ELM LE-BLANC GVM C23

WARNING - IMPORTA

Next: &21, *

EXCESSIVE SYSTEM PRESSURE

ROTARY SWITCH TO CH/DHW POSITION
CH THERMOSTAT TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: &nff, !f124

CENTRAL HEATING

ROTARY SWITCH TO CH/DHW POSITION
CH THERMOSTAT TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: &1, ?118, ?120, ?122

HOT WATER

ROTARY SWITCH TO DHW POSITION
DHW TEMPERATURE CONTROL TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: &2, !f126

CH MODULATION

ROTARY SWITCH TO CH/DHW POSITION
CH THERMOSTAT TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: &3, !f116

CH BURNER HIGH FLAME

ROTARY SWITCH TO CH/DHW POSITION
CH THERMOSTAT TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: &4, !f115

CH HIGH FAN

ROTARY SWITCH TO CH/DHW POSITION
CH THERMOSTAT TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: &5, !f114

CH FLOW VALVE OPERATION

ROTARY SWITCH TO CH/DHW POSITION
CH THERMOSTAT TO MAXIMUM
HOLD IN BOILER CASING SWITCH

Next: &6, f103

DHW MODULATION

ROTARY SWITCH TO DHW POSITION
DHW TEMPERATURE CONTROL TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: &7, f100

DHW BURNER HIGH FLAME

ROTARY SWITCH TO DHW POSITION
DHW TEMPERATURE CONTROL TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: &8, !f97

DHW BURNER LOW FLAME

ROTARY SWITCH TO DHW POSITION
DHW TEMPERATURE CONTROL TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: &9, f78

DHW HIGH FAN

ROTARY SWITCH TO DHW POSITION
DHW TEMPERATURE CONTROL TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: &10, !f77

DHW DEMAND

{ISOLATEMAINSPOWER}

Next: &11, f70

PILOT OUT GAS CHECK

ROTARY SWITCH TO DHW POSITION
HOLD IN BOILER CASE SWITCH

Next: &12, !f69

PILOT OUT

ROTARY SWITCH TO DHW POSITION
HOLD IN BOILER CASE SWITCH

Next: &13, !f68

PILOT ESTABLISHED

ROTARY SWITCH TO DHW POSITION
HOLD IN BOILER CASE SWITCH

Next: &14, f59

PILOT IGNITES

ROTARY SWITCH TO DHW POSITION
HOLD IN BOILER CASE SWITCH

Next: &15, f54

PILOT SPARKING

ROTARY SWITCH TO DHW POSITION
HOLD IN BOILER CASE SWITCH

Next: &16, f39

PILOT HIGH FAN

ROTARY SWITCH TO DHW POSITION
HOLD IN BOILER CASE SWITCH

Next: &17, f36

PILOT SLOW FAN

ROTARY SWITCH TO DHW POSITION
HOLD IN BOILER CASE SWITCH

Next: &18, f24

SYSTEM CHECKS

{ISOLATEMAINSPOWER}

Next: &19, !f23

ELM LE-BLANC GVM C23

G.C. NUMBER 47 241 0

Next: &20, !f22

DHW MODULATION

MODULATING BOX

Next: End

CH FLOW VALVE OPERATION

ROTARY SWITCH

Next: End

CH FLOW VALVE OPERATION

CLOCK/LINK

Next: End

CH FLOW VALVE OPERATION

WATER VALVE SWITCHES

Next: End

CH HIGH FAN

OPERATIVE CH THERMOSTAT

Next: End

CH BURNER HIGH FLAME

DIFFERENTIAL FLOW VALVE MICROSWITCH

Next: End

CH MODULATION

OPERATIVE CH THERMOSTAT

Next: End

EXCESSIVE SYSTEM PRESSURE

EXPANSION VESSEL

Next: End

HOT WATER

SCALED PRIMARY HEAT EXCHANGER

Next: End

PILOT SLOW FAN

BOILER CASE SWITCH

Next: End

DHW DEMAND

SCALED PRIMARY HEAT EXCHANGER

Next: End

ELECTRICAL CHECKS

ELECTRICAL CHECKS

Next: End

SYSTEM CHECKS

SYSTEM CHECKS

Next: End

PILOT SLOW FAN

240V MAINS SUPPLY

