WORCESTER 28I RSF

WARNING - IMPORTA

Next: &18, *

RE-IGNITE DELAY

SELECTOR SWITCH TO CH - MID POSITION

Next: &nff, !f168

OVERRUN OPERATION

SELECTOR SWITCH TO CH - MAX POSITION

Next: &1, f162

CH MODULATION

ATTACH A U-GAUGE TO

Next: &2, f253

SYSTEM PRESSURE RISE

Next: &3, !f158

CH OPERATION

ATTACH A U-GAUGE TO

Next: &4, ?148, ?150, ?152

DHW MODULATION

ATTACH A U-GAUGE TO THE GAS VALVE BURNER PRESSURE TEST POINT

Next: &5, f143

DHW OPERATION

Next: &6, ?129, ?131, ?133, ?135, ?427

AUTO FROST PROTECTION

Next: &7, f126

CH BURNER IGNITES

SELECTOR SWITCH TO CH - MAX POSITION

Next: &8, f115

DHW MAXIMUM GAS PRESSURE

Next: &9, f378

BURNER ESTABLISHES AT MINIMUM PRESSURE

ATTACH A U-GAUGE TO

Next: &10, ?88, ?90, ?185, ?511

DHW BURNER IGNITES

SELECTOR SWITCH IN DHW POSITION

Next: &11, f75

DHW SPARKING

REMOVE INNER CASING COVER
SELECTOR SWITCH IN DHW POSITION

Next: &12, f262

DHW FAN RUNS

SELECTOR SWITCH IN DHW POSITION

Next: &13, ?34, ?36

CH DEMAND PUMP RUN

SELECTOR SWITCH TO CH
ENSURE PUMP IS AT MAX SPEED SETTING

Next: &14, f8

DHW FLOW RATE

Next: &15, f3

WORCESTER 28I RSF

G.C. NUMBER 47 311 5

Next: &328, !f1

TYPE OF DIAGNOSTIC MODEL

PLEASE SELECT FROM O

Next: &16, !f329

FUSE INVESTIGATION TREE

OUTSIDE MODEL

Next: &nff, f402

HOW TO SET MULTIMETER TO DIODE TEST

THE IMAGES BELOW SHO

Next: &nff, !f481

ELECTRICAL SAFETY CHECKS

ELECTRICAL SAFETY CHECKS

Next: End

CH BURNER IGNITES

EXT CONTROLS - PROGRAMMER

Next: End

CH BURNER IGNITES

EXT CONTROLS - ROOM THERMOSTAT

Next: End

AUTO FROST PROTECTION

THERMISTOR / SENSOR - ELMWOOD

Next: End

DHW OPERATION

FAN ASSEMBLY

Next: End

DHW OPERATION

FLUE

Next: End

DHW OPERATION

INJECTOR NO7 4.5MM

Next: End

DHW MODULATION

THERMISTOR / SENSOR - ELMWOOD

Next: End

CH OPERATION

PIPE ASSEMBLY - BY - PASS

Next: End

CH OPERATION

THERMISTOR / SENSOR - ELMWOOD

Next: End

SYSTEM PRESSURE RISE

EXPANSION VESSEL

Next: End

OVERRUN OPERATION

THERMISTOR / SENSOR - ELMWOOD

Next: End

RE-IGNITE DELAY

PCB

Next: End

CH DEMAND PUMP RUN

EXT CONTROLS - PROGRAMMER

Next: End

BURNER ESTABLISHES AT MINIMUM PRESSURENR

INLET PRESSURE

Next: End

DHW SPARKING6666123

AIR PRESSURE TUBES

Next: End

AIR CHECK123

KIT - SWITCH AIR PRESSURE

Next: End

DHW SPARKING6666123

PROBE - AIR PRESSURE SENSING - FIRST PRESS

Next: End

BROKEN - TURNED OFF

KNOB - CONTROL - AZTEC TOOLING & MOULDING

Next: End

FAN DOES NOT RUN

KIT - SWITCH AIR PRESSURE

Next: End

CH BURNER IGNITES

KNOB - CONTROL - AZTEC TOOLING & MOULDING

Next: End

CH MODULATION

THERMISTOR / SENSOR - ELMWOOD

Next: End

FLUE123

FLUE

Next: End

DHW SPARKING9992222

SAFETY TEMPERATURE LIMITER

Next: End

AIR CHECKNSP

KIT - SWITCH AIR PRESSURE

Next: End

DHW SPARKING9992222NSP

SPARK ELECTRODE ASSEMBLY

Next: End

OVERHEAT THERMOSTAT (RESISTANCE)9992222NSP

HARNESS ASSEMBLY - IGNITION

Next: End

DHW SPARKING6666NSP

AIR PRESSURE TUBES

Next: End

DHW SPARKING6666NSP

PROBE - AIR PRESSURE SENSING - FIRST PRESS

Next: End

FLUENSP

FLUE

Next: End

OVERHEAT INVESTIGATION

SYSTEM PRESSURE

Next: End

DHW SPARKING - WILL NOT RESET

SAFETY TEMPERATURE LIMITER

Next: End

TYPE OF DIAGNOSTIC PROCEDURE

Z REDIRECT

Next: End

RUNNING SLOW - OVERHEAT INVESTIGATION

PUMP AND HARNESS ASSEMBLY

Next: End

MIN PRESSURE OUT

GAS VALVE

Next: End

OVERHEAT INVESTIGATION

PIPE ASSEMBLY - BY - PASS

Next: End

OVERHEAT INVESTIGATION CH SENSOR

THERMISTOR / SENSOR - ELMWOOD

Next: End

DHW MAXIMUM GAS PRESSURE

INLET PRESSURE

Next: End

CH DEMAND PUMP RUNS

FUSE MAINS

Next: End

CH DEMAND PUMP RUN

KIT - FUSE 1.25A & 2A 20MM

Next: End

DHW FLOW RATE

FILTER GAUZE - EXPAMET

Next: End

CH DEMAND PUMP RUN

FUSE 2A 20MM - SLOW BLOW

Next: End

FUSE INVESTIGATION

PUMP AND HARNESS ASSEMBLY

Next: End

FUSE INVESTIGATION

FAN ASSEMBLY

Next: End

FUSE INVESTIGATION GV1/2

GAS VALVE

Next: End

FUSE INVESTIGATION GV3

GAS VALVE

Next: End

CH OPERATION - TURNED LOW

KNOB - CONTROL - AZTEC TOOLING & MOULDING

Next: End

CH MODULATION - NOT TURNING DOWN

KNOB - CONTROL - AZTEC TOOLING & MOULDING

Next: End

DHW MAX GAS PRESSURE - MODUREG

GAS VALVE

Next: End

DHW MODULATION MECHANICAL

GAS VALVE

Next: End

GAS VALVE 1 2 VOLTAGE

GAS VALVE

Next: End

DHW FAN RUNS

AIR PRESSURE TUBES

Next: End

DHW TOO HOT

THERMISTOR / SENSOR - ELMWOOD

Next: End

DHW MAX PRESSURE

THERMISTOR / SENSOR - ELMWOOD

Next: End

DHW BURNER IGNITES

HARNESS - GAS VALVE - DUNGS

Next: End

DHW BURNER IGNITES

PCB

Next: End

DHW FAN RUNS

PROBE - AIR PRESSURE SENSING - FIRST PRESS

Next: End

FUSE INVESTIGATION

HARNESS - GAS VALVE - DUNGS

Next: End

BLANK FOR MULTIMETER PAGE

Z DIRECTION CHOICE OR CONTINUE

Next: End

CH DEMAND PUMP RUNS

WATER LEAK OR TAP

Next: End

BURNER DOES NOT IGNITE

BURNER ASSEMBLY

Next: End

CH DEMAND PUMP RUN

THERMISTOR / SENSOR - ELMWOOD

Next: End

CH DEMAND PUMP RUN

THERMISTOR / SENSOR - ELMWOOD

Next: End

DHW FAN RUNS

THERMISTOR / SENSOR - ELMWOOD

Next: End

DHW FAN RUNS

THERMISTOR / SENSOR - ELMWOOD

Next: End

CH BURNER IGNITES

THERMISTOR / SENSOR - ELMWOOD

Next: End

BURNER DOES NOT CROSSLIGHT

BURNER ASSEMBLY

Next: End

MINIMUM BURNER PRESSURE INCORRECT

INLET PRESSURE

Next: End

FAN RUNS SLOW

PCB

Next: End

DHW FLOW RATE

FLOW REGULATOR

Next: End

DHW BURNER IGNITES

INLET PRESSURE

Next: End

DHW BURNER IGNITES

SPARK ELECTRODE ASSEMBLY

Next: End

BURNER ESTABLISHES AT MINIMUM PRESSURE (FAIL)

PROBE - FLAME SENSOR C/W LEAD

Next: End

AUTO FROST PROTECTION

PCB

Next: End

HEAT EXCHANGER NOISY (KETTLES) DURING DHW OPERATION

HEAT EXCHANGER - GAS TO WATER - PRB 20/501

Next: End

DHW OPERATION

PCB

Next: End

DHW OPERATION

HEAT EXCHANGER - GAS TO WATER - PRB 20/501

Next: End

DHW MODULATION

GAS VALVE

Next: End

DHW MODULATION

PCB

Next: End

CH OPERATION

Next: End

CH OPERATION

HEAT EXCHANGER - GAS TO WATER - PRB 20/501

Next: End

CH OPERATION

PCB

Next: End

MAINS POWER SUPPLY

Next: End

OVERRUN OPERATON

PCB

Next: End

BURNER ESTABLISHES AT MINIMUM PRESSURE (PASS)

PROBE - FLAME SENSOR C/W LEAD

Next: End

DHW QUIET OPERATION, RADIATORS COLD

HEAT EXCHANGER - GAS TO WATER - PRB 20/501

Next: End

HEAT EXCHANGER (SECONDARY COIL)

HEAT EXCHANGER - GAS TO WATER - PRB 20/501

Next: End

CH DEMAND PUMP RUN

EXT CONTROLS - ROOM THERMOSTAT

Next: End

CH DEMAND PUMP RUN

PUMP AND HARNESS ASSEMBLY

Next: End

CH MODULATION

PCB

Next: End

SPARKING ELECTRODES123

FAN ASSEMBLY

Next: End

SPARKING ELECTRODESNSP

FAN ASSEMBLY

Next: End

OVERHEAT INVESTIGATION

HEAT EXCHANGER - GAS TO WATER - PRB 20/501

Next: End

TRIPPING EARLY - OVERHEAT INVESTIGATION

SAFETY TEMPERATURE LIMITER

Next: End

NO FAULT FOUND

OVERHEAT

Next: End

DHW MAXIMUM GAS PRESSURE

PCB

Next: End

FAN DOES NOT RUN

FAN ASSEMBLY

Next: End

CH DEMAND PUMP RUN

Next: End

MAINS FUSE

Z REDIRECT

Next: End

FUSE F2

Z REDIRECT

Next: End

FUSE F1

Z REDIRECT

Next: End

FUSE INVESTIGATION

NO FAULT FUSE INVESTIGATION

Next: End

NOT RUNNING - OVERHEAT INVESTIGATION

PUMP AND HARNESS ASSEMBLY

Next: End

DHW BURNER IGNITES

GAS VALVE ADJUSTMENT

Next: End

DHW TOO HOT

GAS VALVE

Next: End

DHW TOO HOT

PCB

Next: End

DHW MAX PRESSURE

GAS VALVE ADJUSTMENT

Next: End

DHW FAN RUNS

HARNESS - TURBINE FLOW SWITCH ASSEMBLY

Next: End

DHW FAN RUNS

KIT - SWITCH AIR PRESSURE

Next: End

DHW MAX PRESSURE

HARNESS - TURBINE FLOW SWITCH ASSEMBLY

Next: End

CH DEMAND PUMP RUN

HARNESS - TURBINE FLOW SWITCH ASSEMBLY

Next: End

DHW BURNER IGNITES

INJECTOR NO7 4.5MM

Next: End

PUMP DOES NOT RUN 2

HARNESS MAIN

Next: End

PUMP DOES NOT RUN

HARNESS MAIN

Next: End

FAN DOES NOT RUN 2

HARNESS MAIN

Next: End

FAN DOES NOT RUN

HARNESS MAIN

Next: End

CH BURNER IGNITES

HARNESS MAIN

Next: End

FAN DOES NOT RUN

PCB

Next: End

BURNER DOES NOT CROSSLIGHT

INJECTOR NO7 4.5MM

Next: End

BURNER ESTABLISHES AT MIN PRESSURE

GAS VALVE ADJUSTMENT

Next: End

FAN RUNS SLOW

FAN ASSEMBLY

Next: End

BURNER BAFFLES OUT DURING FULL DEMAND

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p130

HEAT EXCHANGER NOISY (KETTLES) DURING DHW OPERATION

CHARACTERISTIC TEST FROM DHW OPERATION

Next: !p132

DHW TOO COOL-RADIATORS REMAIN COOL WITH NO HEAT DEMAND-BOILER QUIET

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p134

DHW QUIET OPERATION, BUT PUMP RUNS AND RADIATORS HEAT

CHARACTERISTIC TEST FROM DHW OPERATION

Next: !p136

RADIATORS HEAT UP BUT HEAT EXCHANGER NOISY (KETTLES)

CHARACTERISTIC TEST FROM CH OPERATION

Next: p149

SYSTEM DOES NOT HEAT, BUT BOILER REACHES TEMPERATURE

CHARACTERISTIC TEST FROM CH OPERATION

Next: !p151

BURNER PRESSURE DOESN'T RAMP UP, RADIATORS AND BOILER STAY COOL

CHARACTERISTIC TEST FROM CH OPERATION

Next: p418

BURNER IGNITES,SPARK STOPS,BURNER SHUTS DOWN, SEQUENCE RESTARTS

CHARACTERISTIC TEST FROM BURNER ESTABLISHES AT MINIMUM PRESSURE

Next: p187

FAN DOES NOT RUN

CHARACTERISTIC TEST FROM DHW FAN RUNS

Next: p35

FAN RUNS SLOW

CHARACTERISTIC TEST FROM DHW FAN RUNS

Next: p37

OVERHEAT TRIPS BEFORE 82°C

CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER UP TO TEMPERATURE

Next: !p371

FLOW TEMPERATURE ABOVE 82°C AND BOILER DOES NOT SHUT DOWN

CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER UP TO TEMPERATURE

Next: p373

DHW TOO HOT

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p444

MINIMUM BURNER PRESSURE CORRECT BUT DOES NOT FULLY CROSSLIGHT

CHARACTERISTIC TEST FROM BURNER ESTABLISHES AT MINIMUM PRESSURE

Next: p512

BURNER FULLY CROSSLIGHTS, SPARK DOESN'T STOP, BOILER LOCKS OUT

CHARACTERISTIC TEST FROM BURNER ESTABLISHES AT MINIMUM PRESSURE

Next: p89

MINIMUM BURNER PRESSURE INCORRECT

CHARACTERISTIC TEST FROM BURNER ESTABLISHES AT MINIMUM PRESSURE

Next: p515

MAINS POWER SUPPLY

Next: p14, f389

EXTERNAL CONTROLS - ROOM THERMOSTAT (INPUT)

{GAINPCBACS}

Next: p117, f116

CH THERMISTOR SENSOR

REMOVE THE RED LEADS FROM CH THERMISTOR

Next: !p128, !f127

DHW MODULATION VOLTAGE

SET DHW FLOW RATE AT TAP TO APPROXIMATELY 5 L/MIN
AND ALLOW DHW TO RUN COLD

Next: !p145, f144

DHW THERMISTOR SENSOR

REMOVE THE YELLOW LE

Next: !p147, !f146

CH THERMISTOR SENSOR

REMOVE THE RED LEADS FROM CH THERMISTOR

Next: !p164, !f163

AIR PRESSURE SWITCH DROPPING OUT

DISCONNECT THE GREEN WIRE (NORMALLY OPEN CONNECTION) FROM THE AIR PRESSURE SWITCH AND MAKE SAFE

Next: !p192, f193

AIR PRESSURE TUBES

Next: p194, !f195

FUSE F2 (1.25 AMP)

