SET TO MAX
SELECTOR SWITCH IN HEATING & HOT WATER POSITION

Next: &716, ?577, ?579, ?583

OBSERVATION PUMP OVERRUN

SELECTOR SWITCH IN HEATING & HOT WATER POSITION
CH TEMPERATURE SET TO MAX

Next: &nff, !f604

FUSE FURTHER INVESTIGATION

OUTSIDE MODEL

Next: &nff, f670

TYPE OF DIAGNOSTIC PROCEDURE

PLEASE SELECT FROM O

Next: &667, !f668

SEQUENCE OF OPERATION

Next: &164, !f669

OBSERVATION DHW MODULATION

ADJUST DHW FLOW RATE

Next: &468, f705

OBSERVATION CH MODULATION

CH TEMPERATURE CONTR

Next: &931, f717

OBSERVATION BOILER STANDBY

ENSURE NO DEMANDS
SELECTOR SWITCH IN HEATING & HOT WATER POSITION

Next: &666, ?802, ?804

OBSERVATION PUMP PROVING MICROSWITCH MOVEMENT

SELECTOR SWITCH IN HOT WATER POSITION

Next: &469, f984

PUMP PROVING FAULT CODE

OUTSIDE MODEL

Next: &nff, f1164

BAFFLING - FLUEWAYS RESTRICTED

HEAT EXCHANGER

Next: End

BLOCKED - BAFFLES

BURNER BLADE ASSEMBLY - WORGAS

Next: End

BLOCKED - BAFFLES

FLUE

Next: End

OVERHEAT INVESTIGATION CH SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

OVERHEAT INVESTIGATION - NO PUMP OVERRUN

PCB - HONEYWELL

Next: End

NO SPARKING

HARNESS - IGNITION

Next: End

NO SPARKING - POOR CONDITION

ELECTRODE - IGNITION

Next: End

OPEN CIRCUIT TO PUMP

HARNESS - PUMP

Next: End

RESTRICTED - CUTTING OUT DURING OPERATION

TUBE 10MM - CLEAR SILICONE

Next: End

CUTTING OUT DURING OPERATION

PRESSURE SWITCH - AIR

Next: End

DHW RUNS HOT COLD - WATERWAYS RESTRICTED

HEAT EXCHANGER

Next: End

DHW RUNS HOT COLD

INLET PRESSURE

Next: End

NOT RECTIFYING

HARNESS - IGNITION

Next: End

PUMP PROVING FAULTBLOCKED

PIPE - HIGH / LOW PRESSURE DHW

Next: End

PUMP PROVING FAULT CODE DHW NOT MAKING

MICROSWITCH ASSEMBLY

Next: End

PUMP PROVING FAULT CODE PUMP PROVING SPINDLE STUCK OUT

KIT - DIVERTER VALVE SERVICE

Next: End

PUMP PROVING FAULT CODE SPINDLE STUCK IN

PUMP 6M - GRUNDFOS UPS 15/16

Next: End

PUMP PROVING FAULT CODE STUCK IN FAN RUNS FOR 4 SECONDS

KIT - SERVICE - WATER PRESSURE SWITCH

Next: End

PUMP PROVING FAULT CODE

MICROSWITCH ASSEMBLY

Next: End

PUMP PROVING FAULT CODE SPINDLE MOVING SLOWLY

PUMP 6M - GRUNDFOS UPS 15/16

Next: End

PUMP PROVING FAULT CODE SPINDLE MOVING SLOWLY

KIT - SERVICE - WATER PRESSURE SWITCH

Next: End

PUMP PROVING FAULT CODE DHW SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

PUMP PROVING FAULT CODE CH SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

