JOHNSON & STARLEY INTEJAN EKKA 32
WARNING - IMPORTA
JOHNSON & STARLEY INTEJAN EKKA 32
G.C. NUMBER 53 416 3
SYSTEM CHECKS
PLEASE ENSURE THE FOLLOWING SYSTEM CHECKS ARE COMPLETED
FAN DOES NOT RUN (NEITHER)
FUSE T3
FAN DOES NOT RUN (NEITHER)
3-WAY SWITCH
FAN DOES NOT RUN (NEITHER)
3-WAY SWITCH
OPEN CIRCUIT (NEITHER)
AIR PRESSURE SWITCH
FAN DOES NOT RUN (NEITHER)
AIR PRESSURE SWITCH TUBES
FAN DOES NOT RUN (NEITHER)
VENTURI
SPARKING BUT NO IGNITION (BOTH WC NOT SATISFACTORY)
CONTROL MODULE
FAN RUNS FOR 10 SECONDS (NO AH)
FDC AND LIMIT SWITCH (CH)
SPARKING BUT NO IGNITION (BOTH WC NOT SATISFACTORY)
GAS VALVE - (MULTIFUNCTIONAL CONTROL-WATER CIRCULATOR)
SPARKING BUT NO IGNITION (BOTH WC NOT SATISFACTORY)
IGNITION BURNER INJECTOR (WATER CIRCULATOR)
SPARKING BUT NO IGNITION (BOTH WC NOT SATISFACTORY)
IGNITION BURNER ASSEMBLY (WATER CIRCULATOR)
NO SPARKING (BOTH WC NOT SATISFACTORY)
CONTROL MODULE
NO SPARKING (BOTH WC NOT SATISFACTORY)
FUSE - ELECTRIC FLAME CONTROL DEVICE (WATER CIRCULATOR)
NO SPARKING (BOTH WC NOT SATISFACTORY)
IGNITION BURNER ASSEMBLY (WATER CIRCULATOR)
NO SPARKING (BOTH WC NOT SATISFACTORY)
IGNITER LEAD-(WATER CIRCULATOR)
BURNER IGNITES (BOTH WC NOT SATISFACTORY)
GAS SUPPLY
FAN RUNS FOR 10 SECONDS (NO AH)
AIR PRESSURE SWITCH
BURNER IGNITES (BOTH WC NOT SATISFACTORY)
CONTROL MODULE
BURNER IGNITES (BOTH WC NOT SATISFACTORY)
GAS VALVE - (MULTIFUNCTIONAL CONTROL-WATER CIRCULATOR)
FAN RUNS FOR 10 SECONDS (NO AH)
AIR PRESSURE SWITCH TUBES
SPARKING BUT NO IGNITION (BOTH AH NOT SATISFACTORY)
FDC AND LIMIT SWITCH (CH)
SPARKING BUT NO IGNITION (BOTH AH NOT SATISFACTORY)
CONTROL MODULE
SPARKING BUT NO IGNITION (BOTH AH NOT SATISFACTORY)
GAS VALVE - (MULTIFUNCTIONAL CONTROL-AIR HEATER)
FAN RUNS FOR 10 SECONDS (NO AH)
VENTURI
SPARKING BUT NO IGNITION (BOTH AH NOT SATISFACTORY)
IGNITION BURNER INJECTOR (AIR HEATER)
SPARKING BUT NO IGNITION (BOTH AH NOT SATISFACTORY)
IGNITION BURNER ASSEMBLY (AIR HEATER)
NO SPARKING (BOTH AH NOT SATISFACTORY)
CONTROL MODULE
NO SPARKING (BOTH AH NOT SATISFACTORY)
FUSE - ELECTRIC FLAME CONTROL DEVICE (AIR HEATER)
NO SPARKING (BOTH AH NOT SATISFACTORY)
IGNITION BURNER ASSEMBLY (AIR HEATER)
NO SPARKING (BOTH AH NOT SATISFACTORY)
IGNITER LEAD (AIR HEATER)
FAN DOES NOT RUN (NO WC)
THERMOSTAT (WATER CIRCULATOR)
FAN DOES NOT RUN (NO WC)
3-WAY SWITCH
FAN RUNS FOR 10 SECONDS (NO WC)
AIR PRESSURE SWITCH
FAN RUNS FOR 10 SECONDS (NO WC)
AIR PRESSURE SWITCH TUBES
FAN RUNS FOR 10 SECONDS (NO WC)
VENTURI
FAN DOES NOT RUN (NO AH)
3-WAY SWITCH
FAN DOES NOT RUN (NO AH)
THERMISTOR-STAT (AIR HEATER)
DOES COMBUSTION FAN RUN TIMED
CLOCK/TIMER
AH OR WC PROBLEM
GAS SUPPLY
AH OR WC PROBLEM
CONTROL MODULE
AH OR WC PROBLEM
GAS VALVE - (MULTIFUNCTIONAL CONTROL-AIR HEATER)
ELECTRICAL SAFETY CHECKS
ELECTRICAL SAFETY CHECKS
INSUFFICIENT AIR FLOW
AIR FLOW FILTER (AIR HEATER)
INSUFFICIENT AIR FLOW (BOTH AH NOT SATISFACTORY)
CONTROL MODULE
INSUFFICIENT AIR FLOW (BOTH AH NOT SATISFACTORY)
AIR CIRCULATOR FAN SCROLL (AIR HEATER)
SYSTEM CYCLING (BOTH AH NOT SATISFACTORY)
AIR FLOW FILTER (AIR HEATER)
SYSTEM CYCLING (BOTH AH NOT SATISFACTORY)
CONTROL MODULE
SYSTEM CYCLING (BOTH AH NOT SATISFACTORY)
AIR CIRCULATOR FAN (AIR HEATER)
COOL AIR (BOTH AH NOT SATISFACTORY)
GAS SUPPLY
WATER TOO COLD (BOTH WC NOT SATISFACTORY)
BURNER PRESSURE ADJUSTER
WATER TOO COLD (BOTH WC NOT SATISFACTORY)
MAIN INJECTOR NOZZLE (WATER CIRCULATOR)
WATER TOO COLD (BOTH WC NOT SATISFACTORY)
THERMOSTAT (WATER CIRCULATOR)
NOISY OPERATION (BOTH WC NOT SATISFACTORY)
BURNER PRESSURE ADJUSTER
NOISY OPERATION (BOTH WC NOT SATISFACTORY)
MAIN INJECTOR NOZZLE (WATER CIRCULATOR)
NOISY OPERATION
THERMOSTAT (WATER CIRCULATOR)
NOISY OPERATION (BOTH WC NOT SATISFACTORY)
GAS VALVE - (MULTIFUNCTIONAL CONTROL-WATER CIRCULATOR)
SYSTEM CHECKS
SYSTEM CHECKS
FAN DOES NOT RUN (NEITHER)
COMBUSTION AIR FAN
FAN DOES NOT RUN (NEITHER)
CONTROL MODULE
FAN DOES NOT RUN VOLTAGE (NEITHER)
CONTROL MODULE
SPARKING BUT NO IGNITION (BOTH WC NOT SATISFACTORY)
ELECTRIC FLAME CONTROL DEVICE (WATER CIRCULATOR)
NO SPARKING (BOTH WC NOT SATISFACTORY)
ELECTRIC FLAME CONTROL DEVICE (WATER CIRCULATOR)
BURNER IGNITES (BOTH WC NOT SATISFACTORY)
MAIN INJECTOR NOZZLE (WATER CIRCULATOR)
BURNER IGNITES (BOTH WC NOT SATISFACTORY)
ELECTRIC FLAME CONTROL DEVICE (WATER CIRCULATOR)
SPARKING BUT NO IGNITION (BOTH AH NOT SATISFACTORY)
ELECTRIC FLAME CONTROL DEVICE (AIR HEATER)
FAN RUNS FOR 10 SECONDS (NO AH)
CONTROL MODULE
NO SPARKING (BOTH AH NOT SATISFACTORY)
ELECTRIC FLAME CONTROL DEVICE (AIR HEATER)
FAN RUNS WITH WATER CIRCULATOR DEMAND BUT NOT AIR HEATING
CONTROL MODULE
FAN RUNS FOR 10 SECONDS (NO WC)
CONTROL MODULE
FAN RUNS STOPS RUNS LOCKOUT (NO WC)
OVERHEAT CUT-OFF SWITCH (WATER CIRCULATOR)
FAN DOES NOT RUN (NO WC)
CONTROL MODULE
DOES COMBUSTION FAN RUN TIMED
3-WAY SWITCH
AH OR WC PROBLEM
MAIN BURNER INJECTOR (AIR HEATER)
AH OR WC PROBLEM
ELECTRIC FLAME CONTROL DEVICE (AIR HEATER)
AIR HEATING
NO FAULT FOUND
INSUFFICIENT AIR FLOW (BOTH AH NOT SATISFACTORY)
AIR CIRCULATOR FAN (AIR HEATER)
INSUFFICIENT AIR FLOW (BOTH AH NOT SATISFACTORY)
AIR CIRCULATOR FAN MOTOR (AIR HEATER)
SYSTEM CYCLING (BOTH AH NOT SATISFACTORY)
AIR CIRCULATOR FAN MOTOR (AIR HEATER)
COOL AIR (BOTH AH NOT SATISFACTORY)
HEAT EXCHANGER (AIR HEATER)
COOL AIR (BOTH AH NOT SATISFACTORY)
MAIN BURNER INJECTOR (AIR HEATER)
COOL AIR (BOTH AH NOT SATISFACTORY)
GAS VALVE - (MULTIFUNCTIONAL CONTROL-AIR HEATER)
WATER CIRCULATOR
NO FAULT FOUND
WATER TOO COLD (BOTH WC NOT SATISFACTORY)
HEAT EXCHANGER - MAIN BODY ASSEMBLY (WATER CIRCULATOR)
NOISY OPERATION (BOTH WC NOT SATISFACTORY)
HEAT EXCHANGER - MAIN BODY ASSEMBLY (WATER CIRCULATOR)
FAN RUNS WITH WATER CIRCULATOR DEMAND BUT NOT AIR HEATING
CHARACTERISTIC TEST FROM DOES COMBUSTION FAN RUN CONTINUOUS
FAN RUNS WITH WATER CIRCULATOR, WITH AIR HEATING FAN RUNS FOR APPROXIMATELY 10 SECONDS THEN STOPS
CHARACTERISTIC TEST FROM DOES COMBUSTION FAN RUN CONTINUOUS
AIR HEATING NOT SATISFACTORY
CHARACTERISTIC TEST FROM AIR HEATER OR WATER CIRCULATOR PROBLEM
WATER CIRCULATOR NOT SATISFACTORY
CHARACTERISTIC TEST FROM AIR HEATER OR WATER CIRCULATOR PROBLEM
NO SPARKING
CHARACTERISTIC TEST FROM PILOT IGNITES (AIR HEATING)
SPARKING BUT PILOT DOES NOT IGNITE
CHARACTERISTIC TEST FROM PILOT IGNITES (AIR HEATING)
NO SPARKING
CHARACTERISTIC TEST FROM PILOT IGNITES (AIR HEATING)
SPARKING BUT PILOT DOES NOT IGNITE
CHARACTERISTIC TEST FROM PILOT IGNITES (AIR HEATING)
FAN RUNS WITH AIR HEATING DEMAND BUT NOT WATER CIRCULATOR
CHARACTERISTIC TEST FROM DOES COMBUSTION FAN RUN CONTINUOUS
FAN RUNS WITH AIR HEATING, WITH WATER CIRCULATOR DEMAND FAN RUNS FOR APPROXIMATELY 10 SECONDS THEN STOPS
CHARACTERISTIC TEST FROM DOES COMBUSTION FAN RUN CONTINUOUS
FAN RUNS WITH AIR HEATING, WITH WATER CIRCULATOR FAN RUNS FOR APPROXIMATELY 10 SECONDS, RESETS THEN RUNS FOR APPROXIMATELY 20 SECONDS BEFORE GOING TO LOCKOUT
CHARACTERISTIC TEST FROM DOES COMBUSTION FAN RUN CONTINUOUS
INSUFICIENT AIR FLOW
CHARACTERISTIC TEST FROM PROBLEM WITH AIR HEATING
SYSTEM CYCLING
CHARACTERISTIC TEST FROM PROBLEM WITH AIR HEATING
COOL AIR
CHARACTERISTIC TEST FROM PROBLEM WITH AIR HEATING
WATER TOO COLD BURNER REMAINS ALIGHT
CHARACTERISTIC TEST FROM PROBLEM WITH WATER CIRCULATOR
WATER TOO COLD BUT APPLIANCE SHUTS DOWN
CHARACTERISTIC TEST FROM PROBLEM WITH WATER CIRCULATOR
NOISY OPERATION
CHARACTERISTIC TEST FROM PROBLEM WITH WATER CIRCULATOR
FAN DOES NOT RUN WITH EITHER DEMAND
CHARACTERISTIC TEST FROM DOES COMBUSTION FAN RUN CONTINUOUS
26/07/2012 13:27:59 3_1_50_1 27/07/2012 13:07:05
26/07/2012 13:34:05
BURNER PRESSURE (WATER CIRCULATOR)
{ISOLATEMAINSPOWER}<
GAS INLET PRESSURE
{ISOLATEMAINSPOWER}<
BURNER PRESSURE (AIR HEATER)
{ISOLATEMAINSPOWER}<
CLOCK/TIMER OUTPUT
ENSURE CLOCK/TIMER IS CALLING
GAS INLET PRESSURE
{ISOLATEMAINSPOWER}<
AIR CIRCULATING FAN VOLTAGE
AIR HEATER SWITCH SET TO CONSTANT
BURNER PRESSURE (AIR HEATER)
{ISOLATEMAINSPOWER}<
GAS INLET PRESSURE
{ISOLATEMAINSPOWER}<
COMBUSTION AIR FAN VOLTAGE
AIR HEATER SWITCH SET TO CONSTANT
FUSE
{ISOLATEMAINSPOWER}<
AIR HEATER SWITCH
{ISOLATEMAINSPOWER}
REMOVE THE LEADS FROM THE AIR HEATER SWITCH
WATER HEATER SWITCH
{ISOLATEMAINSPOWER}
REMOVE THE LEADS FROM THE WATER HEATER SWITCH
AIR PRESSURE SWITCH TUBES
{ISOLATEMAINSPOWER}
VENTURI
{ISOLATEMAINSPOWER}
AIR HEATER SWITCH
{ISOLATEMAINSPOWER}
REMOVE THE LEADS FROM THE AIR HEATER SWITCH
FDC RESISTANCE
{ISOLATEMAINSPOWER}
PILOT IGNITES (AIR HEATING)
AIR HEATER SWITCH SET TO CONSTANT
PILOT IGNITES (WATER CIRCULATOR)
WATER HEATER SWITCH SET TO CONSTANT
SET THERMOSTAT TO MID POSITION
AIR PRESSURE SWITCH VOLTAGE
AIR HEATER SWITCH SET TO CONSTANT
BURNER IGNITES (WATER CIRCULATOR)
WATER HEATER SWITCH SET TO CONSTANT
SET THERMOSTAT TO MID POSITION
CONTROL MODULE OUTPUT
WATER HEATER SWITCH SET TO CONSTANT
SET THERMOSTAT TO MID POSITION
GAS INLET PRESSURE
{ISOLATEMAINSPOWER}<
PILOT GAS VALVE VOLTAGE
WATER HEATER SWITCH SET TO CONSTANT
REMOVE THE UPPER ELECTRONIC FLAME CONTROL DEVICE
GAS VALVE PILOT SOLENOID RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE THE UPPER ELECTRONIC FLAME CONTROL DEVICE
IGNITION BURNER INJECTOR-WATER CIRCULATOR
{ISOLATEMAINSPOWER}
IGNITION BURNER ASSEMBLY- WATER CIRCULATOR
{ISOLATEMAINSPOWER}
FUSE (ELECTRIC FLAME CONTROL DEVICE)
{ISOLATEMAINSPOWER}<
IGNITION BURNER ASSEMBLY- WATER CIRCULATOR
{ISOLATEMAINSPOWER}
IGNITER LEAD
{ISOLATEMAINSPOWER}
DISCONNECT THE IGNITION LEAD
AIR PRESSURE SWITCH TUBES
{ISOLATEMAINSPOWER}
GAS VALVE VOLTAGE
WATER HEATER SWITCH SET TO CONSTANT
