GLOBALLY REPLACED
OBSERVATION DISPLAY OPERATES
ON/OFF SWITCH ON
DHW AND CH THERMOSTATS TO MIN (FULLY ANTI-CLOCKWISE)
OPERATION CH
CH THERMOSTAT SET TO MAX
OBSERVATION WARMSTART OPERATION
ENSURE APPLIANCE PRIMARY CIRCUIT TEMPERATURE IS BELOW 40°C
TURN DHW THERMOSTAT FULLY CLOCKWISE
OBSERVATION DHW DEMAND RECOGNISED
TURN HOT WATER TAP O
HEADER FOR F25 (LOW SYSTEM PRESSURE)
HEADER FOR FAULT CODE - NOT USED
HEADER FOR F64 (SENSORS OR ELECTRONIC FAULT)
HEADER FOR FAULT CODE - NOT USED
HEADER FOR F20, F22, F23, F24 (CIRCULATION / OVERHEAT ISSUES)
HEADER FOR FAULT CODE - NOT USED
HEADER FOR F3 AND F13 (DHW SENSOR)
HEADER FOR FAULT CODE - NOT USED
HEADER FOR FAULT CODE F32, F34, F37 (FAN FAULT)
HEADER FOR FAULT CODE - NOT USED
HEADER FOR F60 AND F61 (GAS VALVE ELECTRICAL FAULT)
HEADER FOR FAULT CODE - NOT USED
HEADER FOR FUSE INVESTIGATION
HEADER FOR FUSE INVESTIGATION - NOT USED
VIEWING AND ADJUSTING DIAGNOSTIC CODES GUIDE
THE METHOD OF CHANGI
PRESSURE GAS INLET (BURNER LIT AND ESTABLISHED)
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
HEADER FOR F27, F62, F67 (FALSE FLAME / GAS VALVE PASSING)
HEADER FOR FAULT CODE - NOT USED
HEADER FOR F1 AND F11 (RETURN SENSOR FAULT)
HEADER FOR FAULT CODE NOT USED
HEADER FOR F0 AND F10 (FLOW SENSOR FAULT)
HEADER FOR FAULT CODE - NOT USED
HEADER FOR FAULT CODE F43
HEADER FOR FAULT CODE - NOT USED
BAFFLING OUT (BLOCKED)
PIPE - AIR - INLET
BURNER BAFFLING
GAS INLET PRESSURE
DIVERTER VALVE MOTOR
CABLE TREE
POOR DHW FLOW
DHW ISOLATION VALVE
DHW FLOW RATE
COLD WATER SUPPLY
FAN DOES NOT RUN
PCB
FAN DOES NOT RUN
CABLE TREE
CALLING UP THE INSTALLER LEVEL
Z DIRECTION CHOICE OR CONTINUE
FAULT CODE F32
PCB
FAULT CODE F32 2
PCB
FAULT CODE F32 1
PCB
FAULT CODE F32
CABLE TREE
FAULT CODE F61
GAS VALVE
FAULT CODE F61
PCB
F13
PCB
TYPE OF DIAGNOSTIC PROCEDURE
Z DIRECTION CHOICE OR CONTINUE
F23 F24 F83 F84
SENSOR - NTC
F23 F24 F83 F84
SENSOR - NTC - CH FLOW / CH RETURN
BLANK FOR CASE OFF
Z DIRECTION CHOICE OR CONTINUE
TOO LOW
GAS INLET PRESSURE
BAFFLING
HEAT EXCHANGER
BAFFLING
BURNER
BAFFLING
CONDENSATE TRAP, PIPEWORK OR EXTERNAL CONDENSATE DRAIN
BAFFLING
FLUE ASSEMBLY
BLOWN STAND BY MODE AT POWER UP
FUSE (MAINS)
FAULT CODE F32 1
CABLE TREE
F32
CABLE TREE
FAULT CODE F68
CONDENSATE TRAP, PIPEWORK OR EXTERNAL CONDENSATE DRAIN
FAULT CODE F68
FLUE ASSEMBLY
FAULT CODE F68
IGNITION WIRE
FAULT CODE F68
ELECTRODE IGNITION/MONITORING
BLANK FOR FAULT CODES 2
Z DIRECTION CHOICE OR CONTINUE
FUSE F1
FUSE F1
PCB MAIN
PCB
S34
SENSOR - NTC
S34
SENSOR - NTC - CH FLOW / CH RETURN
DHW SPINDLE SNAPPED
SET - 3 OFF - KNOBS
FROST PROTECTION
SENSOR - NTC
FROST PROTECTION
SENSOR - NTC - CH FLOW / CH RETURN
STUCK
AQUA SENSOR - IMPELLER ONLY
DC HALL SENSOR
CABLE TREE
NOT IGNITING
CONDENSATE TRAP, PIPEWORK OR EXTERNAL CONDENSATE DRAIN
BURNER NOT IGNITING
GAS INLET PRESSURE
BURNER DOES NOT IGNITE
PCB AND GAS SECTION
SPARKING BUT NOT LIGHTING
GAS VALVE
HIGH FAN PRESSURE
PIPE - AIR - INLET
RESTRICTED FAN PRESSURE
FLUE ASSEMBLY
RESTRICTED FAN PRESSURE
BURNER
RESTRICTED FAN PRESSURE
HEAT EXCHANGER
FAN PRESSURE INCORRECT
FAN ASSEMBLY
NOT IGNITING
ELECTRODE IGNITION/MONITORING
RESTRICTED OR BLOCKED
AQUA SENSOR - IMPELLER ONLY
NO DEMAND TO FAN
SENSOR - NTC
NO DEMAND FOR FAN
SENSOR - NTC - CH FLOW / CH RETURN
NO DEMAND TO FAN DUE TO EXCESSIVE DIFFERENTIAL
FILTER PRIMARY CIRCUIT
NO FAN DEMAND DUE TO EXCESSIVE DIFFERENTIAL
HEAT EXCHANGER - 12 PLATES - DHW
DHW SPINDLE SNAPPED 2
SET - 3 OFF - KNOBS
DHW SPINDLE SNAPPED 3
SET - 3 OFF - KNOBS
DHW TOO COOL
SENSOR - NTC
DHW TOO COOL
SENSOR - NTC - CH FLOW / CH RETURN
SLOW OR WEAK
PUMP
DHW TOO COOL RADS COLD EXCESSIVE DIFFERENTIAL
FILTER PRIMARY CIRCUIT
POOR HOT WATER
EXTERNAL MIXING
DHW SPINDLE SNAPPED 4
SET - 3 OFF - KNOBS
SHORTED TO EARTH
SENSOR - NTC
OUT OF CALIBRATION
SENSOR - NTC
OUT OF CALIBRATION 2
SENSOR - NTC
RESTRICTED / BLOCKED
RUBBER TUBE / PIPE
LIMITER TRIPPED
UNDERFLOOR HEATING
IGNITES BUT DOES NOT ESTABLISH
PIPE - AIR - INLET
NOT ESTABLISHING
GAS INLET PRESSURE
NOT RECTIFYING
IGNITION WIRE
NOT RECTIFYING
ELECTRODE IGNITION/MONITORING
CAUSING NO RECTIFICATION
BURNER
NOT ESTABLISHING
CONDENSATE TRAP, PIPEWORK OR EXTERNAL CONDENSATE DRAIN
FLAT
EXPANSION VESSEL 10L
NO WARMSTART
SENSOR - NTC
NO WARMSTART
SENSOR - NTC - CH FLOW / CH RETURN
PREVENTING WARMSTART
SENSOR - NTC
D000
ADJUSTMENT DIAGNOSTIC CODES
CH STAYING TOO COOL
SENSOR - NTC
CH STAYING TOO COOL
SENSOR - NTC - CH FLOW / CH RETURN
PASSING
GAS VALVE
FAULT CODES
SENSOR - NTC
FAULT CODES
SENSOR - NTC - CH FLOW / CH RETURN
FAULT CODE F25
PCB
F13
SENSOR - NTC
NOT MAKING / RESTRICTED OR BLOCKED
SENSOR - PRESSURE
BLOWING FUSE
PUMP
BLOWING FUSE
FAN ASSEMBLY
DIVERTER SECTION SHORTING
CABLE TREE
F68
PCB
F0 OR F10
SENSOR - NTC
F1 OR F11
SENSOR - NTC - CH FLOW / CH RETURN
POOR HOT WATER
PIPE - AIR - INLET
POOR HOT WATER
CONDENSATE TRAP, PIPEWORK OR EXTERNAL CONDENSATE DRAIN
POOR HOT WATER
FLUE ASSEMBLY
POOR HOT WATER
BURNER
POOR HOT WATER
FAN ASSEMBLY
POOR HOT WATER
HEAT EXCHANGER
POOR HOT WATER UNABLE TO GAS RATE
PIPE - AIR - INLET
POOR HOT WATER UNABLE TO GAS RATE
CONDENSATE TRAP, PIPEWORK OR EXTERNAL CONDENSATE DRAIN
POOR HOT WATER UNABLE TO GAS RATE
FLUE ASSEMBLY
POOR HOT WATER UNABLE TO GAS RATE
FAN ASSEMBLY
POOR HOT WATER UNABLE TO GAS RATE
HEAT EXCHANGER
SPARKING
IGNITION WIRE
DHW RUNS HOT THEN COLD
SENSOR - NTC
DHW RUNS HOT THEN COLD
SENSOR - NTC - CH FLOW / CH RETURN
OUT OF CALIBRATION 3
SENSOR - NTC
NOISY
PUMP
RESTRICTED / BLOCKED 2
RUBBER TUBE / PIPE
DHW RUNS HOT THEN COLD
FILTER PRIMARY CIRCUIT
OVERHEAT
CHECK VALVE / SERVICE COCK - CH
WEAK
PUMP
CLOSED TOO MUCH OR BLOCKED
AUTO BYPASS VALVE
EXCESSIVE DIFFERENTIAL AND TEMP RISE FAULT CODE
FILTER PRIMARY CIRCUIT
AIR IN APPLIANCE / SYSTEM
AIR / DE-AERATOR
AIR IN APPLIANCE / SYSTEM 2
AIR / DE-AERATOR
AIR IN APPLIANCE / SYSTEM 3
AIR / DE-AERATOR
AIR IN BOILER / SYSTEM 4
AIR / DE-AERATOR
TURNED OFF
CHECK VALVE / SERVICE COCK - CH
DIVERTER VALVE MOTOR CH
CABLE TREE
NOT OPENING TO RADS POSITION
VALVE - DIVERTER
OPEN TOO MUCH SO BYPASSING RADS
AUTO BYPASS VALVE
SPLIT / LEAKING
FLUE COLLECTOR / SEALS
BLOWN
FUSE F2
CH SPINDLE SNAPPED
SET - 3 OFF - KNOBS
DHW SPINDLE SNAPPED 5
SET - 3 OFF - KNOBS
D71
ADJUSTMENT DIAGNOSTIC CODES
F20 F22 F23 AND F24
RUBBER TUBE / PIPE
CODING RESISTOR
CABLE TREE
FAULT CODE F43
PCB
NO DEMAND TO FAN DUE TO EXCESSIVE DIFFERENTIAL
RUBBER TUBE / PIPE
WARMSTART ISSUES
SENSOR - NTC
WARMSTART ISSUES
SENSOR - NTC - CH FLOW / CH RETURN
TO AQUA SENSOR
CABLE TREE
HEAT EXCHANGER - DHW
HEAT EXCHANGER - 12 PLATES - DHW
FLOW LIMITER
LIMITER
PASSING TO RADS
MOTOR - DIVERTER VALVE
FILTER DHW
FILTER DHW
BAFFLING
GAS VALVE
NOT RUNNING WITH CORRECT VOLTAGES
FAN ASSEMBLY
F32
FAULT CODE RESET
FAULT CODE F32
FAN ASSEMBLY
FAULT CODE F61
CABLE TREE
F61
FAULT CODE RESET
F13
FAULT CODE RESET
F13
CABLE TREE
FURTHER INVESTIGATION MAINS
Z DIRECTION CHOICE OR CONTINUE
FAULT CODE F32 1
FAN ASSEMBLY
FAULT CODE F32 3
PCB
BLANK FOR FAULT CODES
Z DIRECTION CHOICE OR CONTINUE
FURTHER INVESTIGATION FUSE F1
Z DIRECTION CHOICE OR CONTINUE
DISPLAY PCB
DISPLAY - PRINTED CIRCUIT
OPERATION CORRECTLY
FROST PROTECTION - NORMAL OPERATION
TAP OPEN OR LEAKING DHW DRAW OFF
TAP OPEN OR LEAKING DHW DRAW OFF
NOT SENSING DEMAND
SENSOR - HALL
HALL SENSOR SIGNAL
FAN ASSEMBLY
BURNER DOES NOT IGNITE
PCB AND HARNESS
SOLENOID NOT OPENING
GAS VALVE
SPARKING BUT NOT LIGHTING
CABLE TREE
INCORRECT MIX
GAS VALVE
PASSING TO RADS
VALVE - DIVERTER
DHW TOO COOL
PCB
DHW SECTION SHORTED
CABLE TREE
DHW SECTION OPEN CIRCUIT
CABLE TREE
DHW TOO COOL
HEAT EXCHANGER - 12 PLATES - DHW
DHW TOO COOL
HEAT EXCHANGER
BLOCKED
PIPE CONNECTION
DHW SECTION OPEN CIRCUIT 2
CABLE TREE
RAD TEMP LOW
Z DIRECTION CHOICE OR CONTINUE
THERMISTOR FAULT CODES FLOW SENSOR
CABLE TREE
THERMISTOR FAULT CODES RETURN SENSOR
CABLE TREE
BLOCKED
MANOMETER
LOW CAUSING F25
SYSTEM PRESSURE
LOW PRESSURE SWITCH SECTION OPEN CIRCUIT
CABLE TREE
FAN SECTION SHORTING
CABLE TREE
BLANK DISPLAY
FUSE FURTHER INVESTIGATION
BLOWING FUSE
MOTOR - DIVERTER VALVE
FLOW SENSOR SECTION
CABLE TREE
RETURN SENSOR SECTION
CABLE TREE
POOR HOT WATER
GAS VALVE
SPARKING
ELECTRODE IGNITION/MONITORING
NOT SPARKING
PCB
DHW RUNS HOT THEN COLD
HEAT EXCHANGER
NOISY
HEAT EXCHANGER - 12 PLATES - DHW
F23 F24 F83 F84
HEAT EXCHANGER - 12 PLATES - DHW
BLOCKED 2
MANOMETER
DHW RUNS HOT THEN COLD
SYSTEM PRESSURE
BLOCKED 3
MANOMETER
DHW COOL RADS COOL
SYSTEM PRESSURE
BLOCKED 4
MANOMETER
F23 F24 F83 F84
SYSTEM PRESSURE
BLOCKED 5
MANOMETER
BOILER TO TEMP RADS COOL
SYSTEM PRESSURE
PASSING TO RADS CH
MOTOR - DIVERTER VALVE
NOT RUNNING
PUMP
OVERHEAT
PUMP
FUSE F2 FURTHER INVESTIGATION
Z DIRECTION CHOICE OR CONTINUE
FAULTY SENSOR OR WATER INGRESS
SENSOR - HALL (SHORTED)
F0 AND F10
FAULT CODE RESET
F1 AND F11
FAULT CODE RESET
F25
FAULT CODE RESET
F64
FAULT CODE RESET
FALSE FLAME / PASSING GAS VALVE
FAULT CODE RESET
MAXIMUM HEATING TEMPERATURE ADJUSTMENT BLANK
Z DIRECTION CHOICE OR CONTINUE
F23 F24 F83 F84
HEAT EXCHANGER
F43
FAULT CODE RESET
SER DISPLAYED
SERVICE INTERVAL EXPIRED
S53 OR S54 WAITING TIME
HEAT EXCHANGER
LIMITER BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION FLOW LIMITER AND FILTER
FILTER BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION FLOW LIMITER AND FILTER
FAN DOES NOT RUN
CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS - FAULT CODE F32
FAN RUNS BUT FAN RELATED FAULT CODE REOCCURS
CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS - FAULT CODE F32
SPARKING OCCURS BUT BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
BURNER IGNITES BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
BURNER IGNITES BUT BAFFLES OUT/NOISY
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
DHW TOO HOT
CHARACTERISTIC TEST FROM OPERATION DHW
TEMPERATURE RISE UNSATISFACTORY, RADIATORS REMAIN COOL
CHARACTERISTIC TEST FROM OPERATION DHW
DISPLAY DOES NOT OPERATE
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY ILLUMINATES
TEMPERATURE RISE UNSATISFACTORY, RADIATORS HEAT WITH NO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION DHW
DHW RUNS HOT THEN COLD
CHARACTERISTIC TEST FROM OPERATION DHW
FAULT CODE SHOWN
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY ILLUMINATES
PUMP RUNS CONTINUOUSLY OR BOILER TRIES TO FIRE WITH NO DEMAND
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY ILLUMINATES
SPARKING DOES NOT OCCUR
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
DIFFERENTIAL EXCESSIVE
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER
BOILER DOES NOT RESPOND TO CENTRAL HEATING
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER
EXCESSIVE SYSTEM PRESSURE RISE
CHARACTERISTIC TEST FROM OPERATION CH
PRESSURE CORRECT BUT DOES NOT INCREASE WHEN PRESSURE ADDED
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND INCREASE
PRESSURE LOW BUT INCREASES WHEN PRESSURE ADDED
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND INCREASE
GAS RATE INCORRECT
CHARACTERISTIC TEST FROM GAS RATE
UNABLE TO GAS RATE APPLIANCE I E LPG INSTALLATION OR NO METER
CHARACTERISTIC TEST FROM GAS RATE
DIFFERENTIAL EXCESSIVE
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER
BOILER DOES NOT RESPOND TO CENTRAL HEATING
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER
DIFFERENTIAL EXCESSIVE
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER
BOILER DOES NOT RESPOND TO CENTRAL HEATING
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER
PRESSURE CORRECT BUT DOES NOT INCREASE WHEN PRESSURE ADDED
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND INCREASE
PRESSURE LOW BUT INCREASES WHEN PRESSURE ADDED
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND INCREASE
PRESSURE CORRECT BUT DOES NOT INCREASE WHEN PRESSURE ADDED
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND INCREASE
PRESSURE LOW BUT INCREASES WHEN PRESSURE ADDED
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND INCREASE
PRESSURE CORRECT BUT DOES NOT INCREASE WHEN PRESSURE ADDED
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND INCREASE
PRESSURE LOW BUT INCREASES WHEN PRESSURE ADDED
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND INCREASE
PRESSURE CORRECT BUT DOES NOT INCREASE WHEN PRESSURE ADDED
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND INCREASE
PRESSURE LOW BUT INCREASES WHEN PRESSURE ADDED
CHARACTERISTIC TEST FROM OBSERVATION SYSTEM PRESSURE AND INCREASE
WARMSTART IS NOT RECOGNISED ON THE DISPLAY
CHARACTERISTIC TEST FROM OBSERVATION WARMSTART OPERATION
SER FLASHES ON DISPLAY
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY ILLUMINATES
BOILER UP TO TEMP RADS COLD
CHARACTERISTIC TEST FROM OPERATION CH
BOILER AND SYSTEM TEMPERATURE LOW
CHARACTERISTIC TEST FROM OPERATION CH
WARMSTART IS RECOGNISED ON THE DISPLAY BUT DOES NOT OPERATE
CHARACTERISTIC TEST FROM OBSERVATION WARMSTART OPERATION
WARMSTART RECOGNISED AND OPERATES BUT DOES NOT HEAT SUFFICIENTLY
CHARACTERISTIC TEST FROM OBSERVATION WARMSTART OPERATION
13/05/2019 10:07:06 1903_1_50_1 01/07/2019 09:57:10
21/05/2019 08:50:29
VOLTAGE DIVERTER VALVE
REMOVE CONNECTOR FROM THE DIVERTER VALVE AND MAKE SAFE
ENSURE NO DEMANDS
ON/OFF SWITCH OFF
VOLTAGE DC PWM DEMAND AT FAN
{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR FROM FAN ASSEMBLY AND MAKE SAFE
OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
GAIN ACCESS TO THE PCB
RESISTANCE GAS VALVE AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
RESISTANCE GAS VALVE
REMOVE THE ELECTRICAL CONNECTOR FROM THE GAS VALVE
RESISTANCE PUMP AND HARNESS
REMOVE THE PUMP CONNECTOR FROM THE PCB
RESISTANCE DHW SENSOR
REMOVE THE CONNECTOR FROM THE DHW SENSOR
RESET APPLIANCE - ENSURE APPLIANCE IS COOL
ENSURE NO DEMANDS ARE PRESENT
ENSURE APPLIANCE IS COOL
RESISTANCE FLOW SENSOR
REMOVE THE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE MAINS SUPPLY FUSE
REMOVE THE MAINS 3A FUSE FROM ITS HOLDER
RESISTANCE FAN HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
REMOVE THE DC FAN CONNECTOR FROM THE FAN ASSEMBLY
INSPECTION SPINDLE DHW
GAIN ACCESS TO PCB
TURN THE DHW THERMOSTAT SO IT IS POINTING STRAIGHT UPWARDS
VOLTAGE PUMP AT PCB
{GAINPCBACS}
RESISTANCE FAN HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
REMOVE THE DC FAN CONNECTOR FROM THE FAN ASSEMBLY
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
RESISTANCE GAS VALVE AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
RESISTANCE GAS VALVE
REMOVE THE ELECTRICAL CONNECTOR FROM THE GAS VALVE
RESISTANCE GAS VALVE
REMOVE THE ELECTRICAL CONNECTOR FROM THE GAS VALVE
INSPECTION SPINDLE DHW
GAIN ACCESS TO PCB
TURN THE DHW THERMOSTAT SO IT IS POINTING STRAIGHT UPWARDS
TEMPERATURE DIFFERENTIAL PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE C
RESISTANCE DHW SENSOR
REMOVE THE CONNECTOR FROM THE DHW SENSOR
RESISTANCE DHW SENSOR
REMOVE THE CONNECTOR FROM THE DHW SENSOR
VOLTAGE FROM 24V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE TO 24V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE FROM 24V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE TO 24V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
RESISTANCE DHW SENSOR
REMOVE THE CONNECTOR FROM THE DHW SENSOR
RESISTANCE FLOW SENSOR AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
RESISTANCE FLOW SENSOR
REMOVE THE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
RESISTANCE LOW PRESSURE SWITCH
REMOVE AIR INTAKE PIPE
REMOVE THE 2 BLACK WIRES FROM THE LOW PRESSURE SWITCH
RESISTANCE FAN
REMOVE THE CONNECTOR FROM THE FAN ASSEMBLY
RESISTANCE DIVERTER VALVE HARNESS
REMOVE CONNECTOR X4 FROM THE PCB
REMOVE THE CONNECTOR FROM THE DIVERTER VALVE MOTOR
RESISTANCE FLOW SENSOR AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
RESISTANCE FLOW SENSOR
REMOVE THE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
RESISTANCE RETURN SENSOR
REMOVE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
RESISTANCE IGNITION LEAD
REMOVE THE IGNITION LEAD FROM THE PCB
REMOVE THE IGNITION LEAD FROM THE SPARK ELECTRODE
TEMPERATURE DIFFERENTIAL PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE C
VOLTAGE FROM 24V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE TO 24V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE PUMP AT PCB
{GAINPCBACS}
TEMPERATURE DIFFERENTIAL PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE C
VOLTAGE FROM 24V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE TO 24V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE DIVERTER VALVE
REMOVE CONNECTOR FROM THE DIVERTER VALVE AND MAKE SAFE
ENSURE NO DEMANDS
ON/OFF SWITCH OFF
VOLTAGE TO 240V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE TO 240V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE TO 240V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE TO 240V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE TO AQUA SENSOR (DISCONNECTED)
DISCONNECT THE IN-LINE CONNECTOR TO THE AQUA SENSOR AND MAKE SAFE
RESISTANCE CODING RESISTOR
REMOVE CONNECTOR X2 FROM THE PCB
VOLTAGE DEMAND FROM AQUA SENSOR
{GAINPCBACS}
ENSURE A FLOW RATE ABOVE 2 LITRES PER MINUTE
RESISTANCE DHW SENSOR AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
INSPECTION AIR INTAKE TUBE
REMOVE AIR INTAKE TUBE
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
INSPECTION FLOW LIMITER AND FILTER
DHW SUPPLY ISOLATED AND DRAINED
REMOVE THE FLOW LIMITER AND FILTER FROM THE FLOW SENSOR ASSEMBLY
RESISTANCE DIVERTER VALVE HARNESS
REMOVE CONNECTOR X4 FROM THE PCB
REMOVE THE CONNECTOR FROM THE DIVERTER VALVE MOTOR
INSPECTION BURNER
REMOVE THE COMBUSTION FRONT ASSEMBLY
INSPECTION PRIMARY HEAT EXCHANGER FLUEWAYS
REMOVE THE BURNER DOOR ASSEMBLY
VOLTAGE FAN 22VDC AT PCB
{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR FROM FAN ASSEMBLY AND MAKE SAFE
RESISTANCE FAN HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
REMOVE THE DC FAN CONNECTOR FROM THE FAN ASSEMBLY
VOLTAGE FROM 240V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE DC PWM DEMAND AT FAN
{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR FROM FAN ASSEMBLY AND MAKE SAFE
VOLTAGE FAN HALL SENSOR
{GAINPCBACS}
VOLTAGE FAN 22VDC AT PCB
{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR FROM FAN ASSEMBLY AND MAKE SAFE
RESISTANCE FAN HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
REMOVE THE DC FAN CONNECTOR FROM THE FAN ASSEMBLY
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESISTANCE RETURN SENSOR
REMOVE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
VOLTAGE MAINS POWER INPUT TO APPLIANCE
{GAINPCBACS}
INSPECTION DIVERTER VALVE MOTOR OPERATION
REMOVE THE DIVERTER
RESISTANCE FAN HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
REMOVE THE DC FAN CONNECTOR FROM THE FAN ASSEMBLY
RESISTANCE IGNITION LEAD
REMOVE THE IGNITION LEAD FROM THE PCB
REMOVE THE IGNITION LEAD FROM THE SPARK ELECTRODE
INSPECTION SPARK ELECTRODE
REMOVE THE SPARK ELECTRODE ASSEMBLY
RESISTANCE FUSE F1
REMOVE FUSE F1 FROM ITS HOLDER ON THE PCB
VOLTAGE DC DISPLAY PCB
{GAINPCBACS}
REMO
RESISTANCE FLOW SENSOR
REMOVE THE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
RESISTANCE FLOW SENSOR
REMOVE THE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
OBSERVATION DHW DEMAND INCORRECTLY RECOGNISED
HOT WATER TAPS OFF
OBSERVATION ISOLATE MAINS WATER - DOES DEMAND STOP ?
TURN OFF THE DHW ISOLATION VALVE
INSPECTION FLOW TURBINE
DHW ISOLATED AND DRAINED
VOLTAGE FAN HALL SENSOR
{GAINPCBACS}
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
PRESSURE GAS INLET DROP
ATTACH A PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
ENSURE NO DEMANDS
RESISTANCE GAS VALVE AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
INSPECTION AIR INTAKE TUBE
REMOVE AIR INTAKE TUBE
INSPECTION BURNER
REMOVE THE COMBUSTION FRONT ASSEMBLY
INSPECTION PRIMARY HEAT EXCHANGER FLUEWAYS
REMOVE THE BURNER DOOR ASSEMBLY
INSPECTION SPARK ELECTRODE
REMOVE THE SPARK ELECTRODE ASSEMBLY
INSPECTION FLOW TURBINE
DHW ISOLATED AND DRAINED
INSPECTION SPINDLE DHW
GAIN ACCESS TO PCB
TURN THE DHW THERMOSTAT SO IT IS POINTING STRAIGHT UPWARDS
RESISTANCE FLOW SENSOR
REMOVE THE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
RESISTANCE DHW SENSOR AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
OBSERVATION STATUS CODE S53 OR S54
DHW THERMOSTAT SET TO 3 O'CLOCK POSITION
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE DRAINED AND DISCHARGED
INSPECTION PLATE HEAT EXCHANGER
DHW AND PRIMARY CIRCUIT ISOLATED AND DRAINED
REMOVE THE PLATE HEAT EXCHANGER
RESISTANCE FLOW SENSOR
REMOVE THE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
TEMPERATURE DIFFERENTIAL DHW HEAT EXCHANGER
ATTACH TEMPERATURE C
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE DRAINED AND DISCHARGED
OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
GAIN ACCESS TO THE PCB
VOLTAGE FROM 240V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
RESISTANCE DHW SENSOR
REMOVE THE CONNECTOR FROM THE DHW SENSOR
INSPECTION SPINDLE DHW
GAIN ACCESS TO PCB
TURN THE DHW THERMOSTAT SO IT IS POINTING STRAIGHT UPWARDS
RESISTANCE DHW SENSOR AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
INSPECTION FLOW PIPE / HOSES
PRIMARY CIRCUIT DRAI
RESISTANCE UNDERFLOOR OVERHEAT THERMOSTAT
IF NO LINK IS FITTED
INSPECTION AIR INTAKE TUBE
REMOVE AIR INTAKE TUBE
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
RESISTANCE IGNITION LEAD
REMOVE THE IGNITION LEAD FROM THE PCB
REMOVE THE IGNITION LEAD FROM THE SPARK ELECTRODE
INSPECTION SPARK ELECTRODE
REMOVE THE SPARK ELECTRODE ASSEMBLY
INSPECTION BURNER
REMOVE THE COMBUSTION FRONT ASSEMBLY
PRESSURE EXPANSION VESSEL
APPLIANCE PRIMARY CIRCUIT DRAINED AND DISCHARGED
RESISTANCE FLOW SENSOR
REMOVE THE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
OBSERVATION HEATING OUTPUT
ENSURE NO DEMANDS
RESISTANCE FLOW SENSOR
REMOVE THE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
D 0 NOW SET CORRECTLY
THE HEATING OUTPUT S
RESISTANCE RETURN SENSOR
REMOVE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
RESISTANCE RETURN SENSOR AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESISTANCE LOW PRESSURE SWITCH AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESISTANCE FAN AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
RESISTANCE DIVERTER VALVE AND HARNESS
REMOVE CONNECTOR X4 FROM THE PCB
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
INSPECTION AIR INTAKE TUBE
REMOVE AIR INTAKE TUBE
INSPECTION BURNER
REMOVE THE COMBUSTION FRONT ASSEMBLY
INSPECTION PRIMARY HEAT EXCHANGER FLUEWAYS
REMOVE THE BURNER DOOR ASSEMBLY
INSPECTION AIR INTAKE TUBE
REMOVE AIR INTAKE TUBE
INSPECTION BURNER
REMOVE THE COMBUSTION FRONT ASSEMBLY
INSPECTION PRIMARY HEAT EXCHANGER FLUEWAYS
REMOVE THE BURNER DOOR ASSEMBLY
OBSERVATION SPARKING
REMOVE THE IGNITION
RESISTANCE FLOW SENSOR
REMOVE THE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
RESISTANCE DHW SENSOR
REMOVE THE CONNECTOR FROM THE DHW SENSOR
TEMPERATURE DIFFERENTIAL DHW HEAT EXCHANGER
ATTACH TEMPERATURE C
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE DRAINED AND DISCHARGED
INSPECTION FLOW PIPE / HOSES
PRIMARY CIRCUIT DRAI
OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
GAIN ACCESS TO THE PCB
VOLTAGE FROM 240V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
TEMPERATURE DIFFERENTIAL DHW HEAT EXCHANGER
ATTACH TEMPERATURE C
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE DRAINED AND DISCHARGED
OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
GAIN ACCESS TO THE PCB
VOLTAGE FROM 240V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
INSPECTION INTEGRAL BYPASS
APPLIANCE DRAINED AND DISCHARGED
REMOVE THE INTEGRAL BYPASS ASSEMBLY
INSPECTION DIVERTER VALVE MOTOR OPERATION
REMOVE THE DIVERTER
INSPECTION DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER VALVE MOTOR FROM THE BODY
RESISTANCE DIVERTER VALVE HARNESS
REMOVE CONNECTOR X4 FROM THE PCB
REMOVE THE CONNECTOR FROM THE DIVERTER VALVE MOTOR
INSPECTION INTEGRAL BYPASS
APPLIANCE DRAINED AND DISCHARGED
REMOVE THE INTEGRAL BYPASS ASSEMBLY
RESISTANCE FUSE F2
REMOVE FUSE F1 FROM ITS HOLDER ON THE PCB
INSPECTION SPINDLE CH
GAIN ACCESS TO PCB
TURN THE CH THERMOSTAT SO IT IS POINTING STRAIGHT UPWARDS
INSPECTION SPINDLE DHW
GAIN ACCESS TO PCB
TURN THE DHW THERMOSTAT SO IT IS POINTING STRAIGHT UPWARDS
OBSERVATION MAXIMUM HEATING TEMPERATURE
ENSURE NO DEMANDS
D 71 NOW SET CORRECTLY
THE HEATING TEMPERAT
INSPECTION FLOW PIPE / HOSES
PRIMARY CIRCUIT DRAI
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
INSPECTION FLOW PIPE / HOSES
PRIMARY CIRCUIT DRAI
RESISTANCE DHW SENSOR AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
RESISTANCE FLOW SENSOR
REMOVE THE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE AIR INTAKE PIPE
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
RESISTANCE HARNESS AQUA SENSOR
REMOVE THE CONNECTOR FROM THE AQUA SENSOR
REMOVE CONNECTOR X2 FROM THE PCB