WORCESTER HIGHFLOW 400 BF LPG
G.C. NUMBER 47 311 2
COOLING FAN
{GAINPCBACS}
HEAT
CH SATISFIED
HEATING TEMPERATURE SELECTOR TO MID-RANGE
HOT WATER TEMPERATURE SELECTOR TO OFF
SYSTEM PRESSURE RISE
HEATING TEMPERATURE SELECTOR TO MAXIMUM
HOT WATER TEMPERATURE SELECTOR TO OFF
DHW OPERATION
HEATING TEMPERATURE
HEATBANK SATISFIED
PROGRAMMER OR SELECT
BURNER IGNITION (CH DEMAND)
HEATING TEMPERATURE SELECTOR TO MAXIMUM
HOT WATER TEMPERATURE SELECTOR TO OFF
DHW MAXIMUM PRESSURE
ATTACH U-GAUGE TO BU
BURNER IGNITION (HEATBANK)
HEATING TEMPERATURE
PUMP RUNS
HEATING TEMPERATURE
PILOT OPERATION
GAS ON
WORCESTER HIGHFLOW 400 BF LPG
G.C. NUMBER 47 311 2
DIVERTER VALVE OPERATION
HEATING TEMPERATURE SELECTOR TO MAXIMUM
HOT WATER TEMPERATURE SELECTOR TO OFF
CH OPERATION
HEATING TEMPERATURE SELECTOR TO MAXIMUM
HOT WATER TEMPERATURE SELECTOR TO OFF
PUMP OVERRUN
HEATING TEMPERATURE SELECTOR TO MAXIMUM
HOT WATER TEMPERATURE SELECTOR TO OFF
ROOM THERMOSTAT VOLTS IN
SELECTOR SWITCH / PROGRAMMER
CH CONTROL THERMOSTAT VOLTS OUT
FLOW SWITCH
DHW CONTROL THERMOSTAT (RESISTANCE
THERMOSTAT - RANCO K36P1333 (DHW STAT)
PRIMARY HEAT EXCHANGER
HEAT EXCHANGER - GIANNONI
BOILER SHUTS DOWN BEFORE DEMANDS ARE SATISFIED
THERMOSTAT - HEATBANK OVERHEAT
BOILER SHUTS DOWN BEFORE DEMAND IS SATISFIED
THERMOSTAT - RANCO K36P1333 (DHW STAT)
DHW DOES NOT REACH TEMPERATURE
BURNER INJECTOR
DHW RUNS COLD OR TAKES TOO LONG TO REFIRE
FLOW SWITCH
EXPANSION VESSEL
EXPANSION VESSEL
CH SATISFIED
THERMOSTAT - RANCO K36P1332 (CH STAT)
ELECTRICAL SAFETY CHECKS
ELECTRICAL SAFETY CHECKS
COOLING FAN VOLTAGE
KIT - PCB 400 REPLACEMENT
OVERHEAT THERMOSTAT (SAFETY TEMPERATURE LIMITER)
THERMOSTAT C/W LEAD ELMWOOD (OVERHEAT)
SYSTEM CHECKS
SYSTEM CHECKS
PILOT OP THERMOCOUPLE INTERRUPTOR CONS (2) FAIL
OVERHEAT THERMOSTAT (ECO CONNECTIONS)
SPARK ELECTRODE
ELECTRODE - IGNITION
BURNER IGNITION (CH DEMAND)
THERMOSTAT - RANCO K36P1332 (CH STAT)
CH PIPE NOT HEATING
FLOW SWITCH
CH PIPE DOES NOT HEAT
THERMOSTAT - RANCO K36P1333 (DHW STAT)
FLOW SWITCH (RESISTANCE)
THERMOSTAT - RANCO K36P1333 (DHW STAT)
BY-PASS ADJUSTING SCREW
SYSTEM BY-PASS
CH OPERATION
SYSTEM BY-PASS
NOT ADJUSTED
GAS VALVE
RELAY A STICKING
KIT - PCB 400 REPLACEMENT
MAIN PCB (VOLTS OUT)
KIT - PCB 400 REPLACEMENT
FAN RUNS
SELECTOR SWITCH / PROGRAMMER
DIVERTER VALVE
PUMP AND HOUSING
DIVERTER VALVE PRESSURE RELIEF PIPE
PIPE 6MM - PRESSURE RELIEF ASSEMBLY
HEATBANK SATISFIED - POWER STUCK TO DIVERTER
KIT - PCB 400 REPLACEMENT
DHW OPERATION - POWER STUCK TO DIVERTER
KIT - PCB 400 REPLACEMENT
NOT ADJUSTED - TOO LOW
GAS VALVE
DHW OPERATION
EXTERNAL MIXING
CH OP - UP TO TEMP RADS COOL
ISOLATING VALVE 22MM
DIVERTER VALVE OPERATION
FILTER - CYLINDRICAL
DIVERTER VALVE OPERATION
ISOLATING VALVE 22MM
DHW OPERATION - DHW COOL RADS COOL
FILTER - CYLINDRICAL
HEATBANK CH HEATS
ISOLATING VALVE 22MM
DHW OPERATION
ISOLATING VALVE 22MM
COIL 230V AC - DIVERTER VALVE
COIL 230V AC - DIVERTER VALVE
PUMP OVERRUN LED STUCK ON
KIT - PCB 400 REPLACEMENT
SPARK ELECTRODE LEAD
LEAD 220MM LONG 0.7 PTFE CABLE - SPARK ELECTRODE
NO SPARKING SEEN AT ELECTRODE TIP
SPARK ELECTRODE GAP
THERMOCOUPLE INTERRUPTER CONNECTIONS
OVERHEAT THERMOSTAT (ECO CONNECTIONS)
SPARKING SEEN AT ELECTRODE TIP BUT PILOT DOES NOT IGNITE
SPARK ELECTRODE GAP
INLET PRESSURE PILOT
INLET PRESSURE
PILOT INJECTOR
INJECTOR - PILOT
INLET FILTER
FILTER GAUZE - EXPAMET
FLOW REGULATOR
FLOW REGULATOR
HEATBANK OVERHEAT THERMOSTAT RESISTANCE
THERMOSTAT - HEATBANK OVERHEAT
FUSE 3 AMP
FUSE 3 AMP
FLOW SWITCH
FLOW SWITCH
DHW LIMIT THERMOSTAT
HARNESS - HOT WATER OVERHEAT (DHW LIMIT STAT)
ORANGE LINK
ORANGE LINK
MAIN GAS VALVE (RESISTANCE)
GAS VALVE
INLET PRESSURE
INLET PRESSURE
GAS VALVE VOLTAGE G3
KIT - PCB 400 REPLACEMENT
GAS VALVE VOLTAGE G3
INLET PRESSURE
SELECTOR SWITCH
KIT - PCB 400 REPLACEMENT
BURNER IGNITION (CH DEMAND)
KIT - PCB 400 REPLACEMENT
DHW CONTROL THERMOSTAT(RESISTANCE)
GAS VALVE
CH OPERATION (DIAG)
HEAT EXCHANGER (PLATE)
HEATBANK OVERHEAT RESISTANCE
THERMOSTAT - RANCO K36P1333 (DHW STAT)
BOILER SHUTS DOWN BEFORE DEMAND IS SATISFIED
HARNESS - HOT WATER OVERHEAT (DHW LIMIT STAT)
COOLING FAN IMPELLER
IMPELLOR - COOLING FAN
COOLING FAN MOTOR
MOTOR - COOLING FAN
PUMP RUNS
KIT - PCB 400 REPLACEMENT
GAS VALVE (SUPPLY)
GAS VALVE
GAS VALVE (LOW PRESSURE)
GAS VALVE
SPARK GENERATOR
SPARK GENERATOR - KIGASS CORVETTE 5800
CH CONTROL THERMOSTAT VOLTAGE
KIT - PCB 400 REPLACEMENT
DIVERTER VALVE OPERATION
KIT - PCB 400 REPLACEMENT
DHW OP RELAY C STICKING
KIT - PCB 400 REPLACEMENT
CH OPERATION
THERMOSTAT - RANCO K36P1332 (CH STAT)
PUMP OVERRUN
KIT - PCB 400 REPLACEMENT
FAN RUNS
KIT - PCB 400 REPLACEMENT
DIVERTER VALVE OPERATION
DIVERTER VALVE
DHW OPERATION
HEAT EXCHANGER (PLATE)
HEATBANK SATISFIED
DIVERTER VALVE
DHW OPERATION
DIVERTER VALVE
PUMP RUNS NO DEMAND
SELECTOR SWITCH / PROGRAMMER
THERMOCOUPLE
THERMOCOUPLE
THERMOCOUPLE INTERRUPTER CONNECTIONS
GAS VALVE
FLOW REGULATOR
HEAT EXCHANGER (PLATE)
FUSE 3 AMP
KIT - PCB 400 REPLACEMENT
PUMP
PUMP
DHW CONTROL THERMOSTAT VOLTS IN
THERMOSTAT - RANCO K36P1333 (DHW STAT)
ORANGE LINK
KIT - PCB 400 REPLACEMENT
IGNITION BURNER PRESSURE
BURNER INJECTOR
INLET PRESSURE
GAS VALVE
BOILER DOES NOT SHUT DOWN AT CORRECT TEMPERATURES AND/OR GOES TO OVERHEAT
CHARACTERISTIC TEST FROM HEATBANK SATISFIED
BOILER KETTLES IMMEDIATELY. PILOT SHUTS DOWN
CHARACTERISTIC TEST FROM HEATBANK SATISFIED
BOILER SHUTS DOWN BEFORE DEMAND IS SATISFIED
CHARACTERISTIC TEST FROM HEATBANK SATISFIED
CH SYSTEM HEATS UP
CHARACTERISTIC TEST FROM HEATBANK SATISFIED
BOILER SHUTS DOWN BEFORE DEMAND IS SATISFIED
CHARACTERISTIC TEST FROM DHW OPERATION
DHW DOES NOT REACH TEMPERATURE
CHARACTERISTIC TEST FROM DHW OPERATION
RADIATORS HEAT WITH DHW DEMAND
CHARACTERISTIC TEST FROM DHW OPERATION
DHW RUNS COLD OR BOILER TAKES TOO LONG TO REFIRE
CHARACTERISTIC TEST FROM DHW OPERATION
COOLING FAN DOES NOT RUN
CHARACTERISTIC TEST FROM COOLING FAN
COOLING FAN RUNS BUT IMPELLER DAMAGED OR SLIPS
CHARACTERISTIC TEST FROM COOLING FAN
NO SPARKING SEEN AT THE ELECTRODE TIP
CHARACTERISTIC TEST FROM PILOT OPERATION
PILOT IGNITES BUT GOES OUT WHEN BUTTON IS RELEASED
CHARACTERISTIC TEST FROM PILOT OPERATION
CH NOISY, DHW OK
CHARACTERISTIC TEST FROM CH OPERATION
BOILER SHUTS DOWN, BOILER TEMPERATURE LOW, RADIATOR TEMPERATURE LOW
CHARACTERISTIC TEST FROM CH OPERATION
BOILER REACHES TEMPERATURE, RADIATORS DO NOT HEAT
CHARACTERISTIC TEST FROM CH OPERATION
PUMP DOES NOT OVERRUN
CHARACTERISTIC TEST FROM PUMP OVERRUN
PUMP OVERRUNS OVER 5 MINUTES
CHARACTERISTIC TEST FROM PUMP OVERRUN
PILOT IGNITES AND ESTSBLISHES BUT DOES NOT SWITCH OFF
CHARACTERISTIC TEST FROM PILOT OPERATION
BOILER DOES NOT REACH TEMPERATURE - RADIATORS ONLY GET WARM
CHARACTERISTIC TEST FROM CH OPERATION
SPARKING SEEN AT ELECTRODE TIP BUT PILOT DOES NOT IGNITE
CHARACTERISTIC TEST FROM PILOT OPERATION
09/07/2018 10:20:14 1807_1_50_1 20/07/2018 14:04:36
09/07/2018 14:12:12
EXTERNAL CONTROLS/ROOM THERMOSTAT (VOLTS IN)
{GAINPCBACS}
HEAT
SELECTOR SWITCH / PROGRAMMER
{GAINPCBACS}
HEAT
FLOW SWITCH (RESISTANCE)
DISCONNECT CONNECTOR X1 (BLUE & BROWN WIRES) FROM PCB.
DIVERTER VALVE (VOLTAGE)
{GAINPCBACS}
HEAT
FLOW SWITCH (RESISTANCE)
DISCONNECT CONNECTOR X1 (BLUE & BROWN WIRES) FROM PCB.
SELECTOR SWITCH (VOLTS IN)
{GAINPCBACS}
HEAT
INLET FILTER
DISCHARGE AND DRAIN THE HOT WATER CIRCUIT
HEATBANK OVERHEAT THERMOSTAT (VOLTAGE)
{GAINPCBACS}
HEATING TEMPERATURE SELECTOR TO OFF
HOT WATER TEMPERATURE SELECTOR TO OFF
MAINS POWER SUPPLY
{GAINPCBACS}
HEATING TEMPERATURE SELECTOR TO OFF
HOT WATER TEMPERATURE SELECTOR TO OFF
FLOW SWITCH (RESISTANCE)
DISCONNECT CONNECTOR X1 (BLUE & BROWN WIRES) FROM PCB.
GAS VALVE VOLTAGE
{GAINPCBACS}
PROG
DHW CONTROL THERMOSTAT (VOLTS OUT)
{GAINPCBACS}
PROG
DHW CONTROL THERMOSTAT (VOLTS IN )
{GAINPCBACS}
PROG
INLET PRESSURE
ATTACH U-GAUGE TO IN
GAS VALVE VOLTAGE (GV3)
{GAINPCBACS}
PROG
EXTERNAL CONTROLS/ROOM THERMOSTAT (VOLTS OUT)
{GAINPCBACS}
HEAT
CH CONTROL THERMOSTAT (VOLTS IN)
{GAINPCBACS}
HEAT
DHW CONTROL THERMOSTAT (RESISTANCE)
HEATING TEMPERATURE
CH OPERATION (DIAG)
HEATING TEMPERATURE SELECTOR TO MAXIMUM
HOT WATER TEMPERATURE SELECTOR TO OFF
HEATBANK OVERHEAT (RESISTANCE)
REMOVE CONNECTOR X14
DHW CONTROL THERMOSTAT
{GAINPCBACS}
PROG
FLOW SWITCH (RESISTANCE)
DISCONNECT CONNECTOR X1 (BLUE & BROWN WIRES) FROM PCB.
COOLING FAN (VOLTAGE)
{GAINPCBACS}
HEAT
RESISTANCE CH CONTROL THERMOSTAT
{GAINPCBACS}
CH TEMPERATURE SELECTOR TO MAX
DISCONNECT CONNECTOR X15 FROM PCB
RESISTANCE DHW CONTROL THERMOSTAT (OPEN)
{GAINPCBACS}
HOT WATER TEMPERATURE SELECTOR TO OFF
DISCONNECT CONNECTOR X2 FROM PCB
RESISTANCE DHW CONTROL THERMOSTAT
{GAINPCBACS}
HOT
PRESSURE BURNER (CENTRAL HEATING)
ATTACH U-GAUGE TO BU
THERMOCOUPLE VOLTAGE
ATTACH +VE PROBE OF MULTIMETER TO A SUITABLE EARTH POINT VIA CROCODILE CLIP
GAS ON
OBSERVATION DEMAND LIGHT
PROGRAMMER OR SELECTOR SWITCH SET TO HOT WATER ONLY
SELECTOR SWITCH (VOLTS OUT)
{GAINPCBACS}
HEAT
RESISTANCE DIVERTER VALVE
DISCONNECT CONNECTOR X7 FROM THE PCB
INSPECTION PUMP CHECK VALVE
DRAIN BOILER PRIMARY CIRCUIT
INSPECTION DIVERTER VALVE PRESSURE RELIEF PIPE
DRAIN BOILER PRIMARY CIRCUIT
REMOVE PUMP ASSEMBLY
DIVERTER VALVE (VOLTAGE) - DHW DEMAND
{GAINPCBACS}
HEAT
DIVERTER VALVE (VOLTAGE) - DHW DEMAND
{GAINPCBACS}
HEAT
PRESSURE BURNER (CENTRAL HEATING)
ATTACH U-GAUGE TO BU
INSPECTION NON-RETURN VALVE
DRAIN BOILER AND SYSTEM OF WATER
INSPECTION HEATING FILTER
DRAIN BOILER PRIMARY CIRCUIT
REMOVE THERMOSTAT PHIAL AND PHIAL POCKET
INSPECTION NON-RETURN VALVE
DRAIN BOILER AND SYSTEM OF WATER
INSPECTION HEATING FILTER
DRAIN BOILER PRIMARY CIRCUIT
REMOVE THERMOSTAT PHIAL AND PHIAL POCKET
INSPECTION NON-RETURN VALVE
DRAIN BOILER AND SYSTEM OF WATER
INSPECTION NON-RETURN VALVE
DRAIN BOILER AND SYSTEM OF WATER
OBSERVATION DISCONNECT PROGRAMMER / SELECTOR SWITCH
UNPLUG 4 PIN CONNECTOR AT X12 FROM THE PCB
INLET PRESSURE (PILOT)
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
GAS ON
FLOW REGULATOR
DISCHARGE AND DRAIN THE HOT WATER CIRCUIT
PUMP
{GAINPCBACS}
HEAT
HEATBANK OVERHEAT THERMOSTAT (RESISTANCE)
DISCONNECT CONNECTOR X14 (RED LEADS) FROM PCB
FUSE (3 AMP)
REMOVE FUSE FROM ITS HOLDER ON THE PCB
MAIN GAS VALVE (RESISTANCE)
REMOVE BLACK PLUG FROM MAIN GAS VALVE SOLENOID
DHW LIMIT THERMOSTAT (RESISTANCE)
REMOVE CONNECTOR X16 (BLACK WIRES) FROM PCB
IGNITION BURNER PRESSURE
ATTACH U-GAUGE TO BU
INLET PRESSURE
ATTACH U-GAUGE TO IN