INSUFFICIENT DHW FLOW RATE

VALVE 15MM - BALL

Next: End

INSUFFICIENT PRESSURE

WATER SUPPLY

Next: End

NO IGNITION - LOW PRESSURE

INLET PRESSURE

Next: End

NO IGNITION - NO PRESSURE

INLET PRESSURE

Next: End

NO AC POWER TO GAS VALVE

PCB - HONEYWELL AND VALVE HONEYWELL GAS

Next: End

OPEN CIRCUIT TO GAS VALVE

HARNESS 230V

Next: End

BLOCKED - NO IGNITION

BURNER BLADE ASSEMBLY - WORGAS

Next: End

NOT ESTABLISHING

INLET PRESSURE

Next: End

NOT ESTABLISHING - POOR CONDITION

ELECTRODE - DETECTION

Next: End

BLOCKED - NOT ESTABLISHING

BURNER BLADE ASSEMBLY - WORGAS

Next: End

BLOCKED - NO IGNITION

TUBE 10MM - CLEAR SILICONE

Next: End

BLOCKED - NO IGNITION

FAN VENTURI

Next: End

NO IGNITION - FLUEWAYS RESTRICTED

HEAT EXCHANGER

Next: End

BLOCKED - NO IGNITION

FLUE

Next: End

RUNNING SLOW - OVERHEAT INVESTIGATION

PUMP 6M - GRUNDFOS UPS 15/16

Next: End

OPEN CIRCUIT

THERMOSTAT - OVERHEAT CUT-OFF

Next: End

INFORMATION CASE REMOVAL

Z REDIRECT

Next: End

OVERHEAT INVESTIGATION

INLET PRESSURE

Next: End

RESTRICTED - OVERHEAT INVESTIGATION

PLATE HEAT EXCHANGER - ALFA LAVAL

Next: End

DHW TOO COOL

KNOB PLASTIC

Next: End

RUNNING SLOW - DHW TOO COOL

PUMP 6M - GRUNDFOS UPS 15/16

Next: End

DHW TOO COOL - WATERWAYS RESTRICTED

HEAT EXCHANGER

Next: End

DHW TOO COOL

INLET PRESSURE

Next: End

DHW TOO COOL

VALVE HONEYWELL GAS

Next: End

DHW TOO COOL DHW SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

DHW TOO HOT DHW SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

DHW TOO HOT

KNOB PLASTIC

Next: End

DHW RUNS HOT COLD DHW SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

DHW RUNS HOT COLD CH SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

NOT MAKING PUMP PROVING SWITCH

PUMP 6M - GRUNDFOS UPS 15/16

Next: End

PUMP PROVING DIAPHRAGM BURNER IGNITES BUT CUTS OUT

KIT - SERVICE - WATER PRESSURE SWITCH

Next: End

IGNITES BUT CUTS OUT DHW SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

IGNITES BUT CUTS OUT CH SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

EXCESSIVE PRESSURE RISE

EXPANSION VESSEL

Next: End

BYPASS STUCK OPEN

MANIFOLD - FLOW

Next: End

SHUT - BOILER UP TO TEMP RADS COOL

ISOLATION VALVES FLOW AND RETURN

Next: End

CH STAYS LIT BUT TEMP LOW

KNOB PLASTIC

Next: End

NO PUMP OVERRUN

PCB - HONEYWELL

Next: End

RUNNING SLOW - BOILER UP TO TEMP RADIATORS COOL

PUMP 6M - GRUNDFOS UPS 15/16

Next: End

OPEN CIRCUIT TO APS

HARNESS 230V

Next: End

NO DC POWER TO GAS VALVE

PCB - HONEYWELL AND VALVE HONEYWELL GAS

Next: End

NOT ESTABLISHING GAS VALVE ADJUSTMENT

PCB - HONEYWELL

Next: End

OVERHEAT INVESTIGATION

CH OUTPUT ADJUSTMENT

Next: End

OPEN CIRCUIT TO CLOCK

HARNESS - INLET

Next: End

TYPE OF DIAGNOSTIC PROCEDURE

Z REDIRECT

Next: End

SEQUENCE OF OPERATION

Z REDIRECT

Next: End

SHORT CIRCUIT MOTOR - FUSE INVESTIGATION

TIME CLOCK - GRASSLIN

Next: End

SHORTED - FUSE INVESTIGATION

PUMP 6M - GRUNDFOS UPS 15/16

Next: End

SHORTED - FUSE INVESTIGATION

COMBI FAN ASSEMBLY

Next: End

SHORTED - FUSE INVESTIGATION

VALVE HONEYWELL GAS

Next: End

DHW MODULATION

VALVE HONEYWELL GAS

Next: End

CH DOES NOT MODULATE CH SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

DHW DOES NOT MODULATE DHW SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

CH MODULATION

PCB - HONEYWELL

Next: End

NOT RESETTING

SWITCH - MAIN

Next: End

BLOCKED - APS SHORTED

TUBE 10MM - CLEAR SILICONE

Next: End

BLOCKED - APS SHORTED

FAN VENTURI

Next: End

FAN NOT RUNNING CH SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

FAN NOT RUNNING DHW SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

OPEN CIRCUIT TO FAN

HARNESS 230V

Next: End

NOT MAKING PUMP PROVING SWITCHFAN RUNS FOR 4 SECONDS

PUMP 6M - GRUNDFOS UPS 15/16

Next: End

PUMP PROVING DIAPHRAGM FAN RUNS FOR 4 SECONDS

KIT - SERVICE - WATER PRESSURE SWITCH

Next: End

PUMP PROVING STUCK OPEN FAN RUNS FOR 4 SECONDS

MICROSWITCH ASSEMBLY

Next: End

RUNNING SLOW - DHW RUNS HOT COLD

PUMP 6M - GRUNDFOS UPS 15/16

Next: End

UNABLE TO RESET

THERMOSTAT - OVERHEAT CUT-OFF

Next: End

FIRING WITH NO DEMAND

FROST PROTECTION

Next: End

FIRING WITH NO DEMAND

EXTERNAL ROOM THERMOSTAT OR TIMER

Next: End

BLOCKED

PIPE - HIGH / LOW PRESSURE DHW

Next: End

DHW NOT MAKING

MICROSWITCH ASSEMBLY

Next: End

PUMP PROVING STUCK SHORTED

MICROSWITCH ASSEMBLY

Next: End

PUMP NOT RUNNING CH SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

PUMP NOT RUNNING DHW SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

FIRING WITH NO DEMAND

JUMPER SETTING

Next: End

FAULTY LED

Z REDIRECT

Next: End

POWER ON LED NOT ILLUMINATED

PCB FUSE

Next: End

OPEN CIRCUIT TO PCB

HARNESS - INLET

Next: End

POWER ON LED NOT ILLUMINATED

MAINS FUSE

Next: End

FIRING WITN NO DEMAND CH SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

DHW STUCK MADE

MICROSWITCH ASSEMBLY

Next: End

FAN RUNS FOR 4 SECONDS DHW SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

