4704455 VAILLANT ECOTEC PRO 28 H COMBI HEP
GLOBALLY REPLACED
OBSERVATION DISPLAY ILLUMINATES
ON OFF SWITCH ON (SWITCH FLUSH WITH THE FASCIA ON THE APPLIANCE)
OPERATION CH
CH THERMOSTAT SET TO MAX
OBSERVATION CH DEMAND RECOGNISED
ENSURE EXTERNAL CONTROLS ARE CALLING FOR HEAT
OBSERVATION SYSTEM PRESSURE RISE
BOILER CH THERMOSTAT TO MAX
OBSERVATION WARMSTART OPERATION
ENSURE APPLIANCE PRI
OBSERVATION DHW DEMAND RECOGNISED
TURN HOT WATER TAP ON WITH A FLOW RATE OF 4 L/MIN
OBSERVATION SELF CHECK
NO DEMANDS
ENSURE WARM START TURNED OFF
ENSURE CH TURNED OFF
HEADER FOR F75 FAULT CODE
INTENTIONALLY BLANK HEADER
USER DISPLAY GUIDE
THE USER DISPLAY ON
HEADER FOR F22
INTENTIONALLY BLANK HEADER
HEADER FOR F00,F01,F10,F11,F64,F71,F85
INTENTIONALLY BLANK HEADER
F23, F24, F72, F83, F84
INTENTIONALLY BLANK HEADER
HEADER FOR F13
INTENTIONALLY BLANK HEADER
HEADER FOR F70
INTENTIONALLY BLANK HEADER
HEADER FOR F27, F62
INTENTIONALLY BLANK HEADER
HEADER FOR F32
INTENTIONALLY BLANK HEADER
HEADER FOR F20
INTENTIONALLY BLANK HEADER
HEADER FOR F49
INTENTIONALLY BLANK HEADER
HEADER FOR F61
INTENTIONALLY BLANK HEADER
HEADER FOR FUSE INVESTIGATION
INTENTIONALLY BLANK HEADER
HEADER FOR COMMUNICATION FAULT
INTENTIONALLY BLANK HEADER
USER DISPLAY GUIDE
THE USER DISPLAY ON
HEADER FOR F73, F74
INTENTIONALLY BLANK HEADER
HEADER FOR F76
INTENTIONALLY BLANK HEADER
COMBUSTION PERFORMANCE ANALYSIS
CONNECT FGA TO THE C
PRESSURE GAS INLET
ATTACH PRESSURE GAUG
HEADER FOR F68
INTENTIONALLY BLANK HEADER
HEADER FOR F77
INTENTIONALLY BLANK HEADER
NO COMMUNICATION
CABLE - DISPLAY
BLANK FOR USER DISPLAY GUIDE FOR PREHEAT
Z DIRECTION CHOICE OR CONTINUE
NOT RECOGNISING DHW DEMAND
SENSOR FITMENT
BAFFLING OUT (BLOCKED)
PIPE - INLET - AIR
BURNER BAFFLING
GAS INLET PRESSURE
DIVERTER VALVE MOTOR
HARNESS - WIRING X2
DIVERTER VALVE MOTOR CH
HARNESS - WIRING X2
NOISY
PUMP
NOISY CH
PUMP
NOT ESTABLISHING
GAS INLET PRESSURE
NOT RECTIFYING
CABLE - IGNITION
NOT RECTIFYING
ELECTRODE
CAUSING NO RECTIFICATION
BURNER
IGNITES BUT DOES NOT ESTABLISH
PIPE - INLET - AIR
POOR DHW FLOW
VALVE - CONTROL
DHW FLOW RATE
COLD WATER SUPPLY
NO DEMAND TO FAN
SENSOR - NTC CH FLOW / CH RETURN
FAN DOES NOT RUN
PCB
FAN DOES NOT RUN
HARNESS - WIRING X20
NO DEMAND FOR FAN
SENSOR - NTC - CH FLOW / CH RETURN
DHW OPERATION
SENSOR - NTC CH FLOW / CH RETURN
DHW OPERATION
SENSOR - NTC - CH FLOW / CH RETURN
DHW TOO COOL
SENSOR - