GLOBALLY REPLACED
PUMP OVERRUN
BOILER SWITCH IN ON
CH MODULATION
CENTRAL HEATING SWIT
CH FAN
CENTRAL HEATING SWITCH IN CONSTANT POSITION
BOILER SWITCH IN ON POSITION
ENSURE BOILER IS COOL
DHW WATER PUMP RUNNING
BOILER SWITCH IN ON
RESET LOCKOUT
BOILER SWITCH ON
DHW FAN
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION
DHW DEMAND LED ON
{GAINPCBACS}
BOIL
FROST THERMOSTAT
{GAINPCBACS}
CENTRAL HEATING SWITCH OFF
DISCONNECT PLUG PL1
LOW SYSTEM PRESSURE LED
BOILER SWITCH IN STANDBY POSITION
CENTRAL HEATING SWITCH IN OFF(CENTRAL) POSITION
MAINS LED
BOILER SWITCH IN STANDBY POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION
POTTERTON PUMA 80E SIT
G.C. NUMBER 47 590 1
DHW SPARKING
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF(CENTRAL) POSITION
DHW BURNER PRESSURE MINIMUM
ATTACH PRESSURE GAUG
DHW BURNER PRESSURE MAXIMUM
ATTACH PRESSURE GAUG
HOT WATER OPERATION
BOILER SWITCH IN ON
DHW FLAME LED
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION
DHW DEMAND LED OFF
BOILER SWITCH IN STA
DHW BURNER IGNITES
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION
DHW MODULATION
ATTACH PRESSURE GAUG
CENTRAL HEATING
CENTRAL HEATING SWITCH IN CONSTANT POSITION
BOILER SWITCH IN ON POSITION
OBSERVATION CH FULL RATE
ATTACH PRESSURE GAUG
CH FAN
CH SWITCH
CH SWITCH
MODULATION BOARD
BOILER SWITCH
MODULATION BOARD
CH MODULATION
CH SENSOR
DHW FAN
DHW SENSOR
DHW SPARKING
SPARK ELECTRODE LEAD
DHW SPARKING
FULL SEQUENCE BOARD CABLE
DHW SPARKING
AIR PRESSURE SWITCH
DHW SPARKING
AIR PRESSURE TUBE
NO SPARKING
FAN VENTURI
DHW SPARKING
FLUE
NO SPARKING
FAN
PUMP OVERRUN
MODULATION BOARD
ELECTRICAL SAFETY CHECKS
ELECTRICAL SAFETY CHECKS
DHW FLAME LED
DISPLAY BOARD
DHW FLAME LED
INLET PRESSURE
DHW FLAME LED
FLAME SENSE ELECTRODE ALIGNMENT
DHW FLAME LED
FLAME SENSE ELECTRODE
DHW FLAME LED
FLAME SENSE ELECTRODE LEAD
DHW DEMAND LED OFF
DHW FLOW SWITCH
DHW DEMAND LED OFF
DHW DEMAND MICROSWITCH
DHW DEMAND LED ON
DHW FLOW RATE
DHW BURNER PRESSURE MIN
INLET PRESSURE
DHW BURNER PRESSURE
DHW SENSOR
DHW BURNER PRESSURE
DISPLAY BOARD
DHW BURNER PRESSURE MAX
INLET PRESSURE
LOW SYSTEM PRESSURE LED
SYSTEM PRESSURE
LOW SYSTEM PRESSURE LED
WATER PRESSURE SWITCH
DHW BURNER IGNITES
INLET PRESSURE
DHW BURNER IGNITES
OVERHEAT THERMOSTAT
DHW BURNER IGNITES
SPARK ELECTRODE ALIGNMENT
DHW BURNER IGNITES
GAS VALVE (SOLENOID)
BURNER CYCLES ON AND OFF
AIR PRESSURE SWITCH
BOILER CYCLES ON AND OFF
DHW LIMIT THERMOSTAT
FROST THERMOSTAT
FROST THERMOSTAT
DHW BURNER CYCLING ON AND OFF
FAN VENTURI
DHW BURNER CYLING ON AND OFF
AIR PRESSURE TUBE
DHW BURNER CYCLING ON AND OFF
HEAT EXCHANGER
DHW BURNER MODUALTION
DHW SENSOR
DHW BURNER MODULATION
DISPLAY BOARD
FUSE F1
MODULATION BOARD
MODULATION BOARD VOLTAGE
MODULATION BOARD
MAINS LED
DISPLAY BOARD CABLE
FUSE INVESTIGATION
WATER PUMP
FUSE INVESTIGATION
TRANSFORMER