FAN RUNS FOR 4 SECONDS CH SENSOR

THERMISTOR 10 OHM - CROSSLAND

Next: End

PUMP MICROSWITCH MOVING SLOWLY

KIT - SERVICE - WATER PRESSURE SWITCH

Next: End

PUMP PROVING SPINDLE STUCK OUT

KIT - SERVICE - WATER PRESSURE SWITCH

Next: End

PUMP DOES NOT RUN

REGULATOR 15 LITRE

Next: End

PUMP DOES NOT RUN

KIT - SANITARY WATER SERVICE

Next: End

DHW SPINDLE NOT MOVING

KIT - DIVERTER VALVE SERVICE

Next: End

RUNNING SLOW - BAFFLES

COMBI FAN ASSEMBLY

Next: End

BOILER UP TO TEMP RADS COOL

KIT - DIVERTER VALVE SERVICE

Next: End

FIRING WITH NO DEMAND

DIAPHRAGM - DIVERTER VALVE

Next: End

FIRING WITH NO DEMAND

CHAMBER - DHW DIAPHRAGM

Next: End

BOILER UP TO TEMP RADS COOL

DIAPHRAGM - DIVERTER VALVE

Next: End

BOILER UP TO TEMP RADS COOL

CHAMBER - DHW DIAPHRAGM

Next: End

TRIPPING EARLY - OVERHEAT INVESTIGATION

THERMOSTAT - OVERHEAT CUT-OFF

Next: End

OVERHEAT INVESTIGATION - NOT SHUTTING DOWN

PCB - HONEYWELL

Next: End

NO FAULT FOUND

OVERHEAT

Next: End

NOT RUNNING

PUMP 6M - GRUNDFOS UPS 15/16

Next: End

NO SPARKING

PCB - HONEYWELL

Next: End

NO SPARKING - OPEN CCT

ELECTRODE - IGNITION

Next: End

RUNNING SLOW - CUTTING OUT DURING OPERATION

COMBI FAN ASSEMBLY

Next: End

RESTRICTED - DHW RUNS HOT COLD

PLATE HEAT EXCHANGER - ALFA LAVAL

Next: End

DHW RUNS HOT COLD

GAS VALVE ADJUSTMENT

Next: End

DHW RUNS HOT COLD

VALVE HONEYWELL GAS

Next: End

DHW RUNS HOT COLD - BURNER PRESSURE OK

PCB - HONEYWELL

Next: End

NOT ESTABLISHING - OPEN CIRCUIT

ELECTRODE - DETECTION

Next: End

PUMP PROVING FAULT CODE NO POWER TO PUMP

PCB - HONEYWELL

Next: End

PUMP PROVING FAULT CODE NOT MOVING DHW SPINDLE

DIAPHRAGM - DIVERTER VALVE

Next: End

PUMP PROVING FAULT CODE NOT MOVING SPINDLE

CHAMBER - DHW DIAPHRAGM

Next: End

PUMP PROVING FAULT CODE DHW SPINDLE NOT MOVING

KIT - DIVERTER VALVE SERVICE

Next: End

PUMP PROVING FAULT CODE PUMP DOES NOT RUN

REGULATOR 15 LITRE

Next: End

PUMP PROVING FAULT CODE PUMP DOES NOT RUN

KIT - SANITARY WATER SERVICE

Next: End

PUMP PROVING FAULT CODE NOT RUNNING

PUMP 6M - GRUNDFOS UPS 15/16

Next: End

PUMP PROVING FAULT CODE SPINDLE STUCK IN

PRESSURE GAUGE 4 BAR

Next: End

PUMP PROVING FAULT CODE SPINDLE STUCK IN

SYSTEM PRESSURE

Next: End

PUMP PROVING FAULT CODE STUCK IN

KIT - DIVERTER VALVE SERVICE

Next: End

PUMP PROVING FAULT CODE SPINDLE MOVING SLOWLY

PRESSURE GAUGE 4 BAR

Next: End

PUMP PROVING FAULT CODE MOVING SLOWLY

KIT - DIVERTER VALVE SERVICE

Next: End

PUMP PROVING FAULT CODE STUCK IN FAULT

PCB - HONEYWELL

Next: End

RESTRICTED - LOW FLOW RATE

PLATE HEAT EXCHANGER - ALFA LAVAL

Next: End

RESTRICTED

REGULATOR 15 LITRE

Next: End

DHW FILTER RESTRICTED

KIT - SANITARY WATER SERVICE

Next: End

LOW PRESSURE - NO IGNITION PCB ADJUSTMENT

GAS VALVE ADJUSTMENT

Next: End

NO AC POWER TO GAS VALVE

PCB - HONEYWELL

Next: End

NO IGNITION AC VOLTAGE

PCB - HONEYWELL AND HARNESS 230V

Next: End

BLOCKED - NO IGNITION

INJECTOR

Next: End

NOT RECOGNISING FLAME

PCB - HONEYWELL

Next: End

NO VOLTAGE TO RECTIFICATION CIRCUIT

PCB - HONEYWELL

Next: End

NOT ESTABLISHING

GAS VALVE ADJUSTMENT

Next: End

BLOCKED - NOT ESTABLISHING

INJECTOR

Next: End

RUNNING SLOW - NO IGNITION

COMBI FAN ASSEMBLY

Next: End

OPEN CIRCUIT TO OVERHEAT

HARNESS 230V

Next: End

OVERHEAT INVESTIGATION

GAS VALVE ADJUSTMENT

Next: End

NOT SWITCHING ON

TIME CLOCK - GRASSLIN

Next: End

NOT SWITCHING

EXTERNAL ROOM THERMOSTAT OR TIMER

Next: End

NOT SWITCHING - OVERHEAT INVESTIGATION

EXTERNAL ROOM THERMOSTAT OR TIMER

Next: End

NOT SWITCHING ON - OVERHEAT INVESTIGATION

TIME CLOCK - GRASSLIN

Next: End

STUCK IN - DHW TOO COOL RADIATORS HEAT

KIT - DIVERTER VALVE SERVICE

Next: End

BLOCKED - DHW COOL

INJECTOR

Next: End

RESTRICTED - DHW TOO COOL

PLATE HEAT EXCHANGER - ALFA LAVAL

Next: End

DHW TOO COOL

GAS VALVE ADJUSTMENT

Next: End

DHW TOO HOT

PCB - HONEYWELL

Next: End

BLOCKED BURNER IGNITES BUT CUTS OUT

PRESSURE GAUGE 4 BAR

Next: End

PUMP PROVING SPINDLE STUCK IN BURNER IGNITES BUT CUTS OUT

KIT - DIVERTER VALVE SERVICE

Next: End

IGNITES BUT CUTS OUT

PCB - HONEYWELL

Next: End

EXCESSIVE PRESSURE RISE

HOSE - BRAIDED S/S

Next: End

BOILER AND RADIATOR TEMPERATURE LOW

CH OUTPUT ADJUSTMENT

Next: End

NOT SWITCHING

PRESSURE SWITCH - AIR

Next: End

NO DC POWER TO GAS VALVE

PCB - HONEYWELL

Next: End

NO IGNITION DC VOLTAGE

PCB - HONEYWELL AND HARNESS 230V

Next: End

NO IGNITION NO PRESSURE

VALVE HONEYWELL GAS

Next: End

NOT ESTABLISHING

VALVE HONEYWELL GAS

Next: End

FURTHER INVESTIGATION

