Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
WICKES COMBI 102 FROM SNO AC100000131
WARNING - IMPORTA
WICKES COMBI 102 FROM SNO AC100000131
GC NUMBER 47-333-18
OBSERVATION PUMP RUNS
SET FLOW RATE TO 2.8
OBSERVATION FAN RUNS
GAIN ACCESS TO COMBU
OBSERVATION BURNER IGNITION
REFIT COMBUSTION CHA
OBSERVATION BOILER RESPONDS TO CH DEMAND
CH TEMPERATURE SET TO MAX
SELECTOR SWITCH IN HEATING & HOT WATER POSITION
OPERATION DHW
SELECTOR SWITCH IN HOT WATER POSITION
DHW TEMPERATURE SET TO MAX
OPERATION CH
CH TEMPERATURE CONTROL SET TO MAX
SELECTOR SWITCH IN HEATING & HOT WATER POSITION
OBSERVATION PUMP OVERRUN
SELECTOR SWITCH IN HEATING & HOT WATER POSITION
CH TEMPERATURE SET TO MAX
FUSE FURTHER INVESTIGATION
OUTSIDE MODEL
TYPE OF DIAGNOSTIC PROCEDURE
PLEASE SELECT FROM O
OBSERVATION DHW MODULATION
ADJUST DHW FLOW RATE
OBSERVATION CH MODULATION
CH TEMPERATURE CONTR
OBSERVATION BOILER STANDBY
ENSURE NO DEMANDS
SELECTOR SWITCH IN HEATING & HOT WATER POSITION
OBSERVATION PUMP PROVING MICROSWITCH MOVEMENT
SELECTOR SWITCH IN HOT WATER POSITION
PUMP PROVING FAULT CODE
OUTSIDE MODEL
BAFFLING - FLUEWAYS RESTRICTED
HEAT EXCHANGER
BLOCKED - BAFFLES
BURNER BLADE ASSEMBLY - WORGAS
BLOCKED - BAFFLES
FLUE
OVERHEAT INVESTIGATION CH SENSOR
THERMISTOR 10 OHM - CROSSLAND
OVERHEAT INVESTIGATION - NO PUMP OVERRUN
PCB - HONEYWELL
NO SPARKING
HARNESS - IGNITION
NO SPARKING - POOR CONDITION
ELECTRODE - IGNITION
OPEN CIRCUIT TO PUMP
HARNESS - PUMP
RESTRICTED - CUTTING OUT DURING OPERATIONBLOCKED
FAN VENTURI
RESTRICTED - CUTTING OUT DURING OPERATION
TUBE 10MM - CLEAR SILICONE
CUTTING OUT DURING OPERATION
PRESSURE SWITCH - AIR
DHW RUNS HOT COLD - WATERWAYS RESTRICTED
HEAT EXCHANGER
DHW RUNS HOT COLD
INLET PRESSURE
DHW RUNS HOT COLD - VOLTAGE TO GAS VALVE INCORRECT
PCB - HONEYWELL
NOT RECTIFYING
HARNESS - IGNITION
PUMP PROVING FAULTBLOCKED
PIPE - HIGH / LOW PRESSURE DHW
PUMP PROVING FAULT CODE DHW NOT MAKING
MICROSWITCH ASSEMBLY
PUMP PROVING FAULT CODE OPEN CIRCUIT TO PUMP
HARNESS - PUMP
PUMP PROVING FAULT CODE PUMP PROVING SPINDLE STUCK OUT
KIT - DIVERTER VALVE SERVICE
PUMP PROVING FAULT CODE PUMP PROVING STUCK SHORTED
MICROSWITCH ASSEMBLY
PUMP PROVING FAULT CODE SPINDLE STUCK IN
PUMP 6M - GRUNDFOS UPS 15/16
PUMP PROVING FAULT CODE STUCK IN FAN RUNS FOR 4 SECONDS
KIT - SERVICE - WATER PRESSURE SWITCH
PUMP PROVING FAULT CODE
MICROSWITCH ASSEMBLY
PUMP PROVING FAULT CODE SPINDLE MOVING SLOWLY
PUMP 6M - GRUNDFOS UPS 15/16
PUMP PROVING FAULT CODE SPINDLE MOVING SLOWLY
KIT - SERVICE - WATER PRESSURE SWITCH
PUMP PROVING FAULT CODE DHW SENSOR
THERMISTOR 10 OHM - CROSSLAND
PUMP PROVING FAULT CODE CH SENSOR
THERMISTOR 10 OHM - CROSSLAND
INSUFFICIENT DHW FLOW RATE
VALVE 15MM - BALL
INSUFFICIENT PRESSURE
WATER SUPPLY
NO IGNITION - LOW PRESSURE
INLET PRESSURE
NO IGNITION - NO PRESSURE
INLET PRESSURE
NO AC POWER TO GAS VALVE
PCB - HONEYWELL AND VALVE HONEYWELL GAS
OPEN CIRCUIT TO GAS VALVE
HARNESS 230V
BLOCKED - NO IGNITION
BURNER BLADE ASSEMBLY - WORGAS
NOT ESTABLISHING
INLET PRESSURE
NOT ESTABLISHING - POOR CONDITION
ELECTRODE - DETECTION
BLOCKED - NOT ESTABLISHING
BURNER BLADE ASSEMBLY - WORGAS
BLOCKED - NO IGNITION
TUBE 10MM - CLEAR SILICONE
BLOCKED - NO IGNITION
FAN VENTURI
NO IGNITION - FLUEWAYS RESTRICTED
HEAT EXCHANGER
RUNNING SLOW - OVERHEAT INVESTIGATION
PUMP 6M - GRUNDFOS UPS 15/16
OPEN CIRCUIT
THERMOSTAT - OVERHEAT CUT-OFF
INFORMATION CASE REMOVAL
Z REDIRECT
OVERHEAT INVESTIGATION
INLET PRESSURE
OVERHEAT INVESTIGATION - WATERWAYS RECTRICTED
HEAT EXCHANGER
RESTRICTED - OVERHEAT INVESTIGATION
PLATE HEAT EXCHANGER - ALFA LAVAL
DHW TOO COOL
KNOB PLASTIC
RUNNING SLOW - DHW TOO COOL
PUMP 6M - GRUNDFOS UPS 15/16
DHW TOO COOL - WATERWAYS RESTRICTED
