VAILLANT VCW GB 242 EH
GLOBALLY REPLACED
CENTRAL HEATING
HEATING SWITCH ON
ROOM STAT CALLING FOR HEAT
RADIATOR VALVES OPEN
DIVERTER VALVE CH MODE
HEATING SWITCH ON
ROOM STAT CALLING FOR HEAT
SERVO VALVE CENTRAL HEATING MODE
HEATING SWITCH ON
SYSTEM CALLING FOR HEAT
HIGH FLAME
HEATING SWITCH OFF
ATTACH PRESSURE GAUGE TO BURNER PRESSURE TEST POINT
LOW FLAME TEST
HEATING SWITCH OFF
FAN RUNNING
HEATING SWITCH OFF
DIVERTER VALVE
HEATING SWITCH OFF
OPERATION SERVO VALVE CAM
HEATING SWITCH OFF
MAINS SUPPLY TO BOILER
HEATING SWITCH OFF
(BOTH ON CONTROL PANEL)
VAILLANT VCW GB 242 EH
G.C. NUMBER 47 044 1
YELLOW NEON CHECK
HEATING SWITCH OFF
HOT WATER
HEATING SWITCH OFF
RESISTANCE DHW MICROSWITCH
REMOVE ONE OF THE WIRES FROM THE DHW MICROSWITCH
FUSE F2 2A
SET - 10 OFF FUSES 2.0AT
CH OVERHEAT THERMOSTAT
TEMPERATURE LIMITER
DIFFERENTIAL VALVE
DIFFERENTIAL PRESSURE VALVE
SPARKING HEARD
PCB - FLAME FAILURE DEVICE - IGNITION
DIVERTER VALVE
CONTROL LINE
ELECTRICAL SAFETY CHECKS
ELECTRICAL SAFETY CHECKS
FUSE F1 2A
SET - 10 OFF FUSES 2.0AT
DHW THERMOSTAT
TEMPERATURE LIMITER
NTC RESISTOR
SENSOR - NTC
YELLOW NEON CHECK
WIRE - NTC CONNECTION
MICROSWITCH M1
MICROSWITCH ASSEMBLY
YELLOW NEON
PCB - FLAME FAILURE DEVICE - IGNITION
YELLOW NEON TEST
ELECTRODES (SENSING AND SPARK)
DIVERTER VALVE CH
CONTROL LINE
PUMP
PUMP 230V 5M - GRUNDFOS VP5ZE
FAN RUNNING
PCB - FAN CIRCUIT
ELECTRONIC PCB
PCB - ELECTRONIC CONTROL SYSTEM
DIVERTER VALVE CH BOILER MODULATES MODULATES QUICKLY
CONTROL LINE
DHW MODULATES MODULATES QUICKLY
SENSOR - NTC
DHW MODULATES MODULATES QUICKLY
TEMPERATURE LIMITER
HOT WATER
ELECTRODES (SENSING AND SPARK)
STICKING PREVENTING MOVEMENT
SPINDLE AND SUPPORT PLATE
STICKING NOT RETURNING
SPINDLE AND SUPPORT PLATE
WATER SECTION SPRING DISCONNECTED
SERVO VALVE
CH OPERATION
CONTROL LINE
CH OPERATION 2
CONTROL LINE
DIVERTER VALVE 2
CONTROL LINE
LEAKING PREVENTING HIGH FLAME
BANJO CONNECTOR
HOSE CONNECTION
TUBES TO DIAPHRAGM PUMP
NO POWER TO APS
PCB - FAN CIRCUIT
YELLOW NEON
AIR PRESSURE MONITOR
YELLOW NEON
HOSE SILICONE RUBBER
FLUEWAYS
PRIMARY HEAT EXCHANGER
MICROSWITCH M3
MICROSWITCH M3
OVERHEAT THERMOSTAT
OVERHEAT CUT - OFF DEVICE
FUSE F3 160MA
SET - 10 OFF FUSE 0.16AT
PREVENTING DIVERTER MOVEMENT
SYSTEM PRESSURE / AIR
PREVENTING DIVERTER MOVEMENT 2
SYSTEM PRESSURE / AIR
PREVENTING GAS VALVE OPERATOR MOVING
SYSTEM PRESSURE / AIR
MICROSWITCH M2
MICROSWITCH ASSEMBLY
CONTROL BOX CLICKS, NO SPARKING HEARD FROM ELECTRODE
ELECTRODES (SENSE & SPARK)
CH OPERATION ON HW TREE
CONTROL LINE
DIVERTER VALVE CH BOILER MODULATES POOR DHW
CONTROL LINE
DHW MODULATES POOR DHW
SENSOR - NTC
DHW MODULATES POOR DHW
TEMPERATURE LIMITER
HIGH FLAME
GAS PRESSURE GOVERNOR
RESTRICTED OR BLOCKED
INJECTORS
LOW FLAME TEST (1)
PCB - FLAME FAILURE DEVICE - IGNITION
FLUE
FLUE
BLOCKED / RESTRICTED
ORIFICE / BUSHES
DIVERTER VALVE
TRANSFORMER
LOW FLAME TEST
ELECTRODES (SENSING AND SPARK)
NO SPARKING HEARD
ELECTRODES (SENSE & SPARK)
SPARKING HEARD
GAS PRESSURE GOVERNOR
YELLOW NEON CHECK
TRANSFORMER - IGNITION
DIVERTER VALVE CENTRAL HEATING MODE
DIVERTER VALVE OR PARTS
FAN
FAN
CH DEMAND
PCB
DHW MODULATES MODULATES QUICKLY
HEAT EXCHANGER - SECONDARY - DHW
BOILER MODULATES MODULATES QUICKLY
PRIMARY HEAT EXCHANGER
BOILER MODULATES MODULATES QUICKLY
MICROSWITCH ASSEMBLY
DIVERTER VALVE CENTRAL HEATING MODE BOILER MODULATES MODULATES QUICKLY
DIVERTER VALVE OR PARTS
DHW MODULATES MODULATES QUICKLY
PCB - ELECTRONIC CONTROL SYSTEM
HOT WATER
PCB - FLAME FAILURE DEVICE - IGNITION
NOT RETURNING
SERVO VALVE
CAM NOT MOVING FULLY OVER
WATER VALVE
SPINDLE REMAINS UP
WATER VALVE
SERVO VALVE BOILER MODULATES MODULATES QUICKLY
SERVO VALVE
SERVO VALVE
SERVO VALVE
DIVERTER VALVE
DIVERTER VALVE OR PARTS
DIAPHRAGM PUMP
DIAPHRAGM PUMP
YELLOW NEON
FAN
NOT FIRING FOR CH
PCB - ELECTRONIC CONTROL SYSTEM
DHW MODULATES
HEAT EXCHANGER - SECONDARY - DHW
BOILER MODULATES
PRIMARY HEAT EXCHANGER
SERVO VALVE BOILER MODULATES
SERVO VALVE
BOILER MODULATES
MICROSWITCH ASSEMBLY
CONTROL BOX CLICKS, NO SPARKING HEARD FROM ELECTRODE
GAS PRESSURE GOVERNOR
DIVERTER VALVE CENTRAL HEATING MODE BOILER MODULATES POOR DHW
DIVERTER VALVE OR PARTS
DHW MODULATES POOR DHW
PCB - ELECTRONIC CONTROL SYSTEM
BLANK FOR LED INVESTIGATION
Z DIRECTION CHOICE OR CONTINUE
DIVERTER VALVE POOR DHW
DIVERTER VALVE OR PARTS
LOW FLAME TEST (2)
PCB - FLAME FAILURE DEVICE - IGNITION
IGNITION TRANSFORMER
TRANSFORMER - IGNITION
SERVO VALVE CAM DOES NOT MOVE FULLY OVER
CHARACTERISTIC TEST FROM OPERATION SERVO VALVE CAM
SERVO VALVE CAM DOES NOT FULLY RETURN OR ONLY RETURNS WHEN PRESSED
CHARACTERISTIC TEST FROM OPERATION SERVO VALVE CAM
BOILER DOES NOT GO TO HIGH FLAME
CHARACTERISTIC TEST FROM HIGH FLAME
BOILER GOES TO HIGH FLAME BRIEFLY THEN MODULATES QUICKLY OR CUTS OUT
CHARACTERISTIC TEST FROM HIGH FLAME
BOILER DOES NOT REACT TO CH DEMAND
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER
DIFFERENTIAL EXCESSIVE
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER
BURNER IGNITES BUT SPARKING CONTINUES / LOCKOUT OCCURS
CHARACTERISTIC TEST FROM LOW FLAME TEST
CONTROL BOX CLICKS, BUT NO SPARKING HEARD AT ELECTRODE
CHARACTERISTIC TEST FROM LOW FLAME TEST
NO SPARKING HEARD
CHARACTERISTIC TEST FROM LOW FLAME TEST
SPARKING HEARD BUT BURNER DOES NOT IGNITE AND THEN LOCKS OUT
CHARACTERISTIC TEST FROM LOW FLAME TEST
INSUFFICIENT TEMPERATURE RISE OR BOILER LOCKS OUT - RADIATORS REMAIN COOL
CHARACTERISTIC TEST FROM HOT WATER
INSUFFICIENT TEMPERATURE RISE - RADIATORS BEGIN TO HEAT WITH NO DEMAND
CHARACTERISTIC TEST FROM HOT WATER
BOILER DOES NOT REACT TO CH DEMAND
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER
DIFFERENTIAL EXCESSIVE
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER
PUMP OR FAN OVER RUN DO NOT BEHAVE AS DESCRIBED
CHARACTERISTIC TEST FROM OPERATION PUMP AND FAN OVERRUN
BOILER STAYS ON WITH NO DEMAND
CHARACTERISTIC TEST FROM OPERATION PUMP AND FAN OVERRUN
14/08/2018 08:43:21 1808_1_50_1 16/08/2018 11:11:25
14/08/2018 09:55:01
VOLTAGE PUMP AT PUMP
HEATING SWITCH OFF
REMOVE PUMP TERMINAL COVER
VOLTAGE EXTERNAL CONTROLS OUT
{GAINPCBACS}
HEATING SWITCH ON
WATER PUMP VOLTAGE TEST
HEATING SWITCH OFF
REMOVE PUMP TERMINAL COVER
VOLTAGE AIR PRESSURE SWITCH CHECK
APS IS LOCATED AT RE
VOLTAGE EXTERNAL CONTROLS IN
{GAINPCBACS}
HEATING SWITCH ON
FAN MAINS VOLTAGE CHECK
HEATING SWITCH OFF
DIFFERENTIAL PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE CLAMPS TO PRIMARY FLOW AND RETURN EXITING THE BOILER AS INDICATED
VOLTAGE PUMP AT PUMP
HEATING SWITCH OFF
REMOVE PUMP TERMINAL COVER
VOLTAGE EXTERNAL CONTROLS OUT
{GAINPCBACS}
HEATING SWITCH ON
VOLTAGE EXTERNAL CONTROLS IN
{GAINPCBACS}
HEATING SWITCH ON
INSPECTION SPINDLE AND SUPPORT PLATE
REMOVE THE SECURING
CONTROL LINE BLOCKAGES
WATER OFF
BOILER DRAINED AND DISCHARGED
CONTROL LINE BLOCKAGES
WATER OFF
BOILER DRAINED AND DISCHARGED
VOLTAGE AIR PRESSURE SWITCH (IN)
APS IS LOCATED AT RE
OVERHEAT CUT-OFF DEVICE CHECK
REMOVE COVER FROM THE OVERHEAT CUT-OFF DEVICE
ENSURE APPLIANCE IS COOL
MICROSWITCHES M1 AND M2 CH OPERATION
REMOVE WIRES FROM DIVERTER MICROSWITCHES AND MAKE SAFE
DIFFERENTIAL PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE CLAMPS TO PRIMARY FLOW AND RETURN EXITING THE BOILER AS INDICATED
CONTROL LINE BLOCKAGES
WATER OFF
BOILER DRAINED AND DISCHARGED
VOLTAGE PUMP AT PUMP
HEATING SWITCH OFF
REMOVE PUMP TERMINAL COVER
VOLTAGE EXTERNAL CONTROLS OUT
{GAINPCBACS}
HEATING SWITCH ON
VOLTAGE EXTERNAL CONTROLS IN
{GAINPCBACS}
HEATING SWITCH ON
OPERATOR DC VOLTAGE CHECK
{GAINPCBACS}
HEATING SWITCH OFF
CENTRAL HEATING OVERHEAT THERMOSTAT CHECK
HEATING SWITCH OFF
OPERATOR DC VOLTAGE CHECK
{GAINPCBACS}
HEATING SWITCH OFF
DIFFERENTIAL VALVE MOVEMENT CHECK
HEATING SWITCH OFF
EXTERNAL
{GAINPCBACS}
HEATING SWITCH OFF
OBSERVATION REMOVE WIRES FROM DHW OVERHEAT STAT
HEATING SWITCH OFF
NTC RESISTANCE CHECK
DISCONNECT THE NTC SENSOR FROM THE HARNESS
MICRO SWITCHES M1 & M2 DOMESTIC HOT WATER OPERATION
REMOVE WIRES FROM DIVERTER VALVE MICROSWITCHES AND MAKE SAFE
HOT WATER TAP OFF
IGNITION TRANSFORMER VOLTAGE CHECK
HEATING SWITCH OFF
CONTROL LINE BLOCKAGES
WATER OFF
BOILER DRAINED AND DISCHARGED
GREEN NEON
HEATING SWITCH OFF
DIFFERENTIAL PLATE HEAT EXCHANGER
ATTACH TEMPERATURE C
RESISTANCE NTC-RESISTOR AT SENSOR
DISCONNECT THE NTC SENSOR FROM THE HARNESS
SERVO VALVE CENTRAL HEATING MODE
HEATING SWITCH ON
SYSTEM CALLING FOR HEAT
DIVERTER VALVE CH MODE
HEATING SWITCH ON
ROOM STAT CALLING FOR HEAT
CONTROL LINE BLOCKAGES
WATER OFF
BOILER DRAINED AND DISCHARGED
DISCONNECT OVERHEAT STAT WIRES
HEATING SWITCH OFF
INSPECTION SPINDLE AND SUPPORT PLATE
REMOVE THE SECURING
CONTROL LINE BLOCKAGES
WATER OFF
BOILER DRAINED AND DISCHARGED
FLAME MODULATION CHECK
ATTACH A PRESSURE GA
DIAPHRAGM PUMP TUBE (HOSE) CONNECTION
GAIN ACCESS TO THE TUBES RUNNING FROM THE OPERATOR TO THE DIAPHRAGM PUMP IN THE CONTROL BOX
AIR (FAN) PRESSURE SWITCH CHECK
REMOVE THE AIR PRESSURE SWITCH FROM THE APPLIANCE
IGNITION TRANSFORMER VOLTAGE CHECK
HEATING SWITCH OFF
DIFFERENTIAL PLATE HEAT EXCHANGER
ATTACH TEMPERATURE C
RESISTANCE NTC-RESISTOR AT SENSOR
DISCONNECT THE NTC SENSOR FROM THE HARNESS
SERVO VALVE CENTRAL HEATING MODE
HEATING SWITCH ON
SYSTEM CALLING FOR HEAT
DIVERTER VALVE CH MODE
HEATING SWITCH ON
ROOM STAT CALLING FOR HEAT
CONTROL LINE BLOCKAGES
WATER OFF
BOILER DRAINED AND DISCHARGED
DISCONNECT OVERHEAT STAT WIRES
HEATING SWITCH OFF
OBSERVATION DISCONNECT EXTERNAL CONTROLS
REMOVE WIRING FROM TERMINALS 3 AND 4 AND MAKE SAFE
RESISTANCE TRANSFORMER
{GAINPCBACS}
REMOVE TRANSFORMER CONNECTOR FROM PCB
System Information
- Total Tests: 206
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control