XSol Diagnostic System

Interactive Test Sequence Navigator

Welcome to the XSol Diagnostic System

This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.

Start Diagnostic Sequence

or choose a specific test below:

POTTERTON PUMA 80E SIT

GLOBALLY REPLACED

Next: &18, *

PUMP OVERRUN

BOILER SWITCH IN ON

Next: &nff, !f19

CH MODULATION

CENTRAL HEATING SWIT

Next: &1, f123

CH FAN

CENTRAL HEATING SWITCH IN CONSTANT POSITION
BOILER SWITCH IN ON POSITION
ENSURE BOILER IS COOL

Next: &417, f114

DHW WATER PUMP RUNNING

BOILER SWITCH IN ON

Next: &170, f98

RESET LOCKOUT

BOILER SWITCH ON

Next: &319, f74

DHW FAN

BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION

Next: &149, f45

DHW DEMAND LED ON

{GAINPCBACS}
BOIL

Next: &236, f36

FROST THERMOSTAT

{GAINPCBACS}
CENTRAL HEATING SWITCH OFF
DISCONNECT PLUG PL1

Next: &13, !f34

LOW SYSTEM PRESSURE LED

BOILER SWITCH IN STANDBY POSITION
CENTRAL HEATING SWITCH IN OFF(CENTRAL) POSITION

Next: &14, f29

MAINS LED

BOILER SWITCH IN STANDBY POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION

Next: &15, f370

POTTERTON PUMA 80E SIT

G.C. NUMBER 47 590 1

Next: &16, !f20

DHW SPARKING

BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF(CENTRAL) POSITION

Next: &10, f150

DHW BURNER PRESSURE MINIMUM

ATTACH PRESSURE GAUG

Next: &172, f246

DHW BURNER PRESSURE MAXIMUM

ATTACH PRESSURE GAUG

Next: &331, f250

HOT WATER OPERATION

BOILER SWITCH IN ON

Next: &4, ?206, ?208

DHW FLAME LED

BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION

Next: &7, f225

DHW DEMAND LED OFF

BOILER SWITCH IN STA

Next: &12, f237

DHW BURNER IGNITES

BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION

Next: &224, f320

DHW MODULATION

ATTACH PRESSURE GAUG

Next: &205, ?332, ?334

FUSE FURTHER INVESTIGATION

Next: &nff, f384

CENTRAL HEATING

CENTRAL HEATING SWITCH IN CONSTANT POSITION
BOILER SWITCH IN ON POSITION

Next: &3, ?408, ?410, ?412

OBSERVATION CH FULL RATE

ATTACH PRESSURE GAUG

Next: &407, ?418, ?420, ?426

CH FAN

CH SWITCH

Next: End

CH SWITCH

MODULATION BOARD

Next: End

BOILER SWITCH

MODULATION BOARD

Next: End

CH MODULATION

CH SENSOR

Next: End

DHW FAN

DHW SENSOR

Next: End

DHW SPARKING

SPARK ELECTRODE LEAD

Next: End

DHW SPARKING

FULL SEQUENCE BOARD CABLE

Next: End

DHW SPARKING

AIR PRESSURE SWITCH

Next: End

DHW SPARKING

AIR PRESSURE TUBE

Next: End

NO SPARKING

FAN VENTURI

Next: End

DHW SPARKING

FLUE

Next: End

NO SPARKING

FAN

Next: End

PUMP OVERRUN

MODULATION BOARD

Next: End

ELECTRICAL SAFETY CHECKS

ELECTRICAL SAFETY CHECKS

Next: End

DHW FLAME LED

DISPLAY BOARD

Next: End

DHW FLAME LED

INLET PRESSURE

Next: End

DHW FLAME LED

FLAME SENSE ELECTRODE ALIGNMENT

Next: End

DHW FLAME LED

FLAME SENSE ELECTRODE

Next: End

DHW FLAME LED

FLAME SENSE ELECTRODE LEAD

Next: End

DHW DEMAND LED OFF

DHW FLOW SWITCH

Next: End

DHW DEMAND LED OFF

DHW DEMAND MICROSWITCH

Next: End

DHW DEMAND LED ON

DHW FLOW RATE

Next: End

DHW BURNER PRESSURE MIN

INLET PRESSURE

Next: End

DHW BURNER PRESSURE

DHW SENSOR

Next: End

DHW BURNER PRESSURE

DISPLAY BOARD

Next: End

DHW BURNER PRESSURE MAX

INLET PRESSURE

Next: End

LOW SYSTEM PRESSURE LED

SYSTEM PRESSURE

Next: End

LOW SYSTEM PRESSURE LED

WATER PRESSURE SWITCH

Next: End

DHW BURNER IGNITES

INLET PRESSURE

Next: End

DHW BURNER IGNITES

OVERHEAT THERMOSTAT

Next: End

DHW BURNER IGNITES

SPARK ELECTRODE ALIGNMENT

Next: End

DHW BURNER IGNITES

GAS VALVE (SOLENOID)

Next: End

BURNER CYCLES ON AND OFF

AIR PRESSURE SWITCH

Next: End

BOILER CYCLES ON AND OFF

DHW LIMIT THERMOSTAT

Next: End

FROST THERMOSTAT

FROST THERMOSTAT

Next: End

DHW BURNER CYCLING ON AND OFF

FAN VENTURI

Next: End

DHW BURNER CYLING ON AND OFF

AIR PRESSURE TUBE

Next: End

DHW BURNER CYCLING ON AND OFF

HEAT EXCHANGER

Next: End

DHW BURNER MODUALTION

DHW SENSOR

Next: End

DHW BURNER MODULATION

DISPLAY BOARD

Next: End

FUSE F1

MODULATION BOARD

Next: End

MODULATION BOARD VOLTAGE

MODULATION BOARD

Next: End

MAINS LED

DISPLAY BOARD CABLE

Next: End

FUSE INVESTIGATION

WATER PUMP

Next: End

FUSE INVESTIGATION

FAN

Next: End

FUSE INVESTIGATION

TRANSFORMER

Next: End

MAINS LED

FUSE F1 (2 AMP)

Next: End

FUSE INVESTIGATION

GAS VALVE

Next: End

FUSE INVESTIGATION

SOLENOID OPERATOR - SIT

Next: End

CENTRAL HEATING

DIVERTER VALVE

Next: End

CH FULL RATE - SHUTTING DOWN

CH SENSOR

Next: End

CH FULL RATE - STAYING ON LOW

CH SENSOR

Next: End

DHW DEMAND LED ON

DHW DEMAND MICROSWITCH

Next: End

DHW BURNER MODULATION - CYCLING

DHW SENSOR

Next: End

CH FULL RATE

WATER PUMP

Next: End

MAINS LED

MAINS FUSE

Next: End

FUSE INVESTIGATION

WATER PRESSURE SWITCH

Next: End

OBSERVATION CH FULL RATE

WAX SENSOR

Next: End

BOILER SWITCH (POWER IN)