REMOVE BOTTOM FACIA

Next: p210, f395

INSPECTION CONTROL KNOB ON POTENTIOMETER

REMOVE CONTROL KNOB FROM THE FRONT OF THE BOILER

Next: p254, !f423

OBSERVATION OVERHEAT TRIPPED

Next: p263, f264

OVERHEAT THERMOSTAT (RESISTANCE)

DISCONNECT ONE OF THE ORANGE WIRES ON THE OVERHEAT THERMOSTAT

Next: p265, !f266

AIR PRESSURE SWITCH (AIR CHECK)

REMOVE THE AIR PRESSURE SWITCH FROM THE BOILER
(MAKE A NOTE OF THE CONNECTIONS)

Next: p269, !f270

DHW GAUZE FILTER

TURN OFF DHW INLET VALVE AND DRAIN DOWN THE DHW CIRCUIT

Next: p5, !f4

PUMP VOLTAGE

SELECTOR SWITCH TO CH

Next: !p424, !f425

BY-PASS PIPE

TURN CH FLOW AND RETURN ISOLATING VALVES OFF
DRAIN AND DISCHARGE BOILER

Next: !p366, !f367

GAS PRESSURE (INLET)

ATTACH A U-GAUGE TO THE GAS VALVE INLET PRESSURE TEST POINT

Next: p379, !f380

DHW FLOW SWITCH

GAIN ACCESS TO FLOW SWITCH INLINE CONNECTOR

Next: p41, f452

DHW THERMISTOR SENSOR

REMOVE THE YELLOW LE

Next: p385, !f449

RESISTANCE FUSE (MAINS)

REMOVE THE FUSE FROM THE FUSED SPUR

Next: !p390, f392

FUSE FURTHER INVESTIGATION

Next: !p393, !f394

FUSE FURTHER INVESTIGATION

Next: !p396, !f397

FUSE FURTHER INVESTIGATION

Next: !p399, !f400

RESISTANCE PUMP

REMOVE BOTTOM FACIA PANEL
DISCONNECT CONNECTOR X3 FROM THE PCB MARKED PUMP

Next: p403, !f406

AIR PRESSURE TUBES

Next: p45, !f44

DHW THERMISTOR SENSOR

REMOVE THE YELLOW LE

Next: !p447, !f448

VOLTAGE PCB TO FLOW SWITCH

GAIN ACCESS TO FLOW SWITCH INLINE CONNECTOR
ENSURE HW TAP IS TURNED OFF

Next: !p453, !f454

VOLTAGE PCB TO FLOW SWITCH

GAIN ACCESS TO FLOW SWITCH INLINE CONNECTOR
ENSURE HW TAP IS TURNED OFF

Next: !p486, !f487

OBSERVATION ISOLATE DHW

ISOLATE THE COLD WAT

Next: !p490, !f491

CH THERMISTOR SENSOR

REMOVE THE RED LEADS FROM CH THERMISTOR

Next: !p499, !f500

DHW THERMISTOR SENSOR

REMOVE THE YELLOW LE

Next: !p497, !f498

DHW THERMISTOR SENSOR

REMOVE THE YELLOW LE

Next: !p505, !f507

CH THERMISTOR SENSOR

REMOVE THE RED LEADS FROM CH THERMISTOR

Next: !p503, !f504

CH THERMISTOR SENSOR

REMOVE THE RED LEADS FROM CH THERMISTOR

Next: !p509, !f510

BURNER PRESSURE IGNITION

SELECTOR SWITCH IN DHW POSITION
ATTACH A U-GAUGE TO THE GAS VALVE BURNER PRESSURE TEST POINT

Next: p77, f76

GAS VALVE 1 & 2 VOLTAGE

{GAINPCBACS}
SELECTOR SWITCH IN DHW POSITION

Next: p79, !f456

FLAME SENSOR ELECTRODE GAP

Next: !p166, !f96

PUMP VOLTAGE

SELECTOR SWITCH TO CH

Next: !p22, f21

EXTERNAL CONTROLS - ROOM THERMOSTAT (OUTPUT)