HEAT EXCHANGER
DHW TOO COOL
INLET PRESSURE
DHW TOO COOL
VALVE HONEYWELL GAS
DHW TOO COOL DHW SENSOR
THERMISTOR 10 OHM - CROSSLAND
DHW TOO HOT DHW SENSOR
THERMISTOR 10 OHM - CROSSLAND
DHW TOO HOT
KNOB PLASTIC
DHW RUNS HOT COLD DHW SENSOR
THERMISTOR 10 OHM - CROSSLAND
DHW RUNS HOT COLD CH SENSOR
THERMISTOR 10 OHM - CROSSLAND
NOT MAKING PUMP PROVING SWITCH
PUMP 6M - GRUNDFOS UPS 15/16
PUMP PROVING DIAPHRAGM BURNER IGNITES BUT CUTS OUT
KIT - SERVICE - WATER PRESSURE SWITCH
PUMP PROVING STUCK OPEN BURNER IGNITES BUT CUTS OUT
MICROSWITCH ASSEMBLY
IGNITES BUT CUTS OUT DHW SENSOR
THERMISTOR 10 OHM - CROSSLAND
IGNITES BUT CUTS OUT CH SENSOR
THERMISTOR 10 OHM - CROSSLAND
EXCESSIVE PRESSURE RISE
EXPANSION VESSEL
BYPASS STUCK OPEN
MANIFOLD - FLOW
SHUT - BOILER UP TO TEMP RADS COOL
ISOLATION VALVES FLOW AND RETURN
CH STAYS LIT BUT TEMP LOW
KNOB PLASTIC
UNABLE TO ADJUST CH OUTPUT - BOILER AND RADIATOR TEMP LOW
PCB - HONEYWELL
NO PUMP OVERRUN
PCB - HONEYWELL
RUNNING SLOW - BOILER UP TO TEMP RADIATORS COOL
PUMP 6M - GRUNDFOS UPS 15/16
OPEN CIRCUIT TO APS
HARNESS 230V
NO DC POWER TO GAS VALVE
PCB - HONEYWELL AND VALVE HONEYWELL GAS
NOT CHANGING GAS VALVE VOLTAGE - DOES NOT IGNITE
PCB - HONEYWELL
NOT ESTABLISHING GAS VALVE ADJUSTMENT
PCB - HONEYWELL
OVERHEAT INVESTIGATION
CH OUTPUT ADJUSTMENT
OVERHEAT INVESTIGATION - BURNER PRESSURE ADJUSTMENT
PCB - HONEYWELL
OPEN CIRCUIT TO CLOCK - OVERHEAT INVESTIGATION
HARNESS - INLET
OPEN CIRCUIT TO CLOCK
HARNESS - INLET
TYPE OF DIAGNOSTIC PROCEDURE
Z REDIRECT
SEQUENCE OF OPERATION
Z REDIRECT
SHORT CIRCUIT ON MAINS - FUSE INVESTIGATION
HARNESS - INLET
SHORT CIRCUIT MOTOR - FUSE INVESTIGATION
TIME CLOCK - GRASSLIN
SHORTED - FUSE INVESTIGATION
PUMP 6M - GRUNDFOS UPS 15/16
SHORTED - FUSE INVESTIGATION
COMBI FAN ASSEMBLY
SHORTED - FUSE INVESTIGATION
VALVE HONEYWELL GAS
DHW MODULATION
VALVE HONEYWELL GAS
CH DOES NOT MODULATE CH SENSOR
THERMISTOR 10 OHM - CROSSLAND
DHW DOES NOT MODULATE DHW SENSOR
THERMISTOR 10 OHM - CROSSLAND
CH MODULATION
PCB - HONEYWELL
NOT RESETTING
SWITCH - MAIN
BLOCKED - APS SHORTED
TUBE 10MM - CLEAR SILICONE
BLOCKED - APS SHORTED
FAN VENTURI
FAN NOT RUNNING CH SENSOR
THERMISTOR 10 OHM - CROSSLAND
FAN NOT RUNNING DHW SENSOR
THERMISTOR 10 OHM - CROSSLAND
OPEN CIRCUIT TO FAN
HARNESS 230V
NOT MAKING PUMP PROVING SWITCHFAN RUNS FOR 4 SECONDS
PUMP 6M - GRUNDFOS UPS 15/16
PUMP PROVING DIAPHRAGM FAN RUNS FOR 4 SECONDS
KIT - SERVICE - WATER PRESSURE SWITCH
PUMP PROVING STUCK OPEN FAN RUNS FOR 4 SECONDS
MICROSWITCH ASSEMBLY
RUNNING SLOW - DHW RUNS HOT COLD
PUMP 6M - GRUNDFOS UPS 15/16
UNABLE TO RESET
THERMOSTAT - OVERHEAT CUT-OFF
FIRING WITH NO DEMAND
FROST PROTECTION
FIRING WITH NO DEMAND
EXTERNAL ROOM THERMOSTAT OR TIMER
BLOCKED
PIPE - HIGH / LOW PRESSURE DHW
DHW NOT MAKING
MICROSWITCH ASSEMBLY
PUMP PROVING STUCK SHORTED
MICROSWITCH ASSEMBLY
PUMP NOT RUNNING CH SENSOR
THERMISTOR 10 OHM - CROSSLAND
PUMP NOT RUNNING DHW SENSOR
THERMISTOR 10 OHM - CROSSLAND
FIRING WITH NO DEMAND
JUMPER SETTING
SHORT CIRCUIT TO CLOCK - FIRING WITH NO DEMAND
HARNESS - INLET
FAULTY LED
Z REDIRECT
POWER ON LED NOT ILLUMINATED
PCB FUSE
OPEN CIRCUIT TO PCB
HARNESS - INLET
POWER ON LED NOT ILLUMINATED
MAINS FUSE
FIRING WITN NO DEMAND CH SENSOR
THERMISTOR 10 OHM - CROSSLAND
DHW STUCK MADE
MICROSWITCH ASSEMBLY
FAN RUNS FOR 4 SECONDS DHW SENSOR
THERMISTOR 10 OHM - CROSSLAND
FAN RUNS FOR 4 SECONDS CH SENSOR
THERMISTOR 10 OHM - CROSSLAND
PUMP MICROSWITCH MOVING SLOWLY
KIT - SERVICE - WATER PRESSURE SWITCH
PUMP PROVING SPINDLE STUCK OUT
KIT - SERVICE - WATER PRESSURE SWITCH
PUMP DOES NOT RUN
REGULATOR 15 LITRE
PUMP DOES NOT RUN
KIT - SANITARY WATER SERVICE
DHW SPINDLE NOT MOVING
KIT - DIVERTER VALVE SERVICE
RUNNING SLOW - BAFFLES
COMBI FAN ASSEMBLY
BOILER UP TO TEMP RADS COOL
KIT - DIVERTER VALVE SERVICE
FIRING WITH NO DEMAND
DIAPHRAGM - DIVERTER VALVE
FIRING WITH NO DEMAND
CHAMBER - DHW DIAPHRAGM
BOILER UP TO TEMP RADS COOL
DIAPHRAGM - DIVERTER VALVE
BOILER UP TO TEMP RADS COOL
CHAMBER - DHW DIAPHRAGM
TRIPPING EARLY - OVERHEAT INVESTIGATION
THERMOSTAT - OVERHEAT CUT-OFF
OVERHEAT INVESTIGATION - NOT SHUTTING DOWN
PCB - HONEYWELL
NO FAULT FOUND
OVERHEAT
NOT RUNNING
PUMP 6M - GRUNDFOS UPS 15/16
NO SPARKING
PCB - HONEYWELL
NO SPARKING - OPEN CCT
ELECTRODE - IGNITION
RUNNING SLOW - CUTTING OUT DURING OPERATION
COMBI FAN ASSEMBLY
RESTRICTED - DHW RUNS HOT COLD
PLATE HEAT EXCHANGER - ALFA LAVAL
DHW RUNS HOT COLD
GAS VALVE ADJUSTMENT
DHW RUNS HOT COLD
VALVE HONEYWELL GAS
DHW RUNS HOT COLD - BURNER PRESSURE OK
PCB - HONEYWELL
NOT ESTABLISHING - OPEN CIRCUIT
ELECTRODE - DETECTION
PUMP PROVING FAULT CODE NO POWER TO PUMP
PCB - HONEYWELL
PUMP PROVING FAULT CODE NOT MOVING DHW SPINDLE
DIAPHRAGM - DIVERTER VALVE
PUMP PROVING FAULT CODE NOT MOVING SPINDLE
CHAMBER - DHW DIAPHRAGM
PUMP PROVING FAULT CODE DHW SPINDLE NOT MOVING
KIT - DIVERTER VALVE SERVICE
PUMP PROVING FAULT CODE PUMP DOES NOT RUN
REGULATOR 15 LITRE
PUMP PROVING FAULT CODE PUMP DOES NOT RUN
KIT - SANITARY WATER SERVICE
PUMP PROVING FAULT CODE OPEN CIRCUIT TO DHW MICROSWITCH
HARNESS - LOW VOLTAGE
PUMP PROVING FAULT CODE NOT RUNNING
PUMP 6M - GRUNDFOS UPS 15/16
PUMP PROVING FAULT CODE NO POWER TO PUMP PROVING MICROSWITCH
PCB - HONEYWELL
PUMP PROVING FAULT CODE SHORT CIRCUIT TO PUMP PROVING MICROSWITICH
HARNESS - LOW VOLTAGE
PUMP PROVING FAULT CODE SPINDLE STUCK IN
PRESSURE GAUGE 4 BAR
PUMP PROVING FAULT CODE SPINDLE STUCK IN
SYSTEM PRESSURE
PUMP PROVING FAULT CODE STUCK IN
KIT - DIVERTER VALVE SERVICE
PUMP PROVING FAULT CODE OPEN CIRCUIT TO PUMP PROVING MICROSWITCH
HARNESS - LOW VOLTAGE
PUMP PROVING FAULT CODE SPINDLE MOVING SLOWLY
PRESSURE GAUGE 4 BAR
PUMP PROVING FAULT CODE SPINDLE MOVING SLOWLY
SYSTEM PRESSURE
PUMP PROVING FAULT CODE MOVING SLOWLY
KIT - DIVERTER VALVE SERVICE
PUMP PROVING FAULT CODE STUCK IN FAULT
PCB - HONEYWELL
RESTRICTED - LOW FLOW RATE
PLATE HEAT EXCHANGER - ALFA LAVAL
RESTRICTED
REGULATOR 15 LITRE
DHW FILTER RESTRICTED
KIT - SANITARY WATER SERVICE
LOW PRESSURE - NO IGNITION PCB ADJUSTMENT
GAS VALVE ADJUSTMENT
NO AC POWER TO GAS VALVE
PCB - HONEYWELL
NO IGNITION AC VOLTAGE
PCB - HONEYWELL AND HARNESS 230V
BLOCKED - NO IGNITION
INJECTOR
NOT RECOGNISING FLAME
PCB - HONEYWELL
NO VOLTAGE TO RECTIFICATION CIRCUIT
PCB - HONEYWELL
NOT ESTABLISHING
GAS VALVE ADJUSTMENT
BLOCKED - NOT ESTABLISHING
INJECTOR
RUNNING SLOW - NO IGNITION
COMBI FAN ASSEMBLY
OPEN CIRCUIT TO OVERHEAT
HARNESS 230V
OVERHEAT INVESTIGATION
GAS VALVE ADJUSTMENT
NOT SWITCHING ON
TIME CLOCK - GRASSLIN
NOT SWITCHING
EXTERNAL ROOM THERMOSTAT OR TIMER
NOT SWITCHING - OVERHEAT INVESTIGATION
EXTERNAL ROOM THERMOSTAT OR TIMER
NOT SWITCHING ON - OVERHEAT INVESTIGATION
TIME CLOCK - GRASSLIN
STUCK IN - DHW TOO COOL RADIATORS HEAT
KIT - DIVERTER VALVE SERVICE
BLOCKED - DHW COOL
INJECTOR
RESTRICTED - DHW TOO COOL
PLATE HEAT EXCHANGER - ALFA LAVAL
DHW TOO COOL
GAS VALVE ADJUSTMENT
LOW VOLTAGE TO GAS VALVE MODULATING COIL - DHW TOO COOL
PCB - HONEYWELL
DHW TOO HOT
PCB - HONEYWELL
NO POWER TO PUMP PROVING MICROSWITCH BURNER IGNITES BUT CUTS OUT
PCB - HONEYWELL
BLOCKED BURNER IGNITES BUT CUTS OUT
PRESSURE GAUGE 4 BAR
PUMP PROVING SPINDLE BURNER IGNITES THEN CUTS OUT
SYSTEM PRESSURE
PUMP PROVING SPINDLE STUCK IN BURNER IGNITES BUT CUTS OUT
KIT - DIVERTER VALVE SERVICE
OPEN CIRCUIT TO PUMP PROVING MICROSWITCH BURNER IGNITES THEN CUTS OUT
HARNESS - LOW VOLTAGE
IGNITES BUT CUTS OUT
PCB - HONEYWELL
EXCESSIVE PRESSURE RISE
