Set Appliance State:
Turn Hot Water Tap On
Observation:
With the hot tap fully open measure DHW flow rate.
For 24kW boilers the flow rate should be approximately 8 litres a minute.
For 28kW boilers the flow rate should be approximately 10 litres a minute.
For 24kW boilers the flow rate should be approximately 8 litres a minute.
For 28kW boilers the flow rate should be approximately 10 litres a minute.