WORCESTER HIGHFLOW 400 OF LPG
G.C. NUMBER 47 311 2
COOLING FAN
{GAINPCBACS}
HEAT
CH SATISFIED
HEATING TEMPERATURE SELECTOR TO MID-RANGE
HOT WATER TEMPERATURE SELECTOR TO OFF
SPILLAGE CHECK
HEATING TEMPERATURE SELECTOR TO OFF
HOT WATER TEMPERATURE SELECTOR TO MAXIMUM
SYSTEM PRESSURE RISE
HEATING TEMPERATURE SELECTOR TO MAXIMUM
HOT WATER TEMPERATURE SELECTOR TO OFF
DHW OPERATION
HEATING TEMPERATURE
HEATBANK SATISFIED
PROGRAMMER OR SELECT
BURNER IGNITION (CH DEMAND)
HEATING TEMPERATURE SELECTOR TO MAXIMUM
HOT WATER TEMPERATURE SELECTOR TO OFF
DHW MAXIMUM PRESSURE
ATTACH U-GAUGE TO BU
BURNER IGNITION (HEATBANK)
HEATING TEMPERATURE
PUMP RUNS
HEATING TEMPERATURE
PILOT OPERATION
GAS ON
WORCESTER HIGHFLOW 400 OF LPG
G.C. NUMBER 47 311 2
DIVERTER VALVE OPERATION
HEATING TEMPERATURE SELECTOR TO MAXIMUM
HOT WATER TEMPERATURE SELECTOR TO OFF
CH OPERATION
HEATING TEMPERATURE SELECTOR TO MAXIMUM
HOT WATER TEMPERATURE SELECTOR TO OFF
PUMP OVERRUN
HEATING TEMPERATURE SELECTOR TO MAXIMUM
HOT WATER TEMPERATURE SELECTOR TO OFF
BURNER IGNITION CH DEMAND
SELECTOR SWITCH / PROGRAMMER
CH CONTROLS VOLTS OUT
FLOW SWITCH
BOILER DOES NOT SHUT DOWN GOES TO OVERHEAT
THERMOSTAT - RANCO K36P1333 (DHW STAT)
PRIMARY HEAT EXCHANGER
HEAT EXCHANGER - GIANNONI
HEATBANK SATISIFED
THERMOSTAT - HEATBANK OVERHEAT
HEATBANK SATISFIED
FLUE
DHW OPERATION BOILER SHUTS DOWN BEFORE DEMAND IS SATISFIED
THERMOSTAT - RANCO K36P1333 (DHW STAT)
DHW OPERATION BOILER SHUTS DOWN BEFORE DEMAND IS SATISFIED
HARNESS - HOT WATER OVERHEAT (DHW LIMIT STAT)
DH OPERATION
FLUE
DHW OPERATION
INJECTOR 1/8 X 120DEG X 2.8MM DIA
DHW OPERATION
FLOW SWITCH
EXPANSION VESSEL
EXPANSION VESSEL
FLUE CHECK
FLUE
CH SATISFIED
THERMOSTAT - RANCO K36P1332 (CH STAT)
COOLING FAN VOLTAGE
KIT - PCB 400 REPLACEMENT
OVERHEAT THERMOSTAT (ECO CONNECTIONS)
OVERHEAT THERMOSTAT (ECO CONNECTIONS)
PILOT OP THERMOCOUPLE INTERRUPTOR (2) FAIL
OVERHEAT THERMOSTAT (ECO CONNECTIONS)
ELECTRICAL SAFETY CHECKS
ELECTRICAL SAFETY CHECKS
SYSTEM CHECKS
SYSTEM CHECKS
SPARK ELECTRODE
ELECTRODE - IGNITION
INLET PRESSURE PILOT
INLET PRESSURE
PILOT INJECTOR
INJECTOR - PILOT
BURNER IGNITION (CH DEMAND)
THERMOSTAT - RANCO K36P1332 (CH STAT)
CH PIPE NOT HEATING
FLOW SWITCH
CH PIPE DOES NOT HEAT
THERMOSTAT - RANCO K36P1333 (DHW STAT)