HOSE - BRAIDED S/S
BOILER AND RADIATOR TEMPERATURE LOW
CH OUTPUT ADJUSTMENT
NOT SWITCHING
PRESSURE SWITCH - AIR
NO DC POWER TO GAS VALVE
PCB - HONEYWELL
NO IGNITION DC VOLTAGE
PCB - HONEYWELL AND HARNESS 230V
NO IGNITION NO PRESSURE
VALVE HONEYWELL GAS
NOT ESTABLISHING
VALVE HONEYWELL GAS
FURTHER INVESTIGATION
FUSE BLOWN
SHORT CIRCUIT - FUSE INVESTIGATION
PCB - HONEYWELL
SHORTED - FUSE INVESTIGATION
HARNESS - PUMP
SHORT CIRCUIT TO GAS VALVE - FUSE INVESTIGATION
HARNESS 230V
SHORT CIRCUIT TO CLOCK MOTOR - FUSE INVESTIGATION
HARNESS - INLET
SHORT CIRCUIT TO FAN - FUSE INVESTIGATION
HARNESS 230V
NOT MODULATING ON DHW
PCB - HONEYWELL
DHW MODULATION
GAS VALVE ADJUSTMENT
CH MODULATION
CH OUTPUT ADJUSTMENT
NOT RESETTING
PCB - HONEYWELL
SHORT CIRCUIT TO APS
HARNESS 230V
SHORTED
PRESSURE SWITCH - AIR
NO POWER TO FAN
PCB - HONEYWELL
SEIZED
COMBI FAN ASSEMBLY
NO POWER TO PUMP PROVING MICROSWITCH FAN RUNS FOR 4 SECONDS
PCB - HONEYWELL
BLOCKED FAN RUNS FOR 4 SECONDS
PRESSURE GAUGE 4 BAR
PUMP PROVING SPINDLE FAN RUNS FOR 4 SECONDS
SYSTEM PRESSURE
PUMP PROVING SPINDLE STUCK IN FAN RUNS FOR 4 SECONDS
KIT - DIVERTER VALVE SERVICE
OPEN CIRCUIT TO PUMP PROVING MICROSWITCH FAN RUNS FOR 4 SECONDS
HARNESS - LOW VOLTAGE
BLOCKED OVERHEAT INVESTIGATION
PRESSURE GAUGE 4 BAR
OVERHEAT INVESTIGATION
SYSTEM PRESSURE
BLOCKED DHW RUNS HOT COLD
PRESSURE GAUGE 4 BAR
DHW RUNS HOT / COLD
SYSTEM PRESSURE
BLOCKED DHW TOO COOL
PRESSURE GAUGE 4 BAR
DHW TOO COOL
SYSTEM PRESSURE
NO IGNITION LOW PRESSURE
GAS VALVE + POTENTIOMETERS ADJUSTED
OVERHEAT INVESTIGATION
GAS VALVE + POTENTIOMETERS ADJUSTED
FIRING WITH NO DEMAND
PCB - HONEYWELL
MAINS FUSE BLOWN
Z REDIRECT
PCB FUSE BLOWN
Z REDIRECT
NOT MOVING DHW SPINDLE
DIAPHRAGM - DIVERTER VALVE
NOT MOVING SPINDLE
CHAMBER - DHW DIAPHRAGM
OPEN CIRCUIT TO DHW MICROSWITCH
HARNESS - LOW VOLTAGE
SHORT CIRCUIT TO PUMP PROVING MICROSWITICH
HARNESS - LOW VOLTAGE
CH THERMISTOR
HARNESS - LOW VOLTAGE
NO POWER TO PUMP
PCB - HONEYWELL
DHW THERMISTOR
HARNESS - LOW VOLTAGE
SHORT CIRCUIT - FIRING WITH NO DEMAND
TIME CLOCK - GRASSLIN
FAULTY LED
PCB - HONEYWELL
SHORT CIRCUIT TO DHW MICROSWITCH
HARNESS - LOW VOLTAGE
FAN RUNS FOR 4 SECONDS
PCB - HONEYWELL
PUMP MICROSWITCH MOVING SLOWLY
KIT - DIVERTER VALVE SERVICE
STUCK OUT - FIRING WITH NO DEMAND
KIT - DIVERTER VALVE SERVICE
REGULATOR RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION DHW FILTER AND REGULATOR
FILTER / VENTURI RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION DHW FILTER AND REGULATOR
DHW DIAPHRAGM DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM
SPINDLE OR CHAMBER HOUSING DAMAGED / WORN
CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM
DHW DIAPHRAGM DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM
SPINDLE OR CHAMBER HOUSING DAMAGED / WORN
CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM
OVERHEAT TRIPS BEFORE 82°C
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER UP TO TEMPERATURE
FLOW TEMPERATURE ABOVE 88°C AND BOILER DOES NOT SHUT DOWN
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER UP TO TEMPERATURE
DHW DIAPHRAGM DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM
SPINDLE OR CHAMBER HOUSING DAMAGED / WORN
CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM
REGULATOR RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION DHW FILTER AND REGULATOR
FILTER / VENTURI RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION DHW FILTER AND REGULATOR
VOLTAGE PRESENT ON TEST 1 BUT DOES NOT DROP TO APPROX 0V DC
CHARACTERISTIC TEST FROM VOLTAGE MICROSWITCH PUMP PROVING
NO VOLTAGE PRESENT ON TEST 1
CHARACTERISTIC TEST FROM VOLTAGE MICROSWITCH PUMP PROVING
PRESSURE DOES NOT INCREASE WHEN WATER ADDED TO SYSTEM
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
PRESSURE LOW BUT INCREASES WHEN WATER ADDED TO SYSTEM
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
PRESSURE DOES NOT INCREASE WHEN WATER ADDED TO SYSTEM
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
PRESSURE LOW BUT INCREASES WHEN WATER ADDED TO SYSTEM
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
REGULATOR RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION DHW FILTER AND REGULATOR
FILTER / VENTURI RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION DHW FILTER AND REGULATOR
BURNER IGNITES BUT BAFFLES
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION
BURNER IGNITES SMOOTHLY BUT DOES NOT ESTABLISH (SPARKING CONTINUES)
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION
BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION
PRESSURE PRESENT BUT BELOW APPROX 5MB
CHARACTERISTIC TEST FROM PRESSURE IGNITION
PRESSURE REMAINS AT 0MBAR
CHARACTERISTIC TEST FROM PRESSURE IGNITION
INITIAL 140V ABSENT
CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT
140V PRESENT BUT DOES NOT DROP ON IGNITION
CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT
DIFFERENTIAL EXCESSIVE
CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL CH
BOILER DOES NOT RESPOND TO CH DEMAND
CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL CH
DHW TOO COOL, RADIATORS REMAIN COLD
CHARACTERISTIC TEST FROM OPERATION DHW
DHW TOO COOL, RADIATORS BEGIN TO HEAT
CHARACTERISTIC TEST FROM OPERATION DHW
DHW TOO HOT
CHARACTERISTIC TEST FROM OPERATION DHW
DHW RUNS HOT / COLD
CHARACTERISTIC TEST FROM OPERATION DHW
BURNER IGNITES SMOOTHLY BUT IMMEDIATELY CUTS OUT
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION
VOLTAGE PRESENT ON TEST 1 BUT DOES NOT DROP TO APPROX 0V DC
CHARACTERISTIC TEST FROM VOLTAGE MICROSWITCH PUMP PROVING
NO VOLTAGE PRESENT ON TEST 1
CHARACTERISTIC TEST FROM VOLTAGE MICROSWITCH PUMP PROVING
PRESSURE DOES NOT INCREASE WHEN WATER ADDED TO SYSTEM
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
PRESSURE LOW BUT INCREASES WHEN WATER ADDED TO SYSTEM
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
BOILER UP TO TEMPERATURE RADIATORS COOL
CHARACTERISTIC TEST FROM OPERATION CH
BOILER AND RADIATOR TEMPERATURE LOW
CHARACTERISTIC TEST FROM OPERATION CH
EXCESSIVE SYSTEM PRESSURE RISE
CHARACTERISTIC TEST FROM OPERATION CH
FAN DOES NOT RUN
CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS
FAN RUNS FOR 4 SECONDS THEN STOPS
CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS
VOLTAGE PRESENT ON TEST 1 BUT DOES NOT DROP TO APPROX 0V DC
CHARACTERISTIC TEST FROM VOLTAGE MICROSWITCH PUMP PROVING
NO VOLTAGE PRESENT ON TEST 1
CHARACTERISTIC TEST FROM VOLTAGE MICROSWITCH PUMP PROVING
PRESSURE DOES NOT INCREASE WHEN WATER ADDED TO SYSTEM
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
PRESSURE LOW BUT INCREASES WHEN WATER ADDED TO SYSTEM
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
PRESSURE DOES NOT INCREASE WHEN WATER ADDED TO SYSTEM
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
PRESSURE LOW BUT INCREASES WHEN WATER ADDED TO SYSTEM
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE READS CORRECTLY BUT DOES NOT INCREASE
CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL CH
PRESSURE LOW BUT INCREASES WHEN WATER ADDED TO SYSTEM
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE READS CORRECTLY BUT DOES NOT INCREASE
CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL CH
PRESSURE LOW BUT INCREASES WHEN WATER ADDED TO SYSTEM
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
POWER ON LED DOES NOT ILLUMINATE
CHARACTERISTIC TEST FROM OBSERVATION BOILER STANDBY
PUMP RUNS OR BOILER ATTEMPTS TO FIRE WITH NO DEMAND
CHARACTERISTIC TEST FROM OBSERVATION BOILER STANDBY
DHW DIAPHRAGM DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM
SPINDLE OR CHAMBER HOUSING DAMAGED / WORN
CHARACTERISTIC TEST FROM INSPECTION DHW DIAPHRAGM
28/06/2017 14:12:35 1705_1_50_1 10/07/2017 09:08:45
28/06/2017 15:16:41
INSPECTION DHW DIAPHRAGM
DHW SYSTEM ISOLATED AND DRAINED
RESISTANCE IGNITION LEADS
REMOVE ELECTRODE LEADS FROM SPARK GENERATOR
INSPECTION FAN VENTURI
REMOVE FAN ASSEMBLY
TEMPERATURE DIFFERENTIAL CH
ATTACH A TEMPERATURE
PRESSURE GAS INLET
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION
VOLTAGE DC GAS VALVE AT PCB MAX AND MINIMUM
REMOVE COVER FROM PC
RESISTANCE RECTIFICATION LEAD
DISCONNECT RECTIFICATION LEAD FROM THE PCB AND FROM THE RECTIFICATION ELECTRODE
OBSERVATION PUMP RUNS (FAULT CODE)
SET FLOW RATE TO 2.8
VOLTAGE PUMP AT PCB
SET FLOW RATE TO 2.8
RESISTANCE MICROSWITCH DHW AND HARNESS
SET FLOW RATE TO 2.8 LITRES A MINUTE
DISCONNECT CONNECTOR X4 FROM THE PCB
INSPECTION DHW SPINDLE
SET FLOW RATE TO 2.8 LITRES A MINUTE
INSPECTION DHW DIAPHRAGM
DHW SYSTEM ISOLATED AND DRAINED
VOLTAGE PUMP AT PCB
SET FLOW RATE TO 2.8
RESISTANCE GAS VALVE SOLENOIDS AND HARNESS
DISCONNECT CONNECTOR X6 FROM THE PCB
(AND RECONNECT PLUG FOR GAS VALVE IF NOT ALREADY DONE SO)
RESISTANCE GAS VALVE SOLENOIDS
DISCONNECT LEAD FROM GAS VALVE
PRESSURE GAS INLET
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION
RESISTANCE OVERHEAT AND HARNESS
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE OVERHEAT
DISCONNECT 1 WIRE FROM THE OVERHEAT THERMOSTAT
PRESSURE GAS INLET
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION
OBSERVATION LINK OUT INTEGRAL TIMER
REMOVE PCB COVER
VOLTAGE EXTERNAL CONTROLS INTO BOILER
SELECTOR SWITCH IN HEATING & HOT WATER POSITION
RESISTANCE HARNESS EXTERNAL CONTROLS
DISCONNECT CONNECTOR X9 FROM THE PCB
VOLTAGE EXTERNAL CONTROLS INTO BOILER
SELECTOR SWITCH IN HEATING & HOT WATER POSITION
RESISTANCE HARNESS EXTERNAL CONTROLS
DISCONNECT CONNECTOR X9 FROM THE PCB
TEMPERATURE DIFFERENTIAL CH
ATTACH A TEMPERATURE
VOLTAGE GAS VALVE AT PCB (MAXIMUM)
DHW TEMPERATURE SET TO MAX
SELECTOR SWITCH IN HOT WATER POSITION
RESISTANCE SENSOR DHW
DISCONNECT PLUG FROM DHW SENSOR
ADJUSTMENT PRESSURE CH OUTPUT
REMOVE PCB COVER
RESISTANCE HARNESS AIR PRESSURE SWITCH
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE GAS VALVE SOLENOIDS AND HARNESS
DISCONNECT CONNECTOR X6 FROM THE PCB
(AND RECONNECT PLUG FOR GAS VALVE IF NOT ALREADY DONE SO)
RESISTANCE GAS VALVE SOLENOIDS
DISCONNECT LEAD FROM GAS VALVE
VOLTAGE DC GAS VALVE AT PCB FOR ADJUSTMENT
ADJUST POTENTIOMETER
VOLTAGE DC GAS VALVE AT PCB FOR ADJUSTMENT
ADJUST POTENTIOMETER
VOLTAGE DC GAS VALVE AT PCB MAX AND MINIMUM
REMOVE COVER FROM PC
RESISTANCE MAINS INTO BOILER
REPLACE DAMAGED FUSE
RESISTANCE CLOCK MOTOR AND HARNESS
DISCONNECT X2 CONNECTOR FROM THE PCB
RESISTANCE CLOCK MOTOR
DISCONNECT RED WIRES FROM THE CLOCK
RESISTANCE PUMP
REMOVE PUMP COVER
REMOVE WIRES FROM PUMP CONNECTIONS
RESISTANCE FAN
DISCONNECT WIRES TO THE FAN
RESISTANCE GAS VALVE SOLENOIDS WITH EARTH CHECK
DISCONNECT LEAD FROM GAS VALVE
RESISTANCE SENSOR DHW
DISCONNECT PLUG FROM DHW SENSOR
VOLTAGE DC GAS VALVE MODULATION
ADJUST DHW FLOW RATE
RESISTANCE SENSOR CH
DISCONNECT PLUG FROM CH SENSOR
INSPECTION MAIN SWITCH CONTROL KNOB
REMOVE THE PLASTIC C
RESISTANCE AIR PRESSURE SWITCH AT PCB (OPEN)
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE AIR PRESSURE SWITCH AT APS (OPEN)
DISCONNECT 1 WIRE FROM THE AIR PRESSURE SWITCH
OBSERVATION ISOLATE DHW
REMOVE LOWER PANEL FROM APPLIANCE
TURN DHW ISOLATION VALVE OFF
RESISTANCE FUSE (MAINS FUSE)
REMOVE THE FUSE FROM THE FUSED SPUR
RESISTANCE MICROSWITCH DHW AND HARNESS
SET FLOW RATE TO 2.8 LITRES A MINUTE
DISCONNECT CONNECTOR X4 FROM THE PCB
INSPECTION DHW SPINDLE
SET FLOW RATE TO 2.8 LITRES A MINUTE
INSPECTION DHW DIAPHRAGM
DHW SYSTEM ISOLATED AND DRAINED
RESISTANCE SENSOR CH
DISCONNECT PLUG FROM CH SENSOR
RESISTANCE SENSOR DHW
DISCONNECT PLUG FROM DHW SENSOR
OBSERVATION ISOLATE DHW
REMOVE LOWER PANEL FROM APPLIANCE
TURN DHW ISOLATION VALVE OFF
INSPECTION PUMP PROVING DIAPHRAGM
DRAIN BOILER PRIMARY CIRCUIT
UNCLIP PUMP PROVING SWITCH
INSPECTION DHW DIAPHRAGM
DHW SYSTEM ISOLATED AND DRAINED
OBSERVATION RUN BOILER UP TO TEMPERATURE
ATTACH TEMPERATURE P
OBSERVATION PUMP OVERRUN
SELECTOR SWITCH IN HEATING & HOT WATER POSITION
CH TEMPERATURE SET TO MAX
RESISTANCE SENSOR CH
DISCONNECT PLUG FROM CH SENSOR
RESISTANCE HARNESS PUMP
REMOVE PLASTIC COVER FROM PUMP
DISCONNECT CONNECTOR X3 FROM THE PCB
RESISTANCE IGNITION LEADS AND ELECTRODES
REMOVE ELECTRODE LEADS FROM SPARK GENERATOR ON THE PCB
PRESSURE FAN DIFFERENTIAL
ATTACH TELEGAN ACROSS THE TWO FAN VENTURIS
RESISTANCE AIR PRESSURE SWITCH
DISCONNECT ONE LEAD FROM THE APS
TEMPERATURE DIFFERENTIAL DHW
ATTACH A TEMPERATURE
PRESSURE BURNER MAX AND MIN
REMOVE COVER FROM PC
ADJUSTMENT PRESSURE MAX AND MIN
REMOVE COVER FROM PC
VOLTAGE MICROSWITCH PUMP PROVING
SELECTOR SWITCH IN H
RESISTANCE HARNESS PUMP
REMOVE PLASTIC COVER FROM PUMP
DISCONNECT CONNECTOR X3 FROM THE PCB
RESISTANCE MICROSWITCH DHW
REMOVE THE PLASTIC C
INSPECTION DHW DIFFERENTIAL PIPES
DHW SYSTEM ISOLATED AND DRAINED
INSPECTION DHW FILTER AND REGULATOR
DHW SYSTEM ISOLATED AND DRAINED
OBSERVATION PUMP PROVING MICROSWITCH MOVEMENT
SELECTOR SWITCH IN HOT WATER POSITION
INSPECTION PUMP PROVING SPINDLE
SELECTOR SWITCH IN HOT WATER POSITION
RESISTANCE MICROSWITCH PUMP PROVING AND HARNESS (OPEN)
DISCONNECT CONNECTOR X4 FROM THE PCB
RESISTANCE MICROSWITCH PUMP PROVING (OPEN)
REMOVE THE PLASTIC COVER FROM THE PUMP PROVING
MICROSWITCH AND DISCONNECT WIRES
RESISTANCE MICROSWITCH PUMP PROVING
REMOVE THE PLASTIC COVER FROM THE PUMP PROVING
MICROSWITCH AND DISCONNECT WIRES
INSPECTION PUMP PROVING DIAPHRAGM
DRAIN BOILER PRIMARY CIRCUIT
UNCLIP PUMP PROVING SWITCH
RESISTANCE SENSOR CH
DISCONNECT PLUG FROM CH SENSOR
INSPECTION PUMP PROVING DIAPHRAGM
DRAIN BOILER PRIMARY CIRCUIT
UNCLIP PUMP PROVING SWITCH
RESISTANCE SENSOR DHW
DISCONNECT PLUG FROM DHW SENSOR
INSPECTION DHW FILTER AND REGULATOR
DHW SYSTEM ISOLATED AND DRAINED
VOLTAGE RECTIFICATION CIRCUIT
SELECTOR SWITCH IN HOT WATER POSITION
OBSERVATION SPARKING AT ELECTRODES
GAIN ACCESS TO INNER COMBUSTION CHAMBER
SELECTOR SWITCH IN HOT WATER POSITION
PRESSURE IGNITION
ATTACH U-GAUGE TO BURNER PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION
PRESSURE GAS INLET
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION
PRESSURE GAS INLET
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION
ADJUSTMENT IGNITION PRESSURE (NO IGNITION)
REMOVE PCB COVER
VOLTAGE GAS VALVE AC AT PCB
DISCONNECT LEAD FROM GAS VALVE AND MAKE SAFE
SELECTOR SWITCH IN HOT WATER POSITION
RESISTANCE HARNESS GAS VALVE
DISCONNECT LEAD FROM GAS VALVE
PRESSURE IGNITION
ATTACH U-GAUGE TO BURNER PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION
INSPECTION RECTIFICATION ELECTRODE
GAIN ACCESS TO BURNER
ADJUSTMENT IGNITION PRESSURE (RECTIFICATION)
REMOVE PCB COVER
RESISTANCE AIR PRESSURE SWITCH WITH KIT AT PCB
DISCONNECT CONNECTOR X6 FROM THE PCB
OBSERVATION SPARKING AT ELECTRODES WITH APS KIT
CONNECT THE AIR PRES
INSPECTION FAN VENTURI
REMOVE FAN ASSEMBLY
OVERHEAT FURTHER INVESTIGATION
ENSURE APPLIANCE IS
PRESSURE BURNER MAX AND MIN
REMOVE COVER FROM PC
TEMPERATURE DIFFERENTIAL CH
ATTACH A TEMPERATURE
ADJUSTMENT PRESSURE MAX AND MIN
REMOVE COVER FROM PC
TEMPERATURE DIFFERENTIAL DHW
ATTACH A TEMPERATURE
TEMPERATURE DIFFERENTIAL DHW
ATTACH A TEMPERATURE
RESISTANCE HARNESS CLOCK
DISCONNECT ORANGE WIRES FROM THE CLOCK
OBSERVATION LINK OUT INTEGRAL TIMER
REMOVE PCB COVER
RESISTANCE HARNESS CLOCK
DISCONNECT ORANGE WIRES FROM THE CLOCK
TEMPERATURE DIFFERENTIAL DHW
ATTACH A TEMPERATURE
PRESSURE BURNER MAXIMUM
ATTACH U-GAUGE TO BU
PRESSURE GAS INLET
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
SELECTOR SWITCH IN HOT WATER POSITION
ADJUSTMENT PRESSURE MAX
ATTACH U-GAUGE TO BU
RESISTANCE SENSOR DHW
DISCONNECT PLUG FROM DHW SENSOR
RESISTANCE SENSOR DHW
DISCONNECT PLUG FROM DHW SENSOR
RESISTANCE SENSOR CH
DISCONNECT PLUG FROM CH SENSOR
VOLTAGE MICROSWITCH PUMP PROVING
SELECTOR SWITCH IN H
RESISTANCE SENSOR CH
DISCONNECT PLUG FROM CH SENSOR
INSPECTION PUMP PROVING SPINDLE
SELECTOR SWITCH IN HOT WATER POSITION
RESISTANCE MICROSWITCH PUMP PROVING
REMOVE THE PLASTIC COVER FROM THE PUMP PROVING
MICROSWITCH AND DISCONNECT WIRES
INSPECTION PUMP PROVING DIAPHRAGM
DRAIN BOILER PRIMARY CIRCUIT
UNCLIP PUMP PROVING SWITCH
RESISTANCE SENSOR DHW
DISCONNECT PLUG FROM DHW SENSOR
PRESSURE EXPANSION VESSEL
DISCHARGE PRIMARY SYSTEM WATER
TEMPERATURE INTEGRAL BYPASS
ENSURE RADIATORS ARE
PRESSURE CH OUTPUT SETTING
REMOVE PCB COVER
VOLTAGE GAS VALVE DC AT PCB
DISCONNECT LEAD FROM GAS VALVE AND MAKE SAFE
SELECTOR SWITCH IN HOT WATER POSITION
PRESSURE CH OUTPUT SETTING
REMOVE PCB COVER
RESISTANCE FAN AND HARNESS
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE GAS VALVE SOLENOIDS AND HARNESS WITH EARTH CHECK
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE PUMP AND HARNESS
DISCONNECT CONNECTOR X3 FROM THE PCB
RESISTANCE MAINS INTO BOILER AT PLUG
DISCONNECT CONNECTOR X1 FROM THE PCB
ADJUSTMENT PRESSURE MAX AND MIN
REMOVE COVER FROM PC
ADJUSTMENT CH OUTPUT MINIMUM
REMOVE PCB COVER
OBSERVATION BOILER RESET
REMOVE PCB COVER
VOLTAGE FAN AT PCB
SELECTOR SWITCH IN HOT WATER POSITION
VOLTAGE FAN AT FAN
SELECTOR SWITCH IN HOT WATER POSITION
RESISTANCE SENSOR CH
DISCONNECT PLUG FROM CH SENSOR
INSPECTION FAN VENTURI
REMOVE FAN ASSEMBLY
RESISTANCE SENSOR DHW
DISCONNECT PLUG FROM DHW SENSOR
VOLTAGE MICROSWITCH PUMP PROVING
SELECTOR SWITCH IN H
INSPECTION PUMP PROVING SPINDLE
SELECTOR SWITCH IN HOT WATER POSITION
RESISTANCE MICROSWITCH PUMP PROVING
REMOVE THE PLASTIC COVER FROM THE PUMP PROVING
MICROSWITCH AND DISCONNECT WIRES
INSPECTION PUMP PROVING DIAPHRAGM
DRAIN BOILER PRIMARY CIRCUIT
UNCLIP PUMP PROVING SWITCH
OBSERVATION DISCONNECT X9
DISCONNECT CONNECTOR X9 FROM THE PCB AND MAKE SAFE
RESISTANCE MICROSWITCH DHW (OPEN)
REMOVE THE PLASTIC COVER FROM THE HOT WATER
MICROSWITCH AND DISCONNECT WIRES
RESISTANCE SENSOR CH
DISCONNECT PLUG FROM CH SENSOR
VOLTAGE MAINS POWER IN AT PCB
GAIN ACCESS TO PCB (USE INSULATION MAT AS NECESSARY)
RESISTANCE FUSE (PCB)
REMOVE THE COVER FROM THE PCB
REMOVE THE INTERNAL FUSE FROM THE PCB
RESISTANCE HARNESS MAINS IN
DISCONNECT CONNECTOR MARKED X1 FROM THE PCB
INFORMATION FAULTY LED
TESTS CARRIED OUT HA
RESISTANCE MICROSWITCH PUMP PROVING AND HARNESS (OPEN)
DISCONNECT CONNECTOR X4 FROM THE PCB
RESISTANCE MICROSWITCH DHW
REMOVE THE PLASTIC C
INSPECTION DHW DIFFERENTIAL PIPES
DHW SYSTEM ISOLATED AND DRAINED
RESISTANCE SENSOR CH AND HARNESS
DISCONNECT CONNECTOR X4 FROM THE PCB
RESISTANCE MICROSWITCH PUMP PROVING (OPEN)
REMOVE THE PLASTIC COVER FROM THE PUMP PROVING
MICROSWITCH AND DISCONNECT WIRES
RESISTANCE SENSOR DHW AND HARNESS
DISCONNECT CONNECTOR X4 FROM THE PCB
INSPECTION CLOCK JUMPER SETTING
REMOVE PCB COVER
RESISTANCE SENSOR CH
DISCONNECT PLUG FROM CH SENSOR
RESISTANCE SENSOR DHW
DISCONNECT PLUG FROM DHW SENSOR
INSPECTION DHW FILTER AND REGULATOR
DHW SYSTEM ISOLATED AND DRAINED