BAXI BAHAMA 100 SIT
GLOBALLY REPLACED
BAXI BAHAMA 100 SIT
G.C. NUMBER 47 075 0
DHW PUMP RUNS
SELECTOR SWITCH TO DHW POSITION
CH TEMPERATURE SELECTOR TO MIN
DHW TEMPERATURE SELECTOR TO MAX
DHW BURNER IGNITION
ATTACH U-GAUGE TO GA
DHW BURNER ESTABLISHED (HIGH FLAME)
ATTACH U-GAUGE TO GA
CH IGNITION
ATTACH U-GAUGE TO GA
DHW OPERATION
SELECTOR SWITCH TO DHW POSITION
CH TEMPERATURE SELECTOR TO MIN
DHW TEMPERATURE SELECTOR TO MAX
DHW MODULATION
SET FLOW RATE AT TAP
AUTO FROST
SELECTOR SWITCH TO O
CH OPERATION
SELECTOR SWITCH TO D
SYSTEM PRESSURE RISE
SELECTOR SWITCH TO D
CH MODULATION
ATTACH A U-GAUGE TO
RE-IGNITION DELAY
SELECTOR SWITCH TO D
PUMP OVERRUNS
SELECTOR SWITCH TO D
DHW FAN RUNS
SELECTOR SWITCH TO DHW POSITION
CH TEMPERATURE SELECTOR TO MIN
DHW TEMPERATURE SELECTOR TO MAX
DHW BURNER ESTABLISHED
FLAME SENSE ELECTRODE
DHW BURNER ESTABLISHED
FLAME SENSE ELECTRODE LEAD
DHW BURNER ESTABLISHED
PRIMARY HEAT EXCHANGER FLOW
BURNER IGNITES BUT BAFFLES OUT
GAS INLET PRESSURE
CH IGNITION
DHW FLOW SWITCH
DHW OPERATION
INTEGRAL BYPASS
DHW NOISY OPERATION
MAIN PCB
DHW OPERATION
BURNER MANIFOLD
DHW TEMPERATURE LOW RADIATORS HOT
MAIN PCB
DHW OPERATION
DIVERTER VALVE BODY
DHW MODULATION
NTC SENSOR
AUTO FROST
NTC SENSOR
ELECTRICAL SAFETY CHECKS
ELECTRICAL SAFETY CHECKS
CH OPERATION
NTC SENSOR
BOILER TO TEMPERATURE RADIATORS COLD
INTEGRAL BYPASS
BOILER TO TEMPERATURE RADIATORS COLD
CH FILTER
CH OPERATION
DIVERTER VALVE BODY
BOILER TO TEMPERATURE RADIATORS COLD
MAIN PCB
CH NOISY DHW OK
PUMP
CH NOISY DHW OK
INTEGRAL BYPASS
CH NOISY DHW OK
DIVERTER VALVE BODY
SYSTEM PRESSURE VESSEL
EXPANSION VESSEL
CH MODULATION
MAIN PCB
RE-IGNITION DELAY
MAIN PCB
PUMP OVERRUNS
MAIN PCB
DHW PUMP RUNS
DHW FLOW SWITCH
DHW PUMP RUNS
FUSE F1
DHW FLOW RATE
DHW ISOLATOR
OVERHEAT THERMOSTAT RESISTANCE
ELECTRODE LEADS
DHW BURNER IGNITION
GAS VALVE
DHW BURNER IGNITION
GAS INLET PRESSURE
NO IGNITION NO OUTPUT FROM IGNITION BOARD
IGNITION PCB
DHW FLOW RATE
DHW INLET FILTER RESTRICTOR CARTRIDGE
PUMP RUNS
CH FLOW SWITCH
FAN RUNS 10 SECONDS THEN STOPS
NTC SENSOR
DHW FAN RUNS
OVERHEAT THERMOSTAT
PUMP DOES NOT RUN
NTC SENSOR
CLOCK IN VOLTS INPUT TERMINAL 1
MAIN PCB
CH IGNITION
EXTERNAL CONTROLS TIMER
CH IGNITION
EXTERNAL CONTROLS/ROOM THERMOSTAT CONTROL
DHW PUMP RUNS
MAINS POWER IN
NO CH
PUMP
CH IGNITION
CH FILTER
DHW RUNS HOT COLDDHW OPERATION
INTEGRAL BYPASS
DHW RUNS HOT COLD
CH FLOW SWITCH
DHW RUNS HOT COLD
PUMP
FAN DOES NOT RUN
PUMP
DHW FAN RUNS
AIR PRESSURE SWITCH TUBES
DHW FAN RUNS
VENTURI
DHW FAN RUNS
FLUE
FAN DOES NOT RUN
MAIN PCB
FAN DOES NOT RUN
NTC SENSOR
DHW FAN RUNS
LOCK OUT RESET SWITCH
BURNER CUTS OUT DHW
PUMP
DHW BURNER ESTABLISHED
NTC SENSOR
HIGH FLAME NO OUTPUT FROM IGNITION BOARD
IGNITION PCB
MODULATING SOLENOID
GAS VALVE
BURNER IGNITION PRESSURE LOW OR DIES OUT
GAS INLET PRESSURE
NO SPARK
SPARK GAP
DHW BURNER IGNITION
SPARK ELECTRODE
DHW BURNER IGNITION
EARTH ELECTRODE
DHW BURNER IGNITION
OVERHEAT THERMOSTAT
DHW BURNER IGNITION
AIR PRESSURE SWITCH TUBES
DHW BURNER IGNITION
VENTURI
DHW BURNER IGNITION
FLUE
SPARK GAS PRESENT NO IGNITION
SPARK GAP
DHW BURNER ESTABLISHED
IGNITION PCB
BURNER IGNITES BUT BAFFLES OUT
GAS VALVE
CH IGNITION
GAS VALVE
DHW OPERATION
SECONDARY HEAT EXCHANGER
DHW OPERATION
PRIMARY HEAT EXCHANGER
DHW NOISY OPERATION
DIVERTER VALVE HEAD
DHW TEMPERATURE LOW RADIATORS COLD
SECONDARY HEAT EXCHANGER
DHW TEMPERATURE LOW RADIATORS HOT
DIVERTER VALVE HEAD
DHW MODULATION
MAIN PCB
AUTO FROST
MAIN PCB
BOILER TO TEMPERATURE RADIATORS COLD
DIVERTER VALVE HEAD
SELECTOR SWITCH
SELECTOR SWITCH
DHW PUMP RUNS
FUSE HOLDER
NO SPARK
IGNITION PCB
DHW FLOW RATE
DHW HEAT EXCHANGER
FAN RUNS 10 SECONDS THEN STOPS
MAIN PCB
DHW PUMP RUNS
MAIN PCB
DHW PUMP RUNS
PUMP
SPARK PRESENT NO GAS
GAS VALVE
CH IGNITION
EXTERNAL CONTROLS LINK 1
CH IGNITION
EXTERNAL CONTROLS LINK 2
RTC OUTPUT TERMINAL 4
MAIN PCB
NO CH IGNITION NO PUMP
MAIN PCB
NO CH
CH FLOW SWITCH
DHW RUNS HOT COLDDHW OPERATION
SECONDARY HEAT EXCHANGER
DHW RUNS HOT COLDDHW OPERATION
PRIMARY HEAT EXCHANGER
DHW FAN RUNS
CH FLOW SWITCH
DHW FAN RUNS
AIR PRESSURE SWITCH
DHW FAN RUNS
FAN
FAN DOES NOT RUN 2
MAIN PCB
DHW FAN RUNS
IGNITION PCB
BURNER CUTS OUT DHW
CH FLOW SWITCH
MECHANICAL FAILURE
GAS VALVE
ELECTRODE GAP
ELECTRODE LEADS
DHW BURNER IGNITION
AIR PRESSURE SWITCH
DHW BURNER IGNITION
BURNER MANIFOLD
Burner ignites straight to high flame
CHARACTERISTIC TEST FROM CH IGNITION
No ignition
CHARACTERISTIC TEST FROM CH IGNITION
DHW noisy operation
CHARACTERISTIC TEST FROM DHW OPERATION
DHW temperature low, radiators cold
CHARACTERISTIC TEST FROM DHW OPERATION
DHW temperature low, radiators hot
CHARACTERISTIC TEST FROM DHW OPERATION
Boiler and radiators provide insufficient heat
CHARACTERISTIC TEST FROM CH OPERATION
Boiler to temperature, radiators cold
CHARACTERISTIC TEST FROM CH OPERATION
CH noisy, DHW OK
CHARACTERISTIC TEST FROM CH OPERATION
FAN DOES NOT RUN OR RUNS INTERMITTENTLY
CHARACTERISTIC TEST FROM DHW FAN RUNS
Fan runs for 10-15 seconds then stops
CHARACTERISTIC TEST FROM DHW FAN RUNS
VOLTAGE AS EXPECTED ON TEST 1 BUT DOES NOT DROP ON TEST 2
CHARACTERISTIC TEST FROM VOLTAGE CH FLOW SWITCH DROP
VOLTAGE NOT AS EXPECTED ON TEST 1
CHARACTERISTIC TEST FROM VOLTAGE CH FLOW SWITCH DROP
DHW CUTS OUT OR RUNS HOT COLD
CHARACTERISTIC TEST FROM DHW OPERATION
VOLTAGE AS EXPECTED ON TEST 1 BUT DOES NOT DROP ON TEST 2
CHARACTERISTIC TEST FROM VOLTAGE CH FLOW SWITCH DROP
VOLTAGE NOT AS EXPECTED ON TEST 1
CHARACTERISTIC TEST FROM VOLTAGE CH FLOW SWITCH DROP
VOLTAGE AS EXPECTED ON TEST 1 BUT DOES NOT DROP ON TEST 2
CHARACTERISTIC TEST FROM VOLTAGE CH FLOW SWITCH DROP
VOLTAGE NOT AS EXPECTED ON TEST 1
CHARACTERISTIC TEST FROM VOLTAGE CH FLOW SWITCH DROP
No spark
CHARACTERISTIC TEST FROM DHW BURNER IGNITION
Sparking present, no gas
CHARACTERISTIC TEST FROM DHW BURNER IGNITION
Sparking, gas present, no ignition
CHARACTERISTIC TEST FROM DHW BURNER IGNITION
BURNER IGNITION PRESSURE LOW OR DIES OUT WITHIN 20 SECONDS
CHARACTERISTIC TEST FROM DHW BURNER ESTABLISHED (HIGH FLAME)
Burner ignites but baffles out
CHARACTERISTIC TEST FROM DHW BURNER ESTABLISHED (HIGH FLAME)
Burner ignition spark continues, boiler goes to lockout
CHARACTERISTIC TEST FROM DHW BURNER ESTABLISHED (HIGH FLAME)
07/11/2018 13:53:25 1811_1_50_1 23/11/2018 12:32:33
13/11/2018 09:48:41
DHW DIVERTER VALVE VOLTS
{GAINPCBACS}
SELE
BYPASS CHECK
DISCHARGE AND DRAIN BOILER
SENSOR MODULATION
DISCONNECT RED LEADS FROM THE NTC SENSOR
AUTO FROST SENSOR
DISCONNECT RED LEADS FROM THE NTC SENSOR
DHW DIVERTER VALVE VOLTS
{GAINPCBACS}
SELE
DHW FLOW SWITCH RESISTANCE
{GAINPCBACS}
DISCONNECT CONNECTOR CN1 FROM THE PCB
FUSE F1 RESISTANCE
REMOVE FUSE F1 FROM FUSE HOLDER
POWER TO CONTROL BOARD
{GAINPCBACS}
SELECTOR SWITCH TO DHW POSITION
MAINS POWER IN
{GAINPCBACS}
RTC INPUT TERMINAL 3
{GAINPCBACS}
TIMER (IF FITTED) CALLING FOR HEAT
VOLTAGE CH FLOW SWITCH DURING DEMAND
{GAINPCBACS}
DHW TEMPERATURE SELECTOR TO MAX
VOLTS TO IGNITION PCB
{GAINPCBACS}
SELE
NTC RESISTANCE DEMAND
DISCONNECT RED LEADS FROM THE NTC SENSOR
OVERHEAT THERMOSTAT RESISTANCE
REMOVE LEADS FROM OVERHEAT THERMOSTAT
GAS INLET PRESSURE
ATTACH U GAUGE TO GA
DHW FLOW SWITCH RESISTANCE
{GAINPCBACS}
DISCONNECT CONNECTOR CN1 FROM THE PCB
DHW DIVERTER VALVE OPERATION
CH TEMPERATURE SELEC
DHW DIVERTER VALVE VOLTS
{GAINPCBACS}
SELE
CH OPERATION
SELECTOR SWITCH TO D
DIVERTER VALVE BODY
REMOVE THE DIVERTER VALVE HEAD
DHW DIVERTER VALVE OPERATION
CH TEMPERATURE SELEC
NTC RESISTANCE RAMP UP
DISCONNECT RED LEADS FROM THE NTC SENSOR
CH FILTER
DISCHARGE AND DRAIN BOILER
BYPASS CHECK
DISCHARGE AND DRAIN BOILER
CH FILTER
DISCHARGE AND DRAIN BOILER
DIVERTER VALVE BODY
REMOVE THE DIVERTER VALVE HEAD
BYPASS CHECK
DISCHARGE AND DRAIN BOILER
DIVERTER VALVE BODY
REMOVE THE DIVERTER VALVE HEAD
DHW INLET FILTER RESTRICTOR CARTRIDGE
DHW ISOLATOR VALVE OFF
DHW DISCHARGED AND DRAINED
SELECTOR SWITCH VOLTAGE
SELECTOR SWITCH TO OFF POSITION
GAS VALVE 1 VOLTAGE
{GAINPCBACS}
SELE
GAS VALVE RESISTANCE
DISCONNECT SPARK GENERATOR FROM GAS VALVE
GAS INLET PRESSURE
ATTACH U GAUGE TO GA
CH FLOW SWITCH RESISTANCE (OPEN CIRCUIT CHECK)
{GAINPCBACS}
DISCONNECT CONNECTOR CN1 FROM THE PCB
NTC RESISTANCE DEMAND
DISCONNECT RED LEADS FROM THE NTC SENSOR
OVERHEAT THERMOSTAT RESISTANCE
REMOVE LEADS FROM OVERHEAT THERMOSTAT
PUMP VOLTS
{GAINPCBACS}
SELECTOR SWITCH TO DHW POSITION
DHW TEMPERATURE SELECTOR TO MAX
NTC RESISTANCE DEMAND
DISCONNECT RED LEADS FROM THE NTC SENSOR
OBSERVATION PUMP RUNS CH
SELECTOR SWITCH TO CH AND DHW POSITION
CH TEMPERATURE SELECTOR TO MAX
RTC OUTPUT TERMINAL 4
TIMER AND ROOM THERMOSTAT (IF FITTED) CALLING FOR HEAT
CLOCK OUT VOLTS TERMINAL 2
TIMER (IF FITTED) CALLING FOR HEAT
VOLTAGE CH FLOW SWITCH DROP
{GAINPCBACS}
DHW TEMPERATURE SELECTOR TO MAX
CH FILTER
DISCHARGE AND DRAIN BOILER
CH OPERATION
SELECTOR SWITCH TO D
BYPASS CHECK
DISCHARGE AND DRAIN BOILER
VOLTAGE CH FLOW SWITCH DROP
{GAINPCBACS}
DHW TEMPERATURE SELECTOR TO MAX
AIR PRESSURE SWITCH RESISTANCE
DISCONNECT THE WHITE LEAD FROM THE AIR PRESSURE SWITCH
FAN VOLTS
SELECTOR SWITCH TO OFF POSITION
CH TEMPERATURE SELECTOR TO MIN
DHW TEMPERATURE SELECTOR TO MAX
SWITCHED LIVE TO IGNITION PCB
{GAINPCBACS}
SELE
LOCKOUT RESET SWITCH
REMOVE ONE OF THE WIRES FROM THE LOCKOUT RESET SWITCH
VOLTAGE CH FLOW SWITCH DROP
{GAINPCBACS}
DHW TEMPERATURE SELECTOR TO MAX
NTC RESISTANCE DEMAND
DISCONNECT RED LEADS FROM THE NTC SENSOR
MODULATING SOLENOID VOLTAGE
SELECTOR SWITCH TO DHW POSITION
CH TEMPERATURE SELECTOR TO MIN
DHW TEMPERATURE SELECTOR TO MAX
MODULATING SOLENOID RESISTANCE
REMOVE THE LEADS FROM THE MODULATING SOLENOID
GAS INLET PRESSURE
ATTACH U GAUGE TO GA
AIR PRESSURE SWITCH PROVING
SELECTOR SWITCH TO OFF POSITION
CH TEMPERATURE SELECTOR TO MIN
DHW TEMPERATURE SELECTOR TO MAX
SPARK OUTPUT
SELECTOR SWITCH TO O
System Information
- Total Tests: 234
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control