FLOW SWITCH (RESISTANCE)
THERMOSTAT - RANCO K36P1333 (DHW STAT)
BY-PASS ADJUSTING SCREW
SYSTEM BY-PASS
CH OPERATION
SYSTEM BY-PASS
NOT ADJUSTED
GAS VALVE
CH OPERATION
THERMOSTAT - RANCO K36P1332 (CH STAT)
CH OPERATION
FLUE
RELAY A STICKING
KIT - PCB 400 REPLACEMENT
MAIN PCB (VOLTS OUT)
KIT - PCB 400 REPLACEMENT
FAN RUNS
SELECTOR SWITCH / PROGRAMMER
DIVERTER VALVE
PUMP AND HOUSING
DIVERTER VALVE PRESSURE RELIEF PIPE
PIPE 6MM - PRESSURE RELIEF ASSEMBLY
HEATBANK SATISFIED - POWER STUCK TO DIVERTER
KIT - PCB 400 REPLACEMENT
DHW OPERATION
EXTERNAL MIXING
DHW OPERATION - POWER STUCK TO DIVERTER
KIT - PCB 400 REPLACEMENT
CH OP - UP TO TEMP RADS COOL
ISOLATING VALVE 22MM
NOT ADJUSTED - TOO LOW
GAS VALVE
DIVERTER VALVE OPERATION
FILTER - CYLINDRICAL
DIVERTER VALVE OPERATION
ISOLATING VALVE 22MM
DHW OPERATION - DHW COOL RADS COOL
FILTER - CYLINDRICAL
HEATBANK CH HEATS
ISOLATING VALVE 22MM
DHW OPERATION
ISOLATING VALVE 22MM
DIVERTER VALVE OPERATION
COIL 230V AC - DIVERTER VALVE
PUMP OVERRUN LED STUCK ON
KIT - PCB 400 REPLACEMENT
SPARK ELECTRODE LEAD
LEAD 220MM LONG 0.7 PTFE CABLE - SPARK ELECTRODE
NO SPARKING SEEN AT ELECTRODE TIP
SPARK ELECTRODE GAP
OVERHEAT THERMOSTAT RESISTANCE
THERMOSTAT C/W LEAD ELMWOOD (OVERHEAT)
INLET FILTER
FILTER GAUZE - EXPAMET
FLOW REGULATOR
FLOW REGULATOR
PUMP RUNS
THERMOSTAT - HEATBANK OVERHEAT
FUSE 3 AMP
FUSE 3 AMP
PUMP RUN
FLOW SWITCH
BURNER IGNITION HEATBANK
HARNESS - HOT WATER OVERHEAT (DHW LIMIT STAT)
BURNER IGNITION (HEATBANK)
FSD HARNESS - THERMOSDISC (SPILLAGE STAT)
MAIN GAS VALVE RESISTANCE
GAS VALVE
IGNITION BURNER PRESSURE
INLET PRESSURE
DHW MAXIMUM PRESSURE
KIT - PCB 400 REPLACEMENT
DHW MAXIMUM PRESSURE
INLET PRESSURE
FLOW SWITCH RESISTANCE
KIT - PCB 400 REPLACEMENT
BOILER KETTLES IMMEDIATELY AND SHUTS DOWN
HEAT EXCHANGER (PLATE)
HEATBANK SATISFIED
THERMOSTAT - RANCO K36P1333 (DHW STAT)
HEATBANK SATISFIED
FSD HARNESS - THERMOSDISC (SPILLAGE STAT)
DHW OPERATION
FSD HARNESS - THERMOSDISC (SPILLAGE STAT)
COOLING FAN IMPELLER
IMPELLOR - COOLING FAN
COOLING FAN VOLTAGE
MOTOR - COOLING FAN
GAS VALVE (LOW PRESSURE)
GAS VALVE
SPARK GENERATOR
SPARK GENERATOR - KIGASS CORVETTE 5800
GAS VALVE (SUPPLY)
GAS VALVE (SUPPLY)
CH CONTROL THERMOSTAT VOLTAGE
KIT - PCB 400 REPLACEMENT
DIVERTER VALVE OPERATION
KIT - PCB 400 REPLACEMENT
