Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
BRITISH GAS / BOSCH ICS1 - ZSBR 7-28A
WARNING - IMPORTA
BRITISH GAS/BOSCH ICS1 - ZSBR 7 -28A
{GAINPCBACS}
G.C.
DHW FAN RUNS
CH TEMPERATURE SELECTOR TO OFF POSITION
SYSTEM PRESSURE RISE
CH TEMPERATURE SELECTOR TO HIGH POSITION
CH OPERATION
CH THERMOSTAT TO MAX
CH MODULATION
ENSURE ALL HEATING CONTROLS ARE CALLING FOR HEAT
DHW TEMP SELECTOR TO MINIMUM
DHW BURNER IGNITES
CH TEMPERATURE SELEC
FAULT CODE A7
NOT USED
FAULT CODE B1
NOT USED
FAULT CODE C1
NOT USED
FAULT CODE D3
NOT USED
FAULT CODE E2
NOT USED
FAULT CODE E9
NOT USED
FAULT CODE F7 & FA
NOT USED
FAULT CODE A8
NOT USED
FAULT CODE AC
NOT USED
FAULT CODE FO
NOT USED
FAULT CODE FD
NOT USED
FAULT CODE P1 - P2 - P3
NOT USED
FAULT CODE A1
NOT USED
CH BURNER IGNITION
CENTRAL HEATING THER
DHW PUMP RUNS
CH TEMPERATURE SELECTOR TO OFF POSITION
OBSERVATION FAN PRESSURE (MAX)
ATTACH F.G.A UNIT TO
FAULT CODE FC
NOT USED
DHW OPERATION
CH TEMPERATURE SELECTOR TO OFF POSITION
FAULT CODE FD
PCB
FAULT CODE A1
SYSTEM PRESSURE
FAULT CODE A1 2
PCB
FAULT CODE F7
GAS VALVE
FAULT CODE P1-P2-P3
FUSE 6A T1
FAULT CODE P1-P2-P3
TRANSFORMER
FAULT CODE F7 &FA
SYPHON
FAULT CODE A8
PCB
FAULT CODE A8
WIRING HARNESS (TR2)
DAMAGED
HANDLES - ROTARY (CH)
CH BURNER IGNITION
WIRING HARNESS (TR2)
DHW PUMP RUNS 2
PCB
FAULT CODE A1 3
PCB
FAULT CODE A1 4
PCB
FAULT 2
PUMP ASSEMBLY
EFFICIENCY 2
PUMP ASSEMBLY
FAULT CODE AC
HARNESS - PCB TO DISPLAY
FAULT CODE AC
WIRING HARNESS (TR2)
FAULT CODE AC
PCB
FAULT CODE FO
LEAD - HT - IGNITION
FAULT CODE FO
HARNESS - MAIN
FAULT FO
PCB
FAULT CODE FO
Z REDIRECTION
FAN PRESSURE TEST MAX
FLUEWAYS
FAN PRESSURE TEST MAX
PLATE - BEARING
FAULT CODE OVERHEAT
SYSTEM PRESSURE
FAULT CODE A1 2
PUMP ASSEMBLY
FAULT CODE E9
PUMP ASSEMBLY
LOW 2
GAS INLET PRESSURE
BLOCKED
SYPHON
BLOCKAGE 2
FLUE
FAULT
SET - ELECTRODES (FLAME SENSE)
DHW PUMP RUNS - RESISTANCES
PUMP VARIABLE SPEED
FAULT CODE A1 - RESISTANCE
PUMP VARIABLE SPEED
FAULT CODE E9 - RESISTANCE
PUMP VARIABLE SPEED
FAULT CODE FC
PCB
FAULT CODE FC
HARNESS - PCB TO DISPLAY
FAN RUNS THEN SLOWS
DHW SENSOR
IGNITES BUT BAFFLES
SYPHON
IGNITES BUT BAFFLES
GAS INLET PRESSURE
IGNITES BUT BAFFLES
FLUE
IGNITES BUT BAFFLES
FLUEWAYS
IGNITES BUT BAFFLES
PLATE - BEARING
IGNITES BUT BAFFLES
LIMITER - AIR
IGNITES BUT BAFFLES
PIPE - GAS
FAULT CODE F7 FA
PLATE - BEARING (FAN SPEED)
CH BURNER IGNITION
INTEGRAL PROGRAMMER / MODULE
DAMAGED WITH PROGRAMMER
HANDLES - ROTARY (CH)
BLOWN
PACK - 10 OFF FUSE 5A 20MM - T2
FUSE F3
FUSE 6A T1
FAULTY
TRANSFORMER
BLOWN
FUSE 500MA T0
BOILER HEATS SYSTEM COOL
PUMP ASSEMBLY
FAULT CODE E9
SENSOR - TEMPERATURE
FAULT CODE E9 2
OVERHEAT THERMOSTAT
FAULT CODE E9
SEALS
MECHANICAL 3
DIVERTER VALVE - 3 WAY
DV FUNCTION 3
PCB
NO PROGRAMMEROC/SC
SENSOR - TEMPERATURE
NO PROGRAMMERFAN NOT RUNNING
DHW SENSOR
NO PROGRAMMERFAULTY
CODE PLUG
DHW FAN RUNS NO PROGRAMMER
HANDLES - ROTARY (DHW)
NO PROGRAMMERDAMAGED
HARNESS - FAN
OC/SC
SENSOR - TEMPERATURE
FAN NOT RUNNING
DHW SENSOR
FAULTY
CODE PLUG
DHW FAN RUNS PROGRAMMER
HANDLES - ROTARY (DHW)
FAN VOLTAGE
PCB
FAN OPERATION
PCB
DAMAGED
HARNESS - FAN
FAULT CODE D3
DHW SENSOR
CALIBRATION 2
DHW SENSOR
DHW TOO HOT
PCB
DHW TOO HOT
HARNESS - MAIN
CALIBRATION 2
SENSOR - TEMPERATURE
DV FUNCTION 2
PCB
DIVERTER NOT OPERATING
HARNESS - MAIN
DHW COOL RADS COOL
SYSTEM PRESSURE
DHW NOISEY
SYSTEM PRESSURE
EFFICIENCY 3
PUMP ASSEMBLY
CH OPERATION NOISY
SYSTEM PRESSURE
DHW OPERATION TOO HOT
DIVERTER VALVE - 3 WAY
CH OPERATION BOILER HOT RADS COOL
SYSTEM PRESSURE
EFFICIENCY
PUMP ASSEMBLY
DAMAGED
HANDLES - ROTARY (DHW)
CH OPERATION BOILER HEATS RADS COOL
GAS INLET PRESSURE
CALIBRATION
SENSOR - TEMPERATURE
CALIBRATION
DHW SENSOR
CH OPERATION SHUTS DOWN EARLY
HANDLES - ROTARY (CH)
CH OPERATION LOW RATE
HANDLES - ROTARY (CH)
CH OPERATION LOW RATE
GAS INLET PRESSURE
CH NOISY
HEAT EXCHANGER
FAILED
ELECTRICAL SAFETY CHECKS
CALIBRATION 3
SENSOR - TEMPERATURE
BLOCKED 4
SYPHON
BLOCKAGE 4
FLUE
PRESSURE
EXPANSION VESSEL
CALIBRATION 4
SENSOR - TEMPERATURE
CALIBRATION 5
SENSOR - TEMPERATURE
OPERATIONAL SEQUENCE
SYSTEM CHECKS
DIVERTER VALVE OPERATION CH
HARNESS - MAIN
FAULT CODES
DIRECTION CHOICE OR CONTINUE
OC
OVERHEAT THERMOSTAT
OC
FLUE THERMOSTAT
BLOCKED 2
SYPHON
NO SPARKING
PCB AND LEAD - HT- IGNITION
WEAK OR INCONSTANT SPARK
PCB AND LEAD - HT- IGNITION
BURNER DOES NOT IGNITE 2
FLUEWAYS
BURNER DOES NOT IGNITE 2
PLATE - BEARING
BURNER DOES NOT IGNITE 2
LIMITER - AIR
ADJUSTMENT
PIPE - GAS
SPARK ELECTRODE LEADS
LEAD - HT - IGNITION
BLOCKAGE
FLUE
BURNER DOES NOT IGNITE
