Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
VOKERA UNICA I32
WARNING - IMPORTA
HOW TO CANCEL PUMP PURGE CYCLE
CH & DHW TEMPERATURE
OBSERVATION BOILER SELF CHECK
CH & DHW TEMPERATURE CONTROLS SET TO MAX
A01 - IGNITION FAILURE - DUMMY GO TO BURNER IGNITES
OUTSIDE MODEL
A11 - FALSE FLAME
OUTSIDE MODEL
A08 - RETURN THERMISTOR FAULT, TEMP DIFF INVERTED
OUTSIDE MODEL
A06 - DHW THERMISTOR FAULT
OUTSIDE MODEL
A04 - INSUFFICIENT WATER PRESSURE
OUTSIDE MODEL
A03 - FAN TACHO SIGNAL FAULT
OUTSIDE MODEL
A02 - LIMIT THERMOSTAT FAILURE
OUTSIDE MODEL
HOW TO CANCEL PUMP PURGE CYCLE - FAULT CODES
CH & DHW TEMPERATURE
FUSE FURTHER INVESTIGATION
OUTSIDE MODEL
PRESSURE GAS INLET (DHW DEMAND)
ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT
DHW PREHEAT OPERATION
ENSURE THERE IS A DEMAND FOR PREHEAT, BOILER COOL
DIAGNOSTICS LITE
DIAGNOSIS RELIES ON
QUICK ACCESS DATA AND INFORMATION
THE TABLE BELOW
HEADER FOR QUICK ACCESS DATA FLOW THERMISTOR
OUTSIDE MODEL
HEADER FOR QUICK ACCESS DATA RETURN THERMISTOR
OUTSIDE MODEL
HEADER FOR QUICK ACCESS DATA GAS VALVE VOLTAGE
OUTSIDE MODEL
HEADER FOR QUICK ACCESS DATA PUMP RESISTANCE
OUTSIDE MODEL
HEADER FOR QUICK ACCESS DATA FAN VOLTAGE
OUTSIDE MODEL
HEADER FOR QUICK ACCESS DATA FAN SPEED CONTROL
OUTSIDE MODEL
HEADER FOR QUICK ACCESS DATA SPARK GENERATOR RESISTANCE
OUTSIDE MODEL
HEADER FOR QUICK ACCESS DATA SPARK GENERATOR VOLTAGE
OUTSIDE MODEL
HEADER FOR QUICK ACCESS DATA DIVERTER RESISTANCE
OUTSIDE MODEL
HEADER FOR QUICK ACCESS DATA DIVERTER VOLTAGE
OUTSIDE MODEL
HEADER FOR QUICK ACCESS DATA GAS VALVE RESISTANCE
OUTSIDE MODEL
HEADER FOR QUICK ACCESS DATA PUMP VOLTAGE
OUTSIDE MODEL
HEADER FOR QUICK ACCESS DATA FAN RESISTANCE
OUTSIDE MODEL
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT IGNITE - SPARK GEN
CABLE - IGNITION (CN1 AND CN3)
DHW OPERATION - DHW COOL RADS COOL
HEAT EXCHANGER ASSEMBLY (FLUEWAYS)
DHW OPERATION - DHW COOL RADS COOL - LPG
HEAT EXCHANGER ASSEMBLY (FLUEWAYS)
DHW COOL RADS COOL 2
BY-PASS VALVE
OBSERVATION BOILER SELF CHECK - FIRING NO DEMAND
OPEN TAP OR LEAK
OBSERVATION BOILER SELF CHECK - FIRING NO DEMAND
FROST PROTECTION
OBSERVATION BOILER SELF CHECK - FIRING NO DEMAND
SENSOR - NTC
DHW RADS BEGIN TO HEAT 2
PCB AKL03
DHW RADS BEGIN TO HEAT 2
CABLE - CONTROL - HYDRAULIC (CN4)
DHW RADS BEGIN TO HEAT
PCB AKL03
DHW RADS BEGIN TO HEAT
CABLE - CONTROL - HYDRAULIC (CN4)
CH OPERATION 4
PCB AKL03
CH OPERATION 2
CABLE - CONTROL - HYDRAULIC (CN4)
CH RADS HEAT 2
CARTRIDGE - 3 WAY VALVE
CH OPERATION 3
PUMP
CH OPERATION 2
BY-PASS VALVE
CH OPERATION 2
PCB AKL03
CH OPERATION
PUMP
CH OPERATION
CABLE - CONTROL - HYDRAULIC (CN4)
CH RADS HEAT
CARTRIDGE - 3 WAY VALVE
CH OPERATION
BY-PASS VALVE
FAULT CODES 2
Z REDIRECT
OBSERVATION BOILER SELF CHECK - FAN RUNS CONSTANTLY
CABLE - COMBUSTION (CN10 CN11 FSE)
NO DISPLAY LIGHTS FLASHING
PCB AKL03
NO DISPLAY LIGHTS FLASHING
HARNESS - WIRING (CN8)
OBSERVATION DISPLAY ILLUMINATES - DISPLAY ON NO LEDS
ACTUATOR - DHW
FAULTY LEDS
PCB AKL03
NO DISPLAY ALL OFF
MAINS FUSE
NO DISPLAY ALL OFF
HARNESS - WIRING - POWER (CN2)
OBSERVATION DISPLAY ILLUMINATES
PCB AKL03
OBSERVATION BOILER SELF CHECK - FAN DOES NOT KICK
CABLE - IGNITION (CN1 AND CN3)
FAULT CODES 3
Z REDIRECT
SELF CHECK
PCB AKL03
DHW OPERATION 2
PCB AKL03
DHW OPERATION 4
PCB AKL03
DHW OPERATION 3
PCB AKL03
FAULT CODE A03 - NO AC POWER TO FAN
PCB AKL03
FAULT CODE A03 - FAN DOES NOT KICK
CABLE - IGNITION (CN1 AND CN3)
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT IGNITE - NO VOLTAGE TO GAS VALVE
PCB AKL03 AND SOLENOID - GAS VALVE
BURNER DOES NOT IGNITE
THERMOSTAT - HIGH LIMIT
ONLY 1 ATTEMPT TO IGNITE
PRESSURE SWITCH - WATER
ONLY 1 ATTEMPT TO IGNITE
THERMOSTAT - HIGH LIMIT
BLANK FOR DIAGNOSICS LITE
Z DIRECTION
BLANK FOR QUICK ACCESS DATA AND INFORMATION
Z DIRECTION
OUT OF RANGE (QADAI)
DETECTOR - NTC
OUT OF RANGE (QADAI) 2
DETECTOR - NTC
QADAI
SENSOR - NTC
QADAI
SENSOR - FLUE
NO POWER TO GAS VALVE (QADAI)
PCB AKL03
NO POWER TO FAN (QADAI)
PCB AKL03
FAULT CODE A03 (QADAI)
