POTTERTON PUMA 80 (S.I.T.)
GLOBALLY REPLACED
PUMP OVERRUN
BOILER SWITCH IN ON
CENTRAL HEATING
CENTRAL HEATING SWITCH IN CONSTANT POSITION
BOILER SWITCH IN ON POSITION
CH HIGH FAN
CENTRAL HEATING SWITCH IN CONSTANT POSITION
BOILER SWITCH IN ON POSITION
ENSURE BOILER IS COOL
HOT WATER
BOILER SWITCH IN ON
DHW WATER PUMP RUNNING
BOILER SWITCH IN ON
DHW HIGH FAN
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION
DHW DEMAND LED ON
{GAINPCBACS}
BOIL
SLOW FAN
BOILER SWITCH IN STANDBY POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION
FROST THERMOSTAT
{GAINPCBACS}
CENTRAL HEATING SWITCH OFF
DISCONNECT PLUG PL1
LOW SYSTEM PRESSURE LED
BOILER SWITCH IN STANDBY POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION
MAINS LED
BOILER SWITCH IN STANDBY POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION
ESTABLISH PILOT
BOILER SWITCH IN STA
PILOT IGNITION
BOILER SWITCH IN STA
PILOT SPARKING
BOILER SWITCH IN STANDBY POSITION
CENTRAL HEATING SWITCH IN OFF(CENTRAL) POSITION
POTTERTON PUMA 80 (S.I.T.)
G.C. NUMBER 47 590 1
DHW BURNER IGNITES
BOILER SWITCH IN ON
DHW DEMAND LED OFF
BOILER SWITCH IN STA
DHW BURNER PRESSURE MINIMUM
ATTACH PRESSURE GAUG
DHW BURNER PRESSURE MAXIMUM
ATTACH PRESSURE GAUG
DHW MODULATION
ATTACH PRESSURE GAUG
OBSERVATION CH FULL RATE
ATTACH PRESSURE GAUG
CH PUMP RUNNING
SLACKEN WATER PUMP MANUAL RESTART NUT, TAKE CARE TO SAFELY CONTAIN ANY WATER RELEASED
CH BURNER MODULATION
CENTRAL HEATING SWIT
ELECTRICAL SAFETY CHECKS
ELECTRICAL CHECKS
BOILER SWITCH
MODULATION CONTROL BOARD
CENTRAL HEATING
DIVERTER VALVE
PUMP OVERRUN
MODULATION CONTROL BOARD
PILOT FLAME FAILURE
GAS VALVE (THERMOELECTRIC VALVE)
PILOT SPARKING
ELECTRODE LEAD
PILOT IGNITION
PILOT ASSEMBLY
PILOT SPARKING
SPARK ELECTRODE
ESTABLISH PILOT
THERMOCOUPLE
DHW DEMAND LED OFF
DHW FLOW SWITCH
DHW DEMAND LED OFF
DHW DEMAND SWITCH
ESTABLISH PILOT
OVERHEAT THERMOSTAT
DHW BURNER CYCLING ON AND OFF
FAN VENTURI
DHW BURNER CYLING ON AND OFF
AIR PRESSURE TUBE
DHW BURNER CYCLING ON AND OFF
HEAT EXCHANGER
DHW BURNER MODUALTION
DHW TEMPERATURE SENSOR
DHW BURNER MODULATION
DISPLAY BOARD (DHW POTENTIOMETER)
DHW BURNER IGNITES
AIR PRESSURE SWITCH
DOES NOT CROSS LIGHT
AIR PRESSURE TUBE
DOES NOT CROSS LIGHT
FAN VENTURI
DHW BURNER IGNITES
FLUE
DHW BURNER IGNITES
INLET PRESSURE
PILOT IGNITION
INLET PRESSURE
DHW BURNER PRESSURE MIN
INLET PRESSURE
DHW BURNER PRESSURE
DHW TEMPERATURE SENSOR
DHW BURNER PRESSURE
DISPLAY BOARD (DHW POTENTIOMETER)
DHW BURNER PRESSURE MAX
INLET PRESSURE
BURNER CYCLES ON AND OFF
AIR PRESSURE SWITCH
BOILER CYCLES ON AND OFF
DHW OVERHEAT THERMOSTAT
CH FULL RATE
WATER PUMP
CH FULL RATE - SHUTTING DOWN
CH TEMPERATURE SENSOR
CH FULL RATE - STAYING ON LOW
CH TEMPERATURE SENSOR
CH PUMP RUNNING
MODULATION CONTROL BOARD
MODULATION BOARD VOLTAGE
MODULATION CONTROL BOARD
CH BURNER MODULATION
CH TEMPERATURE SENSOR
DHW MODULATION - CYCLES
DHW TEMPERATURE SENSOR
FUSE INVESTIGATION
WATER PUMP
MAINS LED
DISPLAY BOARD CABLE
FUSE INVESTIGATION
SOLENOID OPERATOR - SIT
FUSE INVESTIGATION
GAS VALVE
FUSE INVESTIGATION
TRANSFORMER
MAINS LED
FUSE F1
FUSE F1
MODULATION CONTROL BOARD
MAINS LED
MAINS FUSE
FUSE INVESTIGATION
WATER PRESSURE SWITCH
OBSERVATION CH FULL RATE
WAX SENSOR
LOW SYSTEM PRESSURE LED
SYSTEM PRESSURE
LOW SYSTEM PRESSURE LED
WATER SYSTEM PRESSURE SWITCH
FROST THERMOSTAT
FROST THERMOSTAT
SLOW FAN
TRANSFORMER
DHW DEMAND LED ON
DHW FLOW SWITCH
DHW DEMAND LED ON
DHW DEMAND SWITCH
DHW BOILER SWITCH (POWER IN)
MODULATION CONTROL BOARD
DHW HIGH FAN
AIR PRESSURE SWITCH
DHW HIGH FAN
DHW OVERHEAT THERMOSTAT
DHW HIGH FAN
DISPLAY BOARD CABLE
DHW HIGH FAN
DHW TEMPERATURE SENSOR
DHW WATER PUMP RUNNING
MODULATION CONTROL BOARD
CH HIGH FAN
CH SWITCH
CH SWITCH
MODULATION CONTROL BOARD
PILOT IGNITION
ELECTRODE ALIGNMENT
CH HIGH FAN
CH TEMPERATURE SENSOR
CENTRAL HEATING
DRIPPING TAP AND/OR LEAKING SUPPLY
PILOT IGNITION
GAS VALVE (THERMOELECTRIC VALVE)
ESTABLISH PILOT
GAS VALVE (THERMOELECTRIC VALVE)
MAINS LED
DISPLAY BOARD (POWER ON NEON)
PILOT SPARKING
PIEZO IGNITER
DHW DEMAND LED OFF
MODULATION CONTROL BOARD
DHW BURNER CYCLING ON AND OFF
MODULATION CONTROL BOARD
DHW BURNER MODULATION
MODULATION CONTROL BOARD
DHW BURNER IGNITES
GAS VALVE
DHW BURNER IGNITES
MODULATION CONTROL BOARD
DHW BURNER MODULATION
GAS VALVE
MINIMUM SET WRONG
GAS VALVE
DHW BURNER PRESSURE
GAS VALVE
DHW BURNER PRESSURE
MODULATION CONTROL BOARD
CH FULL RATE
MODULATION CONTROL BOARD
CH FULL RATE
MODULATION BOARD POT
CH BURNER MODULATION
DISPLAY BOARD (CH POTENTIOMETER)
F1 FUSE INVESTIGATION
Z REDIRECT
MAINS LED
TRANSFORMER
MAINS FUSE FURTHER INVESTIGATION
Z REDIRECT
FUSE INVESTIGATION
FUSE BLOWN
LOW SYSTEM PRESSURE LED
MODULATION CONTROL BOARD
SLOW FAN
FAN
SLOW FAN
MODULATION CONTROL BOARD
DHW DEMAND LED ON
MODULATION CONTROL BOARD
DHW HIGH FAN
ON/OFF SWITCH
AIR PRESSURE SWITCH: NO AIR
MODULATION CONTROL BOARD
DHW WATER PUMP RUNNING
WATER PUMP
HOT WATER
WATER SYSTEM PRESSURE SWITCH
HOT WATER
DHW FLOW LIMITER
BURNER DOES NOT MODULATE
CHARACTERISTIC TEST FROM DHW MODULATION
BURNER REPEATEDLY CUTS OUT BEFORE MODULATION TAKES PLACE
CHARACTERISTIC TEST FROM DHW MODULATION
BOILER REMAINS ON LOW RATE
CHARACTERISTIC TEST FROM OBSERVATION CH FULL RATE
BOILER SHUTS DOWN BEFORE IT CAN RUN FOR 2 MINUTES
CHARACTERISTIC TEST FROM OBSERVATION CH FULL RATE
BOILER INCREASES TO MAXIMUM RATE IMMEDIATELY
CHARACTERISTIC TEST FROM OBSERVATION CH FULL RATE
BURNER CUTS OUT, LOW WATER PRESSURE, NEON LIGHTS
CHARACTERISTIC TEST FROM HOT WATER
FLOW RATE DOES NOT INCREASE WITH RISE IN DHW TEMPERATURE
CHARACTERISTIC TEST FROM HOT WATER
FLOW RATE INCREASES WITH RISE IN DHW TEMPERATURE, BUT NOT TO MAX
CHARACTERISTIC TEST FROM HOT WATER
18/07/2018 11:14:56 1807_1_50_1 20/07/2018 14:22:27
18/07/2018 14:33:33
DIVERTER VALVE OPERATION
TURN OFF THE MAINS W
THERMOCOUPLE VOLTAGE
CLIP ONE LEAD OF MUL
INLET PRESSURE
BOILER SWITCH IN ON
AIR PRESSURE SWITCH AIR DETECT
DISCONNECT LEADS FRO
TRANSFORMER VOLTAGE
{GAINPCBACS}
BOILER SWITCH IN ON POSITION
INLET PRESSURE
BOILER SWITCH IN ON
INLET PRESSURE
BOILER SWITCH IN ON
RESISTANCE PUMP
DISCONNECT INLINE CONNECTOR FOR THE PUMP
FUSE F1
REMOVE FUSE F1 FROM MODULATION CONTROL BOARD
RESISTANCE MAINS FUSE
REMOVE FUSE FROM FUSED SPUR
TRANSFORMER 90V AC
{GAINPCBACS}
BOILER SWITCH (POWER OUT)
{GAINPCBACS}
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION
DHW BOILER SWITCH (POWER IN)
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION
WATER PUMP VOLTAGE
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN CONSTANT POSITION
IGNITE PILOT WITH MATCH
TURN GAS CONTROL KNOB TO PILOT POSITION
INLET PRESSURE PILOT
CONNECT PRESSURE GAU
ROOM THERMOSTAT
{GAINPCBACS}
CENTRAL HEATING SWITCH IN CONSTANT POSITION
ROOM THERMOSTAT CALLING FOR HEAT
CH SWITCH
CENTRAL HEATING SWITCH IN CONSTANT POSITION
SPARK ELECTRODE INSPECTION
REMOVE SPARK ELECTRODE
DHW MICROSWITCH
REMOVE BOTH ORANGE WIRES FROM DHW DEMAND MICROSWITCH
CH OVERHEAT THERMOSTAT
REMOVE WHITE LEADS FROM OVERHEAT THERMOSTAT
MODUREG VOLTAGE
BOILER SWITCH IN ON
INSPECTION FAN VENTURI
REMOVE THE FAN VENTURI, TOP OF HEAT EXCHANGER
AND SIDE OF FAN ASSEMBLY
INSPECTION FAN ASSEMBLY
REMOVE FAN ASSEMBLY FROM BOILER
DHW POTENTIOMETER
TURN/SET THE HOT WATER CONTROL (POTENTIOMETER) TO APPROXIMATELY MID POSITION
GV2 MAIN SOLENOID VOLTAGE
{GAINPCBACS}
BOILER SWITCH IN ON POSITION
CENTRAL HEATING SWITCH IN OFF (CENTRAL) POSITION
INSPECTION FAN VENTURI
REMOVE THE FAN VENTURI, TOP OF HEAT EXCHANGER
AND SIDE OF FAN ASSEMBLY
INSPECTION FAN ASSEMBLY
REMOVE FAN ASSEMBLY FROM BOILER
MODULATION BOARD VOLTAGE
LOWER FRONT FASCIA PANEL
GV3 MODULATING SOLENOID VOLTAGE
BOILER SWITCH IN ON
DHW POTENTIOMETER
TURN/SET THE HOT WATER CONTROL (POTENTIOMETER) TO APPROXIMATELY MID POSITION
AIR PRESSURE SWITCH TEST
DISCONNECT LEADS FRO
DHW LIMIT THERMOSTAT
REMOVE PURPLE WIRES FROM DHW LIMIT THERMOSTAT
DISPLAY BOARD CABLE
VISUAL AND MECHANICAL SOUNDNESS CHECK OF THE CONNECTIONS.
RESISTANCE FAN
DISCONNECT INLINE CONNECTOR FOR THE PUMP
RESISTANCE GAS VALVE OPERATING SOLENOID
REMOVE PLUG FROM THE
RESISTANCE GAS VALVE MOD SOLENOID
DISCONNECT SPADE CONNECTORS FROM MODULATING SOLENOID
RESISTANCE TRANSFORMER
DISCONNECT CONNECTOR PL6 AT THE PCB
MAINS POWER SUPPLY
LOWER CONTROL PANEL (HINGED)
RESISTANCE WATER PRESSURE SWITCH TO EARTH
REMOVE BOTH YELLOW LEADS FROM WATER PRESSURE SWITCH
DIVERTER VALVE OPERATION
TURN OFF THE MAINS W
WATER PRESSURE SWITCH
REMOVE BOTH YELLOW LEADS FROM WATER PRESSURE SWITCH
DHW DEMAND SWITCH
REMOVE BOTH ORANGE WIRES FROM DHW DEMAND SWITCH
AIR PRESSURE SWITCH NO AIR
REMOVE ORANGE AND PURPLE WIRES FROM AIR PRESSURE SWITCH
DHW LIMIT THERMOSTAT
REMOVE PURPLE WIRES FROM DHW LIMIT THERMOSTAT
DISPLAY BOARD CABLE
VISUAL AND MECHANICAL SOUNDNESS CHECK OF THE CONNECTIONS.
BOILER SWITCH
CENTRAL HEATING SWITCH IN CONSTANT POSITION
BOILER SWITCH IN ON POSITION
ROOM THERMOSTAT (VOLTAGE INPUT)
CENTRAL HEATING SWITCH IN CONSTANT POSITION
ROOM THERMOSTAT CALLING FOR HEAT
System Information
- Total Tests: 206
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control