Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
IDEAL ISAR M30/100
GLOBALLY REPLACED
IDEAL ISAR M30/100
{ISOLATEMAINSPOWER}<
FAN RUNS (PREHEAT)
BOILER MAINS SWITCH ON
PREHEAT SATISFACTORY
ENSURE SECONDARY HEA
CH DEMAND
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
DHW OPERATION
BOILER ON OFF SWITCH ON
BOILER DHW THERMOSTAT SET TO MAX
DHW BURNER MODULATION
SET THE DHW FLOW RATE AT THE TAP TO APPROXIMATELY 3.0 L/MIN (0.7GALL/MIN )
CH OPERATION
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAXIMUM
CH BURNER MODULATION
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
PUMP RUNS (PREHEAT)
BOILER MAINS SWITCH ON
BURNER IGNITES (PREHEAT)
BOILER MAINS SWITCH ON
DIAGNOSTIC OPTIONS
PLEASE SELECT FROM O
HEADER FOR FUSE INVESTIGATION
INTENTIONALLY BLANK HEADER FOR FUSE INVESTIGATION
DETACHED
SENSORS
ELECTRICAL SAFETY CHECKS
ELECTRICAL SAFETY CHECKS
POTS
USER CONTROL (DISPLAY UNIT)
H_1 FC DIAGOVERHEAT SECTION
THERMISTOR - BOILER CONTROL ( FLOW)
OVERHEAT SECTIONH_2 FC DIAG
THERMISTOR- BOILER CONTROL (RETURN)
REPAIR AS NEC
HARNESS SENSOR
PREHEAT INPUT CHECK
POWER TO EXT CONTROLS
LINK FAULT
POWER TO EXT CONTROLS
DHW BURNER MODULATION
THERMISTOR - BOILER CONTROL ( FLOW)
DHW MODULATION
SENSOR DHW
O/H SECTION LINK IN SUPPLY CH DEMAND
POWER TO EXT CONTROLS
PUMP RUNS PREHEAT
HARNESS SENSOR
DHW FLOW RATE
FLOW REGULATOR/FILTER
RADS COOL CH OPPREHEAT
SENSOR DHW
RADS COOL CH OPPREHEAT999
SENSOR DHW
PASSING CH DEMAND
TAPS
PASSING CH OPPREHEAT
TAPS
DHW FLOW RATE DHW OP
FLOW REGULATOR/FILTER
PUMP DOES NOT RUN FOR PREHEAT
SENSOR DHW
FC DIAG H_N
POLARITY REVERSAL
LF OR HF DOT FAULT CODE
KIT - FLAME DETECTION ELECTRODE
DOES NOT RECOGNISE DEMAND
SENSOR DHW
DOES NOT RECOGNISE DEMAND
HARNESS FAN
OVERHEAT OPERATED
SENSOR DHW
RADS COOL CH OP
PCB
RADS COOL CH OP
SENSOR DHW
PASSING CH OP
TAPS
RADS TOO COOL BOILER TO TEMP
KIT - DIVERTOR VALVE
1 DASH/DOT FAULT CODE
HARNESS MAIN PCB DISPLAY BOARD
DASH/DOT FAULT CODE
USER CONTROL (DISPLAY UNIT)
NO LIGHTS
PCB AND FAN
POWER UP
HARNESS MAIN PCB DISPLAY BOARD
ONLY ON OFF SWITCH ILLUMINATED
USER CONTROLS HOUSING
DHW TEMP RISE POOR RADS WARM
HARNESS MAINS
BLOCKED
SECONDARY HEAT EXCHANGER
PREHEAT SATISFACTORY
KIT - DIVERTOR VALVE
ON WITH NO DEMAND
THERMISTOR - BOILER CONTROL ( FLOW)
ON WITH NO DEMAND
THERMISTOR- BOILER CONTROL (RETURN)
3 DASHES
THERMISTOR - BOILER CONTROL ( FLOW)
3 DASHES
THERMISTOR- BOILER CONTROL (RETURN)
3 DASHES
SENSOR DHW
3 DASHES FAULT CODE
THERMISTOR - BOILER CONTROL ( FLOW)
3 DASHES FAULT CODE
THERMISTOR- BOILER CONTROL (RETURN)
3 DASHES FAULT CODE
SENSOR DHW
FLASHES LA OR HA
SYSTEM FILL AND VENT
FLASHES LA OR HA
BOILER OVERHEAT
LA OR HA FAULT CODE
OVERHEAT THERMOSTAT
LA OR HA RESETS SHOWS 3 DASHES
BOILER OVERHEAT
3 DASHES
BOILER OVERHEAT
3 DASHES NO RESET
THERMISTOR - BOILER CONTROL ( FLOW)
3 DASHES NO RESET
THERMISTOR- BOILER CONTROL (RETURN)
LA OR HA THEN 3 DASHES
THERMISTOR - BOILER CONTROL ( FLOW)
LA OR HA THEN 3 DASHES
THERMISTOR- BOILER CONTROL (RETURN)
LA OR HA NO RESET
THERMISTOR - BOILER CONTROL ( FLOW)
LA OR HA NO RESET
THERMISTOR- BOILER CONTROL (RETURN)
LA OR HA NO RESET
SENSOR DHW
RESETS SHOWS 3 DASHES
SENSOR DHW
LA OR HA FAULT CODE
SENSOR DHW
BLOCKED DHW OP
SECONDARY HEAT EXCHANGER
DHW QUIET OPERATION RADIATORS WARM
KIT - DIVERTOR VALVE
BURNER IGNITES (PREHEAT)
GAS INLET PRESSURE
BURNER ESTABLISHES (PREHEAT)
KIT - FLAME DETECTION ELECTRODE
DASH/DOT FAULT CODE
USER CONTROLS HOUSING
CH BURNER MODULATION
USER CONTROL (DISPLAY UNIT)
CH MODULATION
USER CONTROL (DISPLAY UNIT)
DHW BURNER MODULATION
THERMISTOR- BOILER CONTROL (RETURN)
DHW BURNER MODULATION
USER CONTROL (DISPLAY UNIT)
DHW MODULATION
USER CONTROL (DISPLAY UNIT)
OVERHEAT
USER CONTROL (DISPLAY UNIT)
OVERHEAT/DOES NOT RESPOND TO CH
POWER TO EXT CONTROLS
POWER UP
HARNESS MAIN PCB DISPLAY BOARD PLUS SWITCH
DOES NOT RUN 2
HARNESS FAN
FAN DOES NOT RUN
KIT - FLAME DETECTION ELECTRODE
DOES NOT RUN 3
HARNESS FAN
FAN DAMAGED PCB
PCB AND FAN
FAN DOES NOT RUN 2
KIT - FLAME DETECTION ELECTRODE
DOES NOT RUN
HARNESS FAN
FAN DAMAGED PCB 2
PCB AND FAN
FAN DOES NOT RUN L8
KIT - FLAME DETECTION ELECTRODE
DOES NOT RUN 3 L8
HARNESS FAN
FAN DAMAGED PCB L8
PCB AND FAN
FAN DOES NOT RUN 2 L8
KIT - FLAME DETECTION ELECTRODE
DOES NOT RUN L8
HARNESS FAN
FAN DAMAGED PCB 2 L8
PCB AND FAN
DOES NOT RUN 2 L8
HARNESS FAN
RADS WARM NO CH DEMAND
HARNESS MAINS
STICKING
KIT - DIVERTOR VALVE
STICKING 2
KIT - DIVERTOR VALVE
NOISY
SYSTEM FILL AND VENT
NOISY 2
SYSTEM FILL AND VENT
NOISY 3
SYSTEM FILL AND VENT
DHW OPERATION
OVERHEAT THERMOSTAT
DHW OPERATION
THERMISTOR - BOILER CONTROL ( FLOW)
DHW OPERATION
THERMISTOR- BOILER CONTROL (RETURN)
DHW OPERATION
FLUE THERMISTOR
OUT OF CALIBRATION 2
SENSOR DHW
RESTRICTED OR BLOCKED
CONDENSATE TRAP AND SEAL
RUNNING SLOW / WEAK
PUMP
DHW OPERATION POOR TEMP RISE
THERMISTOR - BOILER CONTROL ( FLOW)
DHW OPERATION POOR TEMP RISE
THERMISTOR- BOILER CONTROL (RETURN)
DHW OPERATION POOR TEMP RISE
FLUE THERMISTOR
OUT OF CALIBRATION 3
SENSOR DHW
LOW
GAS INLET PRESSURE
PASSING MIXER TAP
PLUMBING ISSUE
RESTRICTED OR BLOCKED
BURNER INJECTOR
RESTRICTED OR BLOCKED - POOR DHW
CONDENSATE TRAP AND SEAL
RESTRICTED POOR DHW
BURNER
RESTRICTED OR BLOCKED 2
CONDENSATE TRAP AND SEAL
LOW 2
GAS INLET PRESSURE
RESTRICTED OR BLOCKED
IMPULSE TUBE
LEAKING CAUSING BAFFLING ETC
TURRET GASKET
DAMAGED OR BLOCKED
BURNER
COLLAPSED IN AFFECTING COMBUSTION
INSULATION COMBUSTION CHAMBER
RESTRICTED OR BLOCKED
FLUE WAYS
RESTRICTED OR BLOCKED 2
BURNER INJECTOR
RADS COOL CH OP 2
THERMISTOR - BOILER CONTROL ( FLOW)
RADS TOO COOL BOILER TO TEMP SHUTS DOWN PREMATURELY
KIT - DIVERTOR VALVE
RADS COOL CH OP SHUTS DOWN PREMATURELY
SENSOR DHW
SHUTS DOWN PREMATURELY 2
KIT - DIVERTOR VALVE
CH OPERATION 2
PUMP
PREMATURE SHUTDOWN 1
USER CONTROL (DISPLAY UNIT)
PREMATURE SHUTDOWN
USER CONTROL (DISPLAY UNIT)
CH OPERATION
TURRET GASKET
RESTRICTED OR BLOCKED 8
CONDENSATE TRAP AND SEAL
PREMATURE SHUTDOWN
TURRET GASKET
PREMATURE SHUTDOWN
CONDENSATE TRAP AND SEAL
FUSE BLOWN 3
HARNESS MAINS
FUSE BLOW
GAS VALVE
ELECTRICAL SHORT
KIT - DIVERTER VALVE ACTUATOR
SHORTED
