4726744 FERROLI OPTIMAX HE PLUS 31C
GLOBALLY REPLACED
4726744 FERROLI OPTIMAX HE PLUS 31C
STEP 1:
RE
OBSERVATION FAN PURGE AND PUMP PULSE
ENSURE NO DEMANDS
ENSURE APPLIANCE IS COOL
ECO MODE ON (ECO ON DISPLAY)
OBSERVATION DHW DEMAND RECOGNISED
ECO MODE ON (ECO ON DISPLAY)
OBSERVATION BURNER IGNITION AND ESTABLISH
ECO MODE ON (ECO IN DISPLAY)
OPERATION DHW
DHW SET TO MAXIMUM TEMPERATURE (65°C)
OPERATION CH
CH THERMOSTAT SET TO MAX
OBSERVATION CH DEMAND RECOGNISED
BOILER CH THERMOSTAT
OBSERVATION SYSTEM PRESSURE RISE
BOILER CH THERMOSTAT TO MAX
OBSERVATION DHW MODULATION
RUN THE HOT WATER TAP WITH A FLOW RATE OF APPROXIMATELY 7 L/MIN
FAN INVESTIGATION F15,A05
INTENTIONALLY BLANK HEADER FOR F15 AND A05
OPERATION PRE HEAT
ENSURE BOILER IS COO
NO DISPLAY (CONTINUE DIAGNOSIS)
INTENTIONALLY BLANK HEADER FOR INVESTIGATION WITH NO DISPLAY
TYPE OF DIAGNOSTIC PROCEDURE
PLEASE SELECT FROM O
RETURN THERMISTOR INVESTIGATION F11
INTENTIONALLY BLANK HEADER FOR F11
PARAMETERS F50
OUTSIDE MODEL
PRESSURE SENSOR INVESTIGATION PRESSURE TOO HIGH
INTENTIONALLY BLANK HEADER FOR PRESSURE TOO HIGH
REPEAT OVERPRESSURE INVESTIGATION A26
INTENTIONALLY BLANK HEADER FOR A26 FAULT CODE
POWER SUPPLY VOLTAGE F34
INTENTIONALLY BLANK HEADER FOR F34
POWER SUPPLY FREQUENCY F35
INTENTIONALLY BLANK HEADER FOR F35
FLAME DETECTED AFTER BURNER SHUTDOWN A02
INTENTIONALLY BLANK HEADER FOR A02 FAULT CODE
CONDENSE LEVEL TOO HIGH F36, A25
INTENTIONALLY BLANK HEADER FOR F36 AND A25
GAS VALVE A62
INTENTIONALLY BLANK HEADER FOR A62 FAULT CODE
OUTSIDE TEMPERATURE ERROR F39
INTENTIONALLY BLANK HEADER FOR F39 FAULT CODE
BURNER SHUTDOWN A06
INTENTIONALLY BLANK HEADER FOR A06
FUSE INVESTIGATION
INTENTIONALLY BLANK HEADER FOR FUSE INVESTIGATION
OVERHEAT INVESTIGATION
INTENTIONALLY BLANK HEADER FOR OVERHEAT INVESTIGATION
SERVICE MODE MAX AND MIN GUIDE
TO ENTER SERVICE
PARAMETERS GUIDE
1. TO ACCESS
FAULT CODE HISTORY
1. PRESS AND
FAULT CODES FOR FAULT CODE HISTORY
PLEASE CHOOSE THE AP
HEADER FOR IGNITION FAULT FROM FAULT CODES HISTORY
INTENTIONALLY BLANK HEADER FOR FAULT CODES FROM FAULT CODE HISTORY
PRESSURE SENSOR INVESTIGATION PRESSURE TOO LOW
INTENTIONALLY BLANK HEADER FOR PRESSURE TOO LOW
F42 INVESTIGATION
INTENTIONALLY BLANK HEADER FOR F42
PRESSURE SENSOR DISCONNECTED F47
INTENTIONALLY BLANK HEADER FOR FAULT CODE F47
DHW THERMISTOR INVESTIGATION F12
OUTSIDE MODEL
BLOCKED NOT SHOWING PRESSURE FLUE OVERHEAT
PRESSURE GAUGE
NOT FITTED CORRECTLY FLUE OVERHEAT
SENSOR FITMENT
TURBINE
HARNESS - WIRING - FULL
PARTIAL RESTRICTION
INJECTOR - NG (31C)
EXPLOSIVE IGNITION
ELECTRODE IGNITION
EXPLOSIVE IGNITION
INJECTOR - NG (31C)
EXPLOSIVE IGNITION
GAS INLET PRESSURE
READING HOT WHEN COLD
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
READING HOT WHEN COLD
SENSOR 10K NTC - EXCHANGER C/W BRACKET
RUNNING SLOW OR WEAK
PUMP ASSEMBLY - WIL0
RESTRICTED WRONG TEMPERATURE DIFFERENTIAL
PRIMARY FILTER
BLANK FOR SERVICE MODE GUIDE
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR PARAMETERS GUIDE
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR FAULT CODE HISTORY
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR FAULT CODES FAULT CODE HISTORY
Z DIRECTION CHOICE OR CONTINUE
LOW WHEN OTHER APPLIANCES ON
GAS INLET PRESSURE
FLAT
VESSEL - EXPANSION 8LTR
PREVENTING DEMAND
SENSOR 10K NTC - EXCHANGER C/W BRACKET
PREVENTING DEMAND
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
PARTIALLY RESTRICTED CAUSING POOR FLUE GAS READINGS 2
INJECTOR - NG (31C)
HIGH RESISTANCE INTERMITTENT
GAS VALVE
POOR IGNTION
PARAMETERS IGNITION FAN SPEED
FAULT CODE
SYSTEM PRESSURE LOW
RESTRICTED OR BLOCKED
KIT - VENTURI
NOT LIGHTING
IGNITION ELECTRODE INTERNAL
CAUSING NO IGNITION
BURNER - CERAMIC (31C)
RESTRICTED OR BLOCKED 2
KIT - VENTURI
DAMAGED CAUSING BAFFLING
BURNER - CERAMIC (31C)
RESTRICTING HEAT EX CAUSING BAFFLING
INSULATION PADS
RESTRICTED OR BLOCKED BAFFLING
HEAT EXCHANGER
EXPLOSIVE IGNITION
KIT - VENTURI
EXPLOSIVE IGNITION
IGNITION ELECTRODE INTERNAL
EXPLOSIVE IGNITION
BURNER - CERAMIC (31C)
A06 FAULT CODE
GAS INLET PRESSURE
A06 FAULT CODE
TRAP CONDENSATE OR PIPE
A06 FAULT CODE
COLLECTOR - CONDENSATE
A06 FAULT CODE
INJECTOR - NG (31C)
A06 FAULT CODE LOCKING OUT
KIT - VENTURI
A06 FAULT CODE
FLUE
A06 FAULT CODE
BURNER - CERAMIC (31C)
A06 FAULT CODE
INSULATION PADS
A06 FAULT CODE
HEAT EXCHANGER
FLUE OVERHEAT
SENSOR - HEAT EXCHANGER / FLUE
OVERHEAT FLUE OVERHEAT
SENSOR 10K NTC - EXCHANGER C/W BRACKET
OVERHEAT FLUE OVERHEAT
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
CAUSING OVERHEAT FLUE OVERHEAT
PUMP ASSEMBLY - WIL0
LEAKING ONTO FLUE STAT
HEAT EXCHANGER GASKETS
FLUE OVERHEAT
FLUE
DAMAGED FLUEWAYS CAUSING FLUE OVERHEAT
HEAT EXCHANGER
DHW COOL RADS COOL
PRIMARY HEAT EXCHANGER AND RETURN FILTER
BLOCKED NOT SHOWING PRESSURE
PRESSURE GAUGE
NOT FITTED CORRECTLY
SENSOR FITMENT
OVERHEAT
SENSOR 10K NTC - EXCHANGER C/W BRACKET
OVERHEAT
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
CAUSING OVERHEAT
PUMP ASSEMBLY - WIL0
RESTRICTED WRONG TEMPERATURE DIFFERENTIAL OVERHEAT
PRIMARY FILTER
RESTRICTED OR BLOCKED OVERHEAT
RETURN FILTER CH
BLOCKED
VALVE - BY-PASS C/W NRV
RESTRICTED OR BLOCKED OVERHEAT
PLATE HEAT EXCHANGER
FULLY OR PARTIALLY CLOSED - OVERHEAT
ISOLATION VALVES FLOW AND RETURN
RESTRICTED OR BLOCKED CAUING POOR FLUE GAS READINGS 2
KIT - VENTURI
DAMAGED CAUSING FLUE GAS FAIL 2
BURNER - CERAMIC (31C)
RESTRICTING HEAT EX CAUSING POOR FLUE GAS READINGS 2
INSULATION PADS
RESTRICTED OR BLOCKED IGNITION PROBLEMS
HEAT EXCHANGER
LOW
GAS INLET PRESSURE
BLOCKED NOT SHOWING FOR FAULT CODE
PRESSURE GAUGE
NOT FITTED CORRECTLY DHW TOO HOT
SENSOR FITMENT
NOT MODULATING DHW
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
NOT MODULATING DHW
SENSOR 10K NTC - EXCHANGER C/W BRACKET
NOT FITTED CORRECTLY DHW NOT MODULATING
SENSOR FITMENT
NOT FITTED CORRECTLY CH NOT MODULATING
SENSOR FITMENT
EXPLOSIVE IGNITION
INSULATION PADS
DHW ISOLATION VALVE
LOOP - FILLING - COCK/VALVE
INSUFFICIENT
WATER SUPPLY
CAUSING INTERMITTIENT LOCKOUT
PARAMETERS IGNITION FAN SPEED - FAULT HISTORY
NOISY ON DHW
SYSTEM PRESSURE LOW
ONLY PARTIALLY OPENING GAS VALVE
AIR IMPULSE TUBE
ONLY PARTIALLY OPENING GAS VALVE
TRAP CONDENSATE OR PIPE
ONLY PARTIALLY OPENING GAS VALVE
COLLECTOR - CONDENSATE
BLOCKED STOPPING IGNITION
INJECTOR - NG (31C)
GAS VALVE DAMAGED PCB
PCB AND GAS VALVE
FAULT CODE F42
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
FULLY OR PARTIALLY CLOSED - OVERHEAT F42
ISOLATION VALVES FLOW AND RETURN
BLOCKED NOT SHOWING PRESSURE F42
PRESSURE GAUGE
NOT FITTED CORRECTLY F42
SENSOR FITMENT
OVERHEAT F42
SENSOR 10K NTC - EXCHANGER C/W BRACKET
CAUSING OVERHEAT F42
PUMP ASSEMBLY - WIL0
RESTRICTED WRONG TEMPERATURE DIFFERENTIAL OVERHEAT F42
PRIMARY FILTER
RESTRICTED OR BLOCKED OVERHEAT F42
RETURN FILTER CH
BLOCKED F42
VALVE - BY-PASS C/W NRV
RESTRICTED OR BLOCKED OVERHEAT F42
PLATE HEAT EXCHANGER
CAUSING PUMP PULSE
SYSTEM PRESSURE LOW
FAN AC SECTION NO DISPLAY
HARNESS - WIRING - FULL
FAN DC SECTION NO DISPLAY
HARNESS - WIRING - FULL
FAN DC SECTION 2 NO DISPLAY
HARNESS - WIRING - FULL
FAULTY HALL SENSOR NO DISPLAY
FAN ASSEMBLY
CAUSING PUMP TO RUN CONTINUALLY NO DISPLAY
SENSOR 10K NTC - EXCHANGER C/W BRACKET
CAUSING PUMP TO RUN CONTINUALLY NO DISPLAY
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
SHORTING
HARNESS - WIRING - FULL
BLANK DISPLAY AND NO RESPONSE
SENSOR 10K NTC - EXCHANGER C/W BRACKET
LOW CAUSING NO RECTIFICATION
GAS INLET PRESSURE
BLANK DISPLAY AND NO RESPONSE
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
TIMER SECTION
HARNESS - WIRING - FULL
TIMER SECTION 2
HARNESS - WIRING - FULL
TIMER SECTION 3
HARNESS - WIRING - FULL
TIMER SECTION 4
HARNESS - WIRING - FULL
NOT RECTIFYING
LEADS - ELECTRODE (RECTIFICATION)
TIMER SECTION 5
HARNESS - WIRING - FULL
PARTIALLY RESTRICTED CAUSING POOR FLUE GAS READINGS 3
INJECTOR - NG (31C)
RESTRICTED OR BLOCKED CAUING POOR FLUE GAS READINGS 3
KIT - VENTURI
DAMAGED CAUSING FLUE GAS FAIL 3
BURNER - CERAMIC (31C)
RESTRICTING HEAT EX CAUSING POOR FLUE GAS READINGS3
INSULATION PADS
RESTRICTED OR BLOCKED CAUSING POOR FLUE GAS READINGS 2
HEAT EXCHANGER
PARTIALLY RESTRICTED CAUSING POOR FLUE GAS READINGS
INJECTOR - NG (31C)
CLOGGED SCROLL POOR DHW
FAN ASSEMBLY
FLUE OVERHEAT
INSULATION PADS
OVERHEATING AFTER DEMAND
PCB PUMP OVER RUN
HOT SPOTS CAUSING OVERHEAT
HEAT EXCHANGER
BLANK FOR INSTALLER MODE
Z DIRECTION CHOICE OR CONTINUE
INCORRECT OVERRUNS MAIN MODEL
PCB PUMP OVER RUN
FAN DC SECTION 3
HARNESS - WIRING - FULL
FAULTY HALL SENSOR 2
FAN ASSEMBLY
FAULTY SPEED CONTROL
FAN ASSEMBLY
FAULTY SPEED CONTROL 2
FAN ASSEMBLY
PRESSURE SWITCH FAULT CODE LOW PRESSURE
HARNESS - WIRING - FULL
NOT READING PRESSURE CORRECTLY FAULT CODELOW PRESSURE
PRESSURE SWITCH - LOW PRESSURE
F47
PARAMETERS LOW WATER PROTECTION
PRESSURE SWITCH PUMP PULSE NO DISPLAY
HARNESS - WIRING - FULL
NOT READING PRESSURE CORRECTLY
PRESSURE SWITCH - LOW PRESSURE
NO SPARKING
SENSOR - DHW
FAULT CODE F12
SENSOR - DHW
DHW TOO HOT
SENSOR - DHW
NOT MODULATING DHW
SENSOR - DHW
DHW COOL RADS COOL
SENSOR - DHW
RESISTANCE HIGH OR POOR CONDITION 2
LEADS - ELECTRODE (IGNITION)
NOT SPARKING 2
ELECTRODE IGNITION
SHORTING TO EARTH 2
LEADS - ELECTRODE (IGNITION)
IGNITION PROBLEMS
LEADS - ELECTRODE (IGNITION)
IGNITION PROBLEMS
ELECTRODE IGNITION
IGNITION PROBLEMS 3
TRAP CONDENSATE OR PIPE
IGNITION PROBLEMS 3
COLLECTOR - CONDENSATE
IGNITION PROBLEMS 3
INJECTOR - NG (31C)
IGNITION PROBLEMS 3
KIT - VENTURI
IGNITION PROBLEMS 3
FLUE
IGNITION PROBLEMS 3
IGNITION ELECTRODE INTERNAL
IGNITION PROBLEMS 3
BURNER - CERAMIC (31C)
IGNITION PROBLEMS 3
INSULATION PADS
RESTRICTED OR BLOCKED IGNITION PROBLEMS 3
HEAT EXCHANGER
BLOCKED CAUSING HIGH FAN PRESSURE
TRAP CONDENSATE OR PIPE
RESTRICTED HIGH FAN PRESSURE
COLLECTOR - CONDENSATE
RESTRICTED CAUSING HIGH FAN PRESSURE
BURNER - CERAMIC (31C)
PUMP
HARNESS - WIRING - FULL
PUMP NO DISPLAY
HARNESS - WIRING - FULL
PUMP OVERHEAT
HARNESS - WIRING - FULL
PUMP F42
HARNESS - WIRING - FULL
FLUE THERMISTOR FAULT CODE
HARNESS - WIRING - FULL
LOW CAUSING BAFFLING
GAS INLET PRESSURE
FLUE THERMISTOR
HARNESS - WIRING - FULL
BLOCKED CAUSING BAFFLING
TRAP CONDENSATE OR PIPE
RESTRICTED OR BLOCKED
COLLECTOR - CONDENSATE
PARTIALLY RESTRICTED CAUSING WRONG MIX
INJECTOR - NG (31C)
GAS VALVE SECTION
HARNESS - WIRING - FULL
SPLIT NOT OPENING GAS VALVE
AIR IMPULSE TUBE
NOT LIGHTING
ELECTRODE IGNITION
NOT RESPONDING TO INCREASE IN TEMPERATURE
SENSOR 10K NTC - EXCHANGER C/W BRACKET
SLOW OR WEAK 2
PUMP ASSEMBLY - WIL0
BLOCKED OR RESTRICTED
PRIMARY FILTER
RESTRICTED OR BLOCKED 2
RETURN FILTER CH
RESTRICTED OR BLOCKED 3
RETURN FILTER CH
DIVERTER VALVE
HARNESS - WIRING - FULL
SLOW OR WEAK 3
PUMP ASSEMBLY - WIL0
FULLY OR PARTIALLY CLOSED
ISOLATION VALVES FLOW AND RETURN
DIVERTER VALVE 2
HARNESS - WIRING - FULL
PASSING
VALVE - BY-PASS C/W NRV
NOT RESPONDING TO INCREASE IN TEMP
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
BLANK FOR F FAULT CODES
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR CASE OFF
Z DIRECTION CHOICE OR CONTINUE
FAN AC SECTION
HARNESS - WIRING - FULL
FAN DC SECTION
HARNESS - WIRING - FULL
FAN DC SECTION 2
HARNESS - WIRING - FULL
FAULTY HALL SENSOR
FAN ASSEMBLY
BLANK FOR FAULT CODES 2
Z DIRECTION CHOICE OR CONTINUE
NO POWER TO PUMP
PCB
CAUSING PUMP TO RUN CONTINUALLY
SENSOR 10K NTC - EXCHANGER C/W BRACKET
CAUSING PUMP TO RUN CONTINUALLY
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
CORRECTLY ACTIVATED APPLIANCE COLD
FROST PROTECTION
READING COLD WHEN NOT
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
SHORTING TO EARTH
ELECTRODE - FLAME SENSING
BLOWN THROUGH FATIGUE
FUSE MAINS
BLANK FOR FUSE FH1
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR FUSE FH2
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR NO DISPLAY INVESTIGATION
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR TYPE OF DIAGNOSTIC PROCEDURE
Z DIRECTION CHOICE OR CONTINUE
FAULT CODE
SENSOR 10K NTC - EXCHANGER C/W BRACKET
FAULT CODE
SENSOR 100 DEGREE C THERMOSTAT / FLOW COMBINED
SET INCORRECTLY NO DHW THERMISTOR
PARAMETERS
BLOCKED F36 A26
TRAP CONDENSATE OR PIPE
BLOCKED F36 A36
COLLECTOR - CONDENSATE
SHORTING TO EARTH F36 A25
ELECTRODE - FLAME SENSING
SHORTING TO EARTH F36 A25
ELECTRODE IGNITION
RESISTANCE INCORRECT
GAS VALVE
F39 FAULT CODE
OUTDOOR SENSOR
BLANK FOR WIRING OR WATER INGRESS
Z DIRECTION CHOICE OR CONTINUE
RESISTANCE INCORRECT FUSE INVESTIGATION
GAS VALVE
SHORTING
PUMP ASSEMBLY - WIL0
DC SECTION SHORTING
FAN ASSEMBLY
AC SECTION SHORTING
FAN ASSEMBLY
NOT RECOGNISING DEMAND
FLOW METER
RESTRICTED OR BLOCKED
PLATE HEAT EXCHANGER
RESTRICTED OR BLOCKED
HEAT EXCHANGER
EXPANSION VESSEL PIPE
EXPANSION VESSEL PIPE
DISPLAY JUMBLED
PCB
PASSING CAUSING A02
GAS VALVE
WRONG MIX NOT IGNITING
GAS VALVE
WRONG MIX BAFFLING
GAS VALVE
WRONG MIX EXPLOSIVE IGNITION
GAS VALVE
A06 FAULT CODE
GAS VALVE
SCALED CAUSING NOISE
HEAT EXCHANGER
RESTRICTED OR BLOCKED OVERHEAT
HEAT EXCHANGER
CAUSING POOR EMISSIONS OR BURNER DROP OUT 2
GAS VALVE ADJUSTMENT
OVERHEAT 2
OVERHEAT - PCB
SCALED POOR DHW FLOW
PLATE HEAT EXCHANGER
POOR DHW FLOW
DHW INLET FILTER
POOR DHW FLOW
RESTRICTOR 12LPM - FLOW
RESTRICTED BLOCKED OR JAMMED
FLOW METER
NOT OPENING
GAS VALVE
HARNESS GONE DAMAGED PCB
PCB AND HARNESS
FLOW THERMISTOR FAULT CODE F42
HARNESS - WIRING - FULL
RESTRICTED OR BLOCKED OVERHEAT F42
HEAT EXCHANGER
OVERHEAT F42
OVERHEAT - PCB
AFTER FURTHER INVESTIGATION
PCB NO DISPLAY
NOT RUNNING WITH AC VOLTAGE NO DISPLAY
FAN ASSEMBLY
NOT RECTIFYING
PCB
NOT RUNNING WITH DEMAND VOLTAGE NO DISPLAY
FAN ASSEMBLY
SHORTING
FLOW METER
RETURN THERMISTOR
HARNESS - WIRING - FULL
FLOW THERMISTOR
HARNESS - WIRING - FULL
NO DISPLAY
PCB
NOT SWITCHING
PROGRAMMER (INTEGRAL TIMER)
NOT RECTIFYING
ELECTRODE - FLAME SENSING
NOT SWITCHING POOR DHW
PROGRAMMER (INTEGRAL TIMER)
NOT SWITCHING (NOISY)
PROGRAMMER (INTEGRAL TIMER)
NOT SWITCHING POOR DHW OVERHEAT
PROGRAMMER (INTEGRAL TIMER)
NOT SWITCHING POOR DHW OVERHEAT F42
PROGRAMMER (INTEGRAL TIMER)
OPEN OR PASSING ALLOWING FLOW
HOT WATER OUTLETS
REGISTERING DEMAND WHEN NONE PRESENT
FLOW METER
CAUSING POOR EMISSIONS OR BURNER DROP OUT 3
GAS VALVE ADJUSTMENT
POOR DHW
PCB
F37 FAULT CODE
PCB
OVERHEATING
PCB
NO SPARK
PCB
F12 FAULT
PCB
DHW THERMISTOR FAULT CODE
HARNESS - WIRING - FULL
NOT SPARKING 2
IGNITION ELECTRODE INTERNAL
CAUSING SHORT TO EARTH 2
IGNITION ELECTRODE INTERNAL
RESTRICTED HIGH PRESSURE
HEAT EXCHANGER
NOT RUNNING
PUMP ASSEMBLY - WIL0
NOT RUNNING NO DISPLAY
PUMP ASSEMBLY - WIL0
NOT RUNNING OVERHEAT
PUMP ASSEMBLY - WIL0
NOT RUNNING F42
PUMP ASSEMBLY - WIL0
FAULT CODE
SENSOR - HEAT EXCHANGER / FLUE
DISPLAY BLANK AND NO RESPONSE
SENSOR - HEAT EXCHANGER / FLUE
DROPPING AWAY COMPLETELY
GAS INLET PRESSURE
BLOCKED CAUSING NOISE
PLATE HEAT EXCHANGER
WINDINGS GONE
MOTOR - DIVERTER VALVE
WINDINGS OK NO MOVEMENT CH
MOTOR - DIVERTER VALVE
WINDINGS GONE 2
MOTOR - DIVERTER VALVE
WINDINGS OK NO MOVEMENT DHW
MOTOR - DIVERTER VALVE
NOT RUNNING WITH AC VOLTAGE
FAN ASSEMBLY
NOT RUNNING WITH DEMAND VOLTAGE
FAN ASSEMBLY
BLANK FOR FAULT CODES
Z DIRECTION CHOICE OR CONTINUE
SHORTING TO EARTH
LEADS - ELECTRODE (RECTIFICATION)
NOT OPERATING
WIRELESS CONTROL
BLANK FOR MAINS FUSE INVESTIGATION
Z DIRECTION CHOICE OR CONTINUE
BLOWN THROUGH FATIGUE
FUSE FH1
BLOWN THROUGH FATIGUE
FUSE FH2
RETURN THERMISTOR FAULT CODE
HARNESS - WIRING - FULL
FLOW THERMISTOR FAULT CODE
HARNESS - WIRING - FULL
SHORTING TO EARTH F36 A25
LEADS - ELECTRODE (RECTIFICATION)
GAS VALVE SECTION A62
HARNESS - WIRING - FULL
GAS VALVE SECTION A62 FUSE INVESTIGATION
HARNESS - WIRING - FULL
PUMP SECTION SHORTING
HARNESS - WIRING - FULL
PCB TAKING OUT FUSES
PCB - FUSE
FAN DC SECTION SHORTING
HARNESS - WIRING - FULL
FAN AC SECTION SHORTING
HARNESS - WIRING - FULL
TEMPERATURE DIFFERENTIAL EXCESSIVE
CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL CH
BOILER DOES NOT RESPOND TO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION CH NOISY?
DISPLAY DOES NOT OPERATE
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY OPERATION
DISPLAY OPERATES BUT IS JUMBLED OR DISTORTED
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY OPERATION
TEMPERATURE DIFFERENTIAL EXCESSIVE
CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL CH
BOILER DOES NOT RESPOND TO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION CH NOISY?
FILTER RESTRICTED OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION FLOW SWITCH, FILTER AND RESTRICTOR
FLOW LIMITER RESTRICTED OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION FLOW SWITCH, FILTER AND RESTRICTOR
FLOW TURBINE ASSEMBLY RESTRICTED BLOCKED OR JAMMED
CHARACTERISTIC TEST FROM INSPECTION FLOW SWITCH, FILTER AND RESTRICTOR
NO SPARKING OBSERVED
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
TEMPERATURE DIFFERENTIAL EXCESSIVE
CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL CH
BOILER DOES NOT RESPOND TO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION CH NOISY?
PUMP DOES NOT RUN BUT FAN BEHAVES AS DESCRIBED ABOVE
CHARACTERISTIC TEST FROM OBSERVATION SELF CHECK (NO DISPLAY)
PUMP RUNS CONTINUOUSLY BUT FAN BEHAVES AS DESCRIBED ABOVE
CHARACTERISTIC TEST FROM OBSERVATION SELF CHECK (NO DISPLAY)
PUMP ONLY PULSES TWICE OR FAN DOES NOT BEHAVE AS DESCRIBED ABOVE
CHARACTERISTIC TEST FROM OBSERVATION SELF CHECK (NO DISPLAY)
PUMP ONLY PULSES TWICE BUT FAN BEHAVES AS DESCRIBED ABOVE
CHARACTERISTIC TEST FROM OBSERVATION SELF CHECK (NO DISPLAY)
FAN DOES NOT STOP WHEN PURGE PERIOD ENDS
CHARACTERISTIC TEST FROM OBSERVATION FAN PURGE AND PUMP PULSE
INLET PRESSURE SATISFACTORY BUT DOES NOT DIP DURING SPARKING
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
INLET PRESSURE DROPS AWAY
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
BOILER STILL NOISY
CHARACTERISTIC TEST FROM OPERATION CH NOISY?
BOILER DOES NOT RESPOND TO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION CH NOISY?
VOLTAGE MISSING FROM PIN 1 OR 4
CHARACTERISTIC TEST FROM VOLTAGE DC DIVERTER VALVE PERMANENT AT PCB
VOLTAGE PRESENT ON PIN 1 AND 4 BUT ABSENT FROM ONE OR MORE OTHER PINS
CHARACTERISTIC TEST FROM VOLTAGE DC DIVERTER VALVE PERMANENT AT PCB
VOLTAGE MISSING FROM PIN 1 OR 4
CHARACTERISTIC TEST FROM VOLTAGE DC DIVERTER VALVE PERMANENT AT PCB
VOLTAGE PRESENT ON PIN 1 AND 4 BUT ABSENT FROM ONE OR MORE OTHER PINS
CHARACTERISTIC TEST FROM VOLTAGE DC DIVERTER VALVE PERMANENT AT PCB
FAULT CODE SHOWN
CHARACTERISTIC TEST FROM OBSERVATION FAN PURGE AND PUMP PULSE
FAN BEHAVES AS DESCRIBED BUT PUMP DOES NOT RUN
CHARACTERISTIC TEST FROM OBSERVATION FAN PURGE AND PUMP PULSE
FAN BEHAVES AS DESCRIBED BUT PUMP RUNS CONTINUOUSLY
CHARACTERISTIC TEST FROM OBSERVATION FAN PURGE AND PUMP PULSE
BOILER TRIES TO RUN AND / OR FIRE STRAIGHT AFTER PUMP AND FAN PURGE
CHARACTERISTIC TEST FROM OBSERVATION FAN PURGE AND PUMP PULSE
BURNER IGNITES BUT LIGHTS WITH EXPLOSIVE IGNITION
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
SPARKING OCCURS BUT BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
BURNER IGNITES BUT THEN BAFFLES OR DROPS OUT
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
BURNER IGNITES SMOOTHLY BUT FAILS TO ESTABLISH (SPARKING CONTINUES)
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
DHW TOO HOT
CHARACTERISTIC TEST FROM OPERATION DHW
DHW TOO COOL RADS REMAIN COOL WITH NO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION DHW
DHW TOO COOL RADS BEGIN TO HEAT WITH NO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION DHW
BOILER NOISY
CHARACTERISTIC TEST FROM OPERATION DHW
BOILER UP TO TEMPERATURE BUT RADS COLD
CHARACTERISTIC TEST FROM OPERATION CH
BOILER AND SYSTEM TEMPERATURE LOW
CHARACTERISTIC TEST FROM OPERATION CH
04/04/2019 11:33:59 1904_1_50_1 23/05/2019 14:23:05
05/04/2019 09:32:30
VOLTAGE DC FROM TURBINE
{GAINPCBACS}
OBSERVATION SYSTEM PRESSURE RISE (OVERHEAT)
OBSERVE THE MANUAL PRESSURE GAUGE ON THE UNDERSIDE OF THE APPLIANCE
TEMPERATURE DIFFERENTIAL CH
BOILER CH THERMOSTAT
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
OBSERVATION RE WIRE (TIMER BYPASSED)
LINK OUT THE OPENTHERM TERMINALS AS SHOWN IN THE IMAGE
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
PRESSURE GAS INLET - FOR FAULT HISTORY
ATTACH PRESSURE GAUG
PRESSURE EXPANSION VESSEL
APPLIANCE PRIMARY CIRCUIT DRAINED AND DISCHARGED
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE FAN VENTURI
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
VOLTAGE GAS VALVE BURNER SHUT DOWN
{GAINPCBACS}
ECO
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
OBSERVATION RE WIRE (TIMER BYPASSED)
LINK OUT THE OPENTHERM TERMINALS AS SHOWN IN THE IMAGE
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
WATER SUPPLY TO PREMISES
TURN ON A COLD WATER TAP
RESISTANCE GAS VALVE AND HARNESS AND TO EARTH
REMOVE CONNECTOR X4 FROM THE PCB
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR FROM THE GAS VALVE
RESISTANCE THERMISTOR FLOW / STAT AND HARNESS
REMOVE CONNECTOR X6 FROM THE PCB
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
OBSERVATION RE WIRE (TIMER BYPASSED)
LINK OUT THE OPENTHERM TERMINALS AS SHOWN IN THE IMAGE
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
OBSERVATION SELF CHECK (NO DISPLAY)
ENSURE NO DEMANDS
OBSERVATION FAN (DC CONNECTOR REMOVED)
REMOVE THE 4 WAY CONNECTOR FROM THE FAN ASSEMBLY
AND MAKE SAFE
RESISTANCE HARNESS FAN AC
REMOVE THE 3 WIRE CONNECTOR FROM THE FAN
REMOVE CONNECTOR X4 FROM THE PCB
RESISTANCE RECTIFICATION LEAD
REMOVE THE CONNECTOR FROM THE FLAME SENSE ELECTRODE
REMOVE CONNECTOR X12 FROM THE PCB
OBSERVATION X5 CONNECTED TURBINE DISCONNECTED (DISPLAY OPERATES?)
REFIT CONNECTOR X5 TO THE PCB
REMOVE THE CONNECTOR FROM THE FLOW TURBINE
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
RESISTANCE HARNESS THERMISTOR HEAT EXCHANGER / FLUE
REMOVE CONNECTOR FRO
OBSERVATION ISOLATE DHW DOES DEMAND STOP
ISOLATE THE DHW SUPPLY TO THE APPLIANCE ON THE
ISOLATING VALVE UNDERNEATH THE APPLIANCE
VOLTAGE DC FROM TURBINE (FIRING WITH NO DEMAND)
{GAINPCBACS}
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE FAN VENTURI
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
RESISTANCE THERMISTOR DHW
REMOVE WIRES FROM THE DHW SENSOR
RESISTANCE THERMISTOR AND HARNESS DHW
REMOVE CONNECTOR X6 FROM THE PCB
RESISTANCE THERMISTOR DHW
REMOVE WIRES FROM THE DHW SENSOR
VOLTAGE PUMP AT PCB
{GAINPCBACS}
VOLTAGE PUMP AT PCB
{GAINPCBACS}
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
OBSERVATION RE WIRE (TIMER BYPASSED)
LINK OUT THE OPENTHERM TERMINALS AS SHOWN IN THE IMAGE
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
OBSERVATION RE WIRE (TIMER BYPASSED)
LINK OUT THE OPENTHERM TERMINALS AS SHOWN IN THE IMAGE
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
VOLTAGE DC DIVERTER VALVE PERMANENT AT PCB
{GAINPCBACS}
INSPECTION FILTER RETURN
BOILER DRAINED AND D
OBSERVATION FAN RUNNING
NO DEMANDS
OBSERVATION FAN (DC CONNECTOR REMOVED)
REMOVE THE 4 WAY CONNECTOR FROM THE FAN ASSEMBLY
AND MAKE SAFE
RESISTANCE HARNESS FAN AC
REMOVE THE 3 WIRE CONNECTOR FROM THE FAN
REMOVE CONNECTOR X4 FROM THE PCB
RESISTANCE RECTIFICATION LEAD AND ELECTRODE TO EARTH
REMOVE CONNECTOR X12 FROM THE PCB
RESISTANCE RECTIFICATION ELECTRODE TO EARTH
REMOVE THE LEAD FROM THE RECTIFICATION ELECTRODE
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
RESISTANCE HARNESS EXTERNAL CONTROLS
REMOVE CONNECTOR X5 FROM THE PCB
VOLTAGE PCB MAINS INPUT
{GAINPCBACS}
RESISTANCE FUSE MAINS
REMOVE FUSE FROM FUSED SPUR OR PLUG
RESISTANCE THERMISTOR AND HARNESS RETURN
REMOVE CONNECTOR X7 FROM THE PCB
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
RESISTANCE THERMISTOR FLOW / STAT AND HARNESS
REMOVE CONNECTOR X6 FROM THE PCB
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
RESISTANCE THERMISTOR HEAT EXCHANGER / FLUE AND HARNESS
REMOVE CONNECTOR X6 FROM THE PCB
RESISTANCE HARNESS THERMISTOR HEAT EXCHANGER / FLUE
REMOVE CONNECTOR FRO
VOLTAGE POLARITY
{GAINPCBACS}
OBSERVATION BURNER EXTINGUISH ON DEMAND END
ECO MODE ON
ENSUR
INSPECTION RECTIFICATION ELECTRODE
REMOVE RECTIFICATION ELECTRODE
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
RESISTANCE GAS VALVE AND HARNESS AND TO EARTH
REMOVE CONNECTOR X4 FROM THE PCB
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR FROM THE GAS VALVE
OBSERVATION DISCONNECT OUTSIDE SENSOR
REMOVE THE TWO WIRES
RESISTANCE PUMP AND HARNESS AND TO EARTH
REMOVE CONNECTOR X3 FROM THE PCB
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR FROM THE GAS VALVE
RESISTANCE PUMP AND TO EARTH
REMOVE THE COVER FROM THE PUMP
RESISTANCE FAN AND TO EARTH (AC)
REMOVE THE 3 WIRE CONNECTOR FROM THE FAN ASSEMBLY
RESISTANCE FAN AND TO EARTH (DC)
REMOVE THE 4 WIRE CONNECTOR FROM THE FAN ASSEMBLY
RESISTANCE HARNESS TURBINE
REMOVE THE CONNECTOR FROM THE FLOW TURBINE
REMOVE CONNECTOR X5 FROM THE PCB
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE FAN VENTURI
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE FAN VENTURI
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
TEMPERATURE DIFFERENTIAL DHW
ATTACH TEMPERATURE CLAMPS AS INDICATED BY THE RED ARROWS
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE PRIMARY CIRCUIT WATER DRAINED
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
INSPECTION FILTER RETURN
BOILER DRAINED AND D
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR FROM THE GAS VALVE
RESISTANCE PRESSURE SWITCH
REMOVE CONNECTORS FROM PRESSURE SWITCH
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE AIR / GAS MIXING NOZZLE
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
INSPECTION ELECTRODE INTERNAL
REMOVE BURNER ASSEMBLY
INSPECTION BURNER
REMOVE BURNER
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE AIR / GAS MIXING NOZZLE
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
INSPECTION BURNER
REMOVE BURNER
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE AIR / GAS MIXING NOZZLE
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
INSPECTION ELECTRODE INTERNAL
REMOVE BURNER ASSEMBLY
INSPECTION BURNER
REMOVE BURNER
OBSERVATION SPARKING FROM PCB
{GAINPCBACS}
USIN
INSPECTION SUMP
REMOVE THE CONDENSAT
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE FAN VENTURI
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE AIR / GAS MIXING NOZZLE
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
INSPECTION BURNER
REMOVE BURNER
RESISTANCE THERMISTOR HEAT EXCHANGER / FLUE AND HARNESS
REMOVE CONNECTOR X6 FROM THE PCB
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
OBSERVATION SYSTEM PRESSURE RISE (OVERHEAT)
OBSERVE THE MANUAL PRESSURE GAUGE ON THE UNDERSIDE OF THE APPLIANCE
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
TEMPERATURE DIFFERENTIAL CH
BOILER CH THERMOSTAT
TEMPERATURE DIFFERENTIAL DHW (OVERHEAT)
ATTACH TEMPERATURE CLAMPS AS INDICATED BY THE RED ARROWS
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE PRIMARY CIRCUIT WATER DRAINED
INSPECTION FILTER RETURN
BOILER DRAINED AND D
INSPECTION INTEGRAL BYPASS (RESTRICTED OR BLOCKED)
APPLIANCE DRAINED AND DISCHARGED
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE AIR / GAS MIXING NOZZLE
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
INSPECTION BURNER
REMOVE BURNER
OBSERVATION SPARKING FROM PCB
{GAINPCBACS}
USIN
PRESSURE GAS INLET FOR DHW
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
OBSERVATION SYSTEM PRESSURE RISE (PRESSURE FAULT CODE)
OBSERVE THE MANUAL PRESSURE GAUGE ON THE UNDERSIDE OF THE APPLIANCE
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
INSPECTION FLOW SWITCH, FILTER AND RESTRICTOR
ISOLATE THE WATER SUPPLY TO THE APPLIANCE
INSPECTION SUMP
REMOVE THE CONDENSAT
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE FAN VENTURI
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
OBSERVATION PUMP RUNNING FOR OVERHEAT
ENSURE APPLIANCE IS
OBSERVATION SPARKING FROM PCB
{GAINPCBACS}
USIN
OBSERVATION SYSTEM PRESSURE RISE (OVERHEAT)
OBSERVE THE MANUAL PRESSURE GAUGE ON THE UNDERSIDE OF THE APPLIANCE
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
OBSERVATION PUMP RUNNING FOR OVERHEAT
ENSURE APPLIANCE IS
TEMPERATURE DIFFERENTIAL CH
BOILER CH THERMOSTAT
TEMPERATURE DIFFERENTIAL DHW (OVERHEAT)
ATTACH TEMPERATURE CLAMPS AS INDICATED BY THE RED ARROWS
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE PRIMARY CIRCUIT WATER DRAINED
INSPECTION FILTER RETURN
BOILER DRAINED AND D
INSPECTION INTEGRAL BYPASS (RESTRICTED OR BLOCKED)
APPLIANCE DRAINED AND DISCHARGED
VOLTAGE DC RECTIFICATION PERMANENT
{GAINPCBACS}
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
OBSERVATION FAN RUNNING
NO DEMANDS
RESISTANCE PRESSURE SWITCH
REMOVE CONNECTORS FROM PRESSURE SWITCH
RESISTANCE HARNESS FAN DC
REMOVE THE 4 WAY CONNECTOR FROM THE FAN ASSEMBLY
REMOVE CONNECTOR X8 FROM THE PCB
VOLTAGE DC TO FAN AT PCB
{GAINPCBACS}
REMOVE FAN DC CONNECTOR (4 WIRE) AND MAKE SAFE
RESISTANCE HARNESS FAN DC
REMOVE THE 4 WAY CONNECTOR FROM THE FAN ASSEMBLY
REMOVE CONNECTOR X8 FROM THE PCB
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
OBSERVATION CONNECTOR X5 REMOVED (DISPLAY OPERATES?)
REMOVE CONNECTOR X5 FROM THE PCB AND MAKE SAFE
RESISTANCE THERMISTOR AND HARNESS RETURN
REMOVE CONNECTOR X7 FROM THE PCB
RESISTANCE THERMISTOR FLOW / STAT AND HARNESS
REMOVE CONNECTOR X6 FROM THE PCB
RESISTANCE THERMISTOR HEAT EXCHANGER / FLUE AND HARNESS
REMOVE CONNECTOR X6 FROM THE PCB
RESISTANCE HARNESS TIMER SECTION
REMOVE THE CONNECTOR FROM THE INTEGRAL TIMER
RESISTANCE HARNESS TIMER SECTION
REMOVE THE CONNECTOR FROM THE INTEGRAL TIMER
RESISTANCE HARNESS TIMER SECTION
REMOVE THE CONNECTOR FROM THE INTEGRAL TIMER
RESISTANCE HARNESS TIMER SECTION
REMOVE THE CONNECTOR FROM THE INTEGRAL TIMER
RESISTANCE HARNESS TIMER SECTION
REMOVE THE CONNECTOR FROM THE INTEGRAL TIMER
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE AIR / GAS MIXING NOZZLE
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
INSPECTION BURNER
REMOVE BURNER
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE FAN VENTURI
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
INSPECTION FAN ASSEMBLY
FAN VENTURI REMOVED FROM FAN
RESISTANCE HARNESS PRESSURE SWITCH
REMOVE CONNECTOR X5 FROM THE PCB
REMOVE THE CONNECTORS FROM THE LOW PRESSURE SWITCH
RESISTANCE HARNESS FAN DC
REMOVE THE 4 WAY CONNECTOR FROM THE FAN ASSEMBLY
REMOVE CONNECTOR X8 FROM THE PCB
INSPECTION SUMP
REMOVE THE CONDENSAT
RESISTANCE HARNESS PRESSURE SWITCH
REMOVE CONNECTOR X5 FROM THE PCB
REMOVE THE CONNECTORS FROM THE LOW PRESSURE SWITCH
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE FAN VENTURI
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
RESISTANCE THERMISTOR DHW
REMOVE WIRES FROM THE DHW SENSOR
RESISTANCE THERMISTOR DHW
REMOVE WIRES FROM THE DHW SENSOR
RESISTANCE THERMISTOR DHW
REMOVE WIRES FROM THE DHW SENSOR
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
RESISTANCE IGNITION LEAD
REMOVE THE IGNITION LEAD FROM THE PCB AND FROM THE SPARK ELECTRODE
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
RESISTANCE IGNITION LEAD
REMOVE THE IGNITION LEAD FROM THE PCB AND FROM THE SPARK ELECTRODE
RESISTANCE IGNITION LEAD
REMOVE THE IGNITION LEAD FROM THE PCB AND FROM THE SPARK ELECTRODE
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
INSPECTION SUMP
REMOVE THE CONDENSAT
INSPECTION INJECTOR
REMOVE THE INJECTOR FROM THE FAN VENTURI
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
INSPECTION NOZZLE AIR GAS MIXING
REMOVE THE AIR / GAS MIXING NOZZLE
(BEHIND FAN, 1 CLIP THEN TWIST TO REMOVE)
INSPECTION ELECTRODE INTERNAL
REMOVE BURNER ASSEMBLY
INSPECTION BURNER
REMOVE BURNER
INSPECTION SUMP
REMOVE THE CONDENSAT
INSPECTION BURNER
REMOVE BURNER
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR X3 FROM THE PCB
REMOVE THE PLUG FROM THE PUMP ASSEMBLY
VOLTAGE PUMP AT PCB
{GAINPCBACS}
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR X3 FROM THE PCB
REMOVE THE PLUG FROM THE PUMP ASSEMBLY
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR X3 FROM THE PCB
REMOVE THE PLUG FROM THE PUMP ASSEMBLY
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR X3 FROM THE PCB
REMOVE THE PLUG FROM THE PUMP ASSEMBLY
INSPECTION ELECTRODE
REMOVE THE ELECTRODE ASSEMBLY FROM THE HEAT EXCHANGER
VOLTAGE DC TO GAS VALVE AT PCB
{GAINPCBACS}
RESISTANCE HARNESS GAS VALVE
REMOVE THE CONNECTOR
PRESSURE FAN
CONNECT A PERFORMANC
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
OPERATION CH NOISY?
BOILER SET TO WINTER MODE (NO SUN SYMBOL IN DISPLAY)
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE PRIMARY CIRCUIT WATER DRAINED
OBSERVATION BOILER RECOGNISES DEMAND (EXT CONTROLS LINKED OUT)
LINK OUT THE EXTERNA
TEMPERATURE SECONDARY HEAT EXCHANGER
ENSURE THE SECONDARY
TEMPERATURE DIFFERENTIAL FLOW AND RETURN
ATTACH TEMPERATURE CLAMPS AS INDICATED BY THE RED ARROWS
VOLTAGE DC DIVERTER VALVE VARIATION
ATTACH BLACK CROCODILE CLIP TO A SUITABLE EARTH POINT
INSPECTION FILTER RETURN
BOILER DRAINED AND D
INSPECTION INTEGRAL BYPASS (STUCK OPEN)
APPLIANCE DRAINED AND DISCHARGED
RESISTANCE HARNESS DIVERTER VALVE
REMOVE CONNECTOR X9 FROM THE PCB
REMOVE THE CONNECTOR FROM THE DIVERTER VALVE MOTOR
VOLTAGE DC DIVERTER VALVE PERMANENT AT PCB
{GAINPCBACS}
VOLTAGE DC DIVERTER VALVE VARIATION
ATTACH BLACK CROCODILE CLIP TO A SUITABLE EARTH POINT
RESISTANCE HARNESS DIVERTER VALVE
REMOVE CONNECTOR X9 FROM THE PCB
REMOVE THE CONNECTOR FROM THE DIVERTER VALVE MOTOR
VOLTAGE DC TO FAN AT PCB
{GAINPCBACS}
REMOVE FAN DC CONNECTOR (4 WIRE) AND MAKE SAFE
RESISTANCE HARNESS FAN DC
REMOVE THE 4 WAY CONNECTOR FROM THE FAN ASSEMBLY
REMOVE CONNECTOR X8 FROM THE PCB
RESISTANCE HARNESS FAN DC
REMOVE THE 4 WAY CONNECTOR FROM THE FAN ASSEMBLY
REMOVE CONNECTOR X8 FROM THE PCB
FAULT CODES (F BLOCKING CODES)
F CODES ARE BLOCKING
VOLTAGE PUMP AT PCB
{GAINPCBACS}
RESISTANCE THERMISTOR RETURN
REMOVE THE TWO SPADE CONNECTORS FROM THE RETURN THERMISTOR
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
OBSERVATION REMOVE EXTERNAL CONTROLS
REMOVE THE EXTERNAL
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
VOLTAGE WIRELESS CONTROL
{GAINPCBACS}
OBSERVATION APPLIANCE RESET (BOILER RESPONDS)
ENSURE NO DEMANDS
RESISTANCE FUSE FH1
REMOVE FUSE FH1 FROM ITS HOLDER
RESISTANCE FUSE FH2
REMOVE FUSE FH2 FROM THE PCB
PCB DISPLAY FAULTY FURTHER INVESTIGATION?
TESTS SO FAR SHOW TH
PRESSURE GAS INLET DROP
ATTACH U GAUGE TO INLET PRESSURE TEST POINT
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
RESISTANCE THERMISTOR FLOW / STAT
REMOVE THE CONNECTOR FROM THE FLOW THERMISTOR
INSPECTION SUMP
REMOVE THE CONDENSAT
RESISTANCE RECTIFICATION LEAD AND ELECTRODE TO EARTH
REMOVE CONNECTOR X12 FROM THE PCB
RESISTANCE IGNITION LEAD AND ELECTRODE TO EARTH
REMOVE THE IGNITION LEAD FROM THE SPARK GENERATOR
RESISTANCE GAS VALVE AND HARNESS AND TO EARTH
REMOVE CONNECTOR X4 FROM THE PCB
RESISTANCE FAN AND HARNESS AND TO EARTH (AC)
REMOVE CONNECTOR X4 FROM THE PCB
RESISTANCE FAN AND HARNESS AND TO EARTH (DC)
REMOVE CONNECTOR X8 FROM THE PCB