Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
ARISTON MICROSYSTEM RFFI 21 AND 28
GLOBALLY REPLACED
OBSERVATION BOILER STANDBY
NO DEMANDS
TYPE OF DIAGNOSTIC PROCEDURE
PLEASE SELECT FROM O
OBSERVATION FAN RUNS
ENSURE BOILER IS COOL
OBSERVATION BURNER IGNITES AND ESTABLISHES
SET BOILER THERMOSTAT TO MAX
PRESSURE BURNER MAX AND MIN
DISCONNECT ONE LEAD
FUSE INVESTIGATION TREE (MAINS)
INTENTIONALLY BLANK - HEADER FOR FUSE INVESTIGATION (MAINS)
FUSE INVESTIGATION TREE (APPLIANCE)
INTENTIONALLY BLANK - HEADER FOR FUSE INVESTIGATION (APPLIANCE)
OBSERVATION RUN BOILER TO TEMPERATURE
ATTACH TEMPERATURE C
LOCKOUT NOT RESETTING INVESTIGATION
OUTSIDE MODEL
INSPECTION INTERNAL BYPASS (OPERATION)
DRAIN BOILER PRIMARY CIRCUIT
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH
THERMOSTAT - REGULATION
OBSERVATION BURNER IGNITES AND ESTABLISHES - NO SPARKING THEN LOCKOUT
ELECTRODE - IGNITION (GAP)
OBSERVATION BURNER IGNITES AND ESTABLISHES - NO SPARKING THEN LOCKOUT
PCB - CB3FF102MX (IGNITION PCB)
OBSERVATION BOILER STANDBY
FAST FUSE 2AT
OBSERVATION BURNER IGNITES AND ESTABLISHES - NO SPARKING NO LOCKOUT
EXCHANGER - MAIN (FLUEWAYS)
OBSERVATION BURNER IGNITES AND ESTABLISHES - BAFFLES
GAS INLET PRESSURE
INFORMATION CASE REMOVAL
Z REDIRECT
OBSERVATION BOILER STANDBY - MAINS
CABLE - PCB TO TERMINAL BOARD
OPERATION CH - NOISY
PUMP
OBSERVATION BOILER STANDBY
FROST PROTECTION
OBSERVATION BOILER STANDBY
THERMOSTAT - ANTI FROST
OBSERVATION BOILER STANDBY - FROST STAT
CABLE - LOW WATER PRESSURE SWITCH
FUSE INVESTIGATION - APPLIANCE
GAS VALVE
FUSE INVESTIGATION - MAINS
GAS VALVE
OBSERVATION FAN RUNS
CABLE - PCB
OBSERVATION PUMP RUNS
SWITCH - PRESSURE - LOW WATER
OBSERVATION PUMP RUNS - PRESSURE SWITCH
CABLE - LOW WATER PRESSURE SWITCH
OBSERVATION PUMP RUNS 1
CABLE - PCB
OBSERVATION PUMP RUNS 2
CABLE - PCB
OPERATION CH - SHUTS DOWN TOO EARLY
KNOB - CONTROL
OPERATION CH - SHUTS DOWN TOO EARLY
THERMOSTAT - REGULATION
OPERATION CH - UP TO TEMP RADS COOL
ISOLATION VALVES
OPERATION CH
EXPANSION VESSEL
TYPE OF DIAGNOSTIC PROCEDURE
Z REDIRECT
FUSE INVESTIGATION - APPLIANCE
CABLE (PLUG) FUSE INVESTIGATION
FUSE INVESTIGATION - MAINS
CABLE (PLUG) FUSE INVESTIGATION
OBSERVATION PUMP RUNS - EXT CONTROLS
CABLE - PCB TO TERMINAL BOARD
OPERATION - SHUTS DOWN THEN BOILER GOES TO LOCKOUT
ISOLATION VALVES
OBSERVATION PUMP RUNS
CABLE - PUMP
OBSERVATION BURNER IGNITES AND ESTABLISHES - SPARKING NO IGNITION
ELECTRODE - IGNITION (GAP)
OPERATION CH - SHUTS DOWN THEN BOILER GOES TO LOCKOUT
THERMOSTAT - REGULATION
OPERATION CH - SHUTS DOWN THEN GOES TO LOCKOUT
THERMOSTAT - OVERHEAT
OPERATION CH - SHUTS DOWN THEN BOILER GOES TO LOCKOUT
THERMOSTAT - REGULATION (FITMENT)
OBSERVATION BOILER STANDBY
MAINS FUSE
OBSERVATION FAN RUNS
PIPE SILICONE - POSITIVE SIGNAL
OBSERVATION FAN RUNS
FAN VENTURI
OBSERVATION PUMP RUNS - CH LED
PCB - CT1 (CONTROL PCB)
LOCKOUT RESET INVESTIGATION
CABLE - PCB
LOCKOUT RESET INVESTIGATION
PCB - CT1 (CONTROL PCB)
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH
GAS INLET PRESSURE
OBSERVATION FAN RUNS
THERMOSTAT - REGULATION
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH
ELECTRODE - DETECTION
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH
INJECTOR - BURNER
FUSE INVESTIGATION - MAINS
THERMOSTAT - OVERHEAT
FUSE INVESTIGATION - APPLIANCE
THERMOSTAT - OVERHEAT
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH
CABLE (DETECTION LEAD)
OBSERVATION FAN RUNS - FAN
CABLE - FAN/AIR PRESSURE SWITCH
OBSERVATION BURNER IGNITES AND ESTABLISHES - BAFFLES
EXCHANGER - MAIN (FLUEWAYS)
OPERATION CH - SHUTS DOWN THEN BOILER GOES TO LOCKOUT
RETURN MANIFOLD (INTERNAL BYPASS)
OBSERVATION BURNER IGNITES AND ESTABLISHES - SPARKING NO IGNITION
GAS INLET PRESSURE
OBSERVATION BURNER IGNITES AND ESTABLISHES - SPARKING NO IGNITION
THERMOSTAT - OVERHEAT
OBSERVATION BURNER IGNITES AND ESTABLISHES - SPARKING NO IGNITION
PCB - CB3FF102MX (IGNITION PCB)
OBSERVATION PUMP RUNS - SUPPLY TO EXT
CABLE - PCB TO TERMINAL BOARD
OPERATION CH - UP TO TEMP RADS COOL
RETURN MANIFOLD (INTERNAL BYPASS)
FUSE INVESTIGATION - MODUREG
GAS VALVE
FUSE INVESTIGATION - MODUREG MAINS
GAS VALVE
OBSERVATION BURNER IGNITES AND ESTABLISHES - NO SPARKING NO LOCKOUT
PIPE SILICONE - POSITIVE SIGNAL
PRESSURE BURNER MAXIMUM AND MINIMUM - MINIMUM WRONG
GAS INLET PRESSURE
PRESSURE BURNER MAXIMUM AND MINIMUM
GAS INLET PRESSURE
PRESSURE BURNER MAX AND MIN
THERMOSTAT - REGULATION
CH OPERATION - RUNS BUT RADS COOL
THERMOSTAT - REGULATION
PRESSURE BURNER MAX AND MIN
GAS VALVE
OBSERVATION RUN BOILER TO TEMPERATURE
THERMOSTAT - REGULATION (FITMENT)
OBSERVATION RUN BOILER TO TEMPERATURE
THERMOSTAT - REGULATION
OBSERVATION RUN BOILER TO TEMPERATURE (LOW RATE)
THERMOSTAT - REGULATION (FITMENT)
OBSERVATION BURNER IGNITES AND ESTABLISHES - NO SPARKING NO LOCKOUT
SWITCH - AIR PRESSURE
OBSERVATION BURNER IGNITES AND ESTABLISHES - NO SPARKING NO LOCKOUT
CABLE - FAN/AIR PRESSURE SWITCH
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT CROSSLIGHT
INJECTOR - BURNER
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT CROSSLIGHT
GAS INLET PRESSURE
CROSS LIGHTING
THERMOSTAT - REGULATION
CROSS LIGHTING
GAS VALVE
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH
PCB - CT1 (CONTROL PCB)
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH
CABLE - TWO STAGE THERMOSTAT
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH
CABLE - MODULATOR
CROSS LIGHTING
GAS VALVE ADJUSTMENT
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH
GAS VALVE ADJUSTMENT
PRESSURE BURNER MAX AND MIN
GAS VALVE ADJUSTMENT (MAX/MIN)
PRESSURE BURNER MAX AND MIN - MIN
GAS VALVE ADJUSTMENT (MAX/MIN)
OBSERVATION BURNER IGNITES AND ESTABLISHES - NO SPARKING THEN LOCKOUT
ELECTRODE - IGNITION
OBSERVATION BURNER IGNITES AND ESTABLISHES - NO SPARKING THEN LOCKOUT
GENERATOR - SPARK
OBSERVATION BOILER STANDBY - INTERNAL FUSE
Z REDIRECT
OBSERVATION BURNER IGNITES AND ESTABLISHES - SPARKING NO IGNITION
INJECTOR - BURNER
OBSERVATION BOILER STANDBY
PCB - CT1 (CONTROL PCB)
OPERATION CH - NOISY
EXCHANGER - MAIN (WATERWAYS)
OBSERVATION BOILER STANDBY - FIRING NO DEMAND
PCB - CT1 (CONTROL PCB)
FUSE INVESTIGATION - APPLIANCE
CABLE - PUMP
FUSE INVESTIGATION - MAINS
CABLE - PUMP
NO APPARENT FAULT
FUSE FURTHER INVESTIGATION (MAINS)
OBSERVATION FAN RUNS
PCB - CT1 (CONTROL PCB)
OBSERVATION PUMP RUNS
PCB - CT1 (CONTROL PCB)
OBSERVATION PUMP RUNS - NO VOLTAGE TO CONTROL PCB
PCB - CB3FF102MX (IGNITION PCB)
OBSERVATION PUMP RUNS - NO VOLTAGE TO IGN
PCB - CT1 (CONTROL PCB)
OPERATION CH - SHUTS DOWN TOO EARLY
PCB - CT1 (CONTROL PCB)
OPERATION CH
PIPE - EXPANSION VESSEL
FUSE INVESTIGATION - MAINS
CABLE - FAN/AIR PRESSURE SWITCH
FUSE INVESTIGATION - APPLIANCE
CABLE - FAN/AIR PRESSURE SWITCH
OPERATION CH - SHUTS DOWN THEN BOILER GOES TO LOCKOUT
PCB - CT1 (CONTROL PCB)
OBSERVATION FAN RUNS - APS
CABLE - FAN/AIR PRESSURE SWITCH
FUSE INVESTIGATION - MAINS
GENERATOR - SPARK
FUSE INVESTIGATION - APPLIANCE
GENERATOR - SPARK
NO POWER INVESTIGATION
Z REDIRECT
OBSERVATION BOILER STANDBY - MAINS FUSE
Z REDIRECT
NO APPARENT FAULT
FUSE FURTHER INVESTIGATION (APPLIANCE)
OBSERVATION FAN RUNS
SWITCH - AIR PRESSURE
LOCKOUT RESET INVESTIGATION
PCB - CB3FF102MX (IGNITION PCB)
OBSERVATION FAN RUNS
CABLE - TWO STAGE THERMOSTAT
FUSE INVESTIGATION - MAINS
CABLE (OVERHEAT)
FUSE INVESTIGATION - APPLIANCE
CABLE (OVERHEAT)
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH
PCB - CB3FF102MX (IGNITION PCB)
OBSERVATION PUMP RUNS
GAUGE - PRESSURE
OBSERVATION PUMP RUNS
SYSTEM PRESSURE
OPERATION CH - RUNS BUT RADS COOL
GAUGE - PRESSURE
OPERATION CH - UP TO TEMP RADS COOL
SYSTEM PRESSURE
OPERATION CH - NOISY
GAUGE - PRESSURE
OBSERVATION FAN RUNS
PCB - CB3FF102MX (IGNITION PCB)
OPERATION CH - NOISY
SYSTEM PRESSURE
OPERATION CH - UP TO TEMP RADS COOL
GAUGE - PRESSURE
OPERATION CH - RUNS BUT RADS COOL
SYSTEM PRESSURE
OPERATION CH - SHUTS DOWN TOO EARLY
GAUGE - PRESSURE
OPERATION CH - SHUTS DOWN TOO EARLY
SYSTEM PRESSURE
OPERATION CH - SHUTS DOWN THEN BOILER GOES TO LOCKOUT - INTERNAL BYPASS
PCB - CT1 (CONTROL PCB)
OPERATION CH - RUNS BUT RADS COOL CANT GAS RATE
INJECTOR - BURNER
OBSERVATION BURNER IGNITES AND ESTABLISHES - SPARKING NO IGNITION
GENERATOR - SPARK
OBSERVATION BURNER IGNITES AND ESTABLISHES - SPARKING NO IGNITION
GAS VALVE ADJUSTMENT
OBSERVATION PUMP RUNS - NO VOLTAGE TO EXT CONTROLS
PCB - CT1 (CONTROL PCB)
OPERATION CH - UP TO TEMP RADS COOL
SYSTEM RESTRICTION OR BLOCKAGE OR INTERNAL BYPASS
FUSE INVESTIGATION
CABLE - MODULATOR
FUSE INVESTIGATION MAINS
CABLE - MODULATOR
PRESSURE BURNER MAXIMUM AND MINIMUM
PCB - CT1 (CONTROL PCB)
PRESSURE BURNER MAX AND MIN
CABLE - TWO STAGE THERMOSTAT
PRESSURE BURNER MAX AND MIN
CABLE - MODULATOR
OBSERVATION RUN BOILER TO TEMPERATURE
PCB - CT1 (CONTROL PCB)
OBSERVATION RUN BOILER TO TEMPERATURE - LOW RATE
THERMOSTAT - REGULATION
OBSERVATION BURNER IGNITES AND ESTABLISHES - NO SPARKING NO LOCKOUT
PCB - CB3FF102MX (IGNITION PCB)
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT CROSSLIGHT
GAS VALVE SOFT LIGHT
CROSS LIGHTING
PCB - CT1 (CONTROL PCB)
CROSS LIGHTING
CABLE - TWO STAGE THERMOSTAT
CROSS LIGHTING
CABLE - MODULATOR
BURNER BAFFLES OUT OR LIFTS OFF
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
BOILER REACHES TEMPERATURE BUT RADIATORS REMAIN COOL
CHARACTERISTIC TEST FROM OPERATION CH
BOILER SHUTS DOWN BEFORE REACHING TEMPERATURE (NO LOCKOUT)
CHARACTERISTIC TEST FROM OPERATION CH
CH OPERATES SATISFACTORILY BUT BOILER IS NOISY
CHARACTERISTIC TEST FROM OPERATION CH
BOILER CONTINUES TO FIRE BUT RADIATORS ONLY GET WARM
CHARACTERISTIC TEST FROM OPERATION CH
DHW OPERATION UNSATISFACTORY
CHARACTERISTIC TEST FROM OPERATION DHW
BOILER DOES NOT RUN WITH DHW DEMAND
CHARACTERISTIC TEST FROM OPERATION DHW
BURNER SHUTS DOWN THEN BOILER GOES TO LOCKOUT
CHARACTERISTIC TEST FROM OPERATION CH
EXCESSIVE SYSTEM PRESSURE RISE
CHARACTERISTIC TEST FROM OPERATION CH
PUMP RUNS OR BOILER FIRES WITH NO DEMAND
CHARACTERISTIC TEST FROM OBSERVATION BOILER STANDBY
BURNER NOT CROSS LIGHTING PROPERLY
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
SYSTEM PRESSURE OK BUT GAUGE DOES NOT RESPOND TO INCREASE
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE OK BUT GAUGE DOES NOT RESPOND TO INCREASE
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE OK BUT GAUGE DOES NOT RESPOND TO INCREASE
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE OK BUT GAUGE DOES NOT RESPOND TO INCREASE
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE OK BUT GAUGE DOES NOT RESPOND TO INCREASE
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
NO SPARKING SEEN THEN BOILER GOES TO LOCKOUT
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
NO SPARKING SEEN BUT BOILER DOES NOT LOCK OUT
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
POWER LED DOES NOT ILLUMINATE
CHARACTERISTIC TEST FROM OBSERVATION BOILER STANDBY
SPARKING PRESENT BUT BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
MAXIMUM PRESSURE WRONG BUT MINIMUM PRESSURE IS CORRECT
CHARACTERISTIC TEST FROM PRESSURE BURNER MAX AND MIN
MINIMUM PRESSURE INCORRECT
CHARACTERISTIC TEST FROM PRESSURE BURNER MAX AND MIN
BOILER DOES NOT SWITCH TO MINIMUM RATE
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER TO TEMPERATURE
BOILER TEMPERATURE EXCEEDS 85°C BUT BOILER CONTINUES TO FIRE
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER TO TEMPERATURE
BURNER IGNITES SMOOTHLY BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
16/01/2020 09:12:02 1912_3_50_1 06/02/2020 09:54:33
27/01/2020 07:00:49
RESISTANCE THERMOSTAT (LOW FLAME)
{GAINPCBACS}
DISCONNECT WHITE LEADS AT THE THERMOSTAT
RESISTANCE GAS VALVE MODUREG
REMOVE CONNECTOR FROM GAS VALVE MODUREG
VOLTAGE SPARK GENERATOR AT PCB
{GAINPCBACS}
FUSE FURTHER INVESTIGATION (INTERNAL)
THE INFORMATION PROV
RESISTANCE MAINS FUSE
REMOVE FUSE FROM FUSED SPUR
RESISTANCE GAS VALVE
UNPLUG HARNESS / SPARK GENERATOR FROM THE GAS VALVE
RESISTANCE PUMP
REMOVE PUMP PLUG
RESISTANCE GAS VALVE
UNPLUG HARNESS / SPARK GENERATOR FROM THE GAS VALVE
RESISTANCE PUMP
REMOVE PUMP PLUG
RESISTANCE HARNESS PCB TO PCB
DISCONNECT PCB TO PCB HARNESS FROM CN104 ON THE CONTROL PCB AND CN100 ON THE IGNITION PCB
RESISTANCE HARNESS PCB TO PCB
DISCONNECT PCB TO PCB HARNESS FROM CN104 ON THE CONTROL PCB AND CN100 ON THE IGNITION PCB
RESISTANCE FAN (FUSE INVESTIGATION)
DISCONNECT LEADS FROM FAN (TAKE CARE NOT TO DAMAGE SPADES)
RESISTANCE FAN (FUSE INVESTIGATION)
DISCONNECT LEADS FROM FAN (TAKE CARE NOT TO DAMAGE SPADES)
VOLTAGE FAN AT FAN
REMOVE COMBUSTION CASE
RESISTANCE APS (N/C)
DISCONNECT LEADS AT THE COMMON (C) AND NORMALLY CLOSED (N/C) TERMINALS ON THE AIR PRESSURE SWITCH
RESISTANCE APS AND HARNESS (N/C)
{GAINPCBACS}
DISC
FUSE FURTHER INVESTIGATION (MAINS)
THE INFORMATION PROV
RESISTANCE HARNESS PCB TO PCB
DISCONNECT PCB TO PCB HARNESS FROM CN104 ON THE CONTROL PCB AND CN100 ON THE IGNITION PCB
RESISTANCE THERMOSTAT
{GAINPCBACS}
DISCONNECT GREY LEADS AT THE THERMOSTAT
PRESSURE GAS INLET
ATTACH A PRESSURE GA
RESISTANCE OVERHEAT THERMOSTAT (INVESTIGATION)
DISCONNECT LEADS FROM OVERHEAT THERMOSTAT
RESISTANCE OVERHEAT THERMOSTAT (INVESTIGATION)
DISCONNECT LEADS FROM OVERHEAT THERMOSTAT
INSPECTION INTERNAL BYPASS
DRAIN BOILER PRIMARY CIRCUIT
RESISTANCE GAS VALVE AND HARNESS
{GAINPCBACS}
DISCONNECT CN102 FROM THE IGNITION PCB
RESISTANCE OVERHEAT THERMOSTAT AND HARNESS
DISCONNECT INLINE CO
RESISTANCE OVERHEAT THERMOSTAT
DISCONNECT ONE LEAD FROM OVERHEAT THERMOSTAT
OBSERVATION HOW ARE EXTERNAL CONTROLS WIRED
GAIN ACCESS TO BOILER TERMINAL BLOCK
RESISTANCE HARNESS EXTERNAL CONTROLS
DISCONNECT CN100 FROM THE CONTROL PCB
RESISTANCE GAS VALVE MODUREG
REMOVE CONNECTOR FROM GAS VALVE MODUREG
RESISTANCE GAS VALVE MODUREG
REMOVE CONNECTOR FROM GAS VALVE MODUREG
RESISTANCE THERMOSTAT AND HARNESS (LOW FLAME)
DISCONNECT CN101 FROM THE CONTROL PCB
RESISTANCE THERMOSTAT (LOW FLAME)
{GAINPCBACS}
DISCONNECT WHITE LEADS AT THE THERMOSTAT
RESISTANCE GAS VALVE MODUREG
REMOVE CONNECTOR FROM GAS VALVE MODUREG
PRESSURE GAS INLET
ATTACH A PRESSURE GA
RESISTANCE THERMOSTAT AND HARNESS (LOW FLAME)
DISCONNECT CN101 FROM THE CONTROL PCB
RESISTANCE THERMOSTAT (LOW FLAME)
{GAINPCBACS}
DISCONNECT WHITE LEADS AT THE THERMOSTAT
RESISTANCE GAS VALVE MODUREG
REMOVE CONNECTOR FROM GAS VALVE MODUREG
RESISTANCE THERMOSTAT AND HARNESS (LOW FLAME)
DISCONNECT CN101 FROM THE CONTROL PCB
VOLTAGE MAINS IN AT PCB
{GAINPCBACS}
PRESSURE GAS INLET
ATTACH A PRESSURE GA
RESISTANCE INTERNAL FUSE
GAIN ACCESS TO BOILER TERMINAL BLOCK
REMOVE THE INTERNAL FUSE AND HOLDER FROM THE TERMINAL BLOCK
PRESSURE BURNER
ATTACH A PRESSURE GAUGE TO THE BURNER PRESSURE TEST POINT
INSPECTION BURNER
REMOVE ELECTRODE COVER (2X SCREWS) THEN
INNER COMBUSTION COVER (5X SCREWS)
INSPECTION HEAT EXCHANGER
REMOVE ELECTRODE COVER (2X SCREWS) THEN INNER COMBUSTION COVER (5X SCREWS)
OBSERVATION DISCONNECT FROST STAT
DISCONNECT PLUG ON FROST THERMOSTAT AND MAKE SAFE
VOLTAGE EXTERNAL CONTROLS (NO DEMAND)
GAIN ACCESS TO BOILER TERMINAL BLOCK
RESISTANCE FROST STAT HARNESS
DISCONNECT PLUG MARKED CN102 ON THE CONTROL PCB
RESISTANCE GAS VALVE AND HARNESS
{GAINPCBACS}
DISCONNECT CN102 FROM THE IGNITION PCB
RESISTANCE PUMP AND HARNESS
DISCONNECT CN102 FROM THE CONTROL PCB
VOLTAGE EXTERNAL CONTROLS AT TERMINAL BLOCK
GAIN ACCESS TO BOILER TERMINAL BLOCK
RESISTANCE GAS VALVE AND HARNESS
{GAINPCBACS}
DISCONNECT CN102 FROM THE IGNITION PCB
RESISTANCE PUMP AND HARNESS
DISCONNECT CN102 FROM THE CONTROL PCB
RESISTANCE WATER PRESSURE SWITCH
DISCONNECT PLUG FROM
RESISTANCE WATER PRESSURE SWITCH AND HARNESS
ENSURE PLUG HAS BEEN
RESISTANCE HARNESS EXTERNAL CONTROLS
DISCONNECT CN100 FROM THE CONTROL PCB
RESISTANCE HARNESS PCB TO PCB
DISCONNECT PCB TO PCB HARNESS FROM CN104 ON THE CONTROL PCB AND CN100 ON THE IGNITION PCB
RESISTANCE THERMOSTAT
{GAINPCBACS}
DISCONNECT GREY LEADS AT THE THERMOSTAT
VOLTAGE PUMP AT PCB
{GAINPCBACS}
PRESSURE EXPANSION VESSEL
DRAIN BOILER'S PRIMARY CIRCUIT
ATTACH FOOT PUMP TO SCHRADER VALVE ON EXPANSION VESSEL
RESISTANCE FAN AND HARNESS (FUSE INVESTIGATION)
{GAINPCBACS}
DISCONNECT CN200 FROM THE IGNITION PCB
RESISTANCE HARNESS PUMP
DISCONNECT CONNECTOR ON THE PUMP
RESISTANCE FAN AND HARNESS (FUSE INVESTIGATION)
{GAINPCBACS}
DISCONNECT CN200 FROM THE IGNITION PCB
RESISTANCE THERMOSTAT (AT TEMPERATURE)
{GAINPCBACS}
DISCONNECT WHITE LEADS AT THE THERMOSTAT
RESISTANCE OVERHEAT THERMOSTAT AND HARNESS (INVESTIGATION)
DISCONNECT INLINE CO
RESISTANCE OVERHEAT THERMOSTAT AND HARNESS (INVESTIGATION)
DISCONNECT INLINE CO
NO POWER FURTHER INVESTIGATION
THE INFORMATION PROV
RESISTANCE THERMOSTAT AND HARNESS
DISCONNECT CN101 FROM THE CONTROL PCB
INSPECTION FAN VENTURI
REMOVE FAN AND FAN VENTURI
PRESSURE BURNER (CROSS LIGHTING / ESTABLISH)
DISCONNECT COMPENSAT
INSPECTION DETECTION ELECTRODE AND LEAD
REMOVE ELECTRODE COV
INSPECTION BURNER
REMOVE ELECTRODE COVER (2X SCREWS) THEN
INNER COMBUSTION COVER (5X SCREWS)
INSPECTION INJECTORS
REMOVE BURNER ASSEMBLY
RESISTANCE HARNESS DETECTION LEAD
{GAINPCBACS}
DISCONNECT INLINE CONNECTOR FOR FLAME DETECTION ELECTRODE
RESISTANCE HARNESS FAN
DISCONNECT CN200 FROM THE IGNITION PCB
INSPECTION HEAT EXCHANGER
REMOVE ELECTRODE COVER (2X SCREWS) THEN INNER COMBUSTION COVER (5X SCREWS)
INSPECTION BURNER
REMOVE ELECTRODE COVER (2X SCREWS) THEN
INNER COMBUSTION COVER (5X SCREWS)
OBSERVATION SPARKING AT SPARK GENERATOR
DISCONNECT LEADS FRO
INSPECTION BURNER
REMOVE ELECTRODE COVER (2X SCREWS) THEN
INNER COMBUSTION COVER (5X SCREWS)
PRESSURE GAS INLET
ATTACH A PRESSURE GA
DIFFERENTIAL AIR PRESSURE SWITCH
ATTACH BOTH +VE AND
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
RESISTANCE GAS VALVE
UNPLUG HARNESS / SPARK GENERATOR FROM THE GAS VALVE
RESISTANCE APS WITH KIT
DISCONNECT WIRES AND
VOLTAGE SUPPLY TO EXTERNAL CONTROLS AT TERMINAL BLOCK
GAIN ACCESS TO BOILER TERMINAL BLOCK
RESISTANCE GAS VALVE MODUREG AND HARNESS
DISCONNECT CN102 FROM THE CONTROL PCB
INSPECTION FAN VENTURI
REMOVE FAN AND FAN VENTURI
RESISTANCE GAS VALVE MODUREG AND HARNESS
DISCONNECT CN102 FROM THE CONTROL PCB
PRESSURE GAS INLET
ATTACH A PRESSURE GA
PRESSURE GAS INLET
ATTACH A PRESSURE GA
RESISTANCE GAS VALVE MODUREG AND HARNESS
DISCONNECT CN102 FROM THE CONTROL PCB
VOLTAGE MAINS OUT AT TERMINAL BLOCK
GAIN ACCESS TO BOILER TERMINAL BLOCK
VOLTAGE GAS VALVE MODUREG
{GAINPCBACS}
ENSURE BOILER IS COOL
PRESSURE BURNER (CH COOL)
ATTACH A PRESSURE GAUGE TO THE BURNER PRESSURE TEST POINT
RESISTANCE THERMOSTAT (AT TEMPERATURE)
{GAINPCBACS}
DISCONNECT WHITE LEADS AT THE THERMOSTAT
RESISTANCE APS AND HARNESS WITH KIT
{GAINPCBACS}
REFI
PRESSURE BURNER (CROSS LIGHTING / ESTABLISH)
DISCONNECT COMPENSAT
INSPECTION BURNER
REMOVE ELECTRODE COVER (2X SCREWS) THEN
INNER COMBUSTION COVER (5X SCREWS)
INSPECTION INJECTORS
REMOVE BURNER ASSEMBLY
ADJUSTMENT GAS VALVE SOFT LIGHT PRESSURE
REMOVE DUST CAP FROM
VOLTAGE GAS VALVE MODUREG (CROSS LIGHTING / ESTABLISH)
{GAINPCBACS}
ENSURE BOILER IS COOL
RESISTANCE GAS VALVE MODUREG AND HARNESS
DISCONNECT CN102 FROM THE CONTROL PCB
VOLTAGE GAS VALVE MODUREG (CROSS LIGHTING / ESTABLISH)
{GAINPCBACS}
ENSURE BOILER IS COOL
RESISTANCE GAS VALVE MODUREG AND HARNESS
DISCONNECT CN102 FROM THE CONTROL PCB
System Information
- Total Tests: 350
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control