Set Appliance State:
Gas Off
| Isolate Mains Power to appliance as per TOPs P4 |
DHW Demand
| WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure |
Measurement:
Measure the AC volts at the fan on the harness from the live to neutral (the neutral connection should be the blue on the fan connector).
Expected voltage should be between 160v and 240v.
Note:
Ensure a good connection is made.
Expected voltage should be between 160v and 240v.
Note:
Ensure a good connection is made.

Isolate as per TOPs P4
and refit as necessary