Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Gain access to PCB (use Insulation Mat as required)
Ensure a flow rate above 2 litres per minute
Ensure a flow rate above 2 litres per minute
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Measure the DC voltage between pin 1 on connector X2 and a suitable earth.
Expect approximately 2.2 vdc.
Is the voltage measured as expected?
Expect approximately 2.2 vdc.
Is the voltage measured as expected?