This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.

Start Diagnostic Sequence

or choose a specific test below:

4758324 BIASI RIVA PLUS HE M296 24SM/C

WARNING - IMPORTA

Next: &1, *

NO FAULT FOUND

Next: nff

TYPE OF DIAGNOSTIC PROCEDURE

Next: &1142, !f4

POWER UP

ON/OFF SWITCH ON

Next: &50, f29

DHW FLOW RATE

Next: &132, f51

DHW FAN RUNS

Next: &193, f113

DHW DEMAND

Next: &138, f133

DHW PUMP RUNS

Next: &81, f159

FAN RUNS BURNER IGNITES AND ESTABLISHES DHW DEMAND

ATTACH "U"GAUGE TO OUTLET PRESSURE TEST POINT
ON / OFF SWITCH ON

Next: &286, ?196, ?198, ?200, ?202

OPERATION DHW

Next: &1666, ?287, ?289, ?291, ?293, ?295

OPERATION CH

FLOW AND RETURN VALVES FULLY OPEN
CH THERMOSTAT SET TO MAX

Next: &1668, ?597, ?599, ?601, ?603, ?605, ?607

DOES BOILER RESPOND TO CH DEMAND

CH THERMOSTAT UP TO MAX ON BOILER
ON/OFF SWITCH ON

Next: &596, f659

FURTHER INVESTIGATION OVERHEAT

Next: &nff, f1909

FURTHER INVESTIGATION FUSE

Next: &nff, ?980, ?982

OPERATIONAL SEQUENCE

Next: &1144, !f1143

FAULT CODES

Next: &28, !f1145

PRIMARY FAULTY SENSOR LOCKOUT

OUTSIDE MODEL OK TO BE BLANK

Next: &nff, f1467

DHW FAULTY SENSOR LOCKOUT

Next: &nff, f1479

FLUE TEMP NTC LOCKOUT

Next: &nff, f1485

FLUE SENSOR FAULTY LOCKOUT

Next: &nff, f1506

PRIMARY FLOW FAULTY

OK TO BE BLANK, CHARACTERISTICS USED AS A HEADER.

Next: &nff, ?1517, ?1519

AIR PRESSURE SENSOR FAULT

Next: &nff, f1600

SAFETY OVERHEAT LOCKOUT

OUTSIDE MODEL

Next: &nff, f1806

DOES FAN AND PUMP OVERRUN AFTER DHW DEMAND

SELECTOR SWITCH TO HW

Next: &658, !f1667

BOILER FIRES WITH NO DEMAND

OUTSIDE MODEL

Next: &nff, f2093

INFORMATION SERIAL NUMBER DEPENDENT XSOL MODEL

PLEASE NOTE THIS XSO

Next: &3, !f2134

HARNESS - FAN/APS/FLUE NTC

HARNESS - FAN/APS/FLUE NTC

Next: End

FLUEWAYS

HEAT EXCHANGER CONDENSING

Next: End

NO FAN

SENSOR TEMP PRIMARY

Next: End

NO FAN

SENSOR TEMP DHW

Next: End

POOR DHW RADS HOT NO DEMAND

HEAT EXCHANGER DHW

Next: End

DHW KETTLING

TRAP - CONDENSATE

Next: End

OPEN OR SHORT CIRCUITFURTHER INVESTIGATION FUSE F1

GAS VALVE SOLENOID MAIN

Next: End

OPEN OR SHORT CIRCUITFURTHER INVESTIGATION FUSE F1

GAS VALVE SOLENOID MODULATING

Next: End

OPERATIONAL SEQUENCE

DIRECTION CHOICE OR CONTINUE

Next: End

FAULT CODES

DIRECTION CHOICE OR CONTINUE

Next: End

DHW HOT THEN COLDHOT THEN COLD DHWDIFF

HEAT EXCHANGER CONDENSING

Next: End

FURTHER INVESTIGATION F1

DIVERTER VALVE HEAD

Next: End

FURTHER INVEST F2&3

DIVERTER VALVE HEAD

Next: End

DHW HOT THEN COLD

SENSOR TEMP DHW

Next: End

DHW RUNS HOT THEN COLD

SENSOR TEMP PRIMARY

Next: End

NO DHW PUMPDHW PUMP RUNS

HARNESS-PUMP/ DIVERTER/GAS VALVE

Next: End

DHW DEMAND

DHW FLOW SWITCH

Next: End

NO DHW PUMPNO DHW PUMP

SENSOR TEMP PRIMARY

Next: End

NO PUMP DHWNO DHW PUMP

SENSOR TEMP DHW

Next: End

NO PUMP DHWNO DHW PUMP

FLUE NTC PROBE

Next: End

NO PUMPNO DHW PUMP

THERMOSTAT - OVERHEAT - COMBUSTION CHAMBER

Next: End

NO PUMPNO DHW PUMP

SAFETY OVERHEAT STAT

Next: End

NO PUMPNO DHW PUMP

SYSTEM PRESSURE

Next: End

NO PUMPNO DHW PUMP

HARNESS - FAN/APS/FLUE NTC

Next: End

DHW PUMP RUNS

PUMP

Next: End

INCORREST RESISTANCES

PUMP

Next: End

CH LOCKOUT

SENSOR TEMP PRIMARY

Next: End

COOL DHWDHW HOT THEN COLDFLUE SENSOR LOCKOUT

TRAP - CONDENSATE

Next: End

DHW HOT THEN COLDFLUE SENSOR LOCKOUT

FLUE NTC PROBE

Next: End

FAULTY FLUE NTC

FLUE NTC PROBE

Next: End

PRIMARY CIRCUIT FAULTY

SYSTEM PRESSURE

Next: End

LOCKOUT PRIMARY CIRCUIT FAULTY

PRIMARY CIRCUIT PRESSURE SWITCH

Next: End

NO DHW PUMPDHW PUMP RUNSPRIMARY CIRCUIT FAULTY2

HARNESS-PUMP/ DIVERTER/GAS VALVE

Next: End

DHW HOT THEN COLDFAULTY PRIMARY CIRCUIT

SENSOR TEMP DHW

Next: End

DHW RUNS HOT THEN COLDFAULTY PRIMARY CIRCUIT

SENSOR TEMP PRIMARY

Next: End

FAULTY PRIMARY CIRCUIT

PCB

Next: End

FAULTY AIR PRESSURE

HARNESS - FAN/APS/FLUE NTC

Next: End

FAN DOESNT RUN

Z DIRECTION CHOICE OR CONTINUE

Next: End

BOILER GOES TO OVERHEATOVERHEAT

SAFETY OVERHEAT STAT

Next: End

OVERHEATOVERHEAT

THERMOSTAT - OVERHEAT - COMBUSTION CHAMBER

Next: End

NO DHW DEMAND

DHW FLOW SWITCH

Next: End

BOILER TO TEMP RADS COLD

BYPASS (INTEGRAL APPLIANCE)