DHW OP RELAY C STICKING
KIT - PCB 400 REPLACEMENT
BOILER DOES NOT HEAT RADIATORS DO NOT HEAT
THERMOSTAT - RANCO K36P1332 (CH STAT)
CH OPERATION
FSD HARNESS - THERMOSDISC (SPILLAGE STAT)
PUMP OVERRUN
KIT - PCB 400 REPLACEMENT
FAN RUNS
KIT - PCB 400 REPLACEMENT
DIVERTER VALVE OPERATION
DIVERTER VALVE
DHW OPERATION
HEAT EXCHANGER (PLATE)
HEATBANK SATISFIED
DIVERTER VALVE
DHW OPERATION
DIVERTER VALVE
PUMP RUNS NO DEMAND
SELECTOR SWITCH / PROGRAMMER
THERMOCOUPLE
THERMOCOUPLE
SPARKING SEEN AT ELECTRODE TIP BUT PILOT DOES NOT IGNITE
SPARK ELECTRODE GAP
DHW FLOW RATE
HEAT EXCHANGER (PLATE)
HEATBANK OVERHEAT THERMOSTAT RESISTANCE
KIT - PCB 400 REPLACEMENT
PUMP
PUMP
HEATBANK OVERHEAT VOLTAGE
KIT - PCB 400 REPLACEMENT
BURNER IGNITION HEATBANK
THERMOSTAT - RANCO K36P1333 (DHW STAT)
SPILLAGE DISCHARGE SAFETY DEVICE
KIT - PCB 400 REPLACEMENT
IGNITION BURNER PRESSURE
INJECTOR 1/8 X 120DEG X 2.8MM DIA
INLET PRESSURE
GAS VALVE
BOILER DOES NOT SHUT DOWN AT CORRECT TEMPERATURES AND/OR GOES TO OVERHEAT
CHARACTERISTIC TEST FROM HEATBANK SATISFIED
BOILER KETTLES IMMEDIATELY PILOT SHUTS DOWN
CHARACTERISTIC TEST FROM HEATBANK SATISFIED
BOILER SHUTS DOWN BEFORE DEMAND SATISFIED
CHARACTERISTIC TEST FROM HEATBANK SATISFIED
CH SYSTEM HEATS UP
CHARACTERISTIC TEST FROM HEATBANK SATISFIED
BOILER SHUTS DOWN BEFORE DEMAND IS SATISFIED
CHARACTERISTIC TEST FROM DHW OPERATION
DHW DOES NOT REACH TEMPERATURE
CHARACTERISTIC TEST FROM DHW OPERATION
RADIATORS HEAT UP WITH DHW DEMAND
CHARACTERISTIC TEST FROM DHW OPERATION
DHW RUNS COLD OR BOILER TAKES TOO LONG TO REFIRE
CHARACTERISTIC TEST FROM DHW OPERATION
COOLING FAN DOES NOT RUN
CHARACTERISTIC TEST FROM COOLING FAN
COOLING FAN RUNS BUT IMPELLER DAMAGED OR SLIPS
CHARACTERISTIC TEST FROM COOLING FAN
NO SPARKING SEEN AT ELECTRODE TIP
CHARACTERISTIC TEST FROM PILOT OPERATION
PILOT IGNITES BUT GOES OUT WHEN BUTTON RELEASED
CHARACTERISTIC TEST FROM PILOT OPERATION
BOILER SHUTS DOWN BEFORE DEMAND IS SATSFIED
CHARACTERISTIC TEST FROM CH OPERATION
CH NOISY (KETTLING) DHW OK
CHARACTERISTIC TEST FROM CH OPERATION
BOILER REACHES TEMPERATURE BUT RADIATORS DO NOT HEAT
CHARACTERISTIC TEST FROM CH OPERATION
BOILER DOES NOT HEAT, RADIATORS DO NOT HEAT
CHARACTERISTIC TEST FROM CH OPERATION
PILOT IGNITES AND ESTABLISHES BUT DOES NOT SWITCH OFF
CHARACTERISTIC TEST FROM PILOT OPERATION
PUMP DOES NOT OVERRUN
CHARACTERISTIC TEST FROM PUMP OVERRUN
PUMP OVERRUNS OVER 5 MINUTES
CHARACTERISTIC TEST FROM PUMP OVERRUN
SPARKING SEEN AT ELECTRODE TIP BUT PILOT DOES NOT IGNITE
CHARACTERISTIC TEST FROM PILOT OPERATION
BOILER DOES NOT REACH TEMPERATURE - RADIATORS ONLY GET WARM
CHARACTERISTIC TEST FROM CH OPERATION
09/07/2018 12:19:27 1807_1_50_2 20/07/2018 14:04:53
09/07/2018 14:13:21
FLOW SWITCH (RESISTANCE)
DISCONNECT CONNECTOR X1 (BLUE & BROWN WIRES) FROM PCB
HEATBANK OVERHEAT (RESISTANCE)
REMOVE CONNECTOR X14
INLET PRESSURE (PILOT)
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
GAS ON
DIVERTER VALVE (VOLTAGE)
{GAINPCBACS}
HEAT
FLOW SWITCH (RESISTANCE)
DISCONNECT CONNECTOR X1 (BLUE & BROWN WIRES) FROM PCB
SELECTOR SWITCH (VOLTS IN)
{GAINPCBACS}
HEAT
INLET FILTER
DISCHARGE AND DRAIN THE HOT WATER CIRCUIT
HEATBANK OVERHEAT THERMOSTAT (VOLTAGE)
{GAINPCBACS}
HEATING TEMPERATURE SELECTOR TO OFF
HOT WATER TEMPERATURE SELECTOR TO OFF
MAINS POWER SUPPLY
{GAINPCBACS}
HEATING TEMPERATURE SELECTOR TO OFF
HOT WATER TEMPERATURE SELECTOR TO OFF
FLOW SWITCH (RESISTANCE)
DISCONNECT CONNECTOR X1 (BLUE & BROWN WIRES) FROM PCB
GAS VALVE VOLTAGE
{GAINPCBACS}
PROG
DHW CONTROL THERMOSTAT (VOLTS OUT)
{GAINPCBACS}
HEAT
DHW CONTROL THERMOSTAT (VOLTS IN)
{GAINPCBACS}
PROG
INLET PRESSURE
ATTACH U-GAUGE TO IN
GAS VALVE VOLTAGE (GV3)
{GAINPCBACS}
PROG
EXTERNAL CONTROLS/ROOM THERMOSTAT (VOLTS OUT)
{GAINPCBACS}
HEAT
EXTERNAL CONTROLS/ROOM THERMOSTAT (VOLTS IN)
{GAINPCBACS}
HEAT
SELECTOR SWITCH / PROGRAMMER
{GAINPCBACS}
HEAT
DHW CONTROL THERMOSTAT (RESISTANCE)
HEATING TEMPERATURE
CH OPERATION (DIAG)
HEATING TEMPERATURE SELECTOR TO MAXIMUM
HOT WATER TEMPERATURE SELECTOR TO OFF
DHW CONTROL THERMOSTAT
{GAINPCBACS}
PROG
SPILLAGE CHECK
HEATING TEMPERATURE SELECTOR TO OFF
HOT WATER TEMPERATURE SELECTOR TO MAXIMUM
DHW CONTROL THERMOSTAT
{GAINPCBACS}
PROG
FLOW SWITCH (RESISTANCE)
DISCONNECT CONNECTOR X1 (BLUE & BROWN WIRES) FROM PCB
DHW LIMIT THERMOSTAT
{GAINPCBACS}
PROG
SPILLAGE CHECK
HEATING TEMPERATURE SELECTOR TO OFF
HOT WATER TEMPERATURE SELECTOR TO MAXIMUM
COOLING FAN (VOLTAGE)
{GAINPCBACS}
HEAT
RESISTANCE CH CONTROL THERMOSTAT
{GAINPCBACS}
CH TEMPERATURE SELECTOR TO MAX
DISCONNECT CONNECTOR X15 FROM PCB
RESISTANCE DHW CONTROL THERMOSTAT (OPEN)
{GAINPCBACS}
HOT WATER TEMPERATURE SELECTOR TO OFF
DISCONNECT CONNECTOR X2 FROM PCB
RESISTANCE DHW CONTROL THERMOSTAT
{GAINPCBACS}
HOT
CH CONTROL THERMOSTAT (RESISTANCE)
HEATING TEMPERATURE
PRESSURE BURNER (CENTRAL HEATING)
ATTACH U-GAUGE TO BU
SPILLAGE CHECK
HEATING TEMPERATURE SELECTOR TO OFF
HOT WATER TEMPERATURE SELECTOR TO MAXIMUM
OBSERVATION DEMAND LIGHT
PROGRAMMER OR SELECTOR SWITCH SET TO HOT WATER ONLY
SELECTOR SWITCH (VOLTS OUT)
{GAINPCBACS}
HEAT
RESISTANCE DIVERTER VALVE
DISCONNECT CONNECTOR X7 FROM THE PCB
INSPECTION PUMP CHECK VALVE
DRAIN BOILER PRIMARY CIRCUIT
INSPECTION DIVERTER VALVE PRESSURE RELIEF PIPE
DRAIN BOILER PRIMARY CIRCUIT
REMOVE PUMP ASSEMBLY
DIVERTER VALVE (VOLTAGE) - DHW DEMAND
{GAINPCBACS}
HEAT
DIVERTER VALVE (VOLTAGE) - DHW DEMAND
{GAINPCBACS}
HEAT
MANUAL PILOT IGNITION
IF PILOT IS EXTINGUISHED 3 MINUTES MUST ELAPSE BEFORE ATTEMPTING TO RE-LIGHT
GAS ON
INSPECTION NON-RETURN VALVE
DRAIN BOILER AND SYSTEM OF WATER
PRESSURE BURNER (CENTRAL HEATING)
ATTACH U-GAUGE TO BU
INSPECTION HEATING FILTER
DRAIN BOILER PRIMARY CIRCUIT
REMOVE THERMOSTAT PHIAL AND PHIAL POCKET
INSPECTION NON-RETURN VALVE
DRAIN BOILER AND SYSTEM OF WATER
INSPECTION HEATING FILTER
DRAIN BOILER PRIMARY CIRCUIT
REMOVE THERMOSTAT PHIAL AND PHIAL POCKET
INSPECTION NON-RETURN VALVE
DRAIN BOILER AND SYSTEM OF WATER
INSPECTION NON-RETURN VALVE
DRAIN BOILER AND SYSTEM OF WATER
OBSERVATION DISCONNECT PROGRAMMER / SELECTOR SWITCH
UNPLUG 4 PIN CONNECTOR AT X12 FROM THE PCB
THERMOCOUPLE VOLTAGE
IF PILOT IS EXTINGUI
FLOW REGULATOR
DISCHARGE AND DRAIN THE HOT WATER CIRCUIT
HEATBANK OVERHEAT THERMOSTAT (RESISTANCE)
DISCONNECT CONNECTOR X14 (RED WIRES) FROM PCB
FUSE (3 AMP)
REMOVE FUSE FROM ITS HOLDER ON THE PCB
PUMP
{GAINPCBACS}
HEAT
MAIN GAS VALVE (RESISTANCE)
REMOVE BLACK PLUG FROM MAIN GAS VALVE SOLENOID
DHW LIMIT THERMOSTAT (RESISTANCE)
REMOVE CONNECTOR X16 (BLACK WIRES) FROM PCB
SPILLAGE DISCHARGE SAFETY DEVICE (RESISTANCE)
REMOVE CONNECTOR X8 (ORANGE WIRES) FROM PCB
IGNITION BURNER PRESSURE
ATTACH U-GAUGE TO BU
INLET PRESSURE
ATTACH U-GAUGE TO IN
CH CONTROL THERMOSTAT (VOLTS IN)
{GAINPCBACS}
HEAT
System Information
- Total Tests: 215
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control