EMC FILTER
POWER UP
FUSE MAINS
POWER UP
FUSE MAIN PCB F1
BURNER ESTABLISHES (PREHEAT)
CONDENSATE TRAP AND SEAL
BURNER ESTABLISHES (PREHEAT)
TURRET GASKET
GAP
FLAME DETECTION ELECTRODE GAP
BURNER ESTABLISHES (PREHEAT)
BURNER
BURNER IGNITES BUT DOES NOT ESTABLISH
INSULATION COMBUSTION CHAMBER
BURNER ESTABLISH
PRIMARY HEAT EXCHANGER
BURNER DOES NOT IGNITE
IMPULSE TUBE
BURNER IGNITES (PREHEAT)
BURNER INJECTOR
BURNER IGNITES (PREHEAT)
CONDENSATE TRAP AND SEAL
BURNER DOES NOT IGNITE
INSULATION COMBUSTION CHAMBER
SPARKING BUT DOES NOT IGNITE
FLUE WAYS
WATER
IMPULSE TUBE
FAULT FURTHER INVESTIGATION
OVERHEAT THERMOSTAT
BURNER IGNITES (PREHEAT)
GAS VALVE
BURNER DOES NOT IGNITE
CONDENSATE TRAP AND SEAL
BURNER DOES NOT IGNITE
BURNER INJECTOR
BURNER IGNITES (PREHEAT) LF
GAS INLET PRESSURE
BURNER ESTABLISHES (PREHEAT) LF
KIT - FLAME DETECTION ELECTRODE
BURNER ESTABLISHES (PREHEAT) LF
CONDENSATE TRAP AND SEAL
BURNER ESTABLISHES (PREHEAT) LF
TURRET GASKET
GAP LF
FLAME DETECTION ELECTRODE GAP
BURNER IGNITES BUT DOES NOT ESTABLISH LF
INSULATION COMBUSTION CHAMBER
BURNER ESTABLISH LF
PRIMARY HEAT EXCHANGER
PUMP RUNS (PREHEAT)
THERMISTOR - BOILER CONTROL ( FLOW)
NOT IGNITING
IGNITION ELECTRODE WARPED
PUMP RUNS (PREHEAT)
THERMISTOR- BOILER CONTROL (RETURN)
BURNER IGNITES (PREHEAT)
IGNITION ELECTRODE AND LEAD
BURNER IGNITES (PREHEAT) LF
IGNITION ELECTRODE AND LEAD
BURNER DOES NOT IGNITE LF
IMPULSE TUBE
BURNER IGNITES (PREHEAT) LF
BURNER INJECTOR
PUMP RUNS (PREHEAT)
FLUE THERMISTOR
BURNER IGNITES (PREHEAT) LF
CONDENSATE TRAP AND SEAL
BURNER DOES NOT IGNITE LF
INSULATION COMBUSTION CHAMBER
SPARKING BUT DOES NOT IGNITE LF
FLUE WAYS
NOT IGNITING LF
IGNITION ELECTRODE WARPED
WATER LF
IMPULSE TUBE
FAULT FURTHER INVESTIGATION LF
OVERHEAT THERMOSTAT
BURNER IGNITES (PREHEAT) LF
GAS VALVE
PUMP RUNS (PREHEAT)
SENSOR DHW
BURNER DOES NOT IGNITE LF
CONDENSATE TRAP AND SEAL
BURNER DOES NOT IGNITE LF
BURNER INJECTOR
LA OR HA FAULT CODE H9 L9
SENSOR DHW
LA OR HA THEN 3 DASHES H9 L9
THERMISTOR- BOILER CONTROL (RETURN)
LA OR HA THEN 3 DASHES H9 L9
THERMISTOR - BOILER CONTROL ( FLOW)
RESETS SHOWS 3 DASHES H9 L9
SENSOR DHW
3 DASHES NO RESET H9 L9
THERMISTOR- BOILER CONTROL (RETURN)
3 DASHES NO RESET H9 L9
THERMISTOR - BOILER CONTROL ( FLOW)
LA OR HA RESETS SHOWS 3 DASHES H9 L9
BOILER OVERHEAT
LA OR HA FAULT CODE H9 L9
OVERHEAT THERMOSTAT
LA OR HA NO RESET H9 L9
SENSOR DHW
LA OR HA NO RESET H9 L9
THERMISTOR- BOILER CONTROL (RETURN)
LA OR HA NO RESET H9 L9
THERMISTOR - BOILER CONTROL ( FLOW)
FLASHES LA OR HA H9 L9
BOILER OVERHEAT
FLASHES LA OR HA H9 L9
SYSTEM FILL AND VENT
PRE HEATFCDIAG 2
KIT - FLAME DETECTION ELECTRODE
HE / LE 2
FAN
HE OR LE FAULT CODES 2
SENSORS
HE / LE 2
THERMISTOR - BOILER CONTROL ( FLOW)
HE / LE 2
THERMISTOR- BOILER CONTROL (RETURN)
HE / LE
OVERHEAT THERMOSTAT
PRE HEATFCDIAG 2 2
KIT - FLAME DETECTION ELECTRODE
HE / LE 2 2
FAN
HE OR LE FAULT CODES 2 2
SENSORS
HE / LE 2 2
THERMISTOR - BOILER CONTROL ( FLOW)
HE / LE 2 2
THERMISTOR- BOILER CONTROL (RETURN)
HE / LE 2
OVERHEAT THERMOSTAT