FLUEWAYS
BURNER DOES NOT IGNITE
PLATE - BEARING
BURNER DOES NOT IGNITE
LIMITER - AIR
NO PERMANENT RECTIFICATION VOLTAGE
HARNESS - MAIN
FAULT
HARNESS - MAIN
FAULT CODE C1 OCCURS
HARNESS - FAN
BURNER DOES NOT IGNITE
HARNESS - FAN
BURNER DOES NOT IGNITE 2
HARNESS - FAN
BURNER DOES NOT IGNITE 3
HARNESS - FAN
BURNER DOES NOT IGNITE 5
PLATE - BEARING (FAN SPEED)
BURNER DOES NOT IGNITE 4
PLATE - BEARING (FAN SPEED)
BURNER DOES NOT IGNITE 3
PLATE - BEARING (FAN SPEED)
FAULT CODE C1 OCCURS
PLATE - BEARING (FAN SPEED)
FAULT CODE A7
DHW SENSOR
FAULT CODE A7
PCB
FAULT CODE B1
CODE PLUG
FAULT CODE B1 2
CODE PLUG
FAULT CODE C1 2
PCB
FAULT CODE C1
PCB
FAULT CODE C1
HARNESS - FAN
FAULT CODE C1 3
HARNESS - FAN
FAULT CODE C1 3
PLATE - BEARING (FAN SPEED)
FAULT CODE C1 2
HARNESS - FAN
FAULT CODE C1 2
PLATE - BEARING (FAN SPEED)
FAULT CODE C1 4
HARNESS - FAN
FAULT CODE C1
PLATE - BEARING (FAN SPEED)
FAULT CODE D3
PCB
FAULT CODE E2
SENSOR - TEMPERATURE
FAULT CODE E2
PCB
FAULT CODE E9
OVERHEAT THERMOSTAT
FAULT CODE E9
FLUE THERMOSTAT
FAULT CODE E9
PCB
FAULT CODE F7
FLUE
FAULT CODE F7
PCB WATER INGRESS
FAULT CODE F7
SET - ELECTRODES
FAULT CODE FD
FAULT CODE RESET
FAULT CODE A1
FAULT CODE RESET
FAULT CODE P1-P2-P3
FAULT CODE RESET
FAULT CODE F7
PCB
FAULT CODE A8
FAULT CODE RESET
FAULT CODE A8
CONTROL - ROOM TEMPERATURE
FAULT CODE A8
FAULT CODE RESET (A8)
CH FUNCTION
PCB
CH BURNER IGNITION
CONTROL - ROOM TEMPERATURE
DHW PUMP RUNS SINGLE
PUMP ASSEMBLY
DOES PUMP RUN
PUMP VARIABLE SPEED
FAULT CODE A1
PUMP ASSEMBLY
FAULT CODE A1
PUMP VARIABLE SPEED
CH NOISY
PUMP VARIABLE SPEED
CH SHUTS DOWN
PUMP VARIABLE SPEED
FAULT CODE AC
FAULT CODE RESET
FAULT CODE FO
FAULT CODE RESET
FAULT CODE FO 1
Z REDIRECTION
FAULT CODE OVERHEAT
PUMP ASSEMBLY
FAULT CODE OVERHEAT
PUMP VARIABLE SPEED
FAULT CODE A1 2
PUMP VARIABLE SPEED
FAULT CODE E9
PUMP VARIABLE SPEED
DAMAGED OR CHOKED 2
BURNER
DHW PUMP RUNS
PCB
FAULT CODE A1
PCB
FAULT CODE FC
INTEGRAL PROGRAMMER / MODULE
IGNITES BUT BAFFLES
GAS VALVE
TX FUNCTION
PCB
BOILER HEATS SYSTEM COOL
PUMP VARIABLE SPEED
FAULT CODE E9 2
PCB
FAULT CODE E9 2
FLUE THERMOSTAT
FAULT CODE E9
FAULT CODE E9
E9
SYSTEM RESTRICTION OR BLOCKAGE
NO DHW
INTEGRAL PROGRAMMER / MODULE
FAULTY
FAN
DHW TOO HOT
MOTOR - DIVERTER VALVE
DHW TEMP CONTROL
