Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to DC Volts Set meter to measure DC Volts
Gain access to PCB (use Insulation Mat as required)
ECO mode ON
Appliance in WINTER mode (no picture of a sun in the display press reset button to toggle picture of sun on and off)
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow fan purge to complete (2 minutes), allow the burner to ignite and boiler to run in CH mode.
Measure the dc voltage between pin 3 and pin 4 connector X4 with the burner lit (voltage should be approximately 210 vdc).
Put the appliance into summer mode (press the reset button once a sun will appear in the display) while continuing to monitor the voltage.
As soon as the demand ends the voltage should return to approximately 0 vdc.
Does the voltage behave as described above?