4726743 FERROLI OPTIMAX HE 38C HONEYWELL PCB
WARNING - IMPORTA
OBSERVATION FAN PURGE AND PUMP PULSE
ENSURE NO DEMANDS
ENSURE APPLIANCE IS COOL
ECO MODE ON (ECO ON DISPLAY)
OBSERVATION DHW DEMAND RECOGNISED
ECO MODE ON (ECO ON DISPLAY)
OBSERVATION BURNER IGNITION AND ESTABLISH
ECO MODE ON (ECO IN DISPLAY)
OPERATION DHW
DHW SET TO MAXIMUM TEMPERATURE (65°C)
OPERATION CH
CH THERMOSTAT SET TO MAX
OBSERVATION CH DEMAND RECOGNISED
BOILER CH THERMOSTAT
OBSERVATION SYSTEM PRESSURE RISE
BOILER CH THERMOSTAT TO MAX
OBSERVATION DHW MODULATION
RUN THE HOT WATER TAP WITH A FLOW RATE OF APPROXIMATELY 7 L/MIN
FAN INVESTIGATION F15,A05
INTENTIONALLY BLANK HEADER FOR F15 AND A05
OPERATION PRE HEAT
ENSURE BOILER IS COO
NO DISPLAY (CONTINUE DIAGNOSIS)
INTENTIONALLY BLANK HEADER FOR INVESTIGATION WITH NO DISPLAY
TYPE OF DIAGNOSTIC PROCEDURE
PLEASE SELECT FROM O
RETURN THERMISTOR INVESTIGATION F11
INTENTIONALLY BLANK HEADER FOR F11
PRESSURE SENSOR INVESTIGATION PRESSURE TOO HIGH
INTENTIONALLY BLANK HEADER FOR PRESSURE TOO HIGH
REPEAT OVERPRESSURE INVESTIGATION A26
INTENTIONALLY BLANK HEADER FOR A26 FAULT CODE
POWER SUPPLY VOLTAGE F34
INTENTIONALLY BLANK HEADER FOR F34
POWER SUPPLY FREQUENCY F35
INTENTIONALLY BLANK HEADER FOR F35
FLAME DETECTED AFTER BURNER SHUTDOWN A02
INTENTIONALLY BLANK HEADER FOR A02 FAULT CODE
CONDENSE LEVEL TOO HIGH F36, A25
INTENTIONALLY BLANK HEADER FOR F36 AND A25
GAS VALVE A62
INTENTIONALLY BLANK HEADER FOR A62 FAULT CODE
OUTSIDE TEMPERATURE ERROR F39
INTENTIONALLY BLANK HEADER FOR F39 FAULT CODE
BURNER SHUTDOWN A06
INTENTIONALLY BLANK HEADER FOR A06
FUSE INVESTIGATION
INTENTIONALLY BLANK HEADER FOR FUSE INVESTIGATION
OVERHEAT INVESTIGATION
INTENTIONALLY BLANK HEADER FOR OVERHEAT INVESTIGATION
SERVICE MODE MAX AND MIN GUIDE
TO ENTER SERVICE
PARAMETERS GUIDE
1. TO ACCESS
FAULT CODE HISTORY
1. PRESS AND
FAULT CODES FOR FAULT CODE HISTORY
PLEASE CHOOSE THE AP
HEADER FOR IGNITION FAULT FROM FAULT CODES HISTORY
INTENTIONALLY BLANK HEADER FOR FAULT CODES FROM FAULT CODE HISTORY
PRESSURE SENSOR INVESTIGATION PRESSURE TOO LOW
INTENTIONALLY BLANK HEADER FOR PRESSURE TOO LOW
F42 INVESTIGATION
INTENTIONALLY BLANK HEADER FOR F42
HEADER FOR FLUE GAS ANALYSIS WHEN INVESTIGATING CH FROM SEQUENCE OF OPS
INTENTIONALLY BLANK
PRESSURE SENSOR DISCONNECTED F47
INTENTIONALLY BLANK HEADER FOR FAULT CODE F47
BLOCKED NOT SHOWING PRESSURE FLUE OVERHEAT
GAUGE - PRESSURE - PUSH FIT
NOT FITTED CORRECTLY FLUE OVERHEAT
SENSOR FITMENT
TURBINE
HARNESS
NOT SPARKING
ELECTRODE IGNITION
SHORTING TO EARTH F36 A25
LEAD IGNITION W/O PLUG
PARTIAL RESTRICTION
INJECTOR 6.5 - MAIN - NG (38C)
EXPLOSIVE IGNITION
ELECTRODE IGNITION
EXPLOSIVE IGNITION
INJECTOR 6.5 - MAIN - NG (38C)
EXPLOSIVE IGNITION
GAS INLET PRESSURE
READING HOT WHEN COLD
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
READING HOT WHEN COLD
SENSOR 10K NTC - EXCHANGER C/W BRACKET
RUNNING SLOW OR WEAK
PUMP ASSEMBLY - GRUNDFOS (38C)
RESTRICTED WRONG TEMPERATURE DIFFERENTIAL
PRIMARY FILTER
RESISTANCE HIGH OR POOR CONDITION 2
LEAD IGNITION W/O PLUG
NOT SPARKING 2
ELECTRODE IGNITION
BLANK FOR SERVICE MODE GUIDE
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR PARAMETERS GUIDE
Z DIRECTION CHOICE OR CONTINUE
SHORTING TO EARTH 2
LEAD IGNITION W/O PLUG
BLANK FOR FAULT CODE HISTORY
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR FAULT CODES FAULT CODE HISTORY
Z DIRECTION CHOICE OR CONTINUE
LOW WHEN OTHER APPLIANCES ON
GAS INLET PRESSURE
FLAT
EXPANSION VESSEL - 7 LITRE
PREVENTING DEMAND
SENSOR 10K NTC - EXCHANGER C/W BRACKET
PREVENTING DEMAND
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
PARTIALLY RESTRICTED CAUSING POOR FLUE GAS READINGS 2
INJECTOR 6.5 - MAIN - NG (38C)
IGNITION PROBLEMS
LEAD IGNITION W/O PLUG
IGNITION PROBLEMS
ELECTRODE IGNITION
IGNITION PROBLEMS
IGNITION LEAD END DAMAGED
IGNITION PROBLEMS 2
LEAD IGNITION W/O PLUG
IGNITION PROBLEMS
IGNITION CAP
IGNITION PROBLEMS 2
ELECTRODE IGNITION
BLOCKED CAUSING IGNITION PROBLEMS
TRAP CONDENSATE OR PIPE
IGNITION PROBLEMS
SUMP AND PIPE
IGNITION PROBLEMS
INJECTOR 6.5 - MAIN - NG (38C)
HIGH RESISTANCE INTERMITTENT
GAS VALVE
IGNITION PROBLEMS 3
TRAP CONDENSATE OR PIPE
IGNITION PROBLEMS 3
SUMP AND PIPE
IGNITION PROBLEMS 3
INJECTOR 6.5 - MAIN - NG (38C)
POOR IGNTION
PARAMETERS IGNITION FAN SPEED
CAUSING OVER PRESSURE FAULT CODE
SYSTEM PRESSURE TOO HIGH
REPEAT OVER PRESSURE
SYSTEM PRESSURE TOO HIGH
FAULT CODE
SYSTEM PRESSURE LOW
RESTRICTED OR BLOCKED
NOZZLE AIR GAS MIXING CHAMBER
NOT LIGHTING
IGNITION ELECTRODE INTERNAL
CAUSING NO IGNITION
BURNER - CERAMIC (38C)
RESTRICTED OR BLOCKED 2
NOZZLE AIR GAS MIXING CHAMBER
DAMAGED CAUSING BAFFLING
BURNER - CERAMIC (38C)
RESTRICTING HEAT EX CAUSING BAFFLING
INSULATION PADS
RESTRICTED OR BLOCKED BAFFLING
HEAT EXCHANGER (38C)
EXPLOSIVE IGNITION
NOZZLE AIR GAS MIXING CHAMBER
EXPLOSIVE IGNITION
IGNITION ELECTRODE INTERNAL
EXPLOSIVE IGNITION
BURNER - CERAMIC (38C)
A06 FAULT CODE
GAS INLET PRESSURE
A06 FAULT CODE
TRAP CONDENSATE OR PIPE
A06 FAULT CODE
SUMP AND PIPE
A06 FAULT CODE
INJECTOR 6.5 - MAIN - NG (38C)
A06 FAULT CODE LOCKING OUT
NOZZLE AIR GAS MIXING CHAMBER
A06 FAULT CODE
FLUE
A06 FAULT CODE
BURNER - CERAMIC (38C)
A06 FAULT CODE
INSULATION PADS
A06 FAULT CODE
HEAT EXCHANGER (38C)
FLUE OVERHEAT
SENSOR - FLUE C/W COLLAR
OVERHEAT FLUE OVERHEAT
SENSOR 10K NTC - EXCHANGER C/W BRACKET
OVERHEAT FLUE OVERHEAT
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
CAUSING OVERHEAT FLUE OVERHEAT
PUMP ASSEMBLY - GRUNDFOS (38C)
LEAKING ONTO FLUE STAT
HEAT EXCHANGER GASKETS
FLUE OVERHEAT
FLUE
DAMAGED FLUEWAYS CAUSING FLUE OVERHEAT
HEAT EXCHANGER (38C)
DHW COOL RADS COOL
PRIMARY HEAT EXCHANGER AND RETURN FILTER
BLOCKED NOT SHOWING PRESSURE
GAUGE - PRESSURE - PUSH FIT
NOT FITTED CORRECTLY
SENSOR FITMENT
OVERHEAT
SENSOR 10K NTC - EXCHANGER C/W BRACKET
OVERHEAT
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
CAUSING OVERHEAT
PUMP ASSEMBLY - GRUNDFOS (38C)
RESTRICTED WRONG TEMPERATURE DIFFERENTIAL OVERHEAT
PRIMARY FILTER
RESTRICTED OR BLOCKED OVERHEAT
RETURN FILTER CH
BLOCKED
VALVE - BY-PASS C/W NRV
RESTRICTED OR BLOCKED OVERHEAT
PLATE - HEAT EXCHANGER (38C)
FULLY OR PARTIALLY CLOSED - OVERHEAT
ISOLATION VALVES FLOW AND RETURN
RESTRICTED OR BLOCKED CAUING POOR FLUE GAS READINGS 2
NOZZLE AIR GAS MIXING CHAMBER
DAMAGED CAUSING FLUE GAS FAIL 2
BURNER - CERAMIC (38C)
RESTRICTING HEAT EX CAUSING POOR FLUE GAS READINGS 2
INSULATION PADS
RESTRICTED OR BLOCKED IGNITION PROBLEMS
HEAT EXCHANGER (38C)
IGNITION PROBLEMS
NOZZLE AIR GAS MIXING CHAMBER
IGNITION PROBLEMS 2
IGNITION ELECTRODE INTERNAL
DAMAGED CAUSING IGNITION PROBLEMS
BURNER - CERAMIC (38C)
IGNITION PROBLEMS
INSULATION PADS
RESTRICTED OR BLOCKED IGNTION
HEAT EXCHANGER (38C)
IGNITION PROBLEMS 3
NOZZLE AIR GAS MIXING CHAMBER
IGNITION PROBLEMS 3
FLUE
IGNITION PROBLEMS 3
IGNITION ELECTRODE INTERNAL
IGNITION PROBLEMS 3
BURNER - CERAMIC (38C)
IGNITION PROBLEMS 3
INSULATION PADS
RESTRICTED OR BLOCKED IGNITION PROBLEMS 3
HEAT EXCHANGER (38C)
LOW
GAS INLET PRESSURE
BLOCKED NOT SHOWING FOR FAULT CODE
GAUGE - PRESSURE - PUSH FIT
BLOCKED NOT SHOWING PRESSURE FAULT CODE 2
GAUGE - PRESSURE - PUSH FIT
NOT FITTED CORRECTLY DHW TOO HOT
SENSOR FITMENT
NOT MODULATING DHW
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
NOT MODULATING DHW
SENSOR 10K NTC - EXCHANGER C/W BRACKET
NOT FITTED CORRECTLY DHW NOT MODULATING
SENSOR FITMENT
NOT FITTED CORRECTLY CH NOT MODULATING
SENSOR FITMENT
EXPLOSIVE IGNITION
INSULATION PADS
FLAT FAULT CODE
EXPANSION VESSEL - 7 LITRE
NOT READING PRESSURE CORRECTLY FAULT CODE 2
GAUGE - PRESSURE - PUSH FIT
FLAT FAULT CODE FAULT CODE
EXPANSION VESSEL - 7 LITRE
DHW ISOLATION VALVE
VALVE ISOLATION - COLD WATER
INSUFFICIENT
WATER SUPPLY
CAUSING INTERMITTIENT LOCKOUT
PARAMETERS IGNITION FAN SPEED - FAULT HISTORY
NOISY ON DHW
SYSTEM PRESSURE LOW
ONLY PARTIALLY OPENING GAS VALVE
AIR IMPULSE TUBE
ONLY PARTIALLY OPENING GAS VALVE
TRAP CONDENSATE OR PIPE
ONLY PARTIALLY OPENING GAS VALVE
SUMP AND PIPE
BLOCKED STOPPING IGNITION
INJECTOR 6.5 - MAIN - NG (38C)
GAS VALVE DAMAGED PCB
PCB AND GAS VALVE
PUMP OVERHEAT
HARNESS
FAULT CODE F42
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
FULLY OR PARTIALLY CLOSED - OVERHEAT F42
ISOLATION VALVES FLOW AND RETURN
BLOCKED NOT SHOWING PRESSURE F42
GAUGE - PRESSURE - PUSH FIT
NOT FITTED CORRECTLY F42
SENSOR FITMENT
OVERHEAT F42
SENSOR 10K NTC - EXCHANGER C/W BRACKET
PUMP OVERHEAT F42
HARNESS
CAUSING OVERHEAT F42
PUMP ASSEMBLY - GRUNDFOS (38C)
NO SPARK
PCB
RESTRICTED WRONG TEMPERATURE DIFFERENTIAL OVERHEAT F42
PRIMARY FILTER
RESTRICTED OR BLOCKED OVERHEAT F42
RETURN FILTER CH
BLOCKED F42
VALVE - BY-PASS C/W NRV
RESTRICTED OR BLOCKED OVERHEAT F42
PLATE - HEAT EXCHANGER (38C)
CAUSING PUMP PULSE
SYSTEM PRESSURE LOW
PRESSURE SENSOR
HARNESS
FAN AC SECTION NO DISPLAY
HARNESS
FAN DC SECTION NO DISPLAY
HARNESS
FAN DC SECTION 2 NO DISPLAY
HARNESS
FAULTY HALL SENSOR NO DISPLAY
FAN ASSEMBLY
CAUSING PUMP TO RUN CONTINUALLY NO DISPLAY
SENSOR 10K NTC - EXCHANGER C/W BRACKET
CAUSING PUMP TO RUN CONTINUALLY NO DISPLAY
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
PUMP NO DISPLAY
HARNESS
SHORTING
HARNESS
BLANK DISPLAY AND NO RESPONSE
SENSOR 10K NTC - EXCHANGER C/W BRACKET
LOW CAUSING NO RECTIFICATION
GAS INLET PRESSURE
BLANK DISPLAY AND NO RESPONSE
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
DISPLAY BLANK AND NO RESPONSE
SENSOR - FLUE C/W COLLAR
TIMER SECTION
HARNESS
TIMER SECTION 2
HARNESS
TIMER SECTION 3
HARNESS
TIMER SECTION 4
HARNESS
NOT RECTIFYING
RECTIFICATION LEAD
TIMER SECTION 5
HARNESS
PARTIALLY RESTRICTED CAUSING POOR FLUE GAS READINGS 3
INJECTOR 6.5 - MAIN - NG (38C)
RESTRICTED OR BLOCKED CAUING POOR FLUE GAS READINGS 3
NOZZLE AIR GAS MIXING CHAMBER
DAMAGED CAUSING FLUE GAS FAIL 3
BURNER - CERAMIC (38C)
RESTRICTING HEAT EX CAUSING POOR FLUE GAS READINGS3
INSULATION PADS
RESTRICTED OR BLOCKED CAUSING POOR FLUE GAS READINGS 2
HEAT EXCHANGER (38C)
PARTIALLY RESTRICTED CAUSING POOR FLUE GAS READINGS
INJECTOR 6.5 - MAIN - NG (38C)
CLOGGED SCROLL POOR DHW
FAN ASSEMBLY
BLANK FOR FLUE GAS ANALYSIS FROM SEQUENCE OF OPS CH 2
Z DIRECTION CHOICE OR CONTINUE
PRESSURE SENSOR F47
HARNESS
FLUE OVERHEAT
INSULATION PADS
NOT SPARKING
IGNITION LEAD END DAMAGED
F37
PARAMETERS LOW WATER PROTECTION
OVERHEATING AFTER DEMAND
PCB PUMP OVER RUN
HOT SPOTS CAUSING OVERHEAT
HEAT EXCHANGER (38C)
BLANK FOR INSTALLER MODE
Z DIRECTION CHOICE OR CONTINUE
INCORRECT OVERRUNS MAIN MODEL
PCB PUMP OVER RUN
NOT SPARKING
IGNITION CAP
FAN DC SECTION 3
HARNESS
FAULTY HALL SENSOR 2
FAN ASSEMBLY
RESISTANCE HIGH OR POOR CONDITION
LEAD IGNITION W/O PLUG
FAULTY SPEED CONTROL
FAN ASSEMBLY
FAULTY SPEED CONTROL 2
FAN ASSEMBLY
LOW CAUSING BAFFLING
GAS INLET PRESSURE
BLOCKED CAUSING BAFFLING
TRAP CONDENSATE OR PIPE
RESTRICTED OR BLOCKED
SUMP AND PIPE
PARTIALLY RESTRICTED CAUSING WRONG MIX
INJECTOR 6.5 - MAIN - NG (38C)
RESTRICTED HIGH FAN PRESSURE
SUMP AND PIPE
RESTRICTED CAUSING HIGH FAN PRESSURE
BURNER - CERAMIC (38C)
GAS VALVE SECTION
HARNESS
SPLIT NOT OPENING GAS VALVE
AIR IMPULSE TUBE
NOT LIGHTING
ELECTRODE IGNITION
NOT RESPONDING TO INCREASE IN TEMPERATURE
SENSOR 10K NTC - EXCHANGER C/W BRACKET
SLOW OR WEAK 2
PUMP ASSEMBLY - GRUNDFOS (38C)
BLOCKED OR RESTRICTED
PRIMARY FILTER
RESTRICTED OR BLOCKED 2
RETURN FILTER CH
RESTRICTED OR BLOCKED 3
RETURN FILTER CH
DIVERTER VALVE
HARNESS
SLOW OR WEAK 3
PUMP ASSEMBLY - GRUNDFOS (38C)
FULLY OR PARTIALLY CLOSED
ISOLATION VALVES FLOW AND RETURN
DIVERTER VALVE 2
HARNESS
PASSING
VALVE - BY-PASS C/W NRV
BLOCKED CAUSING HIGH FAN PRESSURE
TRAP CONDENSATE OR PIPE
NOT RESPONDING TO INCREASE IN TEMP
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
BLANK FOR F FAULT CODES
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR CASE OFF
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR FUNCTIONAL SEQUENCE
Z DIRECTION CHOICE OR CONTINUE
FAN AC SECTION
HARNESS
FAN DC SECTION
HARNESS
FAN DC SECTION 2
HARNESS
FAULTY HALL SENSOR
FAN ASSEMBLY
BLANK FOR FAULT CODES 2
Z DIRECTION CHOICE OR CONTINUE
PUMP
HARNESS
CAUSING PUMP TO RUN CONTINUALLY
SENSOR 10K NTC - EXCHANGER C/W BRACKET
CAUSING PUMP TO RUN CONTINUALLY
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
CORRECTLY ACTIVATED APPLIANCE COLD
FROST PROTECTION
READING COLD WHEN NOT
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
SHORTING TO EARTH
ELECTRODE - FLAME SENSING
BLOWN THROUGH FATIGUE
FUSE MAINS
BLANK FOR FUSE FH1
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR FUSE FH2
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR NO DISPLAY INVESTIGATION
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR TYPE OF DIAGNOSTIC PROCEDURE
Z DIRECTION CHOICE OR CONTINUE
FAULT CODE
SENSOR 10K NTC - EXCHANGER C/W BRACKET
FAULT CODE
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
SET INCORRECTLY NO DHW THERMISTOR
PARAMETERS
PRESSURE SENSOR FAULT CODE
HARNESS
FAULT CODE
SENSOR - FLUE C/W COLLAR
BLOCKED F36 A26
TRAP CONDENSATE OR PIPE
BLOCKED F36 A36
SUMP AND PIPE
SHORTING TO EARTH F36 A25
ELECTRODE - FLAME SENSING
SHORTING TO EARTH F36 A25
ELECTRODE IGNITION
RESISTANCE INCORRECT
GAS VALVE
F39 FAULT CODE
OUTDOOR SENSOR
BLANK FOR WIRING OR WATER INGRESS
Z DIRECTION CHOICE OR CONTINUE
RESISTANCE INCORRECT FUSE INVESTIGATION
GAS VALVE
SHORTING
PUMP ASSEMBLY - GRUNDFOS (38C)
DC SECTION SHORTING
FAN ASSEMBLY
AC SECTION SHORTING
FAN ASSEMBLY
NOT RECOGNISING DEMAND
FLOW METER
NOT SPARKING
IGNITION ELECTRODE INTERNAL
CAUSING SHORT TO EARTH
IGNITION ELECTRODE INTERNAL
RESTRICTED OR BLOCKED
PLATE - HEAT EXCHANGER (38C)
RESTRICTED OR BLOCKED
HEAT EXCHANGER (38C)
NOT SPARKING 2
IGNITION ELECTRODE INTERNAL
CAUSING SHORT TO EARTH 2
IGNITION ELECTRODE INTERNAL
EXPANSION VESSEL PIPE
EXPANSION VESSEL PIPE
DISPLAY JUMBLED
PCB
PASSING CAUSING A02
GAS VALVE
NOT READING PRESSURE CORRECTLY FAULT CODELOW PRESSURE
SENSOR - LOW WATER PRESSURE KIT
WRONG MIX NOT IGNITING
GAS VALVE
WRONG MIX BAFFLING
GAS VALVE
WRONG MIX EXPLOSIVE IGNITION
GAS VALVE
A06 FAULT CODE
GAS VALVE
SCALED CAUSING NOISE
HEAT EXCHANGER (38C)
RESTRICTED OR BLOCKED OVERHEAT
HEAT EXCHANGER (38C)
CAUSING POOR EMISSIONS OR BURNER DROP OUT 2
GAS VALVE ADJUSTMENT
OVERHEAT 2
OVERHEAT - PCB
NOT READING PRESSURE CORRECTLY REPEAT OVERPESSURE
SENSOR - LOW WATER PRESSURE KIT
BLOCKED FAULT CODE
EXPANSION VESSEL PIPE
BLOCKED FAULT CODE FAULT CODE
EXPANSION VESSEL PIPE
SCALED POOR DHW FLOW
PLATE - HEAT EXCHANGER (38C)
POOR DHW FLOW
DHW INLET FILTER
POOR DHW FLOW
RESTRICTOR - FLOW - 12 LITRE (38C)
RESTRICTED BLOCKED OR JAMMED
FLOW METER
NOT OPENING
GAS VALVE
HARNESS GONE DAMAGED PCB
PCB AND HARNESS
NOT RUNNING OVERHEAT
PUMP ASSEMBLY - GRUNDFOS (38C)
FLOW THERMISTOR FAULT CODE F42
HARNESS
NOT RUNNING OVERHEAT F42
PUMP ASSEMBLY - GRUNDFOS (38C)
RESTRICTED OR BLOCKED OVERHEAT F42
HEAT EXCHANGER (38C)
OVERHEAT F42
OVERHEAT - PCB
AFTER FURTHER INVESTIGATION
PCB NO DISPLAY
NOT READING PRESSURE CORRECTLY
SENSOR - LOW WATER PRESSURE KIT
NOT RUNNING WITH AC VOLTAGE NO DISPLAY
FAN ASSEMBLY
NOT RECTIFYING
PCB
NOT RUNNING WITH DEMAND VOLTAGE NO DISPLAY
FAN ASSEMBLY
NOT RUNNING NO DISPLAY
PUMP ASSEMBLY - GRUNDFOS (38C)
SHORTING
FLOW METER
SHORTING
SENSOR - LOW WATER PRESSURE KIT
RETURN THERMISTOR
HARNESS
FLOW THERMISTOR
HARNESS
NO DISPLAY
PCB
FLUE THERMISTOR
HARNESS
NOT SWITCHING
INTEGRAL TIMER
NOT RECTIFYING
ELECTRODE - FLAME SENSING
NOT SWITCHING POOR DHW
INTEGRAL TIMER
NOT SWITCHING (NOISY)
INTEGRAL TIMER
NOT SWITCHING POOR DHW OVERHEAT
INTEGRAL TIMER
NOT SWITCHING POOR DHW OVERHEAT F42
INTEGRAL TIMER
OPEN OR PASSING ALLOWING FLOW
HOT WATER OUTLETS
REGISTERING DEMAND WHEN NONE PRESENT
FLOW METER
CAUSING POOR EMISSIONS OR BURNER DROP OUT 3
GAS VALVE ADJUSTMENT
POOR DHW
PCB
BLANK FOR FLUE GAS ANALYSIS FROM SEQUENCE OF OPS CH
Z DIRECTION CHOICE OR CONTINUE
NOT REGISTERING PRESSURE F47
SENSOR - LOW WATER PRESSURE KIT
F37 FAULT CODE
PCB
OVERHEATING
PCB
DROPPING AWAY COMPLETELY
GAS INLET PRESSURE
CLOGGED SCROLL
FAN ASSEMBLY
RESTRICTED HIGH PRESSURE
HEAT EXCHANGER (38C)
BLOCKED CAUSING NOISE
PLATE - HEAT EXCHANGER (38C)
WINDINGS GONE
DIVERTER VALVE ASSEMBLY
WINDINGS OK NO MOVEMENT CH
DIVERTER VALVE ASSEMBLY
WINDINGS GONE 2
DIVERTER VALVE ASSEMBLY
WINDINGS OK NO MOVEMENT DHW
DIVERTER VALVE ASSEMBLY
NOT RUNNING WITH AC VOLTAGE
FAN ASSEMBLY
NOT RUNNING WITH DEMAND VOLTAGE
FAN ASSEMBLY
BLANK FOR FAULT CODES
Z DIRECTION CHOICE OR CONTINUE
NOT RUNNING
PUMP ASSEMBLY - GRUNDFOS (38C)
NO POWER TO PUMP
PCB
SHORTING TO EARTH
RECTIFICATION LEAD
NOT OPERATING
WIRELESS CONTROL
BLANK FOR MAINS FUSE INVESTIGATION
Z DIRECTION CHOICE OR CONTINUE
BLOWN THROUGH FATIGUE
FUSE FH1
BLOWN THROUGH FATIGUE
FUSE FH2
RETURN THERMISTOR FAULT CODE
HARNESS
FLOW THERMISTOR FAULT CODE
HARNESS
NOT READING PRESSURE CORRECTLY FAULT CODE
SENSOR - LOW WATER PRESSURE KIT
FLUE THERMISTOR FAULT CODE
HARNESS
SHORTING TO EARTH F36 A25
RECTIFICATION LEAD
GAS VALVE SECTION A62
HARNESS
PUMP SECTION SHORTING
HARNESS
PCB TAKING OUT FUSES
PCB - FUSE
FAN DC SECTION SHORTING
HARNESS
FAN AC SECTION SHORTING
HARNESS
TEMPERATURE DIFFERENTIAL EXCESSIVE
CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL CH
BOILER DOES NOT RESPOND TO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION CH NOISY?
DISPLAY DOES NOT OPERATE
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY OPERATION
DISPLAY OPERATES BUT IS JUMBLED OR DISTORTED
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY OPERATION
TEMPERATURE DIFFERENTIAL EXCESSIVE
CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL CH
BOILER DOES NOT RESPOND TO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION CH NOISY?
FILTER RESTRICTED OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION FLOW SWITCH, FILTER AND RESTRICTOR
FLOW LIMITER RESTRICTED OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION FLOW SWITCH, FILTER AND RESTRICTOR
FLOW TURBINE ASSEMBLY RESTRICTED BLOCKED OR JAMMED
CHARACTERISTIC TEST FROM INSPECTION FLOW SWITCH, FILTER AND RESTRICTOR
NO SPARKING OBSERVED
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
TEMPERATURE DIFFERENTIAL EXCESSIVE
CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL CH
BOILER DOES NOT RESPOND TO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION CH NOISY?
PUMP DOES NOT RUN BUT FAN BEHAVES AS DESCRIBED ABOVE
CHARACTERISTIC TEST FROM OBSERVATION SELF CHECK (NO DISPLAY)
PUMP RUNS CONTINUOUSLY BUT FAN BEHAVES AS DESCRIBED ABOVE
CHARACTERISTIC TEST FROM OBSERVATION SELF CHECK (NO DISPLAY)
PUMP ONLY PULSES TWICE OR FAN DOES NOT BEHAVE AS DESCRIBED ABOVE
CHARACTERISTIC TEST FROM OBSERVATION SELF CHECK (NO DISPLAY)
PUMP ONLY PULSES TWICE BUT FAN BEHAVES AS DESCRIBED ABOVE
CHARACTERISTIC TEST FROM OBSERVATION SELF CHECK (NO DISPLAY)
FAN DOES NOT STOP WHEN PURGE PERIOD ENDS
CHARACTERISTIC TEST FROM OBSERVATION FAN PURGE AND PUMP PULSE
INLET PRESSURE SATISFACTORY BUT DOES NOT DIP DURING SPARKING
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
INLET PRESSURE DROPS AWAY
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
FAN PRESSURE EXCESSIVELY LOW (E G 1MB)
CHARACTERISTIC TEST FROM PRESSURE FAN
FAN PRESSURE EXCESSIVELY HIGH (E G 3MB OR GREATER)
CHARACTERISTIC TEST FROM PRESSURE FAN
BOILER STILL NOISY
CHARACTERISTIC TEST FROM OPERATION CH NOISY?
BOILER DOES NOT RESPOND TO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION CH NOISY?
VOLTAGE MISSING FROM PIN 1 OR 4
CHARACTERISTIC TEST FROM VOLTAGE DC DIVERTER VALVE PERMANENT AT PCB
VOLTAGE PRESENT ON PIN 1 AND 4 BUT ABSENT FROM ONE OR MORE OTHER PINS
CHARACTERISTIC TEST FROM VOLTAGE DC DIVERTER VALVE PERMANENT AT PCB
VOLTAGE MISSING FROM PIN 1 OR 4
CHARACTERISTIC TEST FROM VOLTAGE DC DIVERTER VALVE PERMANENT AT PCB
VOLTAGE PRESENT ON PIN 1 AND 4 BUT ABSENT FROM ONE OR MORE OTHER PINS
CHARACTERISTIC TEST FROM VOLTAGE DC DIVERTER VALVE PERMANENT AT PCB
FAULT CODE SHOWN
CHARACTERISTIC TEST FROM OBSERVATION FAN PURGE AND PUMP PULSE
FAN BEHAVES AS DESCRIBED BUT PUMP DOES NOT RUN
CHARACTERISTIC TEST FROM OBSERVATION FAN PURGE AND PUMP PULSE
FAN BEHAVES AS DESCRIBED BUT PUMP RUNS CONTINUOUSLY
CHARACTERISTIC TEST FROM OBSERVATION FAN PURGE AND PUMP PULSE
BOILER TRIES TO RUN AND / OR FIRE STRAIGHT AFTER PUMP AND FAN PURGE
CHARACTERISTIC TEST FROM OBSERVATION FAN PURGE AND PUMP PULSE
BURNER IGNITES BUT LIGHTS WITH EXPLOSIVE IGNITION
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
SPARKING OCCURS BUT BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
BURNER IGNITES BUT THEN BAFFLES OR DROPS OUT
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
BURNER IGNITES SMOOTHLY BUT FAILS TO ESTABLISH (SPARKING CONTINUES)
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
DHW TOO HOT
CHARACTERISTIC TEST FROM OPERATION DHW
DHW TOO COOL RADS REMAIN COOL WITH NO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION DHW
DHW TOO COOL RADS BEGIN TO HEAT WITH NO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION DHW
BOILER NOISY
CHARACTERISTIC TEST FROM OPERATION DHW
BOILER UP TO TEMPERATURE BUT RADS COLD
CHARACTERISTIC TEST FROM OPERATION CH
BOILER AND SYSTEM TEMPERATURE LOW
CHARACTERISTIC TEST FROM OPERATION CH
09/04/2018 08:25:50 1610_1_50_1 09/04/2018 08:43:25
09/04/2018 08:21:20
VOLTAGE DC FROM TURBINE
{GAINPCBACS}
OBSERVATION SYSTEM PRESSURE RISE (OVERHEAT)
OBSERVE THE MANUAL PRESSURE GAUGE ON THE UNDERSIDE OF THE APPLIANCE
TEMPERATURE DIFFERENTIAL CH
BOILER CH THERMOSTAT
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
OBSERVATION RE WIRE (TIMER BYPASSED)
LINK OUT THE OPENTHERM TERMINALS AS SHOWN IN THE IMAGE
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
RESISTANCE IGNITION LEAD (MODIFIED)
REMOVE THE IGNITION LEAD FROM THE PCB AND FROM THE SPARK ELECTRODE
RESISTANCE IGNITION LEAD (MODIFIED)
REMOVE THE IGNITION LEAD FROM THE PCB AND FROM THE SPARK ELECTRODE
PRESSURE GAS INLET - FOR FAULT HISTORY
ATTACH PRESSURE GAUG
PRESSURE EXPANSION VESSEL
APPLIANCE PRIMARY CIRCUIT DRAINED AND DISCHARGED
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
RESISTANCE IGNITION LEAD (MODIFIED)
REMOVE THE IGNITION LEAD FROM THE PCB AND FROM THE SPARK ELECTRODE
VOLTAGE GAS VALVE BURNER SHUT DOWN
{GAINPCBACS}
ECO
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
OBSERVATION RE WIRE (TIMER BYPASSED)
LINK OUT THE OPENTHERM TERMINALS AS SHOWN IN THE IMAGE
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
PRESSURE EXPANSION VESSEL
APPLIANCE PRIMARY CIRCUIT DRAINED AND DISCHARGED
PRESSURE EXPANSION VESSEL
APPLIANCE PRIMARY CIRCUIT DRAINED AND DISCHARGED
WATER SUPPLY TO PREMISES
TURN ON A COLD WATER TAP
RESISTANCE GAS VALVE AND HARNESS AND TO EARTH
REMOVE CONNECTOR X4 FROM THE PCB
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR FROM THE GAS VALVE
VOLTAGE PUMP AT PUMP
REMOVE THE COVER FROM THE PUMP ASSEMBLY
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR X3 FROM THE PCB
REMOVE THE COVER FROM THE PUMP ASSEMBLY
RESISTANCE THERMISTOR FLOW / STAT AND HARNESS
REMOVE CONNECTOR X6 FROM THE PCB
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
VOLTAGE PUMP AT PUMP
REMOVE THE COVER FROM THE PUMP ASSEMBLY
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR X3 FROM THE PCB
REMOVE THE COVER FROM THE PUMP ASSEMBLY
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
OBSERVATION RE WIRE (TIMER BYPASSED)
LINK OUT THE OPENTHERM TERMINALS AS SHOWN IN THE IMAGE
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
OBSERVATION SELF CHECK (NO DISPLAY)
ENSURE NO DEMANDS
OBSERVATION FAN (DC CONNECTOR REMOVED)
REMOVE THE 4 WAY CONNECTOR FROM THE FAN ASSEMBLY
AND MAKE SAFE
RESISTANCE HARNESS FAN AC
REMOVE THE 3 WIRE CONNECTOR FROM THE FAN
REMOVE CONNECTOR X4 FROM THE PCB
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR X3 FROM THE PCB
REMOVE THE COVER FROM THE PUMP ASSEMBLY
RESISTANCE RECTIFICATION LEAD
REMOVE THE CONNECTOR FROM THE FLAME SENSE ELECTRODE
REMOVE CONNECTOR X12 FROM THE PCB
OBSERVATION X5 CONNECTED TURBINE DISCONNECTED (DISPLAY OPERATES?)
REFIT CONNECTOR X5 TO THE PCB
REMOVE THE CONNECTOR FROM THE FLOW TURBINE
OBSERVATION X5 CONNECTED PRESSURE SENSOR DISCONNECTED
REMOVE THE CONNECTOR FROM THE LOW PRESSURE SENSOR AND MAKE SAFE
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
RESISTANCE THERMISTOR FLUE
REMOVE THE TWO SPADE CONNECTORS FROM THE FLUE THERMISTOR
OBSERVATION ISOLATE DHW DOES DEMAND STOP
ISOLATE THE DHW SUPPLY TO THE APPLIANCE ON THE
ISOLATING VALVE UNDERNEATH THE APPLIANCE
VOLTAGE DC FROM TURBINE (FIRING WITH NO DEMAND)
{GAINPCBACS}
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
VOLTAGE DC FROM PRESSURE SENSOR
{GAINPCBACS}
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
OBSERVATION RE WIRE (TIMER BYPASSED)
LINK OUT THE OPENTHERM TERMINALS AS SHOWN IN THE IMAGE
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
OBSERVATION RE WIRE (TIMER BYPASSED)
LINK OUT THE OPENTHERM TERMINALS AS SHOWN IN THE IMAGE
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
VOLTAGE DC DIVERTER VALVE PERMANENT AT PCB
{GAINPCBACS}
INSPECTION FILTER RETURN
BOILER DRAINED AND D
OBSERVATION FAN RUNNING
NO DEMANDS
OBSERVATION FAN (DC CONNECTOR REMOVED)
REMOVE THE 4 WAY CONNECTOR FROM THE FAN ASSEMBLY
AND MAKE SAFE
RESISTANCE HARNESS FAN AC
REMOVE THE 3 WIRE CONNECTOR FROM THE FAN
REMOVE CONNECTOR X4 FROM THE PCB
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR X3 FROM THE PCB
REMOVE THE COVER FROM THE PUMP ASSEMBLY
RESISTANCE RECTIFICATION LEAD AND ELECTRODE TO EARTH
REMOVE CONNECTOR X12 FROM THE PCB
RESISTANCE RECTIFICATION ELECTRODE TO EARTH
REMOVE THE LEAD FROM THE RECTIFICATION ELECTRODE
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
VOLTAGE PCB MAINS INPUT
{GAINPCBACS}
RESISTANCE FUSE MAINS
REMOVE FUSE FROM FUSED SPUR OR PLUG
RESISTANCE THERMISTOR AND HARNESS RETURN
REMOVE CONNECTOR X7 FROM THE PCB
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
RESISTANCE THERMISTOR FLOW / STAT AND HARNESS
REMOVE CONNECTOR X6 FROM THE PCB
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
RESISTANCE THERMISTOR AND HARNESS FLUE
REMOVE CONNECTOR X6 FROM THE PCB
RESISTANCE THERMISTOR FLUE
REMOVE THE TWO SPADE CONNECTORS FROM THE FLUE THERMISTOR
VOLTAGE POLARITY
{GAINPCBACS}
OBSERVATION BURNER EXTINGUISH ON DEMAND END
ECO MODE ON
ENSUR
INSPECTION RECTIFICATION ELECTRODE
REMOVE RECTIFICATION ELECTRODE
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
RESISTANCE GAS VALVE AND HARNESS AND TO EARTH
REMOVE CONNECTOR X4 FROM THE PCB
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR FROM THE GAS VALVE
OBSERVATION DISCONNECT OUTSIDE SENSOR
REMOVE THE TWO WIRES
RESISTANCE PUMP AND HARNESS AND TO EARTH
REMOVE CONNECTOR X3 FROM THE PCB
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR FROM THE GAS VALVE
RESISTANCE PUMP AND TO EARTH
REMOVE THE COVER FROM THE PUMP
RESISTANCE FAN AND TO EARTH (AC)
REMOVE THE 3 WIRE CONNECTOR FROM THE FAN ASSEMBLY
RESISTANCE FAN AND TO EARTH (DC)
REMOVE THE 4 WIRE CONNECTOR FROM THE FAN ASSEMBLY
RESISTANCE HARNESS TURBINE
REMOVE THE CONNECTOR FROM THE FLOW TURBINE
REMOVE CONNECTOR X5 FROM THE PCB
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
RESISTANCE IGNITION LEAD AND CAP
REMOVE IGNITION LEAD FROM ELECTRODE
REMOVE IGNITION LEAD FROM PCB
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
TEMPERATURE DIFFERENTIAL DHW
ATTACH TEMPERATURE CLAMPS AS INDICATED BY THE RED ARROWS
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE PRIMARY CIRCUIT WATER DRAINED
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
INSPECTION FILTER RETURN
BOILER DRAINED AND D
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
INSPECTION IGNITION LEAD END
REMOVE THE CAP FROM THE SPARK ELECTRODE
UNSCREW IT ANTICLOCKWISE FROM THE IGNITION LEAD
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
RESISTANCE IGNITION LEAD
REMOVE THE IGNITION LEAD FROM THE PCB
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
INSPECTION SUMP
REMOVE THE SUMP COVE
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR FROM THE GAS VALVE
INSPECTION SUMP
REMOVE THE SUMP COVE
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
VOLTAGE DC FROM PRESSURE SENSOR
{GAINPCBACS}
RESISTANCE HARNESS PRESSURE SENSOR
REMOVE CONNECTOR X5 FROM THE PCB
REMOVE THE CONNECTOR FROM THE LOW PRESSURE SENSOR
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE FAN FROM
INSPECTION ELECTRODE INTERNAL
REMOVE BURNER ASSEMBLY
INSPECTION BURNER
REMOVE BURNER
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE FAN FROM
INSPECTION BURNER
REMOVE BURNER
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE FAN FROM
INSPECTION ELECTRODE INTERNAL
REMOVE BURNER ASSEMBLY
INSPECTION BURNER
REMOVE BURNER
OBSERVATION SPARKING FROM PCB
{GAINPCBACS}
USIN
INSPECTION SUMP
REMOVE THE SUMP COVE
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE FAN FROM
INSPECTION BURNER
REMOVE BURNER
RESISTANCE THERMISTOR FLUE
REMOVE THE TWO SPADE CONNECTORS FROM THE FLUE THERMISTOR
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
OBSERVATION SYSTEM PRESSURE RISE (OVERHEAT)
OBSERVE THE MANUAL PRESSURE GAUGE ON THE UNDERSIDE OF THE APPLIANCE
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
TEMPERATURE DIFFERENTIAL CH
BOILER CH THERMOSTAT
TEMPERATURE DIFFERENTIAL DHW (OVERHEAT)
ATTACH TEMPERATURE CLAMPS AS INDICATED BY THE RED ARROWS
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE PRIMARY CIRCUIT WATER DRAINED
INSPECTION FILTER RETURN
BOILER DRAINED AND D
INSPECTION INTEGRAL BYPASS (RESTRICTED OR BLOCKED)
APPLIANCE DRAINED AND DISCHARGED
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE FAN FROM
INSPECTION BURNER
REMOVE BURNER
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE FAN FROM
INSPECTION ELECTRODE INTERNAL
REMOVE BURNER ASSEMBLY
INSPECTION BURNER
REMOVE BURNER
OBSERVATION SPARKING FROM PCB
{GAINPCBACS}
USIN
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE FAN FROM
INSPECTION ELECTRODE INTERNAL
REMOVE BURNER ASSEMBLY
INSPECTION BURNER
REMOVE BURNER
PRESSURE GAS INLET FOR DHW
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
OBSERVATION SYSTEM PRESSURE RISE (PRESSURE FAULT CODE)
OBSERVE THE MANUAL PRESSURE GAUGE ON THE UNDERSIDE OF THE APPLIANCE
OBSERVATION SYSTEM PRESSURE RISE (PRESSURE FAULT CODE)
OBSERVE THE MANUAL PRESSURE GAUGE ON THE UNDERSIDE OF THE APPLIANCE
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
OBSERVATION SYSTEM PRESSURE RISE (PRESSURE FAULT CODE)
OBSERVE THE MANUAL PRESSURE GAUGE ON THE UNDERSIDE OF THE APPLIANCE
VOLTAGE DC FROM PRESSURE SENSOR
{GAINPCBACS}
OBSERVATION SYSTEM PRESSURE RISE
BOILER CH THERMOSTAT TO MAX
RESISTANCE HARNESS PRESSURE SENSOR
REMOVE CONNECTOR X5 FROM THE PCB
REMOVE THE CONNECTOR FROM THE LOW PRESSURE SENSOR
OBSERVATION SYSTEM PRESSURE RISE
BOILER CH THERMOSTAT TO MAX
INSPECTION FLOW SWITCH, FILTER AND RESTRICTOR
ISOLATE THE WATER SUPPLY TO THE APPLIANCE
INSPECTION SUMP
REMOVE THE SUMP COVE
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
OBSERVATION PUMP RUNNING FOR OVERHEAT
ENSURE APPLIANCE IS
OBSERVATION SPARKING FROM PCB
{GAINPCBACS}
USIN
OBSERVATION SYSTEM PRESSURE RISE (OVERHEAT)
OBSERVE THE MANUAL PRESSURE GAUGE ON THE UNDERSIDE OF THE APPLIANCE
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
OBSERVATION PUMP RUNNING FOR OVERHEAT
ENSURE APPLIANCE IS
RESISTANCE IGNITION LEAD
REMOVE THE IGNITION LEAD FROM THE PCB
TEMPERATURE DIFFERENTIAL CH
BOILER CH THERMOSTAT
TEMPERATURE DIFFERENTIAL DHW (OVERHEAT)
ATTACH TEMPERATURE CLAMPS AS INDICATED BY THE RED ARROWS
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE PRIMARY CIRCUIT WATER DRAINED
INSPECTION FILTER RETURN
BOILER DRAINED AND D
INSPECTION INTEGRAL BYPASS (RESTRICTED OR BLOCKED)
APPLIANCE DRAINED AND DISCHARGED
VOLTAGE PUMP AT PUMP
REMOVE THE COVER FROM THE PUMP ASSEMBLY
VOLTAGE DC RECTIFICATION PERMANENT
{GAINPCBACS}
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
OBSERVATION FAN RUNNING
NO DEMANDS
VOLTAGE DC FROM PRESSURE SENSOR
{GAINPCBACS}
RESISTANCE HARNESS PRESSURE SENSOR
REMOVE CONNECTOR X5 FROM THE PCB
REMOVE THE CONNECTOR FROM THE LOW PRESSURE SENSOR
RESISTANCE HARNESS FAN DC
REMOVE THE 4 WAY CONNECTOR FROM THE FAN ASSEMBLY
REMOVE CONNECTOR X8 FROM THE PCB
VOLTAGE DC TO FAN AT PCB
{GAINPCBACS}
REMOVE FAN DC CONNECTOR (4 WIRE) AND MAKE SAFE
RESISTANCE HARNESS FAN DC
REMOVE THE 4 WAY CONNECTOR FROM THE FAN ASSEMBLY
REMOVE CONNECTOR X8 FROM THE PCB
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
OBSERVATION CONNECTOR X5 REMOVED (DISPLAY OPERATES?)
REMOVE CONNECTOR X5 FROM THE PCB AND MAKE SAFE
RESISTANCE THERMISTOR AND HARNESS RETURN
REMOVE CONNECTOR X7 FROM THE PCB
RESISTANCE THERMISTOR FLOW / STAT AND HARNESS
REMOVE CONNECTOR X6 FROM THE PCB
RESISTANCE THERMISTOR AND HARNESS FLUE
REMOVE CONNECTOR X6 FROM THE PCB
RESISTANCE HARNESS TIMER SECTION
REMOVE THE CONNECTOR FROM THE INTEGRAL TIMER
RESISTANCE HARNESS TIMER SECTION
REMOVE THE CONNECTOR FROM THE INTEGRAL TIMER
RESISTANCE HARNESS TIMER SECTION
REMOVE THE CONNECTOR FROM THE INTEGRAL TIMER
RESISTANCE HARNESS TIMER SECTION
REMOVE THE CONNECTOR FROM THE INTEGRAL TIMER
RESISTANCE HARNESS TIMER SECTION
REMOVE THE CONNECTOR FROM THE INTEGRAL TIMER
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE FAN FROM
INSPECTION BURNER
REMOVE BURNER
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
INSPECTION IGNITION LEAD END
REMOVE THE CAP FROM THE SPARK ELECTRODE
UNSCREW IT ANTICLOCKWISE FROM THE IGNITION LEAD
RESISTANCE HARNESS PRESSURE SENSOR
REMOVE CONNECTOR X5 FROM THE PCB
REMOVE THE CONNECTOR FROM THE LOW PRESSURE SENSOR
RESISTANCE HARNESS FAN DC
REMOVE THE 4 WAY CONNECTOR FROM THE FAN ASSEMBLY
REMOVE CONNECTOR X8 FROM THE PCB
INSPECTION SUMP
REMOVE THE SUMP COVE
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE AIR / GAS MANIFOLD
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
VOLTAGE DC TO GAS VALVE AT PCB
{GAINPCBACS}
RESISTANCE HARNESS GAS VALVE
REMOVE THE CONNECTOR
PRESSURE FAN
REMOVE THE AIR IMPUL
INSPECTION SUMP
REMOVE THE SUMP COVE
INSPECTION BURNER
REMOVE BURNER
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
OPERATION CH NOISY?
BOILER SET TO WINTER MODE (NO SUN SYMBOL IN DISPLAY)
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE PRIMARY CIRCUIT WATER DRAINED
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
TEMPERATURE SECONDARY HEAT EXCHANGER
ENSURE THE SECONDARY
TEMPERATURE DIFFERENTIAL FLOW AND RETURN
ATTACH TEMPERATURE CLAMPS AS INDICATED BY THE RED ARROWS
VOLTAGE DC DIVERTER VALVE VARIATION
ATTACH BLACK CROCODILE CLIP TO A SUITABLE EARTH POINT
INSPECTION FILTER RETURN
BOILER DRAINED AND D
INSPECTION INTEGRAL BYPASS (STUCK OPEN)
APPLIANCE DRAINED AND DISCHARGED
RESISTANCE HARNESS DIVERTER VALVE
REMOVE CONNECTOR X9 FROM THE PCB
REMOVE THE CONNECTOR FROM THE DIVERTER VALVE MOTOR
VOLTAGE DC DIVERTER VALVE PERMANENT AT PCB
{GAINPCBACS}
VOLTAGE DC DIVERTER VALVE VARIATION
ATTACH BLACK CROCODILE CLIP TO A SUITABLE EARTH POINT
RESISTANCE HARNESS DIVERTER VALVE
REMOVE CONNECTOR X9 FROM THE PCB
REMOVE THE CONNECTOR FROM THE DIVERTER VALVE MOTOR
VOLTAGE DC TO FAN AT PCB
{GAINPCBACS}
REMOVE FAN DC CONNECTOR (4 WIRE) AND MAKE SAFE
RESISTANCE HARNESS FAN DC
REMOVE THE 4 WAY CONNECTOR FROM THE FAN ASSEMBLY
REMOVE CONNECTOR X8 FROM THE PCB
RESISTANCE HARNESS FAN DC
REMOVE THE 4 WAY CONNECTOR FROM THE FAN ASSEMBLY
REMOVE CONNECTOR X8 FROM THE PCB
FAULT CODES (F BLOCKING CODES)
F CODES ARE BLOCKING
VOLTAGE PUMP AT PUMP
REMOVE THE COVER FROM THE PUMP ASSEMBLY
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
OBSERVATION REMOVE EXTERNAL CONTROLS
REMOVE THE EXTERNAL
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
VOLTAGE WIRELESS CONTROL
{GAINPCBACS}
OBSERVATION APPLIANCE RESET (BOILER RESPONDS)
ENSURE NO DEMANDS
RESISTANCE FUSE FH1
REMOVE FUSE FH1 FROM ITS HOLDER
RESISTANCE FUSE FH2
REMOVE FUSE FH2 FROM THE PCB
PCB DISPLAY FAULTY FURTHER INVESTIGATION?
TESTS SO FAR SHOW TH
PRESSURE GAS INLET DROP
ATTACH U GAUGE TO INLET PRESSURE TEST POINT
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
VOLTAGE DC FROM PRESSURE SENSOR
{GAINPCBACS}
RESISTANCE HARNESS PRESSURE SENSOR
REMOVE CONNECTOR X5 FROM THE PCB
REMOVE THE CONNECTOR FROM THE LOW PRESSURE SENSOR
INSPECTION SUMP
REMOVE THE SUMP COVE
RESISTANCE RECTIFICATION LEAD AND ELECTRODE TO EARTH
REMOVE CONNECTOR X12 FROM THE PCB
RESISTANCE IGNITION LEAD AND ELECTRODE TO EARTH
REMOVE THE IGNITION LEAD FROM THE SPARK GENERATOR
RESISTANCE GAS VALVE AND HARNESS AND TO EARTH
REMOVE CONNECTOR X4 FROM THE PCB
RESISTANCE FAN AND HARNESS AND TO EARTH (AC)
REMOVE CONNECTOR X4 FROM THE PCB
RESISTANCE FAN AND HARNESS AND TO EARTH (DC)
REMOVE CONNECTOR X8 FROM THE PCB
System Information
- Total Tests: 856
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control