CABLE - COMBUSTION (CN10 CN11 FSE)
INCORRECT RESISTANCE (QADAI)
TRANSFORMER - IGNITION
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT IGNITE - NO DROP
COMPENSATION TUBE
NO VOLTAGE TO SPARK GEN (QADAI)
PCB AKL03
INCORRECT RESISTANCE (QADAI)
ACTUATOR
NO VOLTAGE TO DIVERTER (QADAI)
PCB AKL03
RESISTANCE WRONG (QADAI)
GAS VALVE
NO POWER TO PUMP (QADAI)
PCB AKL03
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT IGNITE - DROP SEEN
COMPENSATION TUBE
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT IGNITE - NO DROP
SOLENOID - GAS VALVE
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT IGNITE
ELECTRODE - IGNITION
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT IGNITE - DROP SEEN
HEAT EXCHANGER ASSEMBLY (FLUEWAYS)
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH
COMPENSATION TUBE
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH
GAS INLET PRESSURE
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH
CABLE - COMBUSTION (CN10 CN11 FSE)
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH
ELECTRODE (DETECTION)
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH
HEAT EXCHANGER ASSEMBLY (FLUEWAYS)
OBSERVATION BURNER IGNITES AND ESTABLISHES - BAFFLES OUT
COMPENSATION TUBE
OBSERVATION BURNER IGNITES AND ESTABLISHES - BAFFLES OUT
GAS INLET PRESSURE
OBSERVATION BURNER IGNITES AND ESTABLISHES - BAFFLES OUT
HEAT EXCHANGER ASSEMBLY (FLUEWAYS)
FAULT CODE A06
PCB AKL03
FAULT CODE A11 2
PCB AKL03
FAULT CODE A11
SYPHON
FAULT CODE A11
FLUE
FAULT CODE A11 2
GAS VALVE
FAULT CODE A11 2
ELECTRODE (DETECTION)
FAULT CODE A01
Z REDIRECT
FAULT CODE A09
SENSOR - FLUE
FAULT CODE AO9
PCB AKL03
FAULT CODE A09
PCB AKL03
FAULT CODE A09 - PUMP
HARNESS - WIRING - POWER (CN2)
FAULT CODE A09 2
PUMP
FAULT CODE A09
DETECTOR - NTC
FAULT CODE A08 2
DETECTOR - NTC
FAULT CODE A08
PCB AKL03
FAULT CODE A08 2
PCB AKL03
FAULT CODE A08 - PUMP
HARNESS - WIRING - POWER (CN2)
FAULT CODE A08 2
PUMP
FAULT CODE A08
DETECTOR - NTC
FAULT CODE A08
HEAT EXCHANGER (WATERWAYS)
FAULT CODE A08
VALVE - NON RETURN
FAULT CODE A08
DETECTOR - NTC X2
FAULT CODE A08 3
PCB AKL03
FAULT CODE A07
DETECTOR - NTC
FAULT CODE A07
PCB AKL03
FAULT CODE A07 2
PCB AKL03
FAULT CODE A07 - PUMP
HARNESS - WIRING - POWER (CN2)
FAULT CODE A07 2
PUMP
FAULT CODE A07 2
DETECTOR - NTC
FAULT CODE A07
HEAT EXCHANGER (WATERWAYS)
FAULT CODE A07
VALVE - NON RETURN
FAULT CODE A07
DETECTOR - NTC X2
FAULT CODE A07 3
PCB AKL03
FAULT CODE A04
PCB AKL03
INFORMATION CASE REMOVAL
Z REDIRECT
INFORMATION BOILER SETUP
Z REDIRECT
FAULT CODE A02 2
THERMOSTAT - HIGH LIMIT
TYPE OF DIAGNOSTIC PROCEDURE
Z REDIRECT
FAULT CODE A02 2
PCB AKL03
FAULT CODE A02
HARNESS - WIRING - POWER (CN2)
FAULT CODE A02
PUMP
FAULT CODE A02 2
DETECTOR - NTC
FAULT CODE A02
DETECTOR - NTC
FAULT CODE A02
SENSOR - NTC
FAULT CODE A02
HEAT EXCHANGER (WATERWAYS)
FAULT CODE A02
VALVE - NON RETURN
FAULT CODE A02
PCB AKL03
OBSERVATION DHW FLOW RATE
STOP COCK - WATER SUPPLY
FAULT CODE A03 5- FAN NEED TO CHECK WHAT ITS SUPPOSED TO BE
HARNESS - WIRING - POWER (CN2)
OBSERVATION DHW FLOW RATE
WATER SUPPLY
FAULT CODES
Z REDIRECT
DISABLE PREHEAT
Z REDIRECT
RESISTANCE SPARK GENERATOR
TRANSFORMER - IGNITION
FUSE FURTHER INVESTIGATION
ACTUATOR
FUSE FURTHER INVESTIGATION
SOLENOID - GAS VALVE
FAULT CODE A06 - DHW THERMISTOR
CABLE - LOW TENSION
GAS INLET DHW DEMAMD
GAS INLET PRESSURE
DHW HOT THEN COOL
PUMP
DHW HOT THEN COOL
SENSOR - NTC
DHW HOT THEN COOL
DETECTOR - NTC
DHW HOT THEN COOL
VALVE - NON RETURN
DHW TOO HOT
SENSOR - NTC
DHW COOL RADS COOL
PLUMBING ISSUE
DHW COOL RADS COOL
PUMP
DHW COOL RADS COOL
SENSOR - NTC
DHW COOL RADS COOL
DETECTOR - NTC
DHW COOL RADS COOL
VALVE - NON RETURN
DHW COOL RADS COOL 2
FLUE
DHW COOL RADS COOL 2
MIXER
DHW COOL RADS COOL
FLUE
DHW COOL RADS COOL
MIXER
DHW COOL RADS COOL
BY-PASS VALVE
CH OPERATION
EXPANSION VESSEL
CH OPERATION 2
PUMP
CH OPERATION
DETECTOR - NTC
CH OPERATION 2
DETECTOR - NTC
CH OPERATION
COCK - HEATING
OBSERVATION PUMP RUNS - OPEN CIRCUIT TO DHW FLOW SENSOR
CABLE - LOW TENSION
OBSERVATION BOILER SELF CHECK - NO POWER TO PUMP
HARNESS - WIRING - POWER (CN2)
FAN DOES NOT RUN
DETECTOR - NTC
FAN DOES NOT RUN 2
DETECTOR - NTC
FAN DOES NOT RUN
SENSOR - NTC
FAN DOES NOT RUN 2
CABLE - COMBUSTION (CN10 CN11 FSE)
FAULT CODE A03 3
FAN
DHW PREHEAT OPERATION
PCB AKL03
OBSERVATION FAN RUNS - LWPS
CABLE - LOW TENSION
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT IGNITE
TRANSFORMER - IGNITION
DHW OPERATION - DHW COOL RADS COOL
PCB AKL03
DHW COOL RADS COOL 3
PCB AKL03
DHW RADS BEGIN TO HEAT 2
CARTRIDGE - 3 WAY VALVE
DHW RADS BEGIN TO HEAT 3
ACTUATOR
DHW RADS BEGIN TO HEAT
CARTRIDGE - 3 WAY VALVE
DHW RADS BEGIN TO HEAT 2
ACTUATOR
CH OPERATION 2
ACTUATOR
CH OPERATION
ACTUATOR
NO DISPLAY FAULTY MAIN PCB
Z REDIRECT
NO DISPLAY LIGHTS FLASHING
KIT - CARD READER
OBSERVATION DISPLAY ILLUMINATES - DISPLAY ON NO LEDS
CABLE - LOW TENSION
FAULTY LEDS
Z REDIRECT
NO DISPLAY MAINS FUSE
Z REDIRECT
NO DISPLAY ALL OFF FUSE IN HOLDER
Z REDIRECT
NO DISPLAY ALL OFF
PCB AKL03
NO DISPLAY ALL OFF PCB FUSE
Z REDIRECT
FAULT CODES 1
Z REDIRECT
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT IGNITE - WARPED
ELECTRODE - IGNITION
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT ESTABLISH - WARPED
ELECTRODE (DETECTION)
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT IGNITE
GAS INLET PRESSURE
DHW OPERATION SELF CHECK
EXTERNAL CONTROLS OR WIRING
DHW OPERATION 2
EXTERNAL CONTROLS OR WIRING
DHW OPERATION 4
EXTERNAL CONTROLS OR WIRING
DHW OPERATION 3
EXTERNAL CONTROLS OR WIRING
FAULT CODE A03 - NO KICK
PCB AKL03
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT IGNITE - NO VOLTAGE TO GAS VALVE
PCB AKL03 AND HARNESS - WIRING - POWER
ONL Y 1 ATTEMPT TO IGNITE
PCB AKL03
FLOW THERMISTOR SATISFACTORY
RESULT AS EXPECTED
RETURN THERMISTOR SATISFACTORY
RESULT AS EXPECTED
DHW THERMISTOR SATISFACTORY
RESULT AS EXPECTED
FLUE THERMISTOR SATISFACTORY
RESULT AS EXPECTED
GAS VALVE VOLTAGE SATISFACTORY
RESULT AS EXPECTED
PUMP RESISTANCE SATISFACTORY
RESULT AS EXPECTED
FAN VOLTAGE SATISFACTORY
RESULT AS EXPECTED
FAULT CODE A03 (QADAI)
PCB AKL03
FAULT CODE A03 2 (QADAI)
PCB AKL03
FAN SPEED CONTROL VOLTAGE SATISFACTORY
RESULT AS EXPECTED
FAN SPEED CONTROL RESISTANCE SATISFACTORY
RESULT AS EXPECTED
SPARK GENERATOR SATISFACTORY
RESULT AS EXPECTED
SPARK GENERATOR VOLTAGE SATISFACTORY
RESULT AS EXPECTED
DIVERTER RESISTANCE SATISFACTORY
RESULT AS EXPECTED
DIVERTER VOLTAGE SATISFACTORY
RESULT AS EXPECTED
GAS VALVE RESISTANCE SATISFACTORY
RESULT AS EXPECTED
PUMP VOLTAGE SATISFACTORY
RESULT AS EXPECTED
NO DISPLAY
THERMOSTAT - HIGH LIMIT
FAN RESISTANCE SATISFACTORY
RESULT AS EXPECTED
NO DISPLAY
PRESSURE SWITCH - WATER
OBSERVATION BURNER IGNITES AND ESTABLISHES - DOES NOT IGNITE - NO DROP
HARNESS - WIRING - POWER (CN2)
FAULT CODE A06
SENSOR - NTC
FAULT CODE A06
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CODE A11
ELECTRODE (DETECTION)
FAULT CODE A11
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CODE A09
PRESSURE GAUGE
FAULT CODE A09
SYSTEM PRESSURE
FAULT CODE A09
PUMP
FAULT CODE A09
FAULT CODE RESET - A09
FAULT CODE A09 2
SENSOR - FLUE
FAULT CODE A09
HEAT EXCHANGER ASSEMBLY (FLUEWAYS)
FAULT CODE A08
PRESSURE GAUGE
FAULT CODE A08
SYSTEM PRESSURE
FAULT CODE A08
PUMP
FAULT CODE A08
HEAT EXCHANGER (PLATE)
FAULT CODE A08
FAULT CODE - A02 - A07 -A08
FAULT CODE A07
PRESSURE GAUGE
FAULT CODE A07
SYSTEM PRESSURE
FAULT CODE A07
PUMP
FAULT CODE A07
HEAT EXCHANGER (PLATE)
FAULT CODE A07
FAULT CODE - A02 - A07 -A08
FAULT CODE A04
PRESSURE SWITCH - WATER
FAULT CODE A04
PRESSURE GAUGE
FAULT CODE A04
SYSTEM PRESSURE
FAULT CODE A04
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CODE A02
PRESSURE GAUGE
FAULT CODE A02
SYSTEM PRESSURE
FAULT CODE A02 2
PUMP
FAULT CODE A02
HEAT EXCHANGER (PLATE)
FAULT CODE A02
THERMOSTAT - HIGH LIMIT
FAULT CODE RED A02
PCB AKL03
FAULT CODE A02
FAULT CODE - A02 - A07 -A08
FUSE FURTHER INVESTIGATION - PUMP
HARNESS - WIRING - POWER (CN2)
OBSERVATION DHW FLOW RATE
HEAT EXCHANGER (PLATE)
OBSERVATION GAS VALVE TYPE?