MAINS LED
FUSE F1 (2 AMP)
FUSE INVESTIGATION
GAS VALVE
FUSE INVESTIGATION
SOLENOID OPERATOR - SIT
CENTRAL HEATING
DIVERTER VALVE
CH FULL RATE - SHUTTING DOWN
CH SENSOR
CH FULL RATE - STAYING ON LOW
CH SENSOR
DHW DEMAND LED ON
DHW DEMAND MICROSWITCH
DHW BURNER MODULATION - CYCLING
DHW SENSOR
CH FULL RATE
WATER PUMP
MAINS LED
MAINS FUSE
FUSE INVESTIGATION
WATER PRESSURE SWITCH
OBSERVATION CH FULL RATE
WAX SENSOR
BOILER SWITCH (POWER IN)
MODULATION BOARD
DHW FAN
AIR PRESSURE SWITCH
DHW FAN
DHW LIMIT THERMOSTAT
DHW FAN
DISPLAY BOARD CABLE
RESET LOCKOUT
DISPLAY BOARD
DHW WATER PUMP RUNNING
MODULATION BOARD
DHW WATER PUMP RUNNING
WATER PUMP
CH FAN
CH SENSOR
CH MODULATION
DISPLAY BOARD
DHW SPARKING
SPARK ELECTRODE
DHW SPARKING
IGNITION CONTROL BOARD
HOT WATER OPERATION
HEAT EXCHANGER
HOT WATER OPERATION
DHW FLOW LIMITER
DHW FLAME LED
IGNITION CONTROL BOARD
DHW DEMAND LED OFF
MODULATION BOARD
DHW DEMAND LED ON
DHW FLOW SWITCH
MINIMUM SET WRONG
GAS VALVE
DHW BURNER PRESSURE
GAS VALVE
DHW BURNER PRESSURE
MODULATION BOARD
DHW BURNER IGNITES
MODULATION BOARD
DHW BURNER IGNITES
GAS VALVE
LOW SYSTEM PRESSURE LED
MODULATION BOARD
DHW BURNER CYCLING ON AND OFF
IGNITION CONTROL BOARD
DHW BURNER MODULATION
GAS VALVE
DHW BURNER MODULATION
MODULATION BOARD
MAINS LED
TRANSFORMER
MAINS LED
DISPLAY BOARD
F1 FUSE INVESTIGATION
Z REDIRECT
CENTRAL HEATING
HEAT EXCHANGER
CENTRAL HEATING
DRIPPING TAP OR LEAKING DHW SUPPLY
CH FULL RATE
MODULATION BOARD POT
CH FULL RATE
MODULATION BOARD
DHW DEMAND LED ON
MODULATION BOARD
MAINS FUSE FURTHER INVESTIGATION
Z REDIRECT
FUSE INVESTIGATION
FUSE BLOWN
DHW FAN
BOILER SWITCH
DHW FAN
FAN
FAN VOLTAGE
MODULATION BOARD
RESET LOCKOUT
IGNITION CONTROL BOARD
MARGINAL INCREASE IN FLOW RATE
CHARACTERISTIC TEST FROM HOT WATER OPERATION
NO INCREASE IN FLOW RATE
CHARACTERISTIC TEST FROM HOT WATER OPERATION
BURNER DOES NOT MODULATE
CHARACTERISTIC TEST FROM DHW MODULATION
BURNER REPEATEDLY CUTS OUT BEFORE MODULATION TAKES PLACE
CHARACTERISTIC TEST FROM DHW MODULATION
RADIATORS COLD
CHARACTERISTIC TEST FROM CENTRAL HEATING
NOISY OPERATION, WARM RADIATORS
CHARACTERISTIC TEST FROM CENTRAL HEATING
QUIET OPERATION, WARM RADIATORS
CHARACTERISTIC TEST FROM CENTRAL HEATING
BOILER REMAINS ON LOW RATE
CHARACTERISTIC TEST FROM OBSERVATION CH FULL RATE
BOILER SHUTS DOWN BEFORE IT CAN RUN FOR 2 MINUTES
CHARACTERISTIC TEST FROM OBSERVATION CH FULL RATE
BOILER INCREASES TO MAXIMUM RATE IMMEDIATELY
CHARACTERISTIC TEST FROM OBSERVATION CH FULL RATE
18/07/2018 11:49:52 1807_1_50_1 20/07/2018 14:22:43
18/07/2018 14:33:45
ROOM THERMOSTAT
{GAINPCBACS}
CENT
CH SWITCH
{GAINPCBACS}
CENTRAL HEATING SWITCH IN CONSTANT POSITION
SPARK GENERATOR
REMOVE SPARK ELECTRO
INLET PRESSURE
BOILER SWITCH IN ON
INLET PRESSURE
BOILER SWITCH IN ON
INLET PRESSURE
BOILER SWITCH IN ON
OVERHEAT THERMOSTAT RESISTANCE
REMOVE WHITE WIRES FROM OVERHEAT THERMOSTAT
TRANSFORMER VOLTAGE (24V)
{GAINPCBACS}
BOILER SWITCH IN ON POSITION
FUSE F1
REMOVE FUSE F1 FROM MODULATION CONTROL BOARD
RESISTANCE PUMP
DISCONNECT INLINE CONNECTOR FOR THE PUMP
RESISTANCE MAINS FUSE
REMOVE FUSE FROM FUSED SPUR
BOILER SWITCH (POWER OUT)
{GAINPCBACS}
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION
BOILER SWITCH (POWER IN)
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION
AIR PRESSURE SWITCH - NO AIR
REMOVE ORANGE AND PURPLE LEADS FROM AIR PRESSURE SWITCH
WATER PUMP VOLTAGE
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN CONSTANT POSITION
BOILER SWITCH
CENTRAL HEATING SWITCH IN CONSTANT POSITION
BOILER SWITCH IN ON POSITION
ROOM THERMOSTAT (INPUT)
{GAINPCBACS}
CENT
FULL SEQUENCE BOARD CABLE
VISUAL AND MECHANICAL CHECK OF CABLE AND CONNECTIONS
AIR PRESSURE SWITCH - AIR DETECT
DISCONNECT LEADS FRO
INSPECTION FAN VENTURI
REMOVE THE FAN VENTURI, TOP OF HEAT EXCHANGER
AND SIDE OF FAN ASSEMBLY
INSPECTION FAN ASSEMBLY
REMOVE FAN ASSEMBLY FROM BOILER
INLET PRESSURE
BOILER SWITCH IN ON
DHW MICROSWITCH
REMOVE BOTH ORANGE WIRES FROM DHW DEMAND MICROSWITCH
GAS VALVE 3 VOLTAGE
BOILER SWITCH IN ON
DHW POTENTIOMETER
TURN / SET THE HOT WATER CONTROL (POTENTIOMETER) TO APPROXIMATELY MID POSITION
WATER PRESSURE SWITCH
REMOVE BOTH YELLOW LEADS FROM WATER PRESSURE SWITCH
GAS VALVE 1 & 2 VOLTAGE
{GAINPCBACS}
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION
MODUREG VOLTAGE
BOILER SWITCH IN ON
AIR PRESSURE SWITCH TEST
DISCONNECT LEADS FRO
DHW LIMIT THERMOSTAT
REMOVE PURPLE WIRES FROM DHW LIMIT THERMOSTAT
INSPECTION FAN VENTURI
REMOVE THE FAN VENTURI, TOP OF HEAT EXCHANGER
AND SIDE OF FAN ASSEMBLY
INSPECTION FAN ASSEMBLY
REMOVE FAN ASSEMBLY FROM BOILER
DHW POTENTIOMETER
TURN / SET THE HOT WATER CONTROL (POTENTIOMETER) TO APPROXIMATELY MID POSITION
MODULATION BOARD VOLTAGE
LOWER FRONT FASCIA PANEL
MAINS POWER SUPPLY
LOWER CONTROL PANEL (HINGED)
DISPLAY BOARD CABLE (POTENTIOMETERS)
VISUAL AND MECHANICAL SOUNDNESS CHECK OF THE CONNECTIONS
DHW DEMAND MICROSWITCH
REMOVE BOTH ORANGE WIRES FROM DHW DEMAND MICROSWITCH
BOILER SWITCH IN STANDBY POSITION
RESISTANCE FAN
DISCONNECT INLINE CONNECTOR FOR THE PUMP
RESISTANCE GAS VALVE OPERATING SOLENOID
REMOVE PLUG FROM THE
RESISTANCE TRANSFORMER
DISCONNECT CONNECTOR PL6 AT THE PCB
RESISTANCE GAS VALVE MOD AND SAFETY SOLENOIDS
DISCONNECT SPADE CONNECTORS FROM MODULATING SOLENOID
DISCONNECT PLUG FROM SAFETY SOLENOIDS
DIVERTER VALVE OPERATION
TURN OFF THE MAINS W
RESISTANCE WATER PRESSURE SWITCH TO EARTH
REMOVE BOTH YELLOW LEADS FROM WATER PRESSURE SWITCH
DIVERTER VALVE OPERATION
TURN OFF THE MAINS W
FAN VOLTAGE
BOILER SWITCH ON
DHW LIMIT THERMOSTAT
REMOVE PURPLE WIRES FROM DHW LIMIT THERMOSTAT
DISPLAY BOARD CABLE (POTENTIOMETERS)
VISUAL AND MECHANICAL SOUNDNESS CHECK OF THE CONNECTIONS