SET THERMOSTAT TO MID POSITION
MAIN GAS VALVE RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE THE UPPER ELECTRONIC FLAME CONTROL DEVICE
VENTURI
{ISOLATEMAINSPOWER}
BURNER IGNITES (AIR HEATING)
AIR HEATER SWITCH SET TO CONSTANT
CONTROL MODULE OUTPUT
AIR HEATER SWITCH SET TO CONSTANT
GAS INLET PRESSURE
{ISOLATEMAINSPOWER}<
LIMIT SWITCH RESISTANCE
{ISOLATEMAINSPOWER}
LIMIT SWITCH AND FDC ASSEMBLY IS LOCATED TOP LEFT BEHIND THE SEALING PANEL
PILOT GAS VALVE VOLTAGE
AIR HEATER SWITCH SET TO CONSTANT
GAS VALVE PILOT SOLENOID RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE THE LOWER ELECTRONIC FLAME CONTROL DEVICE
IGNITION BURNER INJECTOR-AIR HEATER
{ISOLATEMAINSPOWER}
IGNITION BURNER ASSEMBLY-AIR HEATER
{ISOLATEMAINSPOWER}
FUSE (ELECTRIC FLAME CONTROL DEVICE)
{ISOLATEMAINSPOWER}<
IGNITION BURNER ASSEMBLY-AIR HEATER
{ISOLATEMAINSPOWER}
IGNITER LEAD
{ISOLATEMAINSPOWER}
DISCONNECT THE IGNITION LEAD
WATER HEATER SWITCH
{ISOLATEMAINSPOWER}
REMOVE THE LEADS FROM THE WATER HEATER SWITCH
THERMOSTAT RESISTANCE
{ISOLATEMAINSPOWER}
AIR PRESSURE SWITCH VOLTAGE
WATER HEATER SWITCH SET TO CONSTANT
SET THERMOSTAT TO MID POSITION
AIR PRESSURE SWITCH TUBES
{ISOLATEMAINSPOWER}
VENTURI
{ISOLATEMAINSPOWER}
THERMISTOR-STAT RESISTANCE
{ISOLATEMAINSPOWER}
SET THE THERMISTOR-STAT TO MAXIMUM
GAS VALVE VOLTAGE
AIR HEATER SWITCH SET TO CONSTANT
MAIN GAS VALVE RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE THE LOWER ELECTRONIC FLAME CONTROL DEVICE
AIR FLOW FILTER
{ISOLATEMAINSPOWER}
AIR CIRCULATING FAN (FULL SPEED)
AIR HEATER SWITCH SET TO CONSTANT
THERMISTOR-STAT SET TO MAXIMUM
FAN SCROLL
{ISOLATEMAINSPOWER}
RESISTOR
{ISOLATEMAINSPOWER}<
FAN POWER CAPACITOR
{ISOLATEMAINSPOWER}<
AIR FLOW FILTER
{ISOLATEMAINSPOWER}
AIR CIRCULATING FAN (FULL SPEED)
AIR HEATER SWITCH SET TO CONSTANT
THERMISTOR-STAT SET TO MAXIMUM
FAN SCROLL
{ISOLATEMAINSPOWER}
BURNER PRESSURE (WATER CIRCULATOR)
{ISOLATEMAINSPOWER}<
THERMOSTAT (EARLY OPERATION)
WATER HEATER SWITCH SET TO CONSTANT
SET THERMOSTAT TO MAX POSITION
IS WATER CIRCULATING?
WATER HEATER SWITCH SET TO CONSTANT
SET THERMOSTAT TO MID POSITION
BURNER PRESSURE (WATER CIRCULATOR)
{ISOLATEMAINSPOWER}<
THERMOSTAT (LATE OPERATION)
WATER HEATER SWITCH SET TO CONSTANT
SET THERMOSTAT TO MID POSITION
System Information
- Total Tests: 197
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control