PCB AKL03 - FUSE BLOWN
FUSE FURTHER INVESTIGATION - GAS VALVE
HARNESS - WIRING - POWER (CN2)
FAULT CODE A04 - LWPS
CABLE - LOW TENSION
FAULT CODE A07 - FLOW THERMISTOR
CABLE - COMBUSTION (CN10 CN11 FSE)
OBSERVATION DHW FLOW RATE
ACTUATOR - DHW
FAULT CODE A09 - FLUE THERMISTOR
CABLE - COMBUSTION (CN10 CN11 FSE)
FAULT CODE A08 - RETURN THERMISTOR
CABLE - COMBUSTION (CN10 CN11 FSE)
FUSE FURTHER INVESTIGATION - FAN
CABLE - IGNITION (CN1 AND CN3)
FUSE FURTHER INVESTIGATION - SPARK GEN
CABLE - IGNITION (CN1 AND CN3)
FUSE FURTHER INVESTIGATION - DIVERTER
CABLE - CONTROL - HYDRAULIC (CN4)
FAULT CODE A02 - OVERHEAT
CABLE - COMBUSTION (CN10 CN11 FSE)
FAULT CODE A02 - STUCK IN FAULT
PCB AKL03
DHW HOT THEN COOL
PRESSURE GAUGE
DHW HOT THEN COOL
SYSTEM PRESSURE
OBSERVATION DHW FLOW RATE
GOVERNOR - FLOW
DHW HOT THEN COOL
PCB AKL03
DHW HOT THEN COOL
HEAT EXCHANGER (WATERWAYS)
DHW HOT THEN COOL
HEAT EXCHANGER (PLATE)
DHW TOO HOT
PCB AKL03
DHW COOL RADS COOL
PRESSURE GAUGE
DHW COOL RADS COOL
SYSTEM PRESSURE
DHW COOL RADS COOL
HEAT EXCHANGER (WATERWAYS)
DHW COOL RADS COOL
HEAT EXCHANGER (PLATE)
DHW COOL RADS COOL
PCB AKL03
CH OPERATION
PIPE (TO EXPANSION VESSEL)
CH OPERATION
PRESSURE GAUGE
CH OPERATION
SYSTEM PRESSURE
CH OPERATION 3
PCB AKL03
CH OPERATION 2
PRESSURE GAUGE
CH OPERATION 2
SYSTEM PRESSURE
OBSERVATION PUMP RUNS
ACTUATOR - DHW
FAN DOES NOT RUN
PRESSURE SWITCH - WATER
FAN DOES NOT RUN
PRESSURE GAUGE
FAN DOES NOT RUN
SYSTEM PRESSURE
FAN DOES NOT RUN 3
PCB AKL03
FAULT CODE A03 - IGNORING HAL SENSOR
PCB AKL03
BOILER ATTEMPTS TO FIRE AFTER SELF CHECK WITH PREHEAT DISABLED
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
FROST SYMBOL DISPLAYED
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY
RADIATOR SYMBOL DISPLAYED
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY
FAULT CODE SHOWN
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
FAN RUNNING CONSTANTLY
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
NO DISPLAY, NO LIGHTS
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY ILLUMIANTES
DISPLAY WORKS BUT LIGHTS DO NOT FLASH
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY ILLUMIANTES
LIGHTS OK BUT DISPLAY DOES NOT WORK
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY ILLUMIANTES
BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
INLET PRESSURE DOES NOT DROP DURING SPARKING STAGE
CHARACTERISTIC TEST FROM PRESSURE GAS INLET AND DROP
BURNER UNSATISFACTORY
CHARACTERISTIC TEST FROM INSPECTION BURNER AND IGNITION ELECTRODE POSITION
INLET PRESSURE DIES AWAY DURING SPARKING STAGE
CHARACTERISTIC TEST FROM PRESSURE GAS INLET AND DROP
ELECTRODE GAP INCORRECT / ELECTRODE WARPED OR DISTORTED
CHARACTERISTIC TEST FROM INSPECTION BURNER AND IGNITION ELECTRODE POSITION
BURNER UNSATISFACTORY
CHARACTERISTIC TEST FROM INSPECTION BURNER AND IGNITION ELECTRODE POSITION
ELECTRODE GAP INCORRECT / ELECTRODE WARPED OR DISTORTED
CHARACTERISTIC TEST FROM INSPECTION BURNER AND IGNITION ELECTRODE POSITION
BOILER GOES TO IGNITION LOCKOUT (A01) AFTER ONLY 1 ATTEMPT AT IGNITION
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
TEST 1 - VOLTAGE NOT AS EXPECTED
CHARACTERISTIC TEST FROM VOLTAGE FAN AT PCB DC (SPEED CONTROL) (QADAI)
TEST 2 - VOLTAGE NOT AS EXPECTED
CHARACTERISTIC TEST FROM VOLTAGE FAN AT PCB DC (SPEED CONTROL) (QADAI)
BURNER IGNITES BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
BURNER IGNITES BUT BAFFLES OUT
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
PRESSURE ON GAUGE OK BUT DOES NOT CHANGE WHEN WATER ADDED
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
FAULT CODE A09 OCCURS - FLUE GAS TEMPERATURE BELOW 90°C
CHARACTERISTIC TEST FROM OBSERVATION FLUE GAS TEMPERATURE
FLUE TEMPERATURE EXCEEDS 90°C & BOILER STILL FIRING
CHARACTERISTIC TEST FROM OBSERVATION FLUE GAS TEMPERATURE
PRESSURE ON GAUGE OK BUT DOES NOT CHANGE WHEN WATER ADDED
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
PRESSURE ON GAUGE OK BUT DOES NOT CHANGE WHEN WATER ADDED
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
PRESSURE ON GAUGE OK BUT DOES NOT CHANGE WHEN WATER ADDED
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
PRESSURE ON GAUGE OK BUT DOES NOT CHANGE WHEN WATER ADDED
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
BOILER GOES TO FAULT CODE A02 BEFORE 80 °C
CHARACTERISTIC TEST FROM OBSERVATION CH - OVERHEAT OCCUR
TEMPERATURE EXCEEDS 85 °C & CONTINUES TO FIRE
CHARACTERISTIC TEST FROM OBSERVATION CH - OVERHEAT OCCUR
DHW FLOW SENSOR BLOCKED OR RESTRICTED OR TURBINE STIFF / DAMAGED
CHARACTERISTIC TEST FROM INSPECTION DHW FLOW SENSOR AND RESTRICTOR
RESTRICTOR DAMAGED RESTRICTED OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION DHW FLOW SENSOR AND RESTRICTOR
DHW COOL - RADIATORS REMAIN COOL OR DO NOT INCREASE IN TEMPERATURE
CHARACTERISTIC TEST FROM DHW OPERATION
DHW COOL - RADIATORS BEGIN TO HEAT OR INCREASE IN TEMPERATURE
CHARACTERISTIC TEST FROM DHW OPERATION
DHW TOO HOT
CHARACTERISTIC TEST FROM DHW OPERATION
DHW RUNS HOT THEN COOL
CHARACTERISTIC TEST FROM DHW OPERATION
PRESSURE ON GAUGE OK BUT DOES NOT CHANGE WHEN WATER ADDED
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
BOILER DOES NOT RESPOND TO CH DEMAND
CHARACTERISTIC TEST FROM CH OPERATION
DIFFERENTIAL TEMPERATURE EXCESSIVELY HIGH
CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL PRIMARY HEAT EXCHANGER
PRESSURE ON GAUGE OK BUT DOES NOT CHANGE WHEN WATER ADDED
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
BOILER DOES NOT RESPOND TO CH DEMAND
CHARACTERISTIC TEST FROM CH OPERATION
DIFFERENTIAL TEMPERATURE EXCESSIVELY HIGH
CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL PRIMARY HEAT EXCHANGER
BOILER DOES NOT RESPOND TO CH DEMAND
CHARACTERISTIC TEST FROM CH OPERATION
BOILER REACHES TEMPERATURE - RADIATORS DO NOT HEAT OR ONLY GET WARM
CHARACTERISTIC TEST FROM CH OPERATION
BOILER TEMPERATURE AND SYSTEM TEMPERATURE LOW - BOILER REMAINS LIT
CHARACTERISTIC TEST FROM CH OPERATION
EXCESSIVE SYSTEM PRESSURE RISE AS SYSTEM HEATS
CHARACTERISTIC TEST FROM CH OPERATION
PRESSURE ON GAUGE OK BUT DOES NOT CHANGE WHEN WATER ADDED
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
PRESSURE ON GAUGE OK BUT DOES NOT CHANGE WHEN WATER ADDED
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
PRESSURE ON GAUGE OK BUT DOES NOT CHANGE WHEN WATER ADDED
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM OBSERVATION PRESSURE SYSTEM
16/11/2022 11:11:54 2209_2_50_1 21/11/2022 09:20:37
17/11/2022 08:49:58
VOLTAGE DIVERTER VALVE AT PCB
{GAINPCBACS}
RESISTANCE ACTUATOR HARNESS
REMOVE ELECTRICAL CONNECTOR FROM DIVERTER VALVE (DV) ACTUATOR
OBSERVATION DIVERTER VALVE OPERATION CH (2X LOCKING PIN)
REMOVE ACTUATOR FROM THE 3-WAY VALVE ASSEMBLY & PLACE IN A SAFE POSITION TO OBSERVE ITS OPERATION
VOLTAGE DIVERTER VALVE AT PCB (CH)
{GAINPCBACS}
RESISTANCE ACTUATOR HARNESS
REMOVE ELECTRICAL CONNECTOR FROM DIVERTER VALVE (DV) ACTUATOR
INFORMATION FAULTY MAIN PCB
THE TESTS CARRIED OU
OBSERVATION DISCONNECT DHW FLOW SENSOR
RECONNECT CN9 AT THE PCB IF YOU HAVE NOT ALREADY DONE SO
DISCONNECT PLUG AT DHW FLOW SENSOR
VOLTAGE MAINS POWER IN AFTER FUSE
{GAINPCBACS}
VOLTAGE MAINS POWER IN BEFORE FUSE
{GAINPCBACS}
RESISTANCE MAINS FUSE
REMOVE FUSE FROM FUSED SPUR
INFORMATION FUSE FURTHER INVESTIGATION
THE INFORMATION PROV
INFORMATION FUSE FURTHER INVESTIGATION
THE INFORMATION PROV
VOLTAGE FAN AT PCB (HV)
{GAINPCBACS}
OBSERVATION DISCONNECT FAN (NOT RUNNING)
DISCONNECT THE 4 WIRE CONNECTOR AT THE FAN AND MAKE SAFE
VOLTAGE FAN AT PCB (HV)
{GAINPCBACS}
RESISTANCE OVERHEAT STAT
REMOVE ELECTRICAL CONNECTORS FROM THE OVERHEAT STAT
RESISTANCE GAS VALVE
DISCONNECT PLUG FROM GAS VALVE
RESISTANCE FLOW THERMISTOR
REMOVE CONNECTORS FROM FLOW SENSOR
RESISTANCE RETURN THERMISTOR
REMOVE CONNECTORS FROM RETURN SENSOR
RESISTANCE DHW THERMISTOR & HARNESS (QADAI)
REMOVE CONNECTOR CN9 FROM THE PCB
RESISTANCE FLUE THERMISTOR
REMOVE RIGHT HAND SI
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
RESISTANCE PUMP
REMOVE PUMP ELECTRICAL COVER
REMOVE ELECTRICAL CONNECTIONS FROM PUMP ASSEMBLY
VOLTAGE FAN AT PCB (HV)
{GAINPCBACS}
VOLTAGE FAN AT PCB DC (SPEED CONTROL) (QADAI)
{GAINPCBACS}
REMOVE CONNECTOR CN10 FROM THE PCB AND MAKE SAFE
ENSURE NO DEMANDS
RESISTANCE FAN SPEED CONTROL AND HARNESS (QADAI)
{GAINPCBACS}
DISCONNECT CN10 AT PCB
RESISTANCE SPARK GENERATOR
REMOVE ELECTRICAL CONNECTOR TO SPARK GENERATOR.
VOLTAGE SPARK GENERATOR AT PCB
{GAINPCBACS}
RESISTANCE DIVERTER VALVE ACTUATOR
REMOVE ELECTRICAL CONNECTOR TO DIVERTER ACTUATOR
VOLTAGE DIVERTER VALVE AT PCB (QADAI)
{GAINPCBACS}
RESISTANCE GAS VALVE
DISCONNECT PLUG FROM GAS VALVE
VOLTAGE PUMP AT PCB
{GAINPCBACS}
OBSERVATION DISCONNECT OVERHEAT STAT
DISCONNECT THE WIRES TO THE OVERHEAT THERMOSTAT AND MAKE SAFE
RESISTANCE FAN
REMOVE POWER ELECTRI
OBSERVATION DISCONNECT LOW WATER PRESSURE SWITCH
REMOVE ELECTRICAL CONNECTORS FROM LWPS AND MAKE SAFE
VOLTAGE SPARK GENERATOR AT PCB
{GAINPCBACS}
RESISTANCE GAS VALVE
DISCONNECT PLUG FROM GAS VALVE
RESISTANCE DHW THERMISTOR AND HARNESS
REMOVE CONNECTOR CN9 FROM THE PCB
RESISTANCE HARNESS DHW THERMISTOR
REMOVE ELECTRICAL CONNECTOR TO DHW TEMPERATURE THERMISTOR
& CONNECTOR CN9 FROM THE PCB
RESET APPLIANCE - FAULT CODE A11
ENSURE NO DEMANDS ARE PRESENT
OBSERVATION DETECTION ELECTRODE DISCONNECTED
DISCONNECT INLINE CONNECTOR FOR DETECTION ELECTRODE, BOTTOM LEFT OF COMBUSTION CHAMBER
RESISTANCE FLUE THERMISTOR & HARNESS - (FAULT CODE)
REMOVE CONNECTOR CN11 FROM THE PCB
ENSURE BOILER IS COOL
RESISTANCE FLUE THERMISTOR
REMOVE RIGHT HAND SI
VOLTAGE PUMP AT PCB
{GAINPCBACS}
RESISTANCE RETURN TEMPERATURE SENSOR & HARNESS - (FAULT CODE)
REMOVE CONNECTOR CN11 FROM THE PCB
ENSURE BOILER IS COOL
RESISTANCE RETURN THERMISTOR
REMOVE CONNECTORS FROM RETURN SENSOR
VOLTAGE PUMP AT PCB
{GAINPCBACS}
TEMPERATURE DIFFERENTIAL PRIMARY HEAT EXCHANGER (FAULT CODE)
ATTACH TEMPERATURE PROBES TO FLOW & RETURN PIPES AT THE BOTTOM LEFT OF THE COMBUSTION CHAMBER
RESISTANCE FLOW TEMPERATURE SENSOR & HARNESS - (FAULT CODE)
REMOVE CONNECTOR CN11 FROM THE PCB
ENSURE BOILER IS COOL
RESISTANCE FLOW THERMISTOR
REMOVE CONNECTORS FROM FLOW SENSOR
VOLTAGE PUMP AT PCB
{GAINPCBACS}
TEMPERATURE DIFFERENTIAL PRIMARY HEAT EXCHANGER (FAULT CODE)
ATTACH TEMPERATURE PROBES TO FLOW & RETURN PIPES AT THE BOTTOM LEFT OF THE COMBUSTION CHAMBER
RESISTANCE LOW WATER PRESSURE SWITCH AND HARNESS
REMOVE CONNECTOR CN9 FROM THE PCB
RESISTANCE LOW WATER PRESSURE SWITCH
REMOVE ELECTRICAL CONNECTORS FROM LWPS
RESET APPLIANCE
ENSURE NO DEMANDS ARE PRESENT
ENSURE BOILER IS COOL
RESISTANCE OVERHEAT STAT & HARNESS
DISCONNECT CN11 FROM THE PCB
RESISTANCE OVERHEAT STAT
REMOVE ELECTRICAL CONNECTORS FROM THE OVERHEAT STAT
VOLTAGE PUMP AT PCB
{GAINPCBACS}
TEMPERATURE DIFFERENTIAL PRIMARY HEAT EXCHANGER (FAULT CODE)
ATTACH TEMPERATURE PROBES TO FLOW & RETURN PIPES AT THE BOTTOM LEFT OF THE COMBUSTION CHAMBER
RESISTANCE PUMP AND HARNESS
REMOVE CONNECTOR CN2 FROM THE PCB
RESISTANCE PUMP
REMOVE PUMP ELECTRICAL COVER
REMOVE ELECTRICAL CONNECTIONS FROM PUMP ASSEMBLY
RESISTANCE FAN
REMOVE POWER ELECTRI
RESISTANCE SPARK GENERATOR
REMOVE ELECTRICAL CONNECTOR TO SPARK GENERATOR.
RESISTANCE DIVERTER VALVE ACTUATOR
REMOVE ELECTRICAL CONNECTOR TO DIVERTER ACTUATOR
RESISTANCE GAS VALVE
DISCONNECT PLUG FROM GAS VALVE
TEMPERATURE DIFFERENTIAL PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE PROBES TO FLOW & RETURN PIPES AT THE BOTTOM LEFT OF THE COMBUSTION CHAMBER
TEMPERATURE DIFFERENTIAL PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE PROBES TO FLOW & RETURN PIPES AT THE BOTTOM LEFT OF THE COMBUSTION CHAMBER
VOLTAGE DHW FLOW SENSOR TO PCB
{GAINPCBACS}
VOLTAGE PCB TO DHW FLOW SENSOR
{GAINPCBACS}
VOLTAGE PUMP AT PCB
{GAINPCBACS}
RESISTANCE LOW WATER PRESSURE SWITCH AND HARNESS
REMOVE CONNECTOR CN9 FROM THE PCB
RESISTANCE LOW WATER PRESSURE SWITCH
REMOVE ELECTRICAL CONNECTORS FROM LWPS
RESISTANCE HARNESS SPARK GENERATOR
REMOVE CN1 FROM THE PCB
INSPECTION HEAT EXCHANGER FLUEWAYS
REMOVE FAN & BURNER ASSEMBLY
INSPECTION BURNER
REMOVE FAN & BURNER ASSEMBLY
INSPECTION HEAT EXCHANGER FLUEWAYS
REMOVE FAN & BURNER ASSEMBLY
INSPECTION BURNER
REMOVE FAN & BURNER ASSEMBLY
INSPECTION BY-PASS VALVE
ENSURE BOILER IS COO
OBSERVATION DISPLAY
ENSURE NO DEMANDS PRESENT
OBSERVATION ISOLATE DHW
TURN DHW ISOLATION VALVE TO "OFF" POSITION UNDERNEATH THE BOILER
RESISTANCE SENSOR FLOW
REMOVE CONNECTORS FROM FLOW SENSOR
RESISTANCE DHW THERMISTOR AND HARNESS
REMOVE CONNECTOR CN9 FROM THE PCB
VOLTAGE DIVERTER VALVE AT PCB
{GAINPCBACS}
RESISTANCE ACTUATOR HARNESS
REMOVE ELECTRICAL CONNECTOR FROM DIVERTER VALVE (DV) ACTUATOR
VOLTAGE DIVERTER VALVE AT PCB (CH)
{GAINPCBACS}
RESISTANCE ACTUATOR HARNESS
REMOVE ELECTRICAL CONNECTOR FROM DIVERTER VALVE (DV) ACTUATOR
INSPECTION BY-PASS VALVE
ENSURE BOILER IS COO
INSPECTION DIVERTER VALVE SPINDLE (1X LOCKING PIN)
ACTUATOR REMOVED AND PRIMARY WATER DRAINED FROM PREVIOUS TEST
INSPECTION BY-PASS VALVE
ENSURE BOILER IS COO
RESISTANCE HARNESS FAN (LV)
REMOVE SIGNAL CONTRO
VOLTAGE FAN AT PCB DC (PERMANENT)
{GAINPCBACS}
REMOVE CONNECTOR CN10 FROM THE PCB AND MAKE SAFE
VOLTAGE FAN AT PCB DC (SPEED CONTROL) - NO DEMAND
{GAINPCBACS}
REMOVE CONNECTOR CN10 FROM THE PCB AND MAKE SAFE
OBSERVATION IS FAN RUNNING CONSTANTLY
REMOVE COMBUSTION COVER
OBSERVATION DISCONNECT CN9
{GAINPCBACS}
VOLTAGE MAIN PCB TO DISPLAY PCB
{GAINPCBACS}
MEASURE THE VOLTAGE BETWEEN
INFORMATION FAULTY LED
AS THE DISPLAY IS IL
OBSERVATION DISCONNECT FAN
DISCONNECT THE 4 WIRE CONNECTOR AT THE FAN AND MAKE SAFE
VOLTAGE MAINS POWER IN AT PCB
{GAINPCBACS}
INFORMATION FUSE FURTHER INVESTIGATION
THE INFORMATION PROV
RESISTANCE FUSE PCB
REMOVE FUSE F1 FROM THE PCB
PRESSURE GAS INLET AND DROP
ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT
OBSERVATION DISCONNECT FAN (NOT RUNNING)
DISCONNECT THE 4 WIRE CONNECTOR AT THE FAN AND MAKE SAFE
OBSERVATION SPARKING OCCURS
REMOVE ELECTRODE LEA
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
RESISTANCE HARNESS FAN (HV)
REMOVE MAINS VOLTAGE CONNECTOR FROM FAN ASSEMBLY
DISCONNECT EXTERNAL CONTROLS - SELF CHECK
{GAINPCBACS}
DISCONNECT EXTERNAL CONTROLS FROM CONNECTOR CN5 & MAKE SAFE
DISCONNECT EXTERNAL CONTROLS - CH OPERATION
{GAINPCBACS}
DISC
DISCONNECT EXTERNAL CONTROLS - CH OPERATION
{GAINPCBACS}
DISC
DISCONNECT EXTERNAL CONTROLS - CH OPERATION
{GAINPCBACS}
DISC
RESISTANCE HARNESS FAN (HV)
REMOVE MAINS VOLTAGE CONNECTOR FROM FAN ASSEMBLY
RESISTANCE GAS VALVE AND HARNESS
REMOVE CN2 FROM THE PCB
RESISTANCE LOW WATER PRESSURE SWITCH
REMOVE ELECTRICAL CONNECTORS FROM LWPS
RESISTANCE OVERHEAT STAT
REMOVE ELECTRICAL CONNECTORS FROM THE OVERHEAT STAT
RESISTANCE HARNESS FAN (LV)
REMOVE SIGNAL CONTRO
INSPECTION IGNITION ELECTRODE AND LEAD
DISCONNECT AND REMOVE IGNITION LEAD FROM HEAT EXCHANGER / SPARK GENERATOR
RESISTANCE GAS VALVE AND HARNESS
REMOVE CN2 FROM THE PCB
INSPECTION HEAT EXCHANGER FLUEWAYS
REMOVE FAN & BURNER ASSEMBLY
INSPECTION BURNER AND IGNITION ELECTRODE POSITION
REMOVE FAN & BURNER ASSEMBLY
REFIT IGNITION ELECTRODE IF YOU HAVE NOT ALREADY DONE SO
PRESSURE GAS INLET
ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT
INSPECTION RECTIFICATION ELECTRODE
DISCONNECT AND REMOVE RECTIFICATION LEAD FROM HEAT EXCHANGER
RESISTANCE HARNESS RECTIFICATION ELECTRODE
DISCONNECT FLAME SENSE LEAD FROM PCB AND INLINE CONNECTOR
INSPECTION HEAT EXCHANGER FLUEWAYS
REMOVE FAN & BURNER ASSEMBLY
INSPECTION BURNER AND RECTIFICATION ELECTRODE POSITION
REMOVE FAN & BURNER ASSEMBLY
REFIT RECTIFICATION ELECTRODE IF YOU HAVE NOT ALREADY DONE SO
PRESSURE GAS INLET
ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT
INSPECTION HEAT EXCHANGER FLUEWAYS
REMOVE FAN & BURNER ASSEMBLY
INSPECTION BURNER
REMOVE FAN & BURNER ASSEMBLY
RESET APPLIANCE - FAULT CODE (SENSORS)
ENSURE NO DEMANDS ARE PRESENT
INSPECTION RECTIFICATION ELECTRODE
DISCONNECT AND REMOVE RECTIFICATION LEAD FROM HEAT EXCHANGER
RESET APPLIANCE - FAULT CODE (SENSORS)
ENSURE NO DEMANDS ARE PRESENT
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR CN2 FROM THE PCB
RESISTANCE FLOW THERMISTOR
REMOVE CONNECTORS FROM FLOW SENSOR
OBSERVATION FLUE GAS TEMPERATURE
INSERT TEMPERATURE PROBE INTO FLUE GAS TEST POINT
RESET APPLIANCE - FAULT CODE (SENSORS)
ENSURE NO DEMANDS ARE PRESENT
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR CN2 FROM THE PCB
RESISTANCE FLOW THERMISTOR
REMOVE CONNECTORS FROM FLOW SENSOR
TEMPERATURE DIFFERENTIAL PLATE HEAT EXCHANGER
ATTACH TEMPERATURE PROBES TO FLOW & RETURN PIPES AT THE BOTTOM LEFT OF THE COMBUSTION CHAMBER
INSPECTION NON-RETURN VALVE
ENSURE BOILER IS COO
RESET APPLIANCE - FAULT CODE (SENSORS)
ENSURE NO DEMANDS ARE PRESENT
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR CN2 FROM THE PCB
RESISTANCE RETURN THERMISTOR
REMOVE CONNECTORS FROM RETURN SENSOR
TEMPERATURE DIFFERENTIAL PLATE HEAT EXCHANGER
ATTACH TEMPERATURE PROBES TO FLOW & RETURN PIPES AT THE BOTTOM LEFT OF THE COMBUSTION CHAMBER
INSPECTION NON-RETURN VALVE
ENSURE BOILER IS COO
RESET APPLIANCE - FAULT CODE A04
ENSURE NO DEMANDS ARE PRESENT
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR CN2 FROM THE PCB
RESISTANCE FLOW THERMISTOR
REMOVE CONNECTORS FROM FLOW SENSOR
RESISTANCE RETURN THERMISTOR
REMOVE CONNECTORS FROM RETURN SENSOR
RESISTANCE DHW THERMISTOR AND HARNESS
REMOVE CONNECTOR CN9 FROM THE PCB
TEMPERATURE DIFFERENTIAL PLATE HEAT EXCHANGER
ATTACH TEMPERATURE PROBES TO FLOW & RETURN PIPES AT THE BOTTOM LEFT OF THE COMBUSTION CHAMBER
OBSERVATION CH - OVERHEAT OCCUR
ATTACH TEMPERATURE P
INSPECTION NON-RETURN VALVE
ENSURE BOILER IS COO
RESISTANCE HARNESS FAN (LV)
REMOVE SIGNAL CONTRO
INSPECTION DHW FLOW SENSOR AND RESTRICTOR
DRAIN THE DOMESTIC H
RESISTANCE FAN AND HARNESS
REMOVE CONNECTOR CN3 FROM THE PCB
RESISTANCE SPARK GENERATOR AND HARNESS
REMOVE CONNECTOR CN1 FROM THE PCB
RESISTANCE DIVERTER VALVE ACTUATOR & HARNESS
REMOVE CONNECTOR CN4 FROM THE PCB
RESISTANCE GAS VALVE AND HARNESS
REMOVE CN2 FROM THE PCB
RESISTANCE DHW THERMISTOR AND HARNESS
REMOVE CONNECTOR CN9 FROM THE PCB
RESISTANCE DHW THERMISTOR AND HARNESS
REMOVE CONNECTOR CN9 FROM THE PCB
RESISTANCE FLOW THERMISTOR
REMOVE CONNECTORS FROM FLOW SENSOR
TEMPERATURE DIFFERENTIAL PLATE HEAT EXCHANGER
ATTACH TEMPERATURE PROBES TO FLOW & RETURN PIPES AT THE BOTTOM LEFT OF THE COMBUSTION CHAMBER
INSPECTION NON-RETURN VALVE
ENSURE BOILER IS COO
RESISTANCE DHW THERMISTOR AND HARNESS
REMOVE CONNECTOR CN9 FROM THE PCB
RESISTANCE FLOW THERMISTOR
REMOVE CONNECTORS FROM FLOW SENSOR
TEMPERATURE DIFFERENTIAL PLATE HEAT EXCHANGER
ATTACH TEMPERATURE PROBES TO FLOW & RETURN PIPES AT THE BOTTOM LEFT OF THE COMBUSTION CHAMBER
INSPECTION NON-RETURN VALVE
ENSURE BOILER IS COO
INSPECTION BY-PASS VALVE
ENSURE BOILER IS COO
INSPECTION EXPANSION VESSEL PRESSURE
DRAIN BOILER PRIMARY SYSTEM WATER
RESISTANCE FLOW THERMISTOR
REMOVE CONNECTORS FROM FLOW SENSOR
RESISTANCE RETURN THERMISTOR
REMOVE CONNECTORS FROM RETURN SENSOR
RESISTANCE HARNESS DHW FLOW TURBINE
REMOVE THE CONNECTOR FROM THE FLOW TURBINE
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR CN2 FROM THE PCB
VOLTAGE FAN AT PCB DC (SPEED CONTROL)
{GAINPCBACS}
REMOVE CONNECTOR CN10 FROM THE PCB AND MAKE SAFE
ENSURE NO DEMANDS
RESISTANCE HARNESS FAN (LV)
REMOVE SIGNAL CONTRO
RESISTANCE FLOW THERMISTOR
REMOVE CONNECTORS FROM FLOW SENSOR
RESISTANCE RETURN THERMISTOR
REMOVE CONNECTORS FROM RETURN SENSOR
RESISTANCE DHW THERMISTOR AND HARNESS
REMOVE CONNECTOR CN9 FROM THE PCB
VOLTAGE FAN AT PCB DC (HALL SENSOR)
{GAINPCBACS}
System Information
- Total Tests: 671
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control