PCB
MECHANICAL 2
DIVERTER VALVE - 3 WAY
MECHANICAL
MOTOR - DIVERTER VALVE
DHW NOISY
PUMP VARIABLE SPEED
DHW COOL RADS COOL
PUMP VARIABLE SPEED
CH TEMP CONTROL
PCB
CH MODULATION
PCB
ELECTRICAL 2
MOTOR - DIVERTER VALVE
FAULT FLUE STAT
HARNESS - MAIN
SPARK FUNCTION
PCB
SPARK FUNCTION 2
PCB
LOW
GAS INLET PRESSURE
BURNER DOES NOT IGNITE
GAS VALVE
MECHANICAL
GAS VALVE
INCORRECT/DAMAGED
SET - ELECTRODES
DAMAGED OR CHOKED
BURNER
FAULT CODE A7
FAULT CODE RESET
FAULT CODE B1
FAULT CODE RESET
FAULT CODE C1
FAN
FAULT CODE C1 2
FAN
FAULT CODE C1 3
FAN
FAULT CODE C1 3
PCB
FAULT CODE C1
DIRECTION CHOICE OR CONTINUE
FAULT CODE D3
FAULT CODE RESET
FAULT CODE E2
HARNESS - MAIN
FAULT CODE E2
FAULT CODE RESET
FAULT CODE E9
HARNESS - MAIN
FAULT CODE F7
FAULT CODE RESET
BURNER IGNITES BUT BAFFLES
CHARACTERISTIC TEST FROM DHW BURNER IGNITES
BOILER GOES TO OVERHEAT BEFORE 88 °C
CHARACTERISTIC TEST FROM OBSERVATION RUN TO MAX TEMP - OVERHEAT OCCUR
BOILER EXCEEDS 90 °C AND CONTINUES TO HEAT
CHARACTERISTIC TEST FROM OBSERVATION RUN TO MAX TEMP - OVERHEAT OCCUR
DHW NOISY (KETTLING)
CHARACTERISTIC TEST FROM DHW OPERATION
BOILER HEATS BUT DHW DOES NOT, RADIATORS COLD
CHARACTERISTIC TEST FROM DHW OPERATION
DHW DOES NOT HEAT, RADIATORS HOT WITH NO CH DEMAND
CHARACTERISTIC TEST FROM DHW OPERATION
DHW TOO HOT
CHARACTERISTIC TEST FROM DHW OPERATION
CH NOISY (KETTLING)
CHARACTERISTIC TEST FROM CH OPERATION
BOILER HEATS UP BUT SYSTEM REMAINS COOL
CHARACTERISTIC TEST FROM CH OPERATION
BOILER SHUTS DOWN BEFORE TEMPERATURE IS SATISFIED
CHARACTERISTIC TEST FROM CH OPERATION
BOILER STAYS AT LOW RATE / INSUFFICIENT OUTPUT
CHARACTERISTIC TEST FROM CH OPERATION
BURNER IGNITES SMOOTHLY BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM DHW BURNER IGNITES
BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM DHW BURNER IGNITES
FAN RUNS THEN SLOWS DOWN, REMAINS SLOW AND EVENTUALLY STOPS
CHARACTERISTIC TEST FROM ? MODE OF FAN OPERATION
WEAK OR INCONSISTANT SPARK OBSERVED
CHARACTERISTIC TEST FROM SPARKING ELECTRODE LEADS
NO SPARKING OBSERVED
CHARACTERISTIC TEST FROM SPARKING ELECTRODE LEADS
INLET PRESSURE DOES NOT DIP
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
INLET PRESSURE DROPS AWAY
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