FUSE BLOWN

Next: End

SHORT CIRCUIT - FUSE INVESTIGATION

PCB - HONEYWELL

Next: End

SHORTED - FUSE INVESTIGATION

HARNESS - PUMP

Next: End

NOT MODULATING ON DHW

PCB - HONEYWELL

Next: End

DHW MODULATION

GAS VALVE ADJUSTMENT

Next: End

CH MODULATION

CH OUTPUT ADJUSTMENT

Next: End

NOT RESETTING

PCB - HONEYWELL

Next: End

SHORT CIRCUIT TO APS

HARNESS 230V

Next: End

SHORTED

PRESSURE SWITCH - AIR

Next: End

NO POWER TO FAN

PCB - HONEYWELL

Next: End

SEIZED

COMBI FAN ASSEMBLY

Next: End

BLOCKED FAN RUNS FOR 4 SECONDS

PRESSURE GAUGE 4 BAR

Next: End

PUMP PROVING SPINDLE STUCK IN FAN RUNS FOR 4 SECONDS

KIT - DIVERTER VALVE SERVICE

Next: End

BLOCKED OVERHEAT INVESTIGATION

PRESSURE GAUGE 4 BAR

Next: End

OVERHEAT INVESTIGATION

SYSTEM PRESSURE

Next: End

BLOCKED DHW RUNS HOT COLD

PRESSURE GAUGE 4 BAR

Next: End

DHW RUNS HOT / COLD

SYSTEM PRESSURE

Next: End

BLOCKED DHW TOO COOL

PRESSURE GAUGE 4 BAR

Next: End

DHW TOO COOL

SYSTEM PRESSURE

Next: End

NO IGNITION LOW PRESSURE

GAS VALVE + POTENTIOMETERS ADJUSTED

Next: End

OVERHEAT INVESTIGATION

GAS VALVE + POTENTIOMETERS ADJUSTED

Next: End

FIRING WITH NO DEMAND

PCB - HONEYWELL

Next: End

FIRING WITH NO DEMAND

TAP

Next: End

MAINS FUSE BLOWN

Z REDIRECT

Next: End

NO POWER TO PCB

Next: End

PCB FUSE BLOWN

Z REDIRECT

Next: End

NOT MOVING DHW SPINDLE

DIAPHRAGM - DIVERTER VALVE

Next: End

NOT MOVING SPINDLE

CHAMBER - DHW DIAPHRAGM

Next: End

OPEN CIRCUIT TO DHW MICROSWITCH

HARNESS - LOW VOLTAGE

Next: End

SHORT CIRCUIT TO PUMP PROVING MICROSWITICH

HARNESS - LOW VOLTAGE

Next: End

CH THERMISTOR

HARNESS - LOW VOLTAGE

Next: End

NO POWER TO PUMP

PCB - HONEYWELL

Next: End

DHW THERMISTOR

HARNESS - LOW VOLTAGE

Next: End

SHORT CIRCUIT - FIRING WITH NO DEMAND

TIME CLOCK - GRASSLIN

Next: End

FAULTY LED

PCB - HONEYWELL

Next: End

SHORT CIRCUIT TO DHW MICROSWITCH

HARNESS - LOW VOLTAGE

Next: End

FAN RUNS FOR 4 SECONDS

PCB - HONEYWELL

Next: End

PUMP MICROSWITCH MOVING SLOWLY

KIT - DIVERTER VALVE SERVICE

Next: End

STUCK OUT - FIRING WITH NO DEMAND

KIT - DIVERTER VALVE SERVICE

Next: End

REGULATOR RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION DHW FILTER AND REGULATOR

Next: !p1002

FILTER / VENTURI RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION DHW FILTER AND REGULATOR

Next: !p1004

DHW DIAPHRAGM DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM

Next: !p1019

SPINDLE OR CHAMBER HOUSING DAMAGED / WORN

CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM

Next: !p1021

DHW DIAPHRAGM DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM

Next: !p1024

SPINDLE OR CHAMBER HOUSING DAMAGED / WORN

CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM

Next: !p1026

OVERHEAT TRIPS BEFORE 82°C

CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER UP TO TEMPERATURE

Next: !p1046

FLOW TEMPERATURE ABOVE 88°C AND BOILER DOES NOT SHUT DOWN

CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER UP TO TEMPERATURE

Next: p1048

DHW DIAPHRAGM DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM

Next: !p1175

SPINDLE OR CHAMBER HOUSING DAMAGED / WORN

CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM

Next: !p1177

REGULATOR RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION DHW FILTER AND REGULATOR

Next: !p1183

FILTER / VENTURI RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION DHW FILTER AND REGULATOR

Next: !p1185

VOLTAGE PRESENT ON TEST 1 BUT DOES NOT DROP TO APPROX 0V DC

CHARACTERISTIC TEST FROM VOLTAGE MICROSWITCH PUMP PROVING

Next: p1193

NO VOLTAGE PRESENT ON TEST 1

CHARACTERISTIC TEST FROM VOLTAGE MICROSWITCH PUMP PROVING

Next: p1195

PRESSURE DOES NOT INCREASE WHEN WATER ADDED TO SYSTEM

CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM

Next: !p1206

PRESSURE LOW BUT INCREASES WHEN WATER ADDED TO SYSTEM

CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM

Next: !p1208

PRESSURE DOES NOT INCREASE WHEN WATER ADDED TO SYSTEM

CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM

Next: !p1219

PRESSURE LOW BUT INCREASES WHEN WATER ADDED TO SYSTEM

CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM

Next: !p1221

REGULATOR RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION DHW FILTER AND REGULATOR

Next: !p196

FILTER / VENTURI RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION DHW FILTER AND REGULATOR

Next: !p197

BURNER IGNITES BUT BAFFLES

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION

Next: p1006

BURNER IGNITES SMOOTHLY BUT DOES NOT ESTABLISH (SPARKING CONTINUES)

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION

Next: p271

BURNER DOES NOT IGNITE

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION

Next: p213

PRESSURE PRESENT BUT BELOW APPROX 5MB

CHARACTERISTIC TEST FROM PRESSURE IGNITION

Next: p232

PRESSURE REMAINS AT 0MBAR

CHARACTERISTIC TEST FROM PRESSURE IGNITION

Next: p234

INITIAL 140V ABSENT

CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT

Next: !p268

140V PRESENT BUT DOES NOT DROP ON IGNITION

CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT

Next: p282

DIFFERENTIAL EXCESSIVE

CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL CH

Next: p419

BOILER DOES NOT RESPOND TO CH DEMAND

CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL CH

Next: p456

DHW TOO COOL, RADIATORS REMAIN COLD

CHARACTERISTIC TEST FROM OPERATION DHW

Next: p471

DHW TOO COOL, RADIATORS BEGIN TO HEAT

CHARACTERISTIC TEST FROM OPERATION DHW

Next: !p473

DHW TOO HOT

CHARACTERISTIC TEST FROM OPERATION DHW

Next: p475

DHW RUNS HOT / COLD

CHARACTERISTIC TEST FROM OPERATION DHW

Next: p477

BURNER IGNITES SMOOTHLY BUT IMMEDIATELY CUTS OUT

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION

Next: p553

VOLTAGE PRESENT ON TEST 1 BUT DOES NOT DROP TO APPROX 0V DC

CHARACTERISTIC TEST FROM VOLTAGE MICROSWITCH PUMP PROVING

Next: p556

NO VOLTAGE PRESENT ON TEST 1

CHARACTERISTIC TEST FROM VOLTAGE MICROSWITCH PUMP PROVING

Next: !p558

PRESSURE DOES NOT INCREASE WHEN WATER ADDED TO SYSTEM

CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM

Next: !p563

PRESSURE LOW BUT INCREASES WHEN WATER ADDED TO SYSTEM

CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM

Next: !p565

BOILER UP TO TEMPERATURE RADIATORS COOL

CHARACTERISTIC TEST FROM OPERATION CH

Next: p578

BOILER AND RADIATOR TEMPERATURE LOW

CHARACTERISTIC TEST FROM OPERATION CH

Next: p580

EXCESSIVE SYSTEM PRESSURE RISE

CHARACTERISTIC TEST FROM OPERATION CH

Next: p584

FAN DOES NOT RUN

CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS

Next: p737

FAN RUNS FOR 4 SECONDS THEN STOPS

CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS

Next: p758

VOLTAGE PRESENT ON TEST 1 BUT DOES NOT DROP TO APPROX 0V DC

CHARACTERISTIC TEST FROM VOLTAGE MICROSWITCH PUMP PROVING

Next: p761

NO VOLTAGE PRESENT ON TEST 1

CHARACTERISTIC TEST FROM VOLTAGE MICROSWITCH PUMP PROVING

Next: !p763

PRESSURE DOES NOT INCREASE WHEN WATER ADDED TO SYSTEM

CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM

Next: !p768

PRESSURE LOW BUT INCREASES WHEN WATER ADDED TO SYSTEM

CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM

Next: !p770

PRESSURE DOES NOT INCREASE WHEN WATER ADDED TO SYSTEM

CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM

Next: !p783

PRESSURE LOW BUT INCREASES WHEN WATER ADDED TO SYSTEM

CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM

Next: !p785

SYSTEM PRESSURE READS CORRECTLY BUT DOES NOT INCREASE

CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL CH

Next: !p788

PRESSURE LOW BUT INCREASES WHEN WATER ADDED TO SYSTEM

CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM

Next: !p790

SYSTEM PRESSURE READS CORRECTLY BUT DOES NOT INCREASE

CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL CH

Next: !p794

PRESSURE LOW BUT INCREASES WHEN WATER ADDED TO SYSTEM

CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM

Next: !p796

POWER ON LED DOES NOT ILLUMINATE

CHARACTERISTIC TEST FROM OBSERVATION BOILER STANDBY

Next: p827

PUMP RUNS OR BOILER ATTEMPTS TO FIRE WITH NO DEMAND

CHARACTERISTIC TEST FROM OBSERVATION BOILER STANDBY

Next: p808

DHW DIAPHRAGM DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM

Next: !p849

SPINDLE OR CHAMBER HOUSING DAMAGED / WORN

CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM

Next: !p851

INSPECTION DHW DIAPHRAGM

DHW SYSTEM ISOLATED AND DRAINED

Next: !p1014, ?1023, ?1025

INSPECTION SPARK ELECTRODES

Next: p1103, !f1108

RESISTANCE IGNITION LEADS

REMOVE ELECTRODE LEADS FROM SPARK GENERATOR

Next: !p1106, !f1107

INSPECTION FAN VENTURI

REMOVE FAN ASSEMBLY

Next: p1138, !f1139

TEMPERATURE DIFFERENTIAL CH

ATTACH A TEMPERATURE

Next: !p1151, !f1152

PRESSURE GAS INLET

ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION

Next: p1154, !f1155

VOLTAGE DC GAS VALVE AT PCB MAX AND MINIMUM

REMOVE COVER FROM PC

Next: !p1158, !f1159

RESISTANCE RECTIFICATION LEAD

DISCONNECT RECTIFICATION LEAD FROM THE PCB AND FROM THE RECTIFICATION ELECTRODE

Next: !p1162, !f1163

OBSERVATION PUMP RUNS (FAULT CODE)

SET FLOW RATE TO 2.8

Next: p1165, f1166

VOLTAGE PUMP AT PCB

SET FLOW RATE TO 2.8

Next: p1167, f1168

RESISTANCE MICROSWITCH DHW AND HARNESS

SET FLOW RATE TO 2.8 LITRES A MINUTE
DISCONNECT CONNECTOR X4 FROM THE PCB

Next: !p1169, f1170

INSPECTION DHW SPINDLE

SET FLOW RATE TO 2.8 LITRES A MINUTE

Next: p1171, f1172

INSPECTION DHW DIAPHRAGM

DHW SYSTEM ISOLATED AND DRAINED

Next: p1173, ?1174, ?1176

INSPECTION PRESSURE SYSTEM

Next: p1204, ?1205, ?1207

INSPECTION PRESSURE SYSTEM

Next: p1217, ?1218, ?1220

VOLTAGE PUMP AT PCB

SET FLOW RATE TO 2.8

Next: p109, f842

INSPECTION ISOLATION VALVE DHW

Next: p188, !f187

RESISTANCE GAS VALVE SOLENOIDS AND HARNESS

DISCONNECT CONNECTOR X6 FROM THE PCB
(AND RECONNECT PLUG FOR GAS VALVE IF NOT ALREADY DONE SO)

Next: !p249, f250

RESISTANCE GAS VALVE SOLENOIDS

DISCONNECT LEAD FROM GAS VALVE

Next: !p251, !f252

PRESSURE GAS INLET

ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION

Next: p288, !f287

OBSERVATION OVERHEAT TRIPPED

Next: p356, f335

RESISTANCE OVERHEAT AND HARNESS

DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p336, f353

RESISTANCE OVERHEAT

DISCONNECT 1 WIRE FROM THE OVERHEAT THERMOSTAT

Next: !p354, !f377

PRESSURE GAS INLET

ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION

Next: p412, !f413

OBSERVATION LINK OUT INTEGRAL TIMER

REMOVE PCB COVER

Next: p443, f450

VOLTAGE EXTERNAL CONTROLS INTO BOILER

SELECTOR SWITCH IN HEATING & HOT WATER POSITION

Next: !p454, f451

RESISTANCE HARNESS EXTERNAL CONTROLS

DISCONNECT CONNECTOR X9 FROM THE PCB

Next: !p455, !f453

VOLTAGE EXTERNAL CONTROLS INTO BOILER

SELECTOR SWITCH IN HEATING & HOT WATER POSITION

Next: !p459, f460

RESISTANCE HARNESS EXTERNAL CONTROLS

DISCONNECT CONNECTOR X9 FROM THE PCB

Next: !p461, !f462

TEMPERATURE DIFFERENTIAL CH

ATTACH A TEMPERATURE

Next: !p493, !f494

VOLTAGE GAS VALVE AT PCB (MAXIMUM)

DHW TEMPERATURE SET TO MAX
SELECTOR SWITCH IN HOT WATER POSITION

Next: p506, f511

RESISTANCE SENSOR DHW

DISCONNECT PLUG FROM DHW SENSOR

Next: !p512, !f513

INSPECTION PRESSURE SYSTEM

Next: p561, ?562, ?564

ADJUSTMENT PRESSURE CH OUTPUT

REMOVE PCB COVER

Next: !p602, !f603

RESISTANCE HARNESS AIR PRESSURE SWITCH

DISCONNECT CONNECTOR X6 FROM THE PCB

Next: !p629, !f630

RESISTANCE GAS VALVE SOLENOIDS AND HARNESS

DISCONNECT CONNECTOR X6 FROM THE PCB
(AND RECONNECT PLUG FOR GAS VALVE IF NOT ALREADY DONE SO)

Next: !p640, f641

RESISTANCE GAS VALVE SOLENOIDS

DISCONNECT LEAD FROM GAS VALVE

Next: !p642, !f643

VOLTAGE DC GAS VALVE AT PCB FOR ADJUSTMENT

ADJUST POTENTIOMETER

Next: !p799, !f650

VOLTAGE DC GAS VALVE AT PCB FOR ADJUSTMENT

ADJUST POTENTIOMETER

Next: !p652, !f653

VOLTAGE DC GAS VALVE AT PCB MAX AND MINIMUM

REMOVE COVER FROM PC

Next: !p800, !f661

RESISTANCE MAINS INTO BOILER

REPLACE DAMAGED FUSE

Next: p674, f678

RESISTANCE CLOCK MOTOR AND HARNESS

DISCONNECT X2 CONNECTOR FROM THE PCB

Next: p679, f682

RESISTANCE CLOCK MOTOR

DISCONNECT RED WIRES FROM THE CLOCK

Next: !p696, !f684

RESISTANCE PUMP

REMOVE PUMP COVER
REMOVE WIRES FROM PUMP CONNECTIONS

Next: !p686, !f687

RESISTANCE FAN

DISCONNECT WIRES TO THE FAN

Next: !p697, !f690

RESISTANCE GAS VALVE SOLENOIDS WITH EARTH CHECK

DISCONNECT LEAD FROM GAS VALVE

Next: !p694, !f693

RESISTANCE SENSOR DHW

DISCONNECT PLUG FROM DHW SENSOR

Next: !p704, !f719

VOLTAGE DC GAS VALVE MODULATION

ADJUST DHW FLOW RATE

Next: p709, f702

RESISTANCE SENSOR CH

DISCONNECT PLUG FROM CH SENSOR

Next: p721, !f718

INSPECTION MAIN SWITCH CONTROL KNOB

REMOVE THE PLASTIC C

Next: !p740, !f741

RESISTANCE AIR PRESSURE SWITCH AT PCB (OPEN)

DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p744, f745

RESISTANCE AIR PRESSURE SWITCH AT APS (OPEN)

DISCONNECT 1 WIRE FROM THE AIR PRESSURE SWITCH

Next: !p746, f747

INSPECTION PRESSURE SYSTEM

Next: p766, ?767, ?769

OBSERVATION ISOLATE DHW

REMOVE LOWER PANEL FROM APPLIANCE
TURN DHW ISOLATION VALVE OFF

Next: !p823, f994

RESISTANCE FUSE (MAINS FUSE)

REMOVE THE FUSE FROM THE FUSED SPUR

Next: p830, f831

FURTHER INVESTIGATION FUSE PCB

Next: !p838, !f881

RESISTANCE MICROSWITCH DHW AND HARNESS

SET FLOW RATE TO 2.8 LITRES A MINUTE
DISCONNECT CONNECTOR X4 FROM THE PCB

Next: p843, f844

INSPECTION DHW SPINDLE

SET FLOW RATE TO 2.8 LITRES A MINUTE

Next: p845, f846

INSPECTION DHW DIAPHRAGM

DHW SYSTEM ISOLATED AND DRAINED

Next: p847, ?848, ?850

RESISTANCE SENSOR CH

DISCONNECT PLUG FROM CH SENSOR

Next: !p864, !f865

RESISTANCE SENSOR DHW

DISCONNECT PLUG FROM DHW SENSOR

Next: !p868, !f869

OBSERVATION ISOLATE DHW

REMOVE LOWER PANEL FROM APPLIANCE
TURN DHW ISOLATION VALVE OFF

Next: !p892, f1013

INSPECTION PUMP PROVING DIAPHRAGM

DRAIN BOILER PRIMARY CIRCUIT
UNCLIP PUMP PROVING SWITCH

Next: !p985, !f986

INSPECTION DHW DIAPHRAGM

DHW SYSTEM ISOLATED AND DRAINED

Next: !p995, ?1018, ?1020

INSPECTION HEAT EXCHANGER

Next: p1007, !f1008

INSPECTION BURNER

Next: p1009, !f1010

INSPECTION FLUE

Next: !p1011, !f1012

INSPECTION EXTERNAL BYPASS

Next: p591, !f1031

OBSERVATION RUN BOILER UP TO TEMPERATURE

ATTACH TEMPERATURE P

Next: p1044, ?1045, ?1047

OBSERVATION PUMP OVERRUN

SELECTOR SWITCH IN HEATING & HOT WATER POSITION
CH TEMPERATURE SET TO MAX

Next: !p1051, !f1052

RESISTANCE SENSOR CH

DISCONNECT PLUG FROM CH SENSOR

Next: !p1049, !f1050

INSPECTION EXTERNAL BYPASS

Next: p409, !f1093

RESISTANCE HARNESS PUMP

REMOVE PLASTIC COVER FROM PUMP
DISCONNECT CONNECTOR X3 FROM THE PCB

Next: !p110, !f111

RESISTANCE IGNITION LEADS AND ELECTRODES

REMOVE ELECTRODE LEADS FROM SPARK GENERATOR ON THE PCB

Next: !p1104, f1105

PRESSURE FAN DIFFERENTIAL

ATTACH TELEGAN ACROSS THE TWO FAN VENTURIS

Next: p1136, f1137

INSPECTION HEAT EXCHANGER

Next: p1140, !f1141

INSPECTION FLUE

Next: !p1142, !f1143

RESISTANCE AIR PRESSURE SWITCH

DISCONNECT ONE LEAD FROM THE APS

Next: p1148, !f1147

TEMPERATURE DIFFERENTIAL DHW

ATTACH A TEMPERATURE

Next: p1149, f1150

PRESSURE BURNER MAX AND MIN

REMOVE COVER FROM PC

Next: !p1160, f1153

ADJUSTMENT PRESSURE MAX AND MIN

REMOVE COVER FROM PC

Next: !p1156, f1157

VOLTAGE MICROSWITCH PUMP PROVING

SELECTOR SWITCH IN H

Next: p1190, ?1192, ?1194

RESISTANCE HARNESS PUMP

REMOVE PLASTIC COVER FROM PUMP
DISCONNECT CONNECTOR X3 FROM THE PCB

Next: !p1188, !f1189

RESISTANCE MICROSWITCH DHW

REMOVE THE PLASTIC C

Next: !p1186, !f1187

INSPECTION DHW DIFFERENTIAL PIPES

DHW SYSTEM ISOLATED AND DRAINED

Next: p1178, !f1179

INSPECTION DHW FILTER AND REGULATOR

DHW SYSTEM ISOLATED AND DRAINED

Next: !p1180, ?1182, ?1184

OBSERVATION PUMP PROVING MICROSWITCH MOVEMENT

SELECTOR SWITCH IN HOT WATER POSITION

Next: p1215, f1216

INSPECTION PUMP PROVING SPINDLE

SELECTOR SWITCH IN HOT WATER POSITION

Next: p1202, f1203

RESISTANCE MICROSWITCH PUMP PROVING AND HARNESS (OPEN)

DISCONNECT CONNECTOR X4 FROM THE PCB

Next: !p1196, f1197

RESISTANCE MICROSWITCH PUMP PROVING (OPEN)

REMOVE THE PLASTIC COVER FROM THE PUMP PROVING
MICROSWITCH AND DISCONNECT WIRES

Next: !p1200, !f1201

RESISTANCE MICROSWITCH PUMP PROVING

REMOVE THE PLASTIC COVER FROM THE PUMP PROVING
MICROSWITCH AND DISCONNECT WIRES

Next: !p1213, !f1214

PUMP LIMPET

Next: p1209, !f1210

INSPECTION PUMP PROVING DIAPHRAGM

DRAIN BOILER PRIMARY CIRCUIT
UNCLIP PUMP PROVING SWITCH

Next: !p1211, !f1212

RESISTANCE SENSOR CH

DISCONNECT PLUG FROM CH SENSOR

Next: p1226, !f1227

PUMP LIMPET

Next: p1222, !f1223

INSPECTION PUMP PROVING DIAPHRAGM

DRAIN BOILER PRIMARY CIRCUIT
UNCLIP PUMP PROVING SWITCH

Next: !p1224, !f1225

RESISTANCE SENSOR DHW

DISCONNECT PLUG FROM DHW SENSOR

Next: !p1228, !f1229

INSPECTION DHW FILTER AND REGULATOR

DHW SYSTEM ISOLATED AND DRAINED

Next: !p191, ?192, ?194

VOLTAGE RECTIFICATION CIRCUIT

SELECTOR SWITCH IN HOT WATER POSITION

Next: !p262, ?267, ?269

OBSERVATION SPARKING AT ELECTRODES

GAIN ACCESS TO INNER COMBUSTION CHAMBER
SELECTOR SWITCH IN HOT WATER POSITION

Next: p229, f317

PRESSURE IGNITION

ATTACH U-GAUGE TO BURNER PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION

Next: p230, ?231, ?233

INSPECTION BURNER

Next: !p260, !f261

PRESSURE GAS INLET

ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION

Next: p235, !f236

PRESSURE GAS INLET

ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION

Next: p237, !f238

ADJUSTMENT IGNITION PRESSURE (NO IGNITION)

REMOVE PCB COVER

Next: !p239, f647

VOLTAGE GAS VALVE AC AT PCB

DISCONNECT LEAD FROM GAS VALVE AND MAKE SAFE
SELECTOR SWITCH IN HOT WATER POSITION

Next: p631, f248

RESISTANCE HARNESS GAS VALVE

DISCONNECT LEAD FROM GAS VALVE

Next: !p646, !f254

PRESSURE IGNITION

ATTACH U-GAUGE TO BURNER PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION

Next: p211, f286

INSPECTION RECTIFICATION ELECTRODE

GAIN ACCESS TO BURNER

Next: p283, !f292

INSPECTION BURNER

Next: !p294, !f296

ADJUSTMENT IGNITION PRESSURE (RECTIFICATION)