Next: End

PILOT SLOW FAN

FUSE 3A

Next: End

PILOT SLOW FAN

PRINTED CIRCUIT BOARD

Next: End

PILOT HIGH FAN

IGNITION SWITCH

Next: End

PILOT SPARKING

CONDENSATE TRAP

Next: End

PILOT SPARKING

FLUE

Next: End

PILOT SPARKING

AIR PRESSURE MICROSWITCH

Next: End

PILOT SPARKING

TRANSFORMER

Next: End

PILOT IGNITES

GAS CONTROL VALVE KNOB

Next: End

PILOT IGNITES

PILOT INJECTOR

Next: End

PILOT ESTABISHED

THERMOCOUPLE

Next: End

PILOT ESTABLISHED

PILOT OFF PUSH BUTTON

Next: End

PILOT OUT

PILOT OFF PUSH BUTTON

Next: End

PILOT OUT GAS CHECK

GAS VALVE ASSEMBLY

Next: End

DHW DEMAND

WATER VALVE DIAPHRAGM

Next: End

DHW DEMAND

WATER VALVE PISTON

Next: End

DHW HIGH FAN

WATER VALVE SWITCHES

Next: End

DHW BURNER LOW FLAME

FUSE 0.25A

Next: End

DHW BURNER LOW FLAME

IGNITION SWITCH

Next: End

DHW BURNER LOW FLAME

TRANSFORMER

Next: End

DHW BURNER LOW FLAME

CH LIMIT THERMOSTAT

Next: End

DHW BURNER LOW FLAME

SOLENOIDS

Next: End

DHW BURNER HIGH FLAME

SOLENOIDS

Next: End

DHW MODULATION

GAS VALVE ASSEMBLY

Next: End

CH FLOW VALVE OPERATION

ROOM THERMOSTAT/LINK

Next: End

CH FLOW VALVE OPERATION

DIFFERENTIAL FLOW VALVE

Next: End

CH FLOW VALVE OPERATION

PUMP

Next: End

CENTRAL HEATING

NON-RETURN VALVE

Next: End

CENTRAL HEATING

Next: End

CENTRAL HEATING

SCALED PRIMARY HEAT EXCHANGER

Next: End

PILOT SLOW FAN

ROTARY SWITCH

Next: End

PILOT SLOW FAN

FAN

Next: End

PILOT HIGH FAN

FAN

Next: End

PILOT SPARKING

IGNITION SWITCH

Next: End

PILOT SPARKING

AIR PRESSURE SWITCH PADDLE AND LINKAGE

Next: End

PILOT SPARKING

SPARK ELECTRODE AND LEAD

Next: End

PILOT SPARKING

SPARK GENERATOR

Next: End

PILOT IGNITES

GAS VALVE ASSEMBLY

Next: End

PILOT ESTABISHED

OVERHEAT THERMOSTAT

Next: End

PILOT ESTABISHED

GAS VALVE ASSEMBLY

Next: End

PILOT ESTABISHED

CH FLOW LIMIT THERMOSTAT

Next: End

DHW DEMAND

WATER VALVE SPINDLE

Next: End

DHW BURNER LOW FLAME

WATER VALVE SWITCHES

Next: End

DHW BURNER LOW FLAME

PRINTED CIRCUIT BOARD

Next: End

DHW BURNER LOW FLAME

DHW LIMIT THERMOSTAT

Next: End

DHW BURNER LOW FLAME

BURNER INJECTORS

Next: End

DHW BURNER LOW FLAME

GAS VALVE ASSEMBLY

Next: End

BOILER CYCLES A LOT OR OVERHEATS, COLD RADIATORS

CHARACTERISTIC TEST FROM CENTRAL HEATING

Next: !p119

CH NOISY OPERATION, WARM OR COLD RADIATORS

CHARACTERISTIC TEST FROM CENTRAL HEATING

Next: !p128

CH QUIET OPERATION, WARM OR COLD RADIATORS

CHARACTERISTIC TEST FROM CENTRAL HEATING

Next: !p123

MODULATING BOX OPERATION

{ISOLATEMAINSPOWER}

Next: !p102, !f101

ROOM THERMOSTAT VOLTAGE

ROTARY SWITCH TO CH/DHW POSITION
CH THERMOSTAT TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: p105, f104

ROTARY SWITCH CH VOLTAGE

ROTARY SWITCH TO CH/DHW POSITION
CH THERMOSTAT TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: p107, !f106

PUMP VOLTAGE

ROTARY SWITCH TO DHW

Next: !p113, !f112

ROTARY SWITCH CH VOLTAGE

ROTARY SWITCH TO CH/DHW POSITION
CH THERMOSTAT TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: p26, f25

MAINS VOLTAGE

ROTARY SWITCH IN OFF POSITION

Next: p28, !f27

IGNITION SWITCH A

{ISOLATEMAINSPOWER}
REMOVE FRONT PANEL OF ELECTRICAL CONTROL BOX

Next: !p38, !f37

SPARK APS VOLTAGE

ROTARY SWITCH TO DHW POSITION
DHW TEMPERATURE CONTROL TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: p41, f40

AIR PRESSURE SWITCH OPERATION

ROTARY SWITCH TO DHW POSITION
DHW TEMPERATURE CONTROL TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: !p43, f42

CONDENSATE TRAP

{ISOLATEMAINSPOWER}

Next: p45, !f44

TRANSFORMER PRIMARY

{ISOLATEMAINSPOWER}
REMOVE FRONT PANEL OF ELECTRICAL CONTROL BOX

Next: !p53, !f52

GAS CONTROL VALVE KNOB

{ISOLATEMAINSPOWER}

Next: p56, !f55

OVERHEAT THERMOSTAT VOLTAGE

ROTARY SWITCH TO DHW POSITION
HOLD IN BOILER CASE SWITCH

Next: p61, f60

THERMOCOUPLE VOLTAGE

{ISOLATEMAINSPOWER}
ROTARY SWITCH TO DHW POSITION
HOLD IN BOILER CASE SWITCH

Next: !p63, !f62

PILOT OFF BUTTON VOLTAGE

ROTARY SWITCH TO DHW POSITION
HOLD IN BOILER CASING SWITCH

Next: !p67, !f66

DHW MINIMUM FLOW RATE

{ISOLATEMAINSPOWER}

Next: p72, !f129

WATER VALVE MICROSWITCH 2 NO VOLTAGE

ROTARY SWITCH TO DHW POSITION
DHW TEMPERATURE CONTROL TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: p80, f79

0.25A FUSE

{ISOLATEMAINSPOWER}

Next: p82, !f81

IGNITION SWITCH B: NC

{ISOLATEMAINSPOWER}
REMOVE FRONT PANEL OF ELECTRICAL CONTROL BOX

Next: p86, !f85

CH LIMIT THERMOSTAT

{ISOLATEMAINSPOWER}

Next: !p92, !f91

SOLENOID 1 RESISTANCE

{ISOLATEMAINSPOWER}

Next: !p96, !f95

PUMP RUNNING

ROTARY SWITCH TO CH/DHW POSITION
CH THERMOSTAT TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: !p111, f110

TIMER / LINK VOLTAGE

ROTARY SWITCH TO CH/DHW POSITION
CH THERMOSTAT TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: !p109, !f108

SLOW FAN VOLTAGE

ROTARY SWITCH TO DHW POSITION
DHW TEMPERATURE CONTROL TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: !p34, !f35

3A FUSE

{ISOLATEMAINSPOWER}

Next: p30, !f29

BOILER CASING SWITCH

{ISOLATEMAINSPOWER}
REMOVE FRONT PANEL OF ELECTRICAL CONTROL BOX

Next: !p32, !f127

AIR DETECT VOLTAGE

ROTARY SWITCH TO DHW POSITION
DHW TEMPERATURE CONTROL TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: p49, !f48

FLUE

Next: !p47, !f46

SPARK LEAD

{ISOLATEMAINSPOWER}
REMOVE SPARK ELECTRODE LEAD FROM ELECTRICAL CONTROL BOX CONNECTOR

Next: !p51, f50

PILOT INJECTOR

{ISOLATEMAINSPOWER}

Next: !p58, !f57

CH FLOW LIMIT THERMOSTAT VOLTAGE

ROTARY SWITCH TO DHW POSITION
HOLD IN BOILER CASE SWITCH

Next: !p65, f64

WATER VALVE DIAPHRAGM

{ISOLATEMAINSPOWER}

Next: p74, !f73

WATER VALVE PISTON

{ISOLATEMAINSPOWER}

Next: !p76, !f75

SOLENOID VOLTAGE

ROTARY SWITCH TO DHW POSITION
DHW TEMPERATURE CONTROL TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: p90, f89

DC POWER SUPPLY

ROTARY SWITCH TO DHW POSITION
DHW TEMPERATURE CONTROL TO MAXIMUM
HOLD IN BOILER CASE SWITCH

Next: !p84, f83

TRANSFORMER SECONDARY

{ISOLATEMAINSPOWER}
REMOVE FRONT PANEL OF ELECTRICAL CONTROL BOX

Next: !p88, !f87

DHW BURNER PRESSURE

ROTARY SWITCH TO DHW

Next: !p94, f93