XSol Diagnostic System

Interactive Test Sequence Navigator

Welcome to the XSol Diagnostic System

This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.

Start Diagnostic Sequence

or choose a specific test below:

POTTERTON PUMA 80 (S.I.T.)

GLOBALLY REPLACED

Next: &20, *

PUMP OVERRUN

BOILER SWITCH IN ON

Next: &nff, !f110

CENTRAL HEATING

CENTRAL HEATING SWITCH IN CONSTANT POSITION
BOILER SWITCH IN ON POSITION

Next: &279, f107

CH HIGH FAN

CENTRAL HEATING SWITCH IN CONSTANT POSITION
BOILER SWITCH IN ON POSITION
ENSURE BOILER IS COOL

Next: &277, f94

HOT WATER

BOILER SWITCH IN ON

Next: &5, ?76, ?78, ?80

DHW WATER PUMP RUNNING

BOILER SWITCH IN ON

Next: &163, f73

DHW HIGH FAN

BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION

Next: &143, f50

DHW DEMAND LED ON

{GAINPCBACS}
BOIL

Next: &157, f43

SLOW FAN

BOILER SWITCH IN STANDBY POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION

Next: &10, f38

FROST THERMOSTAT

{GAINPCBACS}
CENTRAL HEATING SWITCH OFF
DISCONNECT PLUG PL1

Next: &11, !f37

LOW SYSTEM PRESSURE LED

BOILER SWITCH IN STANDBY POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION

Next: &12, f32

MAINS LED

BOILER SWITCH IN STANDBY POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION

Next: &13, f21

PILOT FLAME FAILURE

Next: &14, !f126

ESTABLISH PILOT

BOILER SWITCH IN STA

Next: &15, f15

PILOT IGNITION

BOILER SWITCH IN STA

Next: &16, f8

PILOT SPARKING

BOILER SWITCH IN STANDBY POSITION
CENTRAL HEATING SWITCH IN OFF(CENTRAL) POSITION

Next: &17, f136

POTTERTON PUMA 80 (S.I.T.)

G.C. NUMBER 47 590 1

Next: &18, !f1

DHW BURNER IGNITES

BOILER SWITCH IN ON

Next: &7, f198

DHW DEMAND LED OFF

BOILER SWITCH IN STA

Next: &9, f158

DHW BURNER PRESSURE MINIMUM

ATTACH PRESSURE GAUG

Next: &165, f219

DHW BURNER PRESSURE MAXIMUM

ATTACH PRESSURE GAUG

Next: &175, f222

DHW MODULATION

ATTACH PRESSURE GAUG

Next: &6, ?176, ?178

OBSERVATION CH FULL RATE

ATTACH PRESSURE GAUG

Next: &2, ?265, ?267, ?269

CH PUMP RUNNING

SLACKEN WATER PUMP MANUAL RESTART NUT, TAKE CARE TO SAFELY CONTAIN ANY WATER RELEASED

Next: &264, !f278

CH BURNER MODULATION

CENTRAL HEATING SWIT

Next: &1, f280

FUSE FURTHER INVESTIGATION

Next: &nff, f297

ELECTRICAL SAFETY CHECKS

ELECTRICAL CHECKS

Next: End

BOILER SWITCH

MODULATION CONTROL BOARD

Next: End

CENTRAL HEATING

DIVERTER VALVE

Next: End

PUMP OVERRUN

MODULATION CONTROL BOARD

Next: End

PILOT FLAME FAILURE

GAS VALVE (THERMOELECTRIC VALVE)

Next: End

PILOT SPARKING

ELECTRODE LEAD

Next: End

PILOT IGNITION

PILOT ASSEMBLY

Next: End

PILOT SPARKING

SPARK ELECTRODE

Next: End

ESTABLISH PILOT

THERMOCOUPLE

Next: End

DHW DEMAND LED OFF

DHW FLOW SWITCH

Next: End

DHW DEMAND LED OFF

DHW DEMAND SWITCH

Next: End

ESTABLISH PILOT

OVERHEAT THERMOSTAT

Next: End

DHW BURNER CYCLING ON AND OFF

FAN VENTURI

Next: End

DHW BURNER CYLING ON AND OFF

AIR PRESSURE TUBE

Next: End

DHW BURNER CYCLING ON AND OFF

HEAT EXCHANGER

Next: End

DHW BURNER MODUALTION

DHW TEMPERATURE SENSOR

Next: End

DHW BURNER MODULATION

DISPLAY BOARD (DHW POTENTIOMETER)