FAN DOES NOT RUN
THERMISTOR - BOILER CONTROL ( FLOW)
FAN DOES NOT RUN
THERMISTOR- BOILER CONTROL (RETURN)
INSUFFICIENT OUTPUT
FLUE WAYS
DHW NOISY
PRIMARY HEAT EXCHANGER
DHW OPERATION
PUMP
CH OPERATION
KIT - DIVERTOR VALVE
CH OPERATION
PUMP
PREHEAT SATISFACTORY
CONDENSATE TRAP AND SEAL
FLAME DETECTION
PCB
H_4 FC DIAG 2
FLUE THERMISTOR
FC DIAG H_4 NOT FILLED AND VENTED
SYSTEM FILL AND VENT
H_3 FC DIAG
SENSOR DHW
H_2 FC DIAG
THERMISTOR- BOILER CONTROL (RETURN)
H_1 FC DIAG
THERMISTOR - BOILER CONTROL ( FLOW)
FAULT
EMC FILTER
POWER UP
PCB
PRE HEATFCDIAG99
KIT - FLAME DETECTION ELECTRODE
PREHAT COMPLET9999
PUMP
OVERHEAT PROBLEM
SECONDARY HEAT EXCHANGER
9999999PREHEAT NOISY999
PRIMARY HEAT EXCHANGER
FLOW FC DIAGOVERHEAT SECTION
HARNESS SENSOR
OVERHEAT SECTIONRETURN FC DIAG
HARNESS SENSOR
INCORRECT POSITION
PCB LINKS
FAULT CODE LA
Z DIRECTION CHOICE OR CONTINUE
HA FCODE
FLUE THERMISTOR
FROM PCB
HARNESS MAINS
PREHEAT SATISFACTORY
PRIMARY HEAT EXCHANGER
CH INPUT
MULTI FAULT PCB
EXTERNAL CONTROL
HARNESS INPUT
EXTERNAL CONTROL
MULTI FAULT HARNESS EXTERNAL CONTROL PCB
CH DEMAND
EXTERNAL ROOM THERMOSTAT/ TIMER
FAULTY
MULTI FAULT HARNESS EXTERNAL CONTROL PCB
OH SECTION
MULTI FAULT PCB
DHW FLOW RATE
SECONDARY HEAT EXCHANGER
CH DEMAND
PCB
DHW FLOW RATE DHW OP
SECONDARY HEAT EXCHANGER
PUMP DOES NOT RUN
HARNESS SENSOR
FLASHES H THEN N
PCB
HB OR LB FAULT CODE
USER CONTROL C/W CONTROL KNOB
DOES NOT RECOGNISE DEMAND
HARNESS SENSOR
RADS WARM NO DEMAND
KIT - DIVERTER VALVE ACTUATOR
STICKING RADS WARM NO DEMAND
KIT - DIVERTER VALVE ACTUATOR
STICKING DHW QUIET RADS WARM
KIT - DIVERTER VALVE ACTUATOR
DHW QUIET RADS WARM
KIT - DIVERTER VALVE ACTUATOR
OVERHEAT OPERATED
HARNESS SENSOR
CH OPERATION
KIT - DIVERTER VALVE ACTUATOR
POWER UP
PCB DISPLAY BOARD PLUS SWITCH
POWER UP OUT PUT TO DISPLAY BOARD
PCB MAIN PLUS SWITCH
NO LIGHTS
HARNESS FAN
POWER UP
USER CONTROL (DISPLAY UNIT)
DHW OPERATION
KIT - DIVERTER VALVE ACTUATOR
LETBY PREHEAT
KIT - DIVERTOR VALVE
ON WITH NO DEMAND
EXTERNAL ROOM THERMOSTAT/ TIMER
3 DASHES
PCB
3 DASHES FLOW THERMISTOR
HARNESS SENSOR
3 DASHES RETURN THERMISTOR
HARNESS SENSOR
3 DASHES DHW THERMISTOR
HARNESS SENSOR
3 DASHES FLOW
HARNESS SENSOR
3 DASHES RETURN
HARNESS SENSOR
3 DASHES DHW
HARNESS SENSOR
FLASHES LA OR HA
Z DIRECTION CHOICE OR CONTINUE
LA OR HA FAULT CODE
HARNESS MAINS
OVERHEAT
PCB
LA OR HA RESETS SHOWS 3 DASHES
Z DIRECTION CHOICE OR CONTINUE
OVERHEAT 3 DASHES FAULT CODE
Z DIRECTION CHOICE OR CONTINUE
OVERHEAT TEMP
PCB
RESETS SHOWS 3 DASHES FLOW
HARNESS SENSOR
RESETS SHOWS 3 DASHES RETURN
HARNESS SENSOR
3 DASHES
HARNESS SENSOR
3 DASHES 1
HARNESS SENSOR
LA OR HA NO CONTROL THERMISTOR
HARNESS SENSOR
LA OR HA RETURN THERMISTOR
HARNESS SENSOR
LA OR HA DHW THERMISTOR
HARNESS SENSOR
RESETS SHOW 3 DASHES DHW
HARNESS SENSOR
3 DASHES 2
HARNESS SENSOR
LETBY DHW OPERATION
KIT - DIVERTOR VALVE
CH MODULATION
PCB
DHW MODULATION
PCB
OVERHEAT
SECONDARY HEAT EXCHANGER
NOISY
PRIMARY HEAT EXCHANGER
OVERHEAT/DOES NOT RESPOND TO CH
MULTI FAULT PCB
DOES NOT RESPOND TO CH
MULTI FAULT HARNESS EXTERNAL CONTROL PCB
NO LIGHTS
USER CONTROLS HOUSING PLUS SWITCH
PREHEAT SATISFACTORY
KIT - DIVERTER VALVE ACTUATOR
BOILER CYCLING
PCB
RESTRICTED OR BLOCKED
SECONDARY HEAT EXCHANGER
RESTRICTED OR BLOCKED
PRIMARY HEAT EXCHANGER
RESTRICTED OR BLOCKED POOR TEMP RISE
SECONDARY HEAT EXCHANGER
RESTRICTED OR BLOCKED POOR TEMP RISE
PRIMARY HEAT EXCHANGER
WRONG MIX 2
GAS VALVE
CH OPERATION SHUTS DOWN PREMATURELY
KIT - DIVERTER VALVE ACTUATOR
BLOWING FUSES
PUMP
FUSE BLOWN
HARNESS FAN
FUSE BLOWN 2
HARNESS MAINS
FUSE BLOWN
HARNESS MAINS
PCB - FUSE BLOWN
PCB - FUSE BLOWN
BLANK FOR MAINS FUSE INVESTIGATION
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR PCB FUSE INVESTIGATION
Z DIRECTION CHOICE OR CONTINUE
PRESSURE DROPS AWAY
GAS INLET PRESSURE
BURNER DOES NOT IGNITE
OVERHEAT THERMOSTAT
BURNER DOES NOT IGNITE
HARNESS SENSOR
PUMP RUNS (PREHEAT)
PUMP
WRONG MIX
GAS VALVE
MECH FAULT
GAS VALVE
NO SPARKING PRESENT
IGNITION ELECTRODE GAP
NO SPARKING PRESENT LF
IGNITION ELECTRODE GAP
PRESSURE DROPS AWAY LF
GAS INLET PRESSURE
WRONG MIX LF
GAS VALVE
BURNER DOES NOT IGNITE LF
OVERHEAT THERMOSTAT
BURNER DOES NOT IGNITE LF
HARNESS SENSOR
MECH FAULT LF
GAS VALVE
3 DASHES 2 H9 L9
HARNESS SENSOR
3 DASHES 1 H9 L9
HARNESS SENSOR
3 DASHES H9 L9
HARNESS SENSOR
RESETS SHOW 3 DASHES DHW H9 L9
HARNESS SENSOR
RESETS SHOWS 3 DASHES RETURN H9 L9
HARNESS SENSOR
RESETS SHOWS 3 DASHES FLOW H9 L9
HARNESS SENSOR
LA OR HA RESETS SHOWS 3 DASHES H9 L9
Z DIRECTION CHOICE OR CONTINUE
LA OR HA FAULT CODE H9 L9
HARNESS MAINS
OVERHEAT H9 L9
PCB
LA OR HA DHW THERMISTOR H9 L9
HARNESS SENSOR
LA OR HA RETURN THERMISTOR H9 L9
HARNESS SENSOR
LA OR HA NO CONTROL THERMISTOR H9 L9
HARNESS SENSOR
FLASHES LA OR HA H9 L9
Z DIRECTION CHOICE OR CONTINUE
LA OR HA FAULT CODE H9 L9
Z DIRECTION CHOICE OR CONTINUE
NO DEMAND
DHW SENSOR - PCB
H3 FAULT CODE
DHW SENSOR - PCB
L_E FC DIAG 2
PCB
L_E FC DIAG 2 2
PCB
FAN DOES NOT RUN
PCB
DHW NOISY
SECONDARY HEAT EXCHANGER
CH OPERATION
EXPANSION VESSEL
PREHEAT SATISFACTORY
SECONDARY HEAT EXCHANGER
NOT FOUND
DIAGNOSTICS CODE
H_F FC DIAG
KIT - FLAME DETECTION ELECTRODE
H_4 FC DIAG
PCB
FLUE FC DIAG 2
HARNESS SENSOR
CLEAN REPLACE AS NEC FC DIAG
PRIMARY HEAT EXCHANGER
DHW FC DIAG
HARNESS SENSOR
H_2 FC DIAG
PCB
RETURN FC DIAG
HARNESS SENSOR
H_1 FC DIAG
PCB
FLOW FC DIAG
HARNESS SENSOR
FAULT
HARNESS EMC PCB
POWER UP
ON OFF SWITCH
L_E FC DIAG99
PCB
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
SYSTEM KETTLES (O/H)
CHARACTERISTIC TEST FROM CH OPERATION (HEX PROVING)
SYSTEM DOES NOT REACT TO CH DEMAND
CHARACTERISTIC TEST FROM CH OPERATION (HEX PROVING)
FLASHES H THEN 5
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
BOILER DOES NOT REACT TO CH DEMAND
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
BOILER KETTLES
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
PREHEAT CYCLE DOES NOT COMPLETE
CHARACTERISTIC TEST FROM PREHEAT SATISFACTORY
FLOW RATE INCORRECT
CHARACTERISTIC TEST FROM DHW OPERATION
HB OR LB (B WILL BE IN LOWER CASE)
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