{GAINPCBACS}

Next: p248, !f122

CH THERMISTOR SENSOR & HARNESS

REMOVE CONNECTOR X6 FROM THE PCB

Next: !p125, f508

INSPECTION FAN

Next: p138, !f137

BURNER INJECTOR

REMOVE COMBUSTION CHAMBER COVER
REMOVE BURNER TO GAIN ACCESS TO BURNER INJECTOR

Next: !p167, !f141

FLUE

Next: !p140, !f139

FUSE F1 (2 AMP)

REMOVE BOTTOM FACIA

Next: !p16, f398

BY-PASS PIPE

TURN CH FLOW AND RETURN ISOLATING VALVES OFF
DRAIN AND DISCHARGE BOILER

Next: !p155, !f154

CH THERMISTOR SENSOR

REMOVE THE RED LEADS FROM CH THERMISTOR

Next: !p157, !f156

EXTERNAL CONTROLS - ROOM THERMOSTAT (INPUT)

{GAINPCBACS}

Next: !p20, !f19

GAS PRESSURE (INLET)

ATTACH A U-GAUGE TO THE GAS VALVE INLET PRESSURE TEST POINT

Next: p188, !f189

GAS VALVE VOLTAGE (CONSTANT)

{GAINPCBACS}
SELECTOR SWITCH IN DHW POSITION

Next: !p190, f191

AIR PRESSURE SWITCH (AIR CHECK)

REMOVE THE AIR PRESSURE SWITCH FROM THE BOILER
(MAKE A NOTE OF THE CONNECTIONS)

Next: p196, !f197

FLOW SENSOR (VENTURI)

REMOVE SILICONE RUBBER TUBES FROM THE VENTURI

Next: p198, !f199

INSPECTION FLUE

Next: !p260, !f261

INSPECTION CONTROL KNOB ON POTENTIOMETER

REMOVE CONTROL KNOB FROM THE FRONT OF THE BOILER

Next: p411, !f220

AIR PRESSURE SWITCH RESISTANCE (N/O)

DISCONNECT THE BROWN WIRE FROM THE AIR PRESSURE SWITCH COMMON TERMINAL

Next: p43, !f247

INSPECTION CONTROL KNOB ON POTENTIOMETER

REMOVE CONTROL KNOB FROM THE FRONT OF THE BOILER

Next: p123, !f252

CH THERMISTOR SENSOR

REMOVE THE RED LEADS FROM CH THERMISTOR

Next: !p255, !f256

OVERHEAT FURTHER INVESTIGATION

RESET THE OVERHEAT THERMOSTAT BY PUSHING IN THE BUTTON UNDERNEATH THE BOILER.

Next: p330, !f304

AIR PRESSURE SWITCH TESTING KIT (AIR CHECK)

REMOVE PLUS AND MINU

Next: p267, f268

AIR PRESSURE TUBES

Next: p277, !f278

SPARK ELECTRODES

REMOVE INNER CASING PANEL

Next: p271, !f272

PCB IGNITION RELAY OPERATION

{GAINPCBACS}
SELECTOR SWITCH IN DHW POSITION

Next: p273, !f274

SPARK ELECTRODE LEADS

REMOVE THE ELECTRODE LEADS

Next: !p275, !f276

FLOW SENSOR (VENTURI)

REMOVE SILICONE RUBBER TUBES FROM THE VENTURI

Next: p279, !f280

INSPECTION FLUE

Next: !p281, !f282

INSPECTION PRESSURE SYSTEM

Next: p359, !f285

CH DEMAND PUMP RUN

SELECTOR SWITCH TO CH
ENSURE PUMP IS AT MAX SPEED SETTING

Next: p283, f356

FAN VOLTAGE

SELECTOR SWITCH IN DHW POSITION

Next: !p39, f38

PUMP LIMPET TEST

Next: p360, !f361

PRESSURE MINIMUM ON CH

ATTACH A U-GAUGE TO

Next: p362, !f363

CH OPERATION (OVERHEAT)

ENSURE ALL RADIATORS ARE TURNED ON
SELECTOR SWITCH TO CH - MAX POSITION

Next: p364, f365

OBSERVATION RUN BOILER UP TO TEMPERATURE

ATTACH TEMPERATURE PROBE TO THE FLOW PIPE NEAR TO THE FLOW THERMISTOR
CH TEMPERATURE SET TO MAX

Next: p368, ?370, ?372

OVERRUN OPERATION

SELECTOR SWITCH TO CH - MAX POSITION

Next: !p376, !f377

FAN VOLTAGE

SELECTOR SWITCH IN DHW POSITION

Next: !p53, !f52

CH THERMISTOR SENSOR

REMOVE THE RED LEADS FROM CH THERMISTOR

Next: !p374, !f375

GAS VALVE 3 (RESISTANCE)

REMOVE ONE OF THE BLUE WIRES ATTACHED TO THE MODULATING SOLENOID

Next: p381, !f426

DHW FLOW SWITCH

GAIN ACCESS TO FLOW SWITCH INLINE CONNECTOR

Next: !p387, f485

RESISTANCE FAN

REMOVE BOTTOM FACIA PANEL
DISCONNECT CONNECTOR X4 FROM THE PCB MARKED FAN

Next: p404, !f407

GAS VALVE 1 & 2 RESISTANCE

REMOVE LOWER FACIA PANEL
DISCONNECT THE PLUG FROM THE GAS VALVE

Next: p457, !f408

GAS VALVE 3 (RESISTANCE)

REMOVE ONE OF THE BLUE WIRES ATTACHED TO THE MODULATING SOLENOID

Next: !p409, !f410

AIR PRESSURE SWITCH RESISTANCE (N/C)

DISCONNECT THE BROWN WIRE FROM THE AIR PRESSURE SWITCH COMMON TERMINAL

Next: p240, f42

DHW FLOW SWITCH (NO DEMAND)

GAIN ACCESS TO FLOW SWITCH INLINE CONNECTOR

Next: p412, f489

DHW THERMISTOR SENSOR & HARNESS

REMOVE CONNECTOR X6

Next: p414, f496

CH THERMISTOR SENSOR & HARNESS

REMOVE CONNECTOR X6 FROM THE PCB

Next: !p416, f495

INSPECTION CONTROL KNOB ON POTENTIOMETER

REMOVE CONTROL KNOB FROM THE FRONT OF THE BOILER

Next: p153, !f422

ADJUSTMENT GAS VALVE

ATTEMPT TO ADJUST TH

Next: !p451, !f431

DHW THERMISTOR SENSOR & HARNESS

REMOVE CONNECTOR X6

Next: p49, f501

ADJUSTMENT GAS VALVE

ATTEMPT TO ADJUST TH

Next: !p433, !f434

DHW MODULATION VOLTAGE

SET DHW FLOW RATE AT TAP TO APPROXIMATELY 5 L/MIN
AND ALLOW DHW TO RUN COLD

Next: !p445, f446

FLOW SENSOR (VENTURI)

REMOVE SILICONE RUBBER TUBES FROM THE VENTURI

Next: !p47, !f46

DIODE TEST HARNESS GAS VALVE

DISCONNECT GAS VALVE

Next: p405, !f461

CH THERMISTOR SENSOR & HARNESS

REMOVE CONNECTOR X6 FROM THE PCB

Next: !p51, f502

INSPECTION BURNER

Next: !p493, !f494

DHW FLOW RESTRICTOR

TURN OFF DHW INLET VALVE AND DRAIN DOWN THE DHW CIRCUIT.

Next: !p169, !f6

INSPECTION BURNER

Next: !p513, !f514

GAS PRESSURE (INLET)

ATTACH A U-GAUGE TO THE GAS VALVE INLET PRESSURE TEST POINT

Next: p516, !f519

ADJUSTMENT GAS VALVE

ATTEMPT TO ADJUST TH

Next: !p517, !f518

SPARK ELECTRODES GAP

Next: p492, !f84

DIODE TEST HARNESS GAS VALVE

DISCONNECT GAS VALVE

Next: p81, !f455

GAS PRESSURE (INLET)

ATTACH A U-GAUGE TO THE GAS VALVE INLET PRESSURE TEST POINT

Next: p432, !f82

FLAME SENSE (OUTPUT)

DISCONNECT FLAME SEN

Next: !p170, f94