MODULATION BOARD

Next: End

DHW FAN

AIR PRESSURE SWITCH

Next: End

DHW FAN

DHW LIMIT THERMOSTAT

Next: End

DHW FAN

DISPLAY BOARD CABLE

Next: End

RESET LOCKOUT

DISPLAY BOARD

Next: End

DHW WATER PUMP RUNNING

MODULATION BOARD

Next: End

DHW WATER PUMP RUNNING

WATER PUMP

Next: End

CH FAN

Next: End

CH FAN

CH SENSOR

Next: End

CH MODULATION

DISPLAY BOARD

Next: End

DHW SPARKING

SPARK ELECTRODE

Next: End

DHW SPARKING

IGNITION CONTROL BOARD

Next: End

HOT WATER OPERATION

HEAT EXCHANGER

Next: End

HOT WATER OPERATION

DHW FLOW LIMITER

Next: End

DHW FLAME LED

IGNITION CONTROL BOARD

Next: End

DHW DEMAND LED OFF

MODULATION BOARD

Next: End

DHW DEMAND LED ON

DHW FLOW SWITCH

Next: End

MINIMUM SET WRONG

GAS VALVE

Next: End

DHW BURNER PRESSURE

GAS VALVE

Next: End

DHW BURNER PRESSURE

MODULATION BOARD

Next: End

DHW BURNER IGNITES

MODULATION BOARD

Next: End

DHW BURNER IGNITES

GAS VALVE

Next: End

LOW SYSTEM PRESSURE LED

MODULATION BOARD

Next: End

DHW BURNER CYCLING ON AND OFF

IGNITION CONTROL BOARD

Next: End

DHW BURNER MODULATION

GAS VALVE

Next: End

DHW BURNER MODULATION

MODULATION BOARD

Next: End

MAINS LED

TRANSFORMER

Next: End

MAINS LED

DISPLAY BOARD

Next: End

F1 FUSE INVESTIGATION

Z REDIRECT

Next: End

CENTRAL HEATING

HEAT EXCHANGER

Next: End

CENTRAL HEATING

Next: End

CENTRAL HEATING

DRIPPING TAP OR LEAKING DHW SUPPLY

Next: End

CH FULL RATE

MODULATION BOARD POT

Next: End

CH FULL RATE

MODULATION BOARD

Next: End

DHW DEMAND LED ON

MODULATION BOARD

Next: End

MAINS LED

Next: End

MAINS FUSE FURTHER INVESTIGATION

Z REDIRECT

Next: End

FUSE INVESTIGATION

FUSE BLOWN

Next: End

CH FULL RATE

Next: End

DHW FAN

BOILER SWITCH

Next: End

DHW FAN

FAN

Next: End

FAN VOLTAGE

MODULATION BOARD

Next: End

RESET LOCKOUT

IGNITION CONTROL BOARD

Next: End

MARGINAL INCREASE IN FLOW RATE

CHARACTERISTIC TEST FROM HOT WATER OPERATION

Next: !p207

NO INCREASE IN FLOW RATE

CHARACTERISTIC TEST FROM HOT WATER OPERATION

Next: !p209

BURNER DOES NOT MODULATE

CHARACTERISTIC TEST FROM DHW MODULATION

Next: p333

BURNER REPEATEDLY CUTS OUT BEFORE MODULATION TAKES PLACE

CHARACTERISTIC TEST FROM DHW MODULATION

Next: p335

RADIATORS COLD

CHARACTERISTIC TEST FROM CENTRAL HEATING

Next: p409

NOISY OPERATION, WARM RADIATORS

CHARACTERISTIC TEST FROM CENTRAL HEATING

Next: !p411

QUIET OPERATION, WARM RADIATORS

CHARACTERISTIC TEST FROM CENTRAL HEATING

Next: !p413

BOILER REMAINS ON LOW RATE

CHARACTERISTIC TEST FROM OBSERVATION CH FULL RATE

Next: p419

BOILER SHUTS DOWN BEFORE IT CAN RUN FOR 2 MINUTES

CHARACTERISTIC TEST FROM OBSERVATION CH FULL RATE

Next: p441

BOILER INCREASES TO MAXIMUM RATE IMMEDIATELY

CHARACTERISTIC TEST FROM OBSERVATION CH FULL RATE

Next: !p427

ROOM THERMOSTAT

{GAINPCBACS}
CENT

Next: p116, f115

CH SWITCH

{GAINPCBACS}
CENTRAL HEATING SWITCH IN CONSTANT POSITION

Next: p118, !f117

SPARK GENERATOR

REMOVE SPARK ELECTRO

Next: !p151, f152

SPARK ELECTRODE LEAD

Next: p153, !f154

LOCKOUT OCCURS

Next: p226, !f227

DHW FLOW SWITCH OPERATION

Next: p238, !f239

INLET PRESSURE

BOILER SWITCH IN ON

Next: !p247, !f248

INLET PRESSURE

BOILER SWITCH IN ON

Next: p278, !f293

DHW TEMPERATURE SENSOR

Next: p289, !f290

SYSTEM PRESSURE

Next: p31, !f30

INLET PRESSURE

BOILER SWITCH IN ON

Next: p321, !f322

OVERHEAT THERMOSTAT RESISTANCE

REMOVE WHITE WIRES FROM OVERHEAT THERMOSTAT

Next: !p325, !f326

DHW FLOW SWITCH

Next: p38, f37

DHW TEMPERATURE SENSOR

Next: p366, !f367

WATER FLOW CHECK

Next: !p244, !f245

TRANSFORMER VOLTAGE (24V)

{GAINPCBACS}
BOILER SWITCH IN ON POSITION

Next: p371, f372

FUSE F1

REMOVE FUSE F1 FROM MODULATION CONTROL BOARD

Next: p373, f394

RESISTANCE PUMP

DISCONNECT INLINE CONNECTOR FOR THE PUMP

Next: p385, !f390

FUSE FURTHER INVESTIGATION

Next: !p395, !f396

RESISTANCE MAINS FUSE

REMOVE FUSE FROM FUSED SPUR

Next: !p449, f448

FUSE FURTHER INVESTIGATION

Next: !p450, !f451

BOILER SWITCH (POWER OUT)

{GAINPCBACS}
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION

Next: p47, f46

BOILER SWITCH (POWER IN)

BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION

Next: !p49, !f48

AIR PRESSURE SWITCH - NO AIR

REMOVE ORANGE AND PURPLE LEADS FROM AIR PRESSURE SWITCH

Next: p53, !f52

LOCKOUT RESET SWITCH

Next: !p76, !f75

WATER PUMP VOLTAGE

BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN CONSTANT POSITION

Next: !p100, !f99

BOILER SWITCH

CENTRAL HEATING SWITCH IN CONSTANT POSITION
BOILER SWITCH IN ON POSITION

Next: !p122, !f121

ROOM THERMOSTAT (INPUT)

{GAINPCBACS}
CENT

Next: !p120, !f119

FULL SEQUENCE BOARD CABLE

VISUAL AND MECHANICAL CHECK OF CABLE AND CONNECTIONS

Next: p155, !f156

AIR PRESSURE SWITCH - AIR DETECT

DISCONNECT LEADS FRO

Next: p157, !f158

AIR PRESSURE SWITCH TUBES

Next: p159, !f160

INSPECTION FAN VENTURI

REMOVE THE FAN VENTURI, TOP OF HEAT EXCHANGER
AND SIDE OF FAN ASSEMBLY

Next: p165, !f162

FLUE INSPECTION

Next: !p163, !f164

INSPECTION FAN ASSEMBLY

REMOVE FAN ASSEMBLY FROM BOILER

Next: p161, !f169

INLET PRESSURE

BOILER SWITCH IN ON

Next: p228, !f229

FLAME SENSE ELECTRODE

Next: p232, !f233

FLAME SENSE ELECTRODE LEAD

Next: !p234, !f235

DHW MICROSWITCH

REMOVE BOTH ORANGE WIRES FROM DHW DEMAND MICROSWITCH

Next: !p240, !f241

GAS VALVE 3 VOLTAGE

BOILER SWITCH IN ON

Next: !p287, f288

DHW POTENTIOMETER

TURN / SET THE HOT WATER CONTROL (POTENTIOMETER) TO APPROXIMATELY MID POSITION

Next: !p291, !f292

WATER PRESSURE SWITCH

REMOVE BOTH YELLOW LEADS FROM WATER PRESSURE SWITCH

Next: !p33, !f32

GAS VALVE 1 & 2 VOLTAGE

{GAINPCBACS}
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION

Next: p323, f324

SPARK ELECTRODE ALIGNMENT

Next: p327, !f328

GAS VALVE 2 RESISTANCE

Next: !p329, !f330

MODUREG VOLTAGE

BOILER SWITCH IN ON

Next: !p359, f365

AIR PRESSURE SWITCH TEST

DISCONNECT LEADS FRO

Next: p336, !f337

DHW LIMIT THERMOSTAT

REMOVE PURPLE WIRES FROM DHW LIMIT THERMOSTAT

Next: p428, !f339

INSPECTION FAN VENTURI

REMOVE THE FAN VENTURI, TOP OF HEAT EXCHANGER
AND SIDE OF FAN ASSEMBLY

Next: p340, !f341

AIR PRESSURE SWITCH TUBES

Next: p342, !f343

INSPECTION FAN ASSEMBLY

REMOVE FAN ASSEMBLY FROM BOILER

Next: p344, !f345

HEAT EXCHANGER INSPECTION

Next: p346, !f347

FLUE INSPECTION

Next: !p348, !f349

DHW POTENTIOMETER

TURN / SET THE HOT WATER CONTROL (POTENTIOMETER) TO APPROXIMATELY MID POSITION

Next: !p368, !f369

MODULATION BOARD VOLTAGE

LOWER FRONT FASCIA PANEL

Next: p379, !f380

MAINS POWER SUPPLY

LOWER CONTROL PANEL (HINGED)

Next: p375, f397

TRANSFORMER INPUT (240 VOLTS)

Next: !p377, !f378

DISPLAY BOARD CABLE (POTENTIOMETERS)

VISUAL AND MECHANICAL SOUNDNESS CHECK OF THE CONNECTIONS

Next: !p381, !f382

DHW DEMAND MICROSWITCH

REMOVE BOTH ORANGE WIRES FROM DHW DEMAND MICROSWITCH
BOILER SWITCH IN STANDBY POSITION

Next: !p44, !f43

RESISTANCE FAN

DISCONNECT INLINE CONNECTOR FOR THE PUMP

Next: p386, !f391

RESISTANCE GAS VALVE OPERATING SOLENOID

REMOVE PLUG FROM THE

Next: p401, !f406

RESISTANCE TRANSFORMER

DISCONNECT CONNECTOR PL6 AT THE PCB

Next: p452, !f393

RESISTANCE GAS VALVE MOD AND SAFETY SOLENOIDS

DISCONNECT SPADE CONNECTORS FROM MODULATING SOLENOID
DISCONNECT PLUG FROM SAFETY SOLENOIDS

Next: p388, !f405

DIVERTER VALVE OPERATION

TURN OFF THE MAINS W

Next: !p416, !f415

DHW TEMPERATURE SENSOR

Next: p338, !f440

PUMP LIMPET TEST

Next: p421, !f445

RESISTANCE WATER PRESSURE SWITCH TO EARTH

REMOVE BOTH YELLOW LEADS FROM WATER PRESSURE SWITCH

Next: !p453, !f456

DIVERTER VALVE OPERATION

TURN OFF THE MAINS W

Next: !p458, !f459

FAN VOLTAGE

BOILER SWITCH ON

Next: !p51, f50

DHW LIMIT THERMOSTAT

REMOVE PURPLE WIRES FROM DHW LIMIT THERMOSTAT

Next: p55, !f54

DISPLAY BOARD CABLE (POTENTIOMETERS)

VISUAL AND MECHANICAL SOUNDNESS CHECK OF THE CONNECTIONS

Next: p57, !f56

DHW TEMPERATURE SENSOR

Next: !p59, !f148

System Information

  • Total Tests: 213
  • Sequence Logic: Decoded from encrypted .seq file
  • Navigation: Dynamic based on pass/fail results
  • Source: 4731307 GW SWIFTFLOW 100 SIT Control