1 DASH AND/OR DOT
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES L THEN F. OR H THEN F. (NOTE THE DOT AFTER THE F)
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
DIVERTER VALVE NOT IN CORRECT POSITION
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
DIVERTER VALVE STICKING
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
LEVER CYCLES IN AND OUT CONTINUOUSLY
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
DIVERTER VALVE NOT IN CORRECT POSITION
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
DIVERTER VALVE STICKING
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
LEVER CYCLES IN AND OUT CONTINUOUSLY
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
PREHEAT SATISFACTORY - BOILER FIRES WITH NO DEMAND DISPLAY SHOWS C
CHARACTERISTIC TEST FROM PREHEAT SATISFACTORY
3 DASHES
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
WILL NOT RESET
CHARACTERISTIC TEST FROM CAN BOILER BE RESET
RESETS SHOWS 3 DASHES
CHARACTERISTIC TEST FROM CAN BOILER BE RESET
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
BURNER IGNITES BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM BURNER IGNITES (PREHEAT)
BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM BURNER IGNITES (PREHEAT)
SYSTEM KETTLES (O/H)
CHARACTERISTIC TEST FROM IGNITION ELECTRODE SPARKING AND GAP
SYSTEM DOES NOT REACT TO CH DEMAND
CHARACTERISTIC TEST FROM IGNITION ELECTRODE SPARKING AND GAP
GAS FLOW PRESSURE DROPS AWAY
CHARACTERISTIC TEST FROM GAS FLOW
GAS FLOW PRESSURE DIPS BUT STILL NO IGNITION
CHARACTERISTIC TEST FROM GAS FLOW
PUMP DOES NOT RUN
CHARACTERISTIC TEST FROM PUMP RUNS (PREHEAT)
PUMP RUNS FOR APPROXIMATELY 5 SECONDS THEN STOPS
CHARACTERISTIC TEST FROM PUMP RUNS (PREHEAT)
SPARK GAP INCORRECT
CHARACTERISTIC TEST FROM IGNITION ELECTRODE SPARKING AND GAP
SPARK GAP CORRECT BUT NO SPARK PRESENT
CHARACTERISTIC TEST FROM IGNITION ELECTRODE SPARKING AND GAP
SPARK GAP INCORRECT
CHARACTERISTIC TEST FROM IGNITION ELECTRODE SPARKING AND GAP
SPARK GAP CORRECT BUT NO SPARK PRESENT
CHARACTERISTIC TEST FROM IGNITION ELECTRODE SPARKING AND GAP
GAS FLOW PRESSURE DROPS AWAY
CHARACTERISTIC TEST FROM GAS FLOW
GAS FLOW PRESSURE DIPS BUT STILL NO IGNITION
CHARACTERISTIC TEST FROM GAS FLOW
FLASHES H9 OR L9
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
WILL NOT RESET
CHARACTERISTIC TEST FROM CAN BOILER BE RESET
RESETS SHOWS 3 DASHES
CHARACTERISTIC TEST FROM CAN BOILER BE RESET
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RADIATORS WARM WITH NO CH DEMAND
CHARACTERISTIC TEST FROM PREHEAT SATISFACTORY
BOILER KETTLING
CHARACTERISTIC TEST FROM PREHEAT SATISFACTORY
DHW NOISY
CHARACTERISTIC TEST FROM DHW OPERATION
DHW TEMPRTAURE RISE INSUFFICIENT, RADS BEGIN TO HEAT
CHARACTERISTIC TEST FROM DHW OPERATION
BOILER CYCLING
CHARACTERISTIC TEST FROM DHW OPERATION
DHW TEMPERATURE RISE INSUFFICIENT, RADS REMAIN COLD
CHARACTERISTIC TEST FROM DHW OPERATION
CH NOISY OPERATION
CHARACTERISTIC TEST FROM CH OPERATION
BOILER FIRES FOR CH AND REACHES TEMPERATURE BUT RADIATORS REMAIN COOL
CHARACTERISTIC TEST FROM CH OPERATION
BOILER SHUTS DOWN PREMATURELY OR DOES NOT FIRE FOR CH
CHARACTERISTIC TEST FROM CH OPERATION
EXCESSIVE SYSTEM PRESSURE
CHARACTERISTIC TEST FROM CH OPERATION
FLASHES L THEN E
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES LA OR HA
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES L THEN 8
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN 1
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN 2
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN 3
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN 4
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN F
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN N
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FAULT CODE NOT PRESENT RETURN TO STEP BY STEP DIAGNOSIS
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
NOISE WHEN MODULATING DOWN
CHARACTERISTIC TEST FROM PREHEAT SATISFACTORY
FLASHES H THEN E
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
NO LIGHTS
CHARACTERISTIC TEST FROM POWER UP
ONLY ON OFF SWITCH ILLUMINATED
CHARACTERISTIC TEST FROM POWER UP
FAN DOES NOT RUN
CHARACTERISTIC TEST FROM FAN RUNS (PREHEAT)
FAN HUNTS RUNS SLOWS RUNS SLOWS
CHARACTERISTIC TEST FROM FAN RUNS (PREHEAT)
01/11/2019 09:08:16 1910_1_50_1 20/11/2019 10:37:57
24/10/2019 08:11:45
PUMP VOLTAGE
{ISOLATEMAINSPOWER}<
HARNESS CHECK - THERMISTORS
{ISOLATEMAINSPOWER}
PUMP VOLTAGE AT PCB
BOILER MAINS SWITCH
RESISTANCE DHW THERMISTOR
{ISOLATEMAINSPOWER}
DISCONNECT THE INLINE CONNECTOR TO THE DHW THERMISTOR
FLOW REGULATOR/FILTER
{ISOLATEMAINSPOWER}
WATER OFF
RESISTANCE CONTROL THERMISTOR DHW AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE PLUG FROM PCB
RESISTANCE DHW THERMISTOR
{ISOLATEMAINSPOWER}
DISCONNECT THE INLINE CONNECTOR TO THE DHW THERMISTOR
POWER TO DISPLAY BOARD
{ISOLATEMAINSPOWER}
LOWER MAIN PCB
DISCONNECT DISPLAY HARNESS FROM THE MAIN PCB
RESISTANCE CONTROL THERMISTOR DHW AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE PLUG FROM PCB
RESISTANCE DHW THERMISTOR
{ISOLATEMAINSPOWER}
DISCONNECT THE INLINE CONNECTOR TO THE DHW THERMISTOR
DIVERTER VALVE SPINDLE
{ISOLATEMAINSPOWER}<
DIVERTER VALVE VOLTAGE DHW
BOILER MAINS SWITCH ON
RESISTANCE FAN AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE FAN CONNECTOR FROM THE PCB
RESISTANCE FAN
{ISOLATEMAINSPOWER}
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE CONTROL THERMISTOR FLOW
{ISOLATEMAINSPOWER}
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTORS AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE PLUG FROM PCB
RESISTANCE CONTROL THERMISTORS AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE PLUG FROM PCB
OVERHEAT THERMOSTAT AND HARNESS RESISTANCE
{ISOLATEMAINSPOWER}
RESISTANCE OVERHEAT
{ISOLATEMAINSPOWER}<
RESISTANCE CONTROL THERMISTORS AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE PLUG FROM PCB
RESISTANCE CONTROL THERMISTORS AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE PLUG FROM PCB
OBSERVATION WHICH USER CONTROL IS FITTED ?
{ISOLATEMAINSPOWER}
REMOVE USER CONTROL
RESISTANCE CH POTENTIOMETER
{ISOLATEMAINSPOWER}<
RESISTANCE DHW POTENTIOMETER
{ISOLATEMAINSPOWER}<
RESISTANCE DHW POTENTIOMETER
{ISOLATEMAINSPOWER}<
FLAME DETECTION ELECTRODE AND LEAD
{ISOLATEMAINSPOWER}
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
FLAME DETECTION ELECTRODE AND LEAD
{ISOLATEMAINSPOWER}
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
FLAME DETECTION ELECTRODE AND LEAD
{ISOLATEMAINSPOWER}
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
FLAME DETECTION ELECTRODE AND LEAD
{ISOLATEMAINSPOWER}
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
TEMPERATURE DIFFERENTIAL CH
ATTACH TEMPERATURE C
TEMPERATURE DIFFERENTIAL CH
ATTACH TEMPERATURE C
DIVERTER VALVE SPINDLE
{ISOLATEMAINSPOWER}<
DIVERTER VALVE VOLTAGE DHW
BOILER MAINS SWITCH ON
RESISTANCE CH POTENTIOMETER
{ISOLATEMAINSPOWER}<
RESISTANCE PUMP AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE THE PUMP CONNECTOR FROM THE PCB
RESISTANCE HARNESS PUMP
{ISOLATEMAINSPOWER}<
FAN RESISTANCE
{ISOLATEMAINSPOWER}
DISCONNECT THE HARNESS FROM FAN
GAS VALVE RESISTANCE
{ISOLATEMAINSPOWER}
DISCONNECT LEADS FROM GAS VALVE
DIVERTER VALVE RESISTANCE
{ISOLATEMAINSPOWER}<
GAS VALVE RESISTANCE
{ISOLATEMAINSPOWER}
DISCONNECT LEADS FROM GAS VALVE
IGNITION ELECTRODE SPARKING AND GAP
{ISOLATEMAINSPOWER}<
GAS VALVE RESISTANCE
{ISOLATEMAINSPOWER}
DISCONNECT LEADS FROM GAS VALVE
RESISTANCE CONTROL THERMISTORS AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE PLUG FROM PCB
RESISTANCE CONTROL THERMISTORS AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE PLUG FROM PCB
OVERHEAT THERMOSTAT AND HARNESS RESISTANCE
{ISOLATEMAINSPOWER}
RESISTANCE OVERHEAT
{ISOLATEMAINSPOWER}<
WHAT FAULT CODE IS SHOWN
ON /OFF SWITCH ON
RESISTANCE CONTROL THERMISTOR FLUE AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE PLUG FROM PCB
RESISTANCE CONTROL THERMISTOR FLUE
{ISOLATEMAINSPOWER}<
RESISTANCE DHW THERMISTOR
{ISOLATEMAINSPOWER}
DISCONNECT THE INLINE CONNECTOR TO THE DHW THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
{ISOLATEMAINSPOWER}
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE CONTROL THERMISTOR FLOW
{ISOLATEMAINSPOWER}
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
FUSE RESISTANCE (FUSED SPUR)
{ISOLATEMAINSPOWER}
REMOVE FUSE FROM FUSED SPUR
ON/OFF SWITCH VOLTAGE INPUT
{ISOLATEMAINSPOWER}
REMOVE CONTROL DISPLAY
PUMP RUNS
BOILER MAINS SWITCH
SENSOR FIXINGS
{ISOLATEMAINSPOWER}
DOES PUMP SPIN FREELY
{ISOLATEMAINSPOWER}<
DOES PUMP STOP QUICKLY
BOILER ON OFF SWITCH ON
RESISTANCE CONTROL THERMISTORS AND HARNESS
{ISOLATEMAINSPOWER}
REMOVE PLUG FROM PCB
POTENTIOMETER RESISTANCE (DHW)
{ISOLATEMAINSPOWER}<
CH OPERATION (HEAT EXCHANGER PROVING)
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAXIMUM
RESISTANCE CONTROL THERMISTOR FLOW
{ISOLATEMAINSPOWER}
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
{ISOLATEMAINSPOWER}
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR