Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to Resistance Set meter to measure resistance
Disconnect red leads from the NTC sensor

Measurement:

Check the resistance across the exposed terminals of the sensor.
The resistance measured will depend upon the boiler temperature, the higher the temperature the lower the resistance.
The resistance should conform to the table below.
Temperature °CResistance in kOhms
10-1519.9-15.7
15-2015.7-12.5
20-4012.5-5.3
40-605.3-2.5
60-802.5-1.3
80-1001.3-0.7