Next: End

DHW BURNER IGNITES

AIR PRESSURE SWITCH

Next: End

DOES NOT CROSS LIGHT

AIR PRESSURE TUBE

Next: End

DOES NOT CROSS LIGHT

FAN VENTURI

Next: End

DOES NOT CROSS LIGHT

FAN

Next: End

DHW BURNER IGNITES

FLUE

Next: End

DHW BURNER IGNITES

INLET PRESSURE

Next: End

PILOT IGNITION

INLET PRESSURE

Next: End

DHW BURNER PRESSURE MIN

INLET PRESSURE

Next: End

DHW BURNER PRESSURE

DHW TEMPERATURE SENSOR

Next: End

DHW BURNER PRESSURE

DISPLAY BOARD (DHW POTENTIOMETER)

Next: End

DHW BURNER PRESSURE MAX

INLET PRESSURE

Next: End

BURNER CYCLES ON AND OFF

AIR PRESSURE SWITCH

Next: End

BOILER CYCLES ON AND OFF

DHW OVERHEAT THERMOSTAT

Next: End

CH FULL RATE

WATER PUMP

Next: End

CH FULL RATE - SHUTTING DOWN

CH TEMPERATURE SENSOR

Next: End

CH FULL RATE - STAYING ON LOW

CH TEMPERATURE SENSOR

Next: End

CH PUMP RUNNING

MODULATION CONTROL BOARD

Next: End

MODULATION BOARD VOLTAGE

MODULATION CONTROL BOARD

Next: End

CH BURNER MODULATION

CH TEMPERATURE SENSOR

Next: End

DHW MODULATION - CYCLES

DHW TEMPERATURE SENSOR

Next: End

FUSE INVESTIGATION

WATER PUMP

Next: End

MAINS LED

DISPLAY BOARD CABLE

Next: End

FUSE INVESTIGATION

FAN

Next: End

FUSE INVESTIGATION

SOLENOID OPERATOR - SIT

Next: End

FUSE INVESTIGATION

GAS VALVE

Next: End

FUSE INVESTIGATION

TRANSFORMER

Next: End

MAINS LED

FUSE F1

Next: End

FUSE F1

MODULATION CONTROL BOARD

Next: End

MAINS LED

MAINS FUSE

Next: End

FUSE INVESTIGATION

WATER PRESSURE SWITCH

Next: End

OBSERVATION CH FULL RATE

WAX SENSOR

Next: End

LOW SYSTEM PRESSURE LED

SYSTEM PRESSURE

Next: End

LOW SYSTEM PRESSURE LED

WATER SYSTEM PRESSURE SWITCH

Next: End

FROST THERMOSTAT

FROST THERMOSTAT

Next: End

SLOW FAN

TRANSFORMER

Next: End

DHW DEMAND LED ON

DHW FLOW SWITCH

Next: End

DHW DEMAND LED ON

DHW DEMAND SWITCH

Next: End

DHW BOILER SWITCH (POWER IN)

MODULATION CONTROL BOARD

Next: End

DHW HIGH FAN

AIR PRESSURE SWITCH

Next: End

DHW HIGH FAN

DHW OVERHEAT THERMOSTAT

Next: End

DHW HIGH FAN

DISPLAY BOARD CABLE

Next: End

DHW HIGH FAN

DHW TEMPERATURE SENSOR

Next: End

DHW WATER PUMP RUNNING

MODULATION CONTROL BOARD

Next: End

CH HIGH FAN

CH SWITCH

Next: End

CH SWITCH

MODULATION CONTROL BOARD

Next: End

PILOT IGNITION

ELECTRODE ALIGNMENT

Next: End

CH HIGH FAN

Next: End

CH HIGH FAN

CH TEMPERATURE SENSOR

Next: End

CENTRAL HEATING

DRIPPING TAP AND/OR LEAKING SUPPLY

Next: End

PILOT IGNITION

GAS VALVE (THERMOELECTRIC VALVE)

Next: End

ESTABLISH PILOT

GAS VALVE (THERMOELECTRIC VALVE)

Next: End

MAINS LED

DISPLAY BOARD (POWER ON NEON)

Next: End

PILOT SPARKING

PIEZO IGNITER

Next: End

DHW DEMAND LED OFF

MODULATION CONTROL BOARD

Next: End

DHW BURNER CYCLING ON AND OFF

MODULATION CONTROL BOARD

Next: End

DHW BURNER MODULATION

MODULATION CONTROL BOARD

Next: End

DHW BURNER IGNITES

GAS VALVE

Next: End

DHW BURNER IGNITES

MODULATION CONTROL BOARD

Next: End

DHW BURNER MODULATION

GAS VALVE

Next: End

MINIMUM SET WRONG

GAS VALVE

Next: End

DHW BURNER PRESSURE

GAS VALVE

Next: End

DHW BURNER PRESSURE

MODULATION CONTROL BOARD

Next: End

CH FULL RATE

MODULATION CONTROL BOARD

Next: End

CH FULL RATE

MODULATION BOARD POT

Next: End

CH BURNER MODULATION

DISPLAY BOARD (CH POTENTIOMETER)

Next: End

F1 FUSE INVESTIGATION

Z REDIRECT

Next: End

MAINS LED

TRANSFORMER

Next: End

MAINS LED

Next: End

MAINS FUSE FURTHER INVESTIGATION

Z REDIRECT

Next: End

FUSE INVESTIGATION

FUSE BLOWN

Next: End

CH FULL RATE

Next: End

LOW SYSTEM PRESSURE LED

MODULATION CONTROL BOARD

Next: End

SLOW FAN

FAN

Next: End

SLOW FAN

MODULATION CONTROL BOARD

Next: End

DHW DEMAND LED ON

MODULATION CONTROL BOARD

Next: End

DHW HIGH FAN

ON/OFF SWITCH

Next: End

AIR PRESSURE SWITCH: NO AIR

MODULATION CONTROL BOARD

Next: End

DHW WATER PUMP RUNNING

WATER PUMP

Next: End

HOT WATER

WATER SYSTEM PRESSURE SWITCH

Next: End

HOT WATER

DHW FLOW LIMITER

Next: End

BURNER DOES NOT MODULATE

CHARACTERISTIC TEST FROM DHW MODULATION

Next: p177

BURNER REPEATEDLY CUTS OUT BEFORE MODULATION TAKES PLACE

CHARACTERISTIC TEST FROM DHW MODULATION

Next: p238

BOILER REMAINS ON LOW RATE

CHARACTERISTIC TEST FROM OBSERVATION CH FULL RATE

Next: p266

BOILER SHUTS DOWN BEFORE IT CAN RUN FOR 2 MINUTES

CHARACTERISTIC TEST FROM OBSERVATION CH FULL RATE

Next: p268

BOILER INCREASES TO MAXIMUM RATE IMMEDIATELY

CHARACTERISTIC TEST FROM OBSERVATION CH FULL RATE

Next: !p270

BURNER CUTS OUT, LOW WATER PRESSURE, NEON LIGHTS

CHARACTERISTIC TEST FROM HOT WATER

Next: !p77

FLOW RATE DOES NOT INCREASE WITH RISE IN DHW TEMPERATURE

CHARACTERISTIC TEST FROM HOT WATER

Next: !p79

FLOW RATE INCREASES WITH RISE IN DHW TEMPERATURE, BUT NOT TO MAX

CHARACTERISTIC TEST FROM HOT WATER

Next: !p113

DIVERTER VALVE OPERATION

TURN OFF THE MAINS W

Next: !p109, !f108

ELECTRODE LEAD

Next: p140, !f138

THERMOCOUPLE VOLTAGE

CLIP ONE LEAD OF MUL

Next: p17, !f16

DHW FLOW SWITCH OPERATION

Next: p159, !f160

DHW TEMPERATURE SENSOR

Next: p192, !f193

INLET PRESSURE

BOILER SWITCH IN ON

Next: p199, !f212

AIR PRESSURE SWITCH AIR DETECT

DISCONNECT LEADS FRO

Next: p202, !f203

TRANSFORMER VOLTAGE

{GAINPCBACS}
BOILER SWITCH IN ON POSITION

Next: p23, f308

INLET PRESSURE

BOILER SWITCH IN ON

Next: !p220, !f221

INLET PRESSURE

BOILER SWITCH IN ON

Next: p230, !f237

DHW TEMPERATURE SENSOR

Next: p233, !f234

NTC - CH RESISTANCE

Next: !p281, !f282

RESISTANCE PUMP

DISCONNECT INLINE CONNECTOR FOR THE PUMP

Next: p298, !f299

FUSE F1

REMOVE FUSE F1 FROM MODULATION CONTROL BOARD

Next: p309, f310

FUSE FURTHER INVESTIGATION

Next: !p311, !f312

RESISTANCE MAINS FUSE

REMOVE FUSE FROM FUSED SPUR

Next: !p319, f320

SYSTEM PRESSURE

Next: p34, !f33

FUSE FURTHER INVESTIGATION

Next: !p321, !f323

SLOW FAN VOLTAGE

Next: !p40, f39

TRANSFORMER 90V AC

{GAINPCBACS}

Next: !p42, !f41

DHW FLOW SWITCH

Next: p45, !f44

BOILER SWITCH (POWER OUT)

{GAINPCBACS}
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION

Next: p52, f51

DHW BOILER SWITCH (POWER IN)

BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION

Next: !p54, !f53

WATER PUMP VOLTAGE

BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN CONSTANT POSITION

Next: !p75, !f74

IGNITE PILOT WITH MATCH

TURN GAS CONTROL KNOB TO PILOT POSITION

Next: !p10, f9

INLET PRESSURE PILOT

CONNECT PRESSURE GAU

Next: p12, !f213

ROOM THERMOSTAT

{GAINPCBACS}
CENTRAL HEATING SWITCH IN CONSTANT POSITION
ROOM THERMOSTAT CALLING FOR HEAT

Next: p96, f95

CH SWITCH

CENTRAL HEATING SWITCH IN CONSTANT POSITION

Next: p98, !f97

PILOT BURNER BLOCKED

Next: !p124, !f14

SPARK ELECTRODE INSPECTION

REMOVE SPARK ELECTRODE

Next: !p142, !f141

DHW MICROSWITCH

REMOVE BOTH ORANGE WIRES FROM DHW DEMAND MICROSWITCH

Next: !p161, !f162

CH OVERHEAT THERMOSTAT

REMOVE WHITE LEADS FROM OVERHEAT THERMOSTAT

Next: !p125, !f18

MODUREG VOLTAGE

BOILER SWITCH IN ON

Next: !p218, f191

INSPECTION FAN VENTURI

REMOVE THE FAN VENTURI, TOP OF HEAT EXCHANGER
AND SIDE OF FAN ASSEMBLY

Next: p180, !f181

AIR PRESSURE SWITCH TUBES

Next: p182, !f183

INSPECTION FAN ASSEMBLY

REMOVE FAN ASSEMBLY FROM BOILER

Next: p184, !f185

HEAT EXCHANGER INSPECTION

Next: p186, !f187

FLUE INSPECTION

Next: !p188, !f189

DHW POTENTIOMETER

TURN/SET THE HOT WATER CONTROL (POTENTIOMETER) TO APPROXIMATELY MID POSITION

Next: !p194, !f195

GV2 MAIN SOLENOID VOLTAGE

{GAINPCBACS}
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION

Next: !p200, f201

INSPECTION TUBES AIR PRESSURE

Next: p204, !f205

INSPECTION FAN VENTURI

REMOVE THE FAN VENTURI, TOP OF HEAT EXCHANGER
AND SIDE OF FAN ASSEMBLY

Next: p206, !f207

INSPECTION FAN ASSEMBLY

REMOVE FAN ASSEMBLY FROM BOILER

Next: p208, !f209

FLUE INSPECTION

Next: !p210, !f211

MODULATION BOARD VOLTAGE

LOWER FRONT FASCIA PANEL

Next: p29, !f28

GV3 MODULATING SOLENOID VOLTAGE

BOILER SWITCH IN ON

Next: !p231, f232

DHW POTENTIOMETER

TURN/SET THE HOT WATER CONTROL (POTENTIOMETER) TO APPROXIMATELY MID POSITION

Next: !p235, !f236

AIR PRESSURE SWITCH TEST

DISCONNECT LEADS FRO

Next: p250, !f262

DHW LIMIT THERMOSTAT

REMOVE PURPLE WIRES FROM DHW LIMIT THERMOSTAT

Next: p283, !f263

NTC - CH RESISTANCE

Next: !p275, !f276

PUMP LIMPET TEST

Next: p271, !f272

NTC - CH RESISTANCE

Next: p327, !f274

DHW TEMPERATURE SENSOR

Next: p179, !f295

DISPLAY BOARD CABLE

VISUAL AND MECHANICAL SOUNDNESS CHECK OF THE CONNECTIONS.

Next: !p127, !f30

RESISTANCE FAN

DISCONNECT INLINE CONNECTOR FOR THE PUMP

Next: p300, !f301

RESISTANCE GAS VALVE OPERATING SOLENOID

REMOVE PLUG FROM THE

Next: p302, !f303

RESISTANCE GAS VALVE MOD SOLENOID

DISCONNECT SPADE CONNECTORS FROM MODULATING SOLENOID

Next: p304, !f305

RESISTANCE TRANSFORMER

DISCONNECT CONNECTOR PL6 AT THE PCB

Next: p324, !f307

MAINS POWER SUPPLY

LOWER CONTROL PANEL (HINGED)

Next: p313, f314

TRANSFORMER INPUT (240 VOLTS)

Next: !p317, !f318

RESISTANCE WATER PRESSURE SWITCH TO EARTH

REMOVE BOTH YELLOW LEADS FROM WATER PRESSURE SWITCH

Next: !p325, !f326

DIVERTER VALVE OPERATION

TURN OFF THE MAINS W

Next: !p328, !f329

WATER PRESSURE SWITCH

REMOVE BOTH YELLOW LEADS FROM WATER PRESSURE SWITCH

Next: !p36, !f35

DHW DEMAND SWITCH

REMOVE BOTH ORANGE WIRES FROM DHW DEMAND SWITCH

Next: !p49, !f48

AIR PRESSURE SWITCH NO AIR

REMOVE ORANGE AND PURPLE WIRES FROM AIR PRESSURE SWITCH

Next: p56, !f55

DHW LIMIT THERMOSTAT

REMOVE PURPLE WIRES FROM DHW LIMIT THERMOSTAT

Next: p58, !f57

DISPLAY BOARD CABLE

VISUAL AND MECHANICAL SOUNDNESS CHECK OF THE CONNECTIONS.

Next: p60, !f59

NTC - DHW RESISTANCE

Next: !p62, !f61

BOILER SWITCH

CENTRAL HEATING SWITCH IN CONSTANT POSITION
BOILER SWITCH IN ON POSITION

Next: !p102, !f101

ROOM THERMOSTAT (VOLTAGE INPUT)

CENTRAL HEATING SWITCH IN CONSTANT POSITION
ROOM THERMOSTAT CALLING FOR HEAT

Next: !p100, !f99

System Information

  • Total Tests: 206
  • Sequence Logic: Decoded from encrypted .seq file
  • Navigation: Dynamic based on pass/fail results
  • Source: 4731307 GW SWIFTFLOW 100 SIT Control