REMOVE PCB COVER

Next: !p289, f651

RESISTANCE AIR PRESSURE SWITCH WITH KIT AT PCB

DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p337, f628

OBSERVATION SPARKING AT ELECTRODES WITH APS KIT

CONNECT THE AIR PRES

Next: p339, f1097

INSPECTION FAN VENTURI

REMOVE FAN ASSEMBLY

Next: p347, !f348

INSPECTION HEAT EXCHANGER

Next: p349, !f350

INSPECTION FLUE

Next: !p351, !f352

OVERHEAT FURTHER INVESTIGATION

ENSURE APPLIANCE IS

Next: p357, !f797

INSPECTION PRESSURE SYSTEM

Next: p359, ?782, ?784

PUMP LIMPET

Next: p1053, !f364

PRESSURE BURNER MAX AND MIN

REMOVE COVER FROM PC

Next: p410, f411

TEMPERATURE DIFFERENTIAL CH

ATTACH A TEMPERATURE

Next: p416, ?418, ?420

ADJUSTMENT PRESSURE MAX AND MIN

REMOVE COVER FROM PC

Next: !p414, f659

TEMPERATURE DIFFERENTIAL DHW

ATTACH A TEMPERATURE

Next: p1043, !f426

TEMPERATURE DIFFERENTIAL DHW

ATTACH A TEMPERATURE

Next: p654, !f423

RESISTANCE HARNESS CLOCK

DISCONNECT ORANGE WIRES FROM THE CLOCK

Next: !p445, !f665

OBSERVATION LINK OUT INTEGRAL TIMER

REMOVE PCB COVER

Next: p457, f458

RESISTANCE HARNESS CLOCK

DISCONNECT ORANGE WIRES FROM THE CLOCK

Next: !p463, !f662

INSPECTION DHW POTENTIOMETER

Next: p480, !f490

INSPECTION DHW POTENTIOMETER

Next: p514, !f517

INSPECTION PRESSURE SYSTEM

Next: p520, ?787, ?789

INSPECTION PRESSURE SYSTEM

Next: p481, ?793, ?795

PUMP LIMPET

Next: p482, !f492

TEMPERATURE DIFFERENTIAL DHW

ATTACH A TEMPERATURE

Next: p483, f484

PRESSURE BURNER MAXIMUM

ATTACH U-GAUGE TO BU

Next: !p485, f505

PRESSURE GAS INLET

ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION

Next: p507, !f508

ADJUSTMENT PRESSURE MAX

ATTACH U-GAUGE TO BU

Next: !p509, !f510

RESISTANCE SENSOR DHW

DISCONNECT PLUG FROM DHW SENSOR

Next: !p518, !f516

PUMP LIMPET

Next: p521, !f791

RESISTANCE SENSOR DHW

DISCONNECT PLUG FROM DHW SENSOR

Next: p522, !f526

RESISTANCE SENSOR CH

DISCONNECT PLUG FROM CH SENSOR

Next: p1135, !f527

VOLTAGE MICROSWITCH PUMP PROVING

SELECTOR SWITCH IN H

Next: p554, ?555, ?557

RESISTANCE SENSOR CH

DISCONNECT PLUG FROM CH SENSOR

Next: p572, !f573

INSPECTION PUMP PROVING SPINDLE

SELECTOR SWITCH IN HOT WATER POSITION

Next: p559, f560

RESISTANCE MICROSWITCH PUMP PROVING

REMOVE THE PLASTIC COVER FROM THE PUMP PROVING
MICROSWITCH AND DISCONNECT WIRES

Next: !p570, !f571

PUMP LIMPET

Next: p566, !f567

INSPECTION PUMP PROVING DIAPHRAGM

DRAIN BOILER PRIMARY CIRCUIT
UNCLIP PUMP PROVING SWITCH

Next: !p568, !f569

RESISTANCE SENSOR DHW

DISCONNECT PLUG FROM DHW SENSOR

Next: !p576, !f574

INSPECTION CH POTENTIOMETER

Next: p598, !f599

PRESSURE EXPANSION VESSEL

DISCHARGE PRIMARY SYSTEM WATER

Next: !p585, !f586

PUMP LIMPET

Next: p1027, !f627

TEMPERATURE INTEGRAL BYPASS

ENSURE RADIATORS ARE

Next: !p592, !f593

PRESSURE CH OUTPUT SETTING

REMOVE PCB COVER

Next: !p600, f601

VOLTAGE GAS VALVE DC AT PCB

DISCONNECT LEAD FROM GAS VALVE AND MAKE SAFE
SELECTOR SWITCH IN HOT WATER POSITION

Next: p247, f639

PRESSURE CH OUTPUT SETTING

REMOVE PCB COVER

Next: !p422, !f658

RESISTANCE FAN AND HARNESS

DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p672, f688

RESISTANCE GAS VALVE SOLENOIDS AND HARNESS WITH EARTH CHECK

DISCONNECT CONNECTOR X6 FROM THE PCB

Next: !p673, f691

RESISTANCE PUMP AND HARNESS

DISCONNECT CONNECTOR X3 FROM THE PCB

Next: p671, f685

RESISTANCE MAINS INTO BOILER AT PLUG

DISCONNECT CONNECTOR X1 FROM THE PCB

Next: !p680, !f681

ADJUSTMENT PRESSURE MAX AND MIN

REMOVE COVER FROM PC

Next: !p710, !f711

ADJUSTMENT CH OUTPUT MINIMUM

REMOVE PCB COVER

Next: !p722, !f724

OBSERVATION BOILER RESET

REMOVE PCB COVER

Next: p738, f739

VOLTAGE FAN AT PCB

SELECTOR SWITCH IN HOT WATER POSITION

Next: p742, f743

VOLTAGE FAN AT FAN

SELECTOR SWITCH IN HOT WATER POSITION

Next: !p756, !f757

RESISTANCE SENSOR CH

DISCONNECT PLUG FROM CH SENSOR

Next: p752, !f753

INSPECTION FAN VENTURI

REMOVE FAN ASSEMBLY

Next: !p750, !f751

RESISTANCE SENSOR DHW

DISCONNECT PLUG FROM DHW SENSOR

Next: !p754, !f755

VOLTAGE MICROSWITCH PUMP PROVING

SELECTOR SWITCH IN H

Next: p979, ?760, ?762

INSPECTION PUMP PROVING SPINDLE

SELECTOR SWITCH IN HOT WATER POSITION

Next: p764, f765

RESISTANCE MICROSWITCH PUMP PROVING

REMOVE THE PLASTIC COVER FROM THE PUMP PROVING
MICROSWITCH AND DISCONNECT WIRES

Next: !p775, !f776

PUMP LIMPET

Next: p771, !f772

INSPECTION PUMP PROVING DIAPHRAGM

DRAIN BOILER PRIMARY CIRCUIT
UNCLIP PUMP PROVING SWITCH

Next: !p773, !f774

OBSERVATION DISCONNECT X9

DISCONNECT CONNECTOR X9 FROM THE PCB AND MAKE SAFE

Next: p819, f870

TEMPERATURE AMBIENT

Next: p805, !f812

RESISTANCE MICROSWITCH DHW (OPEN)

REMOVE THE PLASTIC COVER FROM THE HOT WATER
MICROSWITCH AND DISCONNECT WIRES

Next: !p901, !f902

RESISTANCE SENSOR CH

DISCONNECT PLUG FROM CH SENSOR

Next: !p820, !f884

VOLTAGE MAINS POWER IN AT PCB

GAIN ACCESS TO PCB (USE INSULATION MAT AS NECESSARY)

Next: p828, f829

RESISTANCE FUSE (PCB)

REMOVE THE COVER FROM THE PCB
REMOVE THE INTERNAL FUSE FROM THE PCB

Next: p836, f837

RESISTANCE HARNESS MAINS IN

DISCONNECT CONNECTOR MARKED X1 FROM THE PCB

Next: !p834, !f882

INFORMATION FAULTY LED

TESTS CARRIED OUT HA

Next: !p879, !f880

RESISTANCE MICROSWITCH PUMP PROVING AND HARNESS (OPEN)

DISCONNECT CONNECTOR X4 FROM THE PCB

Next: p856, f857

RESISTANCE MICROSWITCH DHW

REMOVE THE PLASTIC C

Next: !p854, !f855

INSPECTION DHW DIFFERENTIAL PIPES

DHW SYSTEM ISOLATED AND DRAINED

Next: p999, !f853

RESISTANCE SENSOR CH AND HARNESS

DISCONNECT CONNECTOR X4 FROM THE PCB

Next: p862, f863

RESISTANCE MICROSWITCH PUMP PROVING (OPEN)

REMOVE THE PLASTIC COVER FROM THE PUMP PROVING
MICROSWITCH AND DISCONNECT WIRES

Next: !p860, !f861

RESISTANCE SENSOR DHW AND HARNESS

DISCONNECT CONNECTOR X4 FROM THE PCB

Next: !p866, f867

INSPECTION CLOCK JUMPER SETTING

REMOVE PCB COVER

Next: p875, !f876

INSPECTION HARNESS CLOCK

Next: !p877, !f878

RESISTANCE SENSOR CH

DISCONNECT PLUG FROM CH SENSOR

Next: p980, !f981

RESISTANCE SENSOR DHW

DISCONNECT PLUG FROM DHW SENSOR

Next: !p982, !f983

INSPECTION DHW FILTER AND REGULATOR

DHW SYSTEM ISOLATED AND DRAINED

Next: !p1005, ?1001, ?1003