ELECTRODE ASSEMBLY POOR CONDITION AND/OR GAP INCORRECT
CHARACTERISTIC TEST FROM INSPECTION BURNER AND ELECTRODE ASSEMBLY
BURNER DAMAGED AND/OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION BURNER AND ELECTRODE ASSEMBLY
FAULT CODE C1 OCCURS ( CAN TAKE UP TO 6 MINS)
CHARACTERISTIC TEST FROM ? MODE OF FAN OPERATION
FAN RUNS DIFFERENTLY THAN OTHER OPTIONS
CHARACTERISTIC TEST FROM ? MODE OF FAN OPERATION
VOLTAGE BELOW 124 VAC
CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB)
VOLTAGE ABOVE 135 VAC
CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB)
VOLTAGE BELOW 124 VAC
CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB)
VOLTAGE ABOVE 135 VAC
CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB)
01/12/2017 10:03:24 1709_2_50_1 09/01/2018 08:33:26
01/12/2017 10:58:42
NO PROGRAMMER
PCB
TRANSFORMER 24 VOLTS
{GAINPCBACS}
FUSE F3 (RESISTANCE)
REMOVE FUSE F3 FROM ITS HOLDER
INSPECTION HARNESS TR2 TO PCB
GAIN ACCESS TO WIRING CONNECTIONS FOR THE
TR2 ROOM STAT AND PROGRAMMER PCB
EXTERNAL CONTROL VOLTAGE (OUTPUT)
{GAINPCBACS}
EXTERNAL CONTROL VOLTAGE (INPUT)
{GAINPCBACS}
OBSERVATION SINGLE OR VARIABLE SPEED PUMP FITTED
{GAINPCBACS}
OBSERVATION SINGLE OR VARIABLE SPEED PUMP FITTED
{GAINPCBACS}
OBSERVATION SINGLE OR VARIABLE SPEED PUMP FITTED
{GAINPCBACS}
OBSERVATION SINGLE OR VARIABLE SPEED PUMP FITTED
{GAINPCBACS}
RESISTANCE HARNESS TIMER/PROGRAMMER
DISCONNECT THE WIRING HARNESS BETWEEN THE MAIN PCB AND THE TIMER MODULE
VOLTAGE POLARITY CHECK
{GAINPCBACS}
OBSERVATION SINGLE OR VARIABLE SPEED PUMP FITTED
{GAINPCBACS}
OBSERVATION SINGLE OR VARIABLE SPEED PUMP FITTED
{GAINPCBACS}
OBSERVATION SINGLE OR VARIABLE SPEED PUMP FITTED
{GAINPCBACS}
GAS INLET PRESSURE
ATTACH U-GAUGE TO THE INLET PRESSURE TEST POINT
VOLTAGE MAIN PCB TO DISPLAY
UNCLIP, DISCONNECT ELECTRICALLY AND REMOVE DISPLAY FROM APPLIANCE
EXTERNAL CONTROL VOLTAGE (OUTPUT)
{GAINPCBACS}
EXTERNAL CONTROL VOLTAGE (INPUT)
{GAINPCBACS}
TRANSFORMER 24 VOLTS
{GAINPCBACS}
ON/OFF SWITCH VOLTAGE
{GAINPCBACS}
BOILER ON/OFF SWITCH ON
FUSE F1 (RESISTANCE)
REMOVE FUSE F1 FROM ITS HOLDER
OBSERVATION SINGLE OR VARIABLE SPEED PUMP FITTED
{GAINPCBACS}
PRIMARY SENSOR
REMOVE THE ORANGE LEADS FROM THE PRIMARY SENSOR
PRIMARY SENSOR
REMOVE THE ORANGE LEADS FROM THE PRIMARY SENSOR
VOLTAGE DIVERTER VALVE DHW AT PCB
{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR FROM DIVERTER VALVE AND MAKE SAFE
VOLTAGE DIVERTER VALVE DHW AT PCB
{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR FROM DIVERTER VALVE AND MAKE SAFE
OBSERVATION SINGLE OR VARIABLE SPEED PUMP FITTED
{GAINPCBACS}
OBSERVATION SINGLE OR VARIABLE SPEED PUMP FITTED
{GAINPCBACS}
VOLTAGE DIVERTER VALVE CH AT PCB
{GAINPCBACS}
REMO
PRIMARY SENSOR
REMOVE THE ORANGE LEADS FROM THE PRIMARY SENSOR
OH THERMOSTAT RESISTANCE
DISCONNECT RED LEADS FROM THE OH THERMOSTAT
FLAME SENSE LEAD INSPECTION
REMOVE THE FLAME SEN
DHW SENSOR
REMOVE THE PLUG OF T
OBSERVATION FAN RUNS (FAULT CODE C1)
BOILER ON/OFF SWITCH OFF
SPARKING ELECTRODE LEADS (FAULT CODE C1)
BOILER ON/OFF SWITCH
FAN VOLTAGE CONTROL (PCB)
BOILER ON/OFF SWITCH
DHW SENSOR
REMOVE THE PLUG OF T
RESISTANCE PRIMARY FLOW SENSOR AND HARNESS
DISCONNECT CONNECTOR PLUG MARKED ST 16 FROM THE PCB
PRIMARY SENSOR
REMOVE THE ORANGE LEADS FROM THE PRIMARY SENSOR
OH CIRCUIT RESISTANCE
REMOVE CONNECTOR MARKED ST16 FROM PCB
OH THERMOSTAT RESISTANCE
DISCONNECT RED LEADS FROM THE OH THERMOSTAT
PUMP TEST
CH TEMPERATURE SELEC
TRANSFORMER RESISTANCE
REMOVE TRANSFORMER F
INSPECTION MODE SELECTOR SWITCH (TR2)
LOCATE TR2 ROOM STAT
INTEGRAL PROGRAMMER
BOILER ON/OFF SWITCH
INSPECTION HARNESS TR2 TO PCB
GAIN ACCESS TO WIRING CONNECTIONS FOR THE
TR2 ROOM STAT AND PROGRAMMER PCB
OBSERVATION REMOVE PUMP DC CONNECTOR
{GAINPCBACS}
REMOVE THE DC PUMP CONNECTOR FROM THE PCB AND MAKE SAFE
OBSERVATION REMOVE PUMP DC CONNECTOR
{GAINPCBACS}
REMOVE THE DC PUMP CONNECTOR FROM THE PCB AND MAKE SAFE
INSPECTION HARNESS TR2 TO PCB
GAIN ACCESS TO WIRING CONNECTIONS FOR THE
TR2 ROOM STAT AND PROGRAMMER PCB
SPARK ELECTRODE LEADS
DISCONNECT ELECTRODE LEADS
FLAME SENSE LEAD INSPECTION
REMOVE THE FLAME SEN
INSPECTION BEARING PLATE
REMOVE AIR INTAKE HO
INSPECTION FLUEWAYS
REMOVE THE FRONT COVER FROM THE HEAT EXCHANGER
DHW PUMP RUNS
CH TEMPERATURE SELECTOR TO OFF POSITION
PUMP TEST
CH TEMPERATURE SELEC
OBSERVATION REMOVE PUMP DC CONNECTOR
{GAINPCBACS}
REMOVE THE DC PUMP CONNECTOR FROM THE PCB AND MAKE SAFE
RESISTANCE PUMP (VARIABLE SPEED)
DISCONNECT PUMP PLUGS FROM PCB
RESISTANCE PUMP (VARIABLE SPEED)
DISCONNECT PUMP PLUGS FROM PCB
RESISTANCE PUMP (VARIABLE SPEED)
DISCONNECT PUMP PLUGS FROM PCB
RESISTANCE HARNESS PCB TO DISPLAY
DISCONNECT THE HARNESS BETWEEN THE PCB AND THE DISPLAY
DHW SENSOR
REMOVE THE PLUG OF T
GAS INLET PRESSURE
ATTACH U-GAUGE TO THE INLET PRESSURE TEST POINT
PRESSURE FAN (IGNITION)
ATTACH F.G.A UNIT TO FAN PRESSURE TEST POINT
INSPECTION FLUEWAYS
REMOVE THE FRONT COVER FROM THE HEAT EXCHANGER
INSPECTION BEARING PLATE
REMOVE AIR INTAKE HO
GAS FLOW REGULATOR
BOILER ON/OFF SWITCH OFF
INSPECTION BEARING PLATE
REMOVE AIR INTAKE HO
OBSERVATION DISCONNECT TR2
CENTRAL HEATING THER
FUSE F2 (RESISTANCE)
REMOVE FUSE F2 FROM ITS HOLDER
FUSE F3 (RESISTANCE)
REMOVE FUSE F3 FROM ITS HOLDER
MAINS POWER SUPPLY
{GAINPCBACS}
TRANSFORMER RESISTANCE
REMOVE TRANSFORMER F
PUMP TEST
CH TEMPERATURE SELEC
DIFFERENTIAL PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE PROBES AS INDICATED BY THE RED ARROWS
CH THERMOSTAT TO MAX
OBSERVATION RUN TO MAX TEMP - OVERHEAT OCCUR
ATTACH TEMPERATURE P
OH THERMOSTAT RESISTANCE
DISCONNECT RED LEADS FROM THE OH THERMOSTAT
PRIMARY SENSOR
REMOVE THE ORANGE LEADS FROM THE PRIMARY SENSOR
DIVERTER VALVE BODY
REMOVE DIVERTER VALVE HEAD (IF NOT ALREADY REMOVED)
INTEGRAL PROGRAMMER DHW
BOILER ON/OFF SWITCH
DHW SENSOR
REMOVE THE PLUG OF T
FAN VOLTAGE
BOILER ON/OFF SWITCH OFF
DISCONNECT FAN CONNECTOR FROM THE PCB
VOLTAGE FAN SWITCHED
ON/OFF SWITCH OFF
DHW SENSOR
REMOVE THE PLUG OF T
FAN VOLTAGE
BOILER ON/OFF SWITCH OFF
DISCONNECT FAN CONNECTOR FROM THE PCB
VOLTAGE FAN SWITCHED
ON/OFF SWITCH OFF
OBSERVATION DIVERTER VALVE HEAD DHW POSITION
REMOVE DIVERTER VALV
DHW SENSOR
REMOVE THE PLUG OF T
OBSERVATION DIVERTER VALVE HEAD DHW POSITION
REMOVE DIVERTER VALV
PRIMARY SENSOR
REMOVE THE ORANGE LEADS FROM THE PRIMARY SENSOR
RESISTANCE CHECK HARNESS DIVERTER VALVE
REMOVE THE DIVERTER
RESISTANCE CHECK HARNESS DIVERTER VALVE
REMOVE THE DIVERTER
PUMP TEST
CH TEMPERATURE SELEC
DIVERTER VALVE BODY
REMOVE DIVERTER VALVE HEAD (IF NOT ALREADY REMOVED)
PUMP TEST
CH TEMPERATURE SELEC
GAS INLET PRESSURE
ATTACH U-GAUGE TO THE INLET PRESSURE TEST POINT
PRIMARY SENSOR
REMOVE THE ORANGE LEADS FROM THE PRIMARY SENSOR
DHW SENSOR
REMOVE THE PLUG OF T
GAS INLET PRESSURE
ATTACH U-GAUGE TO THE INLET PRESSURE TEST POINT
PUMP TEST
CH TEMPERATURE SELEC
OBSERVATION DIVERTER VALVE HEAD CH POSITION
BOILER CH THERMOSTAT
PUMP TEST
CH TEMPERATURE SELEC
PRIMARY SENSOR
REMOVE THE ORANGE LEADS FROM THE PRIMARY SENSOR
PRIMARY SENSOR
REMOVE THE ORANGE LEADS FROM THE PRIMARY SENSOR
RESISTANCE CHECK HARNESS DIVERTER VALVE
REMOVE THE DIVERTER
RECTIFICATION (VOLTAGE OUT)
BOILER ON/OFF SWITCH OFF
OH CIRCUIT RESISTANCE
REMOVE CONNECTOR MARKED ST16 FROM PCB
FLUE THERMOSTAT RESISTANCE
REMOVE RED LEADS FROM THE FLUE TEMPERATURE THERMOSTAT
SPARK GENERATOR OUTPUT
BOILER ON/OFF SWITCH
PRESSURE GAS INLET DROP
ATTACH U GAUGE TO INLET PRESSURE TEST POINT OF THE GAS VALVE
SPARK ELECTRODE LEADS
DISCONNECT ELECTRODE LEADS
SPARK ELECTRODE LEADS
DISCONNECT ELECTRODE LEADS
SPARK ELECTRODE LEADS
DISCONNECT ELECTRODE LEADS
GAS VALVE VOLTAGE
DISCONNECT THE PLUG
PRESSURE FAN (IGNITION)
ATTACH F.G.A UNIT TO FAN PRESSURE TEST POINT
INSPECTION FLUEWAYS
REMOVE THE FRONT COVER FROM THE HEAT EXCHANGER
INSPECTION BEARING PLATE
REMOVE AIR INTAKE HO
GAS FLOW REGULATOR
BOILER ON/OFF SWITCH OFF
PRESSURE FAN (IGNITION)
ATTACH F.G.A UNIT TO FAN PRESSURE TEST POINT
INSPECTION FLUEWAYS
REMOVE THE FRONT COVER FROM THE HEAT EXCHANGER
INSPECTION BEARING PLATE
REMOVE AIR INTAKE HO
INSPECTION BURNER AND ELECTRODE ASSEMBLY
REMOVE THE BURNER AS
RECTIFICATION (VOLTAGE IN)
BOILER ON/OFF SWITCH OFF
FLAME SENSE LEAD INSPECTION
REMOVE THE FLAME SEN
FAN VOLTAGE
BOILER ON/OFF SWITCH OFF
DISCONNECT FAN CONNECTOR FROM THE PCB
INSPECTION BEARING PLATE (FAN SPEED)
REMOVE AIR INTAKE HO
FAN VOLTAGE CONTROL (PCB)
BOILER ON/OFF SWITCH
INSPECTION BEARING PLATE (FAN SPEED)
REMOVE AIR INTAKE HO
INSPECTION BEARING PLATE (FAN SPEED)
REMOVE AIR INTAKE HO
INSPECTION BEARING PLATE (FAN SPEED)
REMOVE AIR INTAKE HO
FAN VOLTAGE
BOILER ON/OFF SWITCH OFF
DISCONNECT FAN CONNECTOR FROM THE PCB
VOLTAGE FAN SWITCHED
ON/OFF SWITCH OFF
INSPECTION BEARING PLATE (FAN SPEED)
REMOVE AIR INTAKE HO
INSPECTION BEARING PLATE (FAN SPEED)
REMOVE AIR INTAKE HO
INSPECTION BEARING PLATE (FAN SPEED)
REMOVE AIR INTAKE HO
FLUE THERMOSTAT RESISTANCE
REMOVE RED LEADS FROM THE FLUE TEMPERATURE THERMOSTAT
INSPECTION PCB (WATER INGRESS)
{GAINPCBACS}
System Information
- Total Tests: 524
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control