Next: End

FLOW AND RETURN VALVES

FLOW AND RETURN VALVES

Next: End

NO DHW OVERUN

PCB

Next: End

CH OVERUN

PCB

Next: End

NO SPARK

HARNESS IGNITION

Next: End

NO FAN

SYSTEM PRESSURE

Next: End

BURNER IGNITES

ELECTRODE SENSE

Next: End

BURNERIGNITES

CABLE - ELECTRODE FLAME DETECTION

Next: End

POSITION

ELECTRODE SENSE

Next: End

BURNER IGNITES BUT DOES NOT ESTABLISH

GAS PRESSURE INLET

Next: End

CANNOT BE ADJUSTED HW HOT THEN COLD

GAS VALVE SOLENOID MODULATING

Next: End

NO CH MODULATION

PCB

Next: End

BOILER TEMP LOW SYSTEM TEMP LOW

SENSOR TEMP PRIMARY

Next: End

IMPELLOR LOOSE

PUMP

Next: End

OVERHEATOVERHEAT FURTHER

PUMP

Next: End

OVERHEATOVERHEAT FURTHER

SENSOR TEMP PRIMARY

Next: End

OVERHEATOVERHEAT FURTHER

SENSOR TEMP DHW

Next: End

OVERHEATOVERHEAT FURTHER

THERMOSTAT - OVERHEAT - COMBUSTION CHAMBER

Next: End

OVERHEATOVERHEAT FURTHER

SAFETY OVERHEAT STAT

Next: End

NO AIR PRESSURE

HEAT EXCHANGER PRIMARY FLUE WAYS BAFFLES

Next: End

BOILER GOES TO OVERHEAT

SAFETY OVERHEAT STAT

Next: End

OVERHEAT

THERMOSTAT - OVERHEAT - COMBUSTION CHAMBER

Next: End

NO SHUT DOWN

GAS VALVE

Next: End

FAN RUNS SPARKING OCCURS BURNER DOES NOT IGNITE

HARNESS-PUMP/ DIVERTER/GAS VALVE

Next: End

NO POWER TO GAS VALVE

PCB

Next: End

COMBUSTION CHAMBER OVERHEAT

TRAP - CONDENSATE

Next: End

OVERHEAT

BURNER

Next: End

OVERHEAT

HEAT EXCHANGER PRIMARY FLUE WAYS BAFFLES

Next: End

CASE REMOVAL

DIRECTION CHOICE OR CONTINUE

Next: End

DHW COOL RADS COOL

PUMP

Next: End

DHW FAN RUNS

FLUE NTC PROBE

Next: End

DHW FAN RUNS NOT

HARNESS - FAN/APS/FLUE NTC

Next: End

DHW FAN RUNS

TUBE IMPULSE AIR PRESSURE

Next: End

NO VOLTAGE TO APS

PCB

Next: End

CANNOT BE ADJUSTED HW TOO HOT

GAS VALVE SOLENOID MODULATING

Next: End

DHW TOO HOT

SENSOR TEMP DHW

Next: End

DHW TOO HOT

SENSOR TEMP PRIMARY

Next: End

CONTAMINATION COMBSTION AIR

FLUE SEALS

Next: End

DHW COOL RADS COLD NO DEMAND

SENSOR TEMP DHW

Next: End

DHW COOL RADS COLD NO DEMAND

SENSOR TEMP PRIMARY

Next: End

COOL DHW

TRAP - CONDENSATE

Next: End

POOR DHW

BYPASS (INTEGRAL APPLIANCE)

Next: End

DHW COOL RADS COOL

HEAT EXCHANGER DHW

Next: End

AIR INTAKE CONTAMINATION

COMBUSTION CHAMBER

Next: End

SYSTEM FAULT

Next: End

FROST

SENSOR TEMP PRIMARY

Next: End

STUCK IN DHW DEMAND

DHW FLOW SWITCH

Next: End

FIRING NO DEMAND

PCB

Next: End

FIRING NO DEMAND 2

PCB

Next: End

NO VOLTAGE TO DIVERTER

PCB

Next: End

POWER DIVERTOR

HARNESS-PUMP/ DIVERTER/GAS VALVE

Next: End

NEW MODEL FLUEWAYS

HEAT EXCHANGER PRIMARY

Next: End

NO POWER TO DIVERTER CH

HARNESS-PUMP/ DIVERTER/GAS VALVE

Next: End

BLANK FOR INFORMATION PAGE

BOILER OVERHEAT

Next: End

POOR SUPPLY

GAS PRESSURE INLET

Next: End

NEW MODELBLOCKED OR DAMAGED

BURNER

Next: End

GAP DAMAGE

ELECTRODES

Next: End

BLOCKED OR DAMAGED FAN RUNS SPARKING DOES NOT OCCUR

TUBE IMPULSE AIR PRESSURE

Next: End

BLOCKED OR DAMAGED

VENTURI

Next: End

NO SPARK

PCB

Next: End

NO SPARK

ELECTRODE SPARK GAP

Next: End

PASSING POOR DHW

DIVERTER VALVE BODY

Next: End

BLOWN STAND BY MODE AT POWER UP

MAIN FUSE FUSED SPUR F1

Next: End

FLOW RATE

FLOW RESTRICTOR

Next: End

FOR TYPE DIAG PROCEDURE

DIRECTION CHOICE OR CONTINUE

Next: End

BLOWN STANDBY MODE AT POWER UP

FUSE MAIN PCB

Next: End

BURNER PRESSUREOPERATION DHW DHW COOL RADS COOL

GAS VALVE ADJUSTMENT

Next: End

BLOWN STANDBY MODE

FUSE MAIN PCB F3

Next: End

BOILER KETTLING DHW OPERATION

BYPASS (INTEGRAL APPLIANCE)

Next: End

LED AT POWER UP

PCB

Next: End

BOILER KETTLING

PUMP

Next: End

SPARKING NO GAS

SAFETY OVERHEAT STAT

Next: End

SPARK NO GAS

THERMOSTAT - OVERHEAT - COMBUSTION CHAMBER

Next: End

POOR FLOW RATE

SERVICE VALVE INLET (WATER INLET)

Next: End

BURNER BAFFLES

TRAP - CONDENSATE

Next: End

FUN RUNS NO SPARK

TRAP - CONDENSATE

Next: End

COOL DHWDHW HOT THEN COLD

TRAP - CONDENSATE

Next: End

UNDER PRESSURE

EXPANSION VESSEL

Next: End

CH OPERATION

SENSOR TEMP PRIMARY

Next: End

NO CH

PCB

Next: End

NO HEATING

PCB

Next: End

INTEGRAL TIMERNO HEATING

PCB

Next: End

DHW HOT THEN COLD

PUMP

Next: End

DHW NOISY

HEAT EXCHANGER CONDENSING

Next: End

CH NOISY

HEAT EXCHANGER CONDENSING

Next: End

NO CH

DIVERTER VALVE BODY

Next: End

CH DEMAND

DHW FLOW SWITCH

Next: End

NO CH DIVERTOR MOVEMENT

PCB

Next: End

CH ANTI-CYCLE

BYPASS (INTEGRAL APPLIANCE)

Next: End

BLOCKED OR DAMAGED

FLUE

Next: End

FURTHER INVESTIGATION

HARNESS-PUMP/ DIVERTER/GAS VALVE

Next: End

FURTHER INVESTION PUMP F2 F3

HARNESS-PUMP/ DIVERTER/GAS VALVE

Next: End

NO FAN

PRIMARY CIRCUIT PRESSURE SWITCH

Next: End

FAN DOES NOT RUN

FAN

Next: End

DHW HOT THEN COLDHOT THEN COLD DHWDIFF

HEAT EXCHANGER DHW

Next: End

DHW HOT THEN COLDHOT THEN COLD DHWDIFF

HEAT EXCHANGER PRIMARY

Next: End

FURTHER INVESTIGATIONF1

HARNESS-PUMP/ DIVERTER/GAS VALVE

Next: End

FURTHER INVEST F2&3

HARNESS-PUMP/ DIVERTER/GAS VALVE

Next: End

DHW HOT THEN COLD

FLUE NTC PROBE

Next: End

NO DHW DEMAND

PCB

Next: End

NO DHW PUMPNO DHW PUMP

HARNESS SENSOR TEMP PRIMARY

Next: End

NO PUMP DHWNO DHW PUMP

HARNESS SENSOR TEMP DHW

Next: End

FLUE SENSOR HARNESS NO PUMPNO DHW PUMP

HARNESS - FAN/APS/FLUE NTC

Next: End

SAFTEY THERMOSTATS NO PUMPNO DHW PUMP

HARNESS - FAN/APS/FLUE NTC

Next: End

NO PUMPNO DHW PUMP

PRIMARY CIRCUIT PRESSURE SWITCH

Next: End

DHW PUMPNO DHW PUMP

PCB

Next: End

NO PUMP[NO DHW PUMP

AIR PRESSURE SENSOR

Next: End

PUMP NOT RUNNING

PUMP CAPACITOR

Next: End

CH LOCKOUT

PCB

Next: End

CH LOCKOUT

HARNESS SENSOR TEMP PRIMARY

Next: End

NO PUMP DHWNO DHW PUMPDHW LOCKOUTDHW LOCKOUT

HARNESS SENSOR TEMP DHW

Next: End

DHW LOCKOUT

PCB

Next: End

FLUE SENSOR LOCKOUT

HARNESS - FAN/APS/FLUE NTC

Next: End

FLUE SENSOR LOCKOUT

PCB

Next: End

FAULTY FLUE NTC

PCB

Next: End

FAULTY FLUE NTC

HARNESS - FAN/APS/FLUE NTC

Next: End

PRIMARY CIRCUIT FAULTY

PCB

Next: End

LOCKOUT PRIMARY CIRCUIT FAULTY

HARNESS PRIMARY CIRCUIT SWITCH

Next: End

PUMP NOT RUNNINGPRIMARY CIRCUIT FAULTY2

PUMP CAPACITOR

Next: End

AIR PRESSURE LOCKOUT

PCB

Next: End

AIR PRESSURE FAULT

AIR PRESSURE SENSOR

Next: End

FAN RUNS

Z DIRECTION CHOICE OR CONTINUE

Next: End

OVERHEAT

BOILER OVERHEAT

Next: End

OVERHEATOVERHEAT

HARNESS SAFETY STATS

Next: End

LEAD NO SPARK

ELECTRODES

Next: End

FLAME SENSE

PCB

Next: End

HIGH_LOW ADJUSTMENT

BURNER PRESSURE ADJUSTMENT

Next: End

IGNITION ADJUSTMENT

BURNER PRESSURE ADJUSTMENT

Next: End

LOW SYSTEM TEMP POT

PCB

Next: End

OVERHEATOVERHEAT

BOILER OVERHEAT

Next: End

UNABLE TO RESET OVERHEAT

PCB

Next: End

SAFTEY STATS OVERHEAT

HARNESS - FAN/APS/FLUE NTC

Next: End

MAIN SOLENIOD

HARNESS-PUMP/ DIVERTER/GAS VALVE

Next: End

FUTHER INVEST F1

HARNESS-PUMP/ DIVERTER/GAS VALVE

Next: End

NO VOLTAGE

CABLE - FAN

Next: End

OVERHEAT

TEMPERATURE OVERHEAT

Next: End

BLOCKAGE

EXPANSION VESSEL PIPE

Next: End

MAINS FUSE

FUSE GONE PCB

Next: End

F1 OR F2

FUSE GONE PCB

Next: End

FUSE F2 F3

CABLE - FAN

Next: End

F1

CABLE - FAN

Next: End

F1

HARNESS MODULATOR

Next: End

F2

HARNESS MODULATOR

Next: End

NO RESET OVERHEAT

PCB

Next: End

OVERHEAT

HARNESS SAFETY STATS

Next: End

OVERHEAT

PCB

Next: End

DHW FAN RUNS

HARNESS - FAN/APS/FLUE NTC

Next: End

DHW FAN RUNS

AIR PRESSURE SENSOR

Next: End

AIR PRESSURE SENSOR

AIR PRESSURE SENSOR

Next: End

DHW TOO HOT

GAS PRESSURE ADJUSTMENT

Next: End

TEMPERATURE CONTROL DHW

PCB

Next: End

AIR INTAKE CONTAMINATION

FLUE

Next: End

POOR DHW OPERATION

FLUE NTC PROBE

Next: End

POOR DHW OPERATION

PCB

Next: End

NO CH BOILER UP TO TEMP

DIVERTER VALVE BODY

Next: End

BOILER FIRES NO DEMAND

FROST PROTECTION

Next: End

CH NO DEMAND

Next: End

FIRING NNO DEMAND

INTEGRAL TIMER

Next: End

VOLTAGE NO MOVEMENT DHW

DIVERTER VALVE HEAD

Next: End

VOLTAGE NO MOVEMENT CH

DIVERTER VALVE HEAD

Next: End

FLAME LIFT OFF

FLUE SEALS

Next: End

DHW NOISY KETTLING

HEAT EXCHANGER DHW

Next: End

PASSING

DIVERTER VALVE BODY

Next: End

FURTHER INVESTIGATION F1

Z DIRECTION CHOICE OR CONTINUE

Next: End

FLOW RATE

HEAT EXCHANGER DHW

Next: End

FURTHER IN VESTIGATION F2

Z DIRECTION CHOICE OR CONTINUE

Next: End

FURTHER IN VESTIGATION F3

DIRECTION CHOICE OR CONTINUE

Next: End

SAFETY THERMOSTATS

HARNESS - FAN/APS/FLUE NTC

Next: End

POOR DHW OPERATIONDHW HOT THEN COLD

FLUE NTC PROBE

Next: End

NO POWER UP

PCB

Next: End

NO CH DEMAND

Next: End

NO CH

INTEGRAL TIMER

Next: End

INTEGRAL TIMERNO CH

INTEGRAL TIMER

Next: End

DHW NOISY KETTLING

HEAT EXCHANGER PRIMARY

Next: End

NO FAN

HARNESS SENSOR TEMP PRIMARY

Next: End

NO FAN

HARNESS SENSOR TEMP DHW

Next: End

CH OPERATION NOISY

HEAT EXCHANGER PRIMARY

Next: End

ANTI CYCLE

PCB

Next: End

FLUE PROBE NTC WITHIN RESISTANCES BUT HOTTER THAN EXPECTED

CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL FLOW RETURN AND TEMPERATURE

Next: p1488

FLUE PROBE NTC AND HARNESS OUT OF RESISTANCE READINGS

CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL FLOW RETURN AND TEMPERATURE

Next: p1501

FAULTY PRIMARY CIRCUIT NO WATER

CHARACTERISTIC TEST FROM PRIMARY FLOW FAULTY

Next: p1523

FAULTY PRIMARY CIRCUIT ABSENCE OF FLOW

CHARACTERISTIC TEST FROM PRIMARY FLOW FAULTY

Next: p1520

FAN RUNS SPARKING DOES NOT OCCUR

CHARACTERISTIC TEST FROM FAN RUNS BURNER IGNITES AND ESTABLISHES DHW DEMAND

Next: p197

FAN RUNS SPARKING OCCURS BURNER DOES NOT IGNITE

CHARACTERISTIC TEST FROM FAN RUNS BURNER IGNITES AND ESTABLISHES DHW DEMAND

Next: p199

BURNER IGNITES BUT DOES NOT ESTABLISH

CHARACTERISTIC TEST FROM FAN RUNS BURNER IGNITES AND ESTABLISHES DHW DEMAND

Next: p1715

BURNER IGNITES BUT BAFFLES OUT OR LIFTS OFF

CHARACTERISTIC TEST FROM FAN RUNS BURNER IGNITES AND ESTABLISHES DHW DEMAND

Next: p203

DHW TOO HOT

CHARACTERISTIC TEST FROM OPERATION DHW

Next: p2037

DHW COOL RADS COLD NO HEAT DEMAND

CHARACTERISTIC TEST FROM OPERATION DHW

Next: p290

DHW COOL RADS HOT WITH NO CH DEMAND

CHARACTERISTIC TEST FROM OPERATION DHW

Next: p292

DHW NOISY KETTLING

CHARACTERISTIC TEST FROM OPERATION DHW

Next: p294

DHW RUNS HOT THEN COLD

CHARACTERISTIC TEST FROM OPERATION DHW

Next: p1771

BOILER KETTLES

CHARACTERISTIC TEST FROM CH OPERATION (FOR HEAT EX DIAG)

Next: p470

FLUE PROBE NTC WITHIN TABLE RANGE BUT TEMP HOTTER THAN 60-70 DEGREES

CHARACTERISTIC TEST FROM RESISTANCE FLUE SENSOR

Next: p564

FLUE PROBE NTC OUT OF RESISTANCE READINGS

CHARACTERISTIC TEST FROM RESISTANCE FLUE SENSOR

Next: !p1287

BOILER NOISY

CHARACTERISTIC TEST FROM OPERATION CH

Next: p598

BOILER UP TO TEMP RADS COLD

CHARACTERISTIC TEST FROM OPERATION CH

Next: p1650

BOILER TEMP LOW SYSTEM TEMP LOW

CHARACTERISTIC TEST FROM OPERATION CH

Next: p1803

OPERATION SATISFACTORY BUT BOILER GOES TO OVER HEAT

CHARACTERISTIC TEST FROM OPERATION CH

Next: p604

SYSTEM PRESSURE RISE EXCESSIVE

CHARACTERISTIC TEST FROM OPERATION CH

Next: p608

TEMP DIFF INCORRECT LOCAL BOILING

CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL FLOW RETURN AND TEMPERATURE

Next: p732

DIFFERENTIAL OK

CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL FLOW RETURN AND TEMPERATURE

Next: !p656

FUSE 1 (3AMP FUSED SPUR)

CHARACTERISTIC TEST FROM FURTHER INVESTIGATION FUSE

Next: p1067

FURTHER INVESTIGATION F1 OR F2 ON PCB

CHARACTERISTIC TEST FROM FURTHER INVESTIGATION FUSE

Next: p1084

NO CH MOVEMENT

DIVERTER VALVE HEAD

Next: End

RESISTANCE GAS VALVE SOLENOID MAIN

REMOVE THE PLUG FROM THE GAS VALVE SOLENOID

Next: !p1905, !f1071

RESISTANCE GAS VALVE SOLENOID MODULATING

REMOVE THE LEADS FROM THE MODULATOR

Next: !p1942, !f1075

PUMP RESISTANCES

Next: !p1108, !f1079

RESISTANCE FAN

Next: !p1941, !f1083

RESISTANCE GAS VALVE SOLENOID MAIN

REMOVE THE PLUG FROM THE GAS VALVE SOLENOID

Next: !p1903, !f1088

RESISTANCE GAS VALVE SOLENOID MODULATING

REMOVE THE LEADS FROM THE MODULATOR

Next: !p1943, !f1092

PUMP RESISTANCES

Next: !p1109, !f1096

RESISTANCE FAN

Next: !p1940, !f1100

VOLTAGE FAN (AT FAN)

Next: !p114, f115

VOLTAGE FAN (AT PCB)

{GAINPCBACS}

Next: !p1907, f117

DIFFERENTIAL ON CH

ON/OFF SWITCH ON
ATTACH TEMPERATURE CLAMPS AS INDICATED BY THE RED ARROWS

Next: !p1165, f1166

INSPECTION CONDENSING HEAT EXCHANGER

TURN OFF FLOW AND RE

Next: !p1167, !f1168

RESISTANCE PRIMARY CIRCUIT SWITCH

DISCONNECT THE BLACK LEADS FROM THE PRIMARY CIRCUIT SWITCH

Next: p174, f119

SYSTEM PRESSURE OK

Next: !p1112, !f173

RESISTANCE OF DIVERTER MOTOR

REMOVE PLUG FROM DIVERTER HEAD

Next: !p1206, !f1207

RESISTANCE OF DIVERTER MOTOR

REMOVE PLUG FROM DIVERTER HEAD

Next: !p1215, !f1216

DHW FLOW SWITCH

DISCONNECT THE X2 CONNECTOR FROM THE PCB

Next: !p137, !f136

RESISTANCE PRIMARY SENSOR AND HARNESS

DISCONNECT X2 PLUG ON THE PCB

Next: p1379, f1380

RESISTANCE PRIMARY SENSOR

REMOVE BLUE LEAD FROM CH SENSOR

Next: !p1381, !f1382

RESISTANCE DHW SENSOR

REMOVE RED WIRED LEAD FROM DHW SENSOR

Next: !p1385, !f1386

RESISTANCE FLUE PROBE NTC

DISCONNECT PLUG FROM FLUE SENSOR

Next: !p1389, !f1390

RESISTANCE COMBUSTION CHAMBER OVERHEAT

DISCONNECT ONE OF THE BLACK LEADS FROM THE COMBUSTION CHAMBER OVERHEAT THERMOSTAT

Next: p1393, !f1394

SYSTEM PRESSURE ABOVE 1BAR

Next: !p1399, !f1400

RESISTANCE AIR PRESSURE SENSOR HARNESS

REMOVE PLUG FROM AIR PRESSURE SENSOR AND REMOVE PLUG FROM PCB ON RIGHT HAND SIDE MARKED X15

Next: !p1403, !f1404

RESISTANCE PRIMARY SENSOR AND HARNESS

DISCONNECT X2 PLUG ON THE PCB

Next: !p1470, f1471

RESISTANCE PRIMARY SENSOR

REMOVE BLUE LEAD FROM CH SENSOR

Next: !p1472, !f1473

RESISTANCE SENSOR TEMP DHW AND HARNESS

DISCONNECT CONNECTOR FROM X2 ON THE PCB

Next: !p1483, f1480

RESISTANCE DHW SENSOR

REMOVE RED WIRED LEAD FROM DHW SENSOR

Next: !p1481, !f1482

RESISTANCE FLUE NTC AND HARNESS

DISCONNECT CONNECTOR FROM X4 ON THE PCB

Next: !p1504, ?1487, ?1489

RESISTANCE FLUE NTC AND HARNESS

DISCONNECT CONNECTOR FROM X4 ON THE PCB

Next: !p1507, f1508

RESISTANCE FLUE PROBE NTC

DISCONNECT PLUG FROM FLUE SENSOR

Next: !p1509, !f1510

RESISTANCE PRIMARY CIRCUIT SWITCH

DISCONNECT THE BLACK LEADS FROM THE PRIMARY CIRCUIT SWITCH

Next: !p1528, !f1529

VOLTAGE AT PCB TO PUMP

DHW DEMAND

Next: p1532, !f1598

VOLTAGE AT PCB TO PUMP

DHW DEMAND

Next: p1348, f1378

DIFFERENTIAL ON CH

ON/OFF SWITCH ON
ATTACH TEMPERATURE CLAMPS AS INDICATED BY THE RED ARROWS

Next: !p1594, f1595

INSPECTION CONDENSING HEAT EXCHANGER

TURN OFF FLOW AND RE

Next: !p1596, !f1597

CAN BOILER BE RESET?

RESET BOILER BY PUTTING SELECTOR SWITCH TO STANDBY THEN TURN BACK ON

Next: p1601, f1602

RESISTANCE AIR PRESSURE SENSOR AND HARNESS

UNPLUG CONNECTOR X15 FROM PCB

Next: !p1603, f1604

RESISTANCE AIR PRESSURE HARNESS

REMOVE PLUG FROM AIR PRESSURE SENSOR AND REMOVE PLUG FROM PCB ON RIGHT HAND SIDE MARKED X15

Next: !p1605, !f1606

RESISTANCE SAFETY STATS AND HARNESS

DISCONNECT CONNECTOR FROM X4 ON THE PCB

Next: !p1946, f1945

RESISTANCE SAFETY STATS AND HARNESS

DISCONNECT CONNECTOR FROM X4 ON THE PCB

Next: !p1815, f1629

RESISTANCE SAFETY THERMOSTAT

Next: p1630, !f1631

FAN RUNS CH DEMAND

Next: p1644, f37

RESISTANCE ELECTRODE SENSE

REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING

Next: p1749, !f1750

PRESSURE GAS INLET

ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT

Next: !p1798, !f1761

CAN HIGH LOW BURNER PRESSURE BE ADJUSTED

DHW TEMPERATURE CONT

Next: !p1796, !f1797

CAN BOILER BE RESET

Next: !p1814, f1627

RESISTANCE SAFETY STATS_HARNESS AT TEMP

Next: p1952, f1879

RESISTANCE COMBUSTION CHAMBER OVERHEAT

DISCONNECT ONE OF THE BLACK LEADS FROM THE COMBUSTION CHAMBER OVERHEAT THERMOSTAT

Next: p1880, !f1881

DOES BOILER FUNCTION WITHOUT OVERHEATING

DHW TEMPERATURE CONT

Next: !p1927, f1816

RESISTANCE SAFETY OVERHEAT STAT

Next: p1949, !f1948

RESISTANCE FLUE PROBE NTC

DISCONNECT PLUG FROM FLUE SENSOR

Next: !p2012, !f2013

RESISTANCE AIR PRESSURE SENSOR HARNESS

REMOVE PLUG FROM AIR PRESSURE SENSOR AND REMOVE PLUG FROM PCB ON RIGHT HAND SIDE MARKED X15

Next: p2023, !f2024

CAN HIGH LOW BURNER PRESSURE BE ADJUSTED

DHW TEMPERATURE CONT

Next: !p2035, !f2036

INSPECTION FLUE SEALS

Next: p206, !f207

IS BOILER IN FROST PROTECTION

Next: !p2094, f2095

RESISTANCE PRIMARY SENSOR

REMOVE BLUE LEAD FROM CH SENSOR

Next: p2096, !f2097

VOLTAGE EXTERNAL CONTROLS NO DEMAND

NO DEMAND FROM EXTERNAL CONTROLS

Next: !p2102, !f2103

VOLTAGE DIVERTER VALVE PCB

{GAINPCBACS}
BOILER MAINS SWITCH ON

Next: p2127, !f2109

PRESSURE GAS INLET

ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT

Next: p230, !f231

INSPECTION TUBES AIR PRESSURE

Next: p242, !f243

VOLTAGE MAINS POWER INPUT TO APPLIANCE

REMOVE CONTROL BOX COVER

Next: p30, f31

RESISTANCE FUSE F1 (FUSED SPUR)

REMOVE FUSE FROM FUSED SPUR

Next: !p32, f33

RESISTANCE FUSE F2 ( APPLIANCE)

REMOVE FUSE FROM FUSE AND HOLDER FROM PCB

Next: p38, f39

BURNER PRESSURE

THERMOSTAT TURNED TO MAX
CONNECT A U-GAUGE TO THE BURNER GAS PRESSURE TEST POINT

Next: !p419, !f420

AIR PRESSURE SWITCH PROVING AT APS AIR FLOW TEST

SET PERFORMANCE TEST

Next: p1052, f241

RESISTANCE SAFETY THERMOSTAT

Next: p505, !f506

INSPECTION SERVICE VALVE DHW

Next: p384, !f53

LINK OUT EXTERNAL CONTROLS

REMOVE WIRES FROM EXTERNAL CONTROLS AND REPLACE WITH A LINK

Next: !p670, !f671

REMOVE INTEGRAL TIMER

REMOVE X11 INTEGRAL TIMER PLUG FROM PCB AND MAKE SAFE

Next: !p672, !f673

REMOVE INTEGRAL TIMER

REMOVE X11 INTEGRAL TIMER PLUG FROM PCB AND MAKE SAFE

Next: !p678, !f679

IS DHW FLOW SWITCH STUCK IN HW MODE

{GAINPCBACS}
DHW TAP OFF
DISCONNECT THE X2 CONNECTOR FROM THE PCB

Next: p683, !f749

RESISTANCE PRIMARY SENSOR

REMOVE BLUE LEAD FROM CH SENSOR

Next: !p727, !f1061

RESISTANCE DHW SENSOR

REMOVE RED WIRED LEAD FROM DHW SENSOR

Next: !p730, !f1062

AIR PRESSURE SENSOR HARNESS CONTINUITY

{GAINPCBACS}
REMO

Next: p2027, !f1054

INSPECTION PRIMARY HEAT EXCHANGER

Next: p1057, !f1934

INSPECTION CONDENSING HEAT EXCHANGER FLUEWAYS

TURN OFF FLOW AND RE

Next: !p1059, !f1060

RESISTANCE GAS VALVE SOLENOID MAIN AND HARNESS

DISCONNECT PLUG MARK

Next: p1068, f1069

RESISTANCE GAS VALVE SOLENOID MODULATING AND HARNESS

REMOVE THE PLUG X2 FROM PCB

Next: p1072, f1073

RESISTANCE PUMP AND HARNESS

DISCONNECT PLUG MARKED X6A FROM PCB

Next: p1199, f1077

RESISTANCE FAN AND HARNESS

DISCONNECT PLUG MARKED X7 FROM THE PCB

Next: !p1938, f1081

RESISTANCE GAS VALVE SOLENOID MAIN AND HARNESS

DISCONNECT PLUG MARK

Next: p1085, f1086

RESISTANCE GAS VALVE SOLENOID MODULATING AND HARNESS

REMOVE THE PLUG X2 FROM PCB

Next: p1089, f1090

RESISTANCE PUMP AND HARNESS

DISCONNECT PLUG MARKED X6A FROM PCB

Next: p1208, f1094

RESISTANCE FAN AND HARNESS

DISCONNECT PLUG MARKED X7 FROM THE PCB

Next: !p1939, f1098

TEMPERATURE DIFFERENTIAL HEAT EXCHANGER DHW1

ON/OFF SWITCH ON
ATTACH TEMPERATURE CLAMPS AS INDICATED BY THE RED ARROWS

Next: !p1169, f1164

RESISTANCE DIVERTER AND HARNESS

REMOVE DIVERTER HEAD FROM BODY, KEEP HARNESS PLUGGED INTO DIVERTER HEAD
REMOVE PLUG X6A FROM PCB

Next: p1076, f1205

RESISTANCE DIVERTER AND HARNESS

REMOVE DIVERTER HEAD FROM BODY, KEEP HARNESS PLUGGED INTO DIVERTER HEAD
REMOVE PLUG X6A FROM PCB

Next: p1093, f1214

RESISTANCE OF PUMP HARNESS

REMOVE CONNECTOR X6A FROM PCB
REMOVE CAPACITOR/PLUG FROM PUMP

Next: p1406, !f1350

RESISTANCE SENSOR TEMP DHW AND HARNESS

DISCONNECT CONNECTOR FROM X2 ON THE PCB

Next: p1383, f1384

RESISTANCE FLUE NTC AND HARNESS

DISCONNECT CONNECTOR FROM X4 ON THE PCB

Next: p1387, f1388

RESISTANCE SAFETY STATS AND HARNESS

DISCONNECT CONNECTOR FROM X4 ON THE PCB

Next: p1391, f1392

RESISTANCE PRIMARY CIRCUIT SWITCH

DISCONNECT THE BLACK LEADS FROM THE PRIMARY CIRCUIT SWITCH

Next: p1397, f1398

RESISTANCE SAFETY THERMOSTAT

Next: !p1395, !f1396

RESISTANCE AIR PRESSURE SENSOR AND HARNESS

UNPLUG CONNECTOR X15 FROM PCB

Next: !p1401, f1402

IS PUMP RUNNING FREELY

Next: p1407, !f1408

PUMP RESISTANCES

Next: !p1409, !f1410

INSPECTION FLUE

Next: !p1493, !f1494

RESISTANCE FLUE PROBE NTC

DISCONNECT PLUG FROM FLUE SENSOR

Next: !p1502, !f1503

RESISTANCE PRIMARY CIRCUIT SWITCH AND HARNESS

REMOVE X2 CONNECTOR ON PCB

Next: !p1521, f1522

IS PUMP RUNNING

Next: p1567, f1531

SYSTEM PRESSURE ABOVE 1BAR

Next: p1518, !f1527

RESISTANCE OF PUMP HARNESS

REMOVE CONNECTOR X6A FROM PCB
REMOVE CAPACITOR/PLUG FROM PUMP

Next: p1560, !f1561

IS PUMP RUNNING FREELY

Next: p1562, !f1563

PUMP RESISTANCES

Next: !p1564, !f1565

PUMP LIMPET

Next: p1568, !f1569

RESISTANCE DHW SENSOR

REMOVE RED WIRED LEAD FROM DHW SENSOR

Next: p1570, !f1571

RESISTANCE PRIMARY SENSOR

REMOVE BLUE LEAD FROM CH SENSOR

Next: p1591, !f1573

TEMPERATURE DIFFERENTIAL HEAT EXCHANGER DHW1

ON/OFF SWITCH ON
ATTACH TEMPERATURE CLAMPS AS INDICATED BY THE RED ARROWS

Next: !p1592, f1593

DOES FAN RUN

RESET BOILER BY TURNING ON/OFF DIAL TO OFF, LEAVE FOR A SECOND THEN TURN BACK ON
DHW TAP ON

Next: !p1607N, !f1608

RESISTANCE COMBUSTION CHAMBER OVERHEAT

DISCONNECT ONE OF THE BLACK LEADS FROM THE COMBUSTION CHAMBER OVERHEAT THERMOSTAT

Next: !p1632, !f1633

DHW FLOW SWITCH

DISCONNECT THE X2 CONNECTOR FROM THE PCB

Next: !p1645, !f1646

INSPECTION INTEGRAL BYPASS

WATER OFF
FLOW AN

Next: p2089, !f1649

RESISTANCE IGNITION LEADS

REMOVE BOTH IGNITION LEADS FROM CONNECTOR AND PCB

Next: !p1684, !f1685

PRESSURE GAS BURNER IGNITION

THERMOSTAT TURNED TO MAX
CONNECT A U-GAUGE TO THE BURNER GAS PRESSURE TEST POINT

Next: p1746, f1759

RESISTANCE PRIMARY SENSOR AND HARNESS

DISCONNECT X2 PLUG ON THE PCB

Next: p175, f726

VOLTAGE RECTIFICATION

GAIN ACCESS TO INNER COMBUSTION CHAMBER
SELECTOR SWITCH TO STANDBY
NO DEMAND

Next: p1747, f1748

RESISTANCE ELECTRODE SENSE HARNESS

REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING

Next: !p1751, !f1752

RESISTANCE SENSOR TEMP DHW AND HARNESS

DISCONNECT CONNECTOR FROM X2 ON THE PCB

Next: p2003, f729

INSPECTION BURNER

REMOVE THE COMBUSTION COVER CASE AND INNER COVER

Next: p1755, !f1756

INSPECTION FLUE

Next: !p1757, !f1758

IS BURNER PRESSURE MODULATING

THERMOSTAT TURNED TO MAX
CONNECT A U-GAUGE TO THE BURNER GAS PRESSURE TEST POINT

Next: p2049, f2034

IS HIGH LOW BURNER PRESSURE CORRECT

DHW TEMPERATURE CONT

Next: p691, f1795

RESISTANCE PRIMARY SENSOR

REMOVE BLUE LEAD FROM CH SENSOR

Next: !p1804, !f1805

PUMP IMPELLOR OK?

REMOVE SCREW FROM MIDDLE OF PUMP (USE TRAY TO CATCH ANY WATER)

Next: p1849, !f1850

PUMP LIMPET TEST

Next: p1851, !f1852

EXTERNAL BYPASS SYSTEM

Next: p1853, !f1854

RESISTANCE PRIMARY SENSOR

REMOVE BLUE LEAD FROM CH SENSOR

Next: p1855, !f1856

RESISTANCE DHW SENSOR

REMOVE RED WIRED LEAD FROM DHW SENSOR

Next: p1908, !f1858

RESISTANCE SAFETY THERMOSTAT

Next: !p1900, !f1883

RESISTANCE COMBUSTION CHAMBER OVERHEAT

DISCONNECT ONE OF THE BLACK LEADS FROM THE COMBUSTION CHAMBER OVERHEAT THERMOSTAT

Next: !p1950, !f1951

INSPECTION GAS VALVE SHUT DOWN

Next: p1848, !f1972

AIR PRESSURE SWITCH PROVING AT PCB

GAIN ACCESS TO PCB
AIR PRESSURE SENSOR PLUG LOCATED ON RIGHT HAND SIDE OF PCB

Next: p275, f422

RESISTANCE GAS VALVE HARNESS

REMOVE HARNESS FROM GAS VALVE
REMOVE CONNECTOR X6A FROM PCB

Next: !p1974, !f1975

INSPECTION BURNER

REMOVE THE COMBUSTION COVER CASE AND INNER COVER

Next: p1980, !f1981

INSPECTION HEAT EXCHANGER PRIMARY (FLUE WAYS)

REMOVE COMBUSTION COVER CASE AND INNER COVER

Next: p1982, !f1983

INSPECTION FLUE

Next: !p1984, !f1985

PUMP LIMPET

Next: p2076, !f2002

PRESSURE GAS BURNER IGNITION

THERMOSTAT TURNED TO MAX
CONNECT A U-GAUGE TO THE BURNER GAS PRESSURE TEST POINT

Next: p228, f229

RESISTANCE FLUE NTC AND HARNESS

DISCONNECT CONNECTOR FROM X4 ON THE PCB

Next: p2014, f2011

RESISTANCE AIR PRESSURE SENSOR AND HARNESS

UNPLUG CONNECTOR X15 FROM PCB

Next: p502, f2022

INSPECTION TUBES AIR PRESSURE

Next: !p2025, !f2026

VOLTAGE PERMANENT FROM PCB APS

TURN ON BOILER AND ALLOW FAN TO RUN

Next: !p2028, !f2029

RESISTANCE DHW SENSOR

REMOVE RED WIRED LEAD FROM DHW SENSOR

Next: p1762, !f2047

INSPECTION FAN MECHANICAL

REMOVE FAN

Next: p545, !f211

RESISTANCE PRIMARY SENSOR

REMOVE BLUE LEAD FROM CH SENSOR

Next: !p2050, !f2051

RESISTANCE DHW SENSOR

REMOVE RED WIRED LEAD FROM DHW SENSOR

Next: p337, !f2074

INSPECTION COMBUSTION CHAMBER

REMOVE FRONT COMBUSTION CASE
REMOVE INNER COVER

Next: !p208, !f209

RESISTANCE PRIMARY SENSOR

REMOVE BLUE LEAD FROM CH SENSOR

Next: p2077, !f2078

RESISTANCE FLUE PROBE NTC

DISCONNECT PLUG FROM FLUE SENSOR

Next: p2079, f2080

INSPECTION INTEGRAL BYPASS

WATER OFF
FLOW AN

Next: p2085, !f2086

INSPECTION FLUE

Next: !p2083, !f2084

TEMP DIFFERENCE ON DHW HEAT EXCHANGER CORRECT

ON/OFF SWITCH ON
ATTACH TEMPERATURE CLAMPS AS INDICATED BY THE RED ARROWS

Next: !p2087, !f2088

INSPECTION EXTERNAL BYPASS

Next: !p2090, !f2091

IS DHW FLOW SWITCH STUCK IN HW MODE

{GAINPCBACS}
DHW TAP OFF
DISCONNECT THE X2 CONNECTOR FROM THE PCB

Next: p2098, !f2099

INSPECTION HEAT EXCHANGER PRIMARY (FLUE WAYS)

REMOVE COMBUSTION COVER CASE AND INNER COVER

Next: p212, !f213

VOLTAGE INTEGRAL TIMER

INTEGRAL TIMER IN OFF POSITION

Next: !p2104, !f2105

INSPECTION FLUE

Next: !p214, !f215

RESISTANCE HARNESS DIVERTER VALVE

REMOVE CONNECTOR X6A FROM THE PCB
REMOVE THE CONNECTOR FROM THE DIVERTER VALVE MOTOR

Next: !p2128, !f2129

RESISTANCE HARNESS DIVERTER VALVE

REMOVE CONNECTOR X6A FROM THE PCB
REMOVE THE CONNECTOR FROM THE DIVERTER VALVE MOTOR

Next: !p2131, !f2132

INSPECTION BURNER

REMOVE THE COMBUSTION COVER CASE AND INNER COVER

Next: p236, !f237

VOLTAGE GAS VALVE (AT PCB)

{GAINPCBACS}
FUNCTION SELECTOR TO DHW POSITION

Next: p1973, !f1976

INSPECTION ELECTRODE AND GAP

Next: !p238, !f239

INSPECTION VENTURI

REMOVE SILICONE RUBBER TUBES FROM THE VENTURI

Next: p244, !f245

INSPECTION FAN

REMOVE FAN

Next: p552, !f247

SPARKING OCCUR AT PCB

GAIN ACCESS TO PCB

Next: p282, !f277

SPARK GAP AND CONDITION

Next: p1683, !f285

PRESSURE GAS INLET

ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT

Next: p2052, !f338

INSPECTION DIVERTER VALVE DHW POSITION

REMOVE DIVERTER VALVE MOTOR
DO NOT HOLD THE ACTUATOR FOR THIS TEST

Next: p327, f2107

INSPECTION CONDENSATE TRAP

Next: p475, !f1064

FAN RUNS DHW DEMAND

Next: p36, f1634

CH OPERATION (FOR HEAT EX DIAG)

FLOW AND RETURN VALVES FULLY OPEN
CH THERMOSTAT SET TO MAX

Next: !p311, ?315

INSPECTION DIVERTER VALVE SPINDLE

REMOVE THE DIVERTER VALVE ACTUATOR FROM THE DIVERTER VALVE BODY

Next: p333, !f334

DIFFERENTIAL TEMP HEAT EXCHANGER DHW

ON/OFF SWITCH ON
ATTACH TEMPERATURE CLAMPS AS INDICATED BY THE RED ARROWS

Next: !p335, !f1063

GAS RATE

Next: p1986, f418

RESISTANCE FUSE F3 ( APPLIANCE)

REMOVE FUSE FROM FUSE AND HOLDER FROM PCB

Next: !p664, f43

DHW FLOW RATE RESTRICTOR

TURN OFF COLD WATER INLET TO BOILER
DRAIN WATER AS APPROPRIATE

Next: !p385, !f386

INSPECTION BYPASS (INTEGRAL APPLIANCE)

WATER OFF
FLOW AN

Next: p723, !f472

PUMP LIMPET

Next: p309, !f492

RESISTANCE SAFETY STATS AND HARNESS

DISCONNECT CONNECTOR FROM X4 ON THE PCB

Next: !p503, f504

RESISTANCE COMBUSTION CHAMBER OVERHEAT

DISCONNECT ONE OF THE BLACK LEADS FROM THE COMBUSTION CHAMBER OVERHEAT THERMOSTAT

Next: !p507, !f508

RESISTANCE DHW SENSOR

REMOVE RED WIRED LEAD FROM DHW SENSOR

Next: p510, !f1285

RESISTANCE PRIMARY SENSOR

REMOVE BLUE LEAD FROM CH SENSOR

Next: p560, !f1286

RESISTANCE FLUE PROBE NTC

DISCONNECT PLUG FROM FLUE SENSOR

Next: p1147, ?563, ?565

INSPECTION FLUE

Next: !p569, !f570

PUMP LIMPET TEST

Next: p643, !f644

CAN BOILER BE RESET

Next: !p1618, f1619

VOLTAGE BOILER SWITCHED LIVE ROOM STAT STILL CALLING

THERMOSTAT TO ON POSITION

Next: p764, !f612

EXPANSION VESSEL PRESSURE

BOILER DISCHARGED

Next: !p1937, !f610

INSPECTION BYPASS SYSTEM

Next: p645, !f646

RESISTANCE PRIMARY SENSOR

REMOVE BLUE LEAD FROM CH SENSOR

Next: p647, !f657

CH BURNER MODULATION

CH TEMPERATURE CONTROL TO MID SETTING
ATTACH A U GAUGE TO BURNER PRESSURE TEST POINT

Next: p649, !f1802

TEMPERATURE DIFFERENTIAL FLOW RETURN AND TEMPERATURE

ON/OFF SWITCH ON
ATTACH TEMPERATURE CLAMPS AS INDICATED BY THE RED ARROWS

Next: !p651, ?653, ?655

EXTERNAL CONTROLS

REMOVE EXTERNAL CONTROLS FROM VOLT FREE CONNECTOR BLOCK, REPLACE WITH A LINK

Next: !p675, f677

DIVERTER VALVE ACTUATOR OPERATION CH MODE

REMOVE DIVERTER VALVE MOTOR
DO NOT HOLD THE ACTUATOR FOR THIS TEST

Next: p736, f682

POWER TO DIVERTER VALVE AT PCB CH

BOILER MAINS SWITCH ON

Next: p2130, !f752

PUMP LIMPET

Next: p509, !f713

INSPECTION CONDENSING HEAT EXCHANGER

TURN OFF FLOW AND RE

Next: !p724, !f725

INSPECTION CONDENSING HEAT EXCHANGER

TURN OFF FLOW AND RE

Next: !p733, !f735

DIVERTER VALVE SPINDLE FREE

REMOVE THE DIVERTER VALVE ACTUATOR FROM THE DIVERTER VALVE BODY

Next: p1647, !f742

INSPECTION INTEGRAL BYPASS

WATER OFF
FLOW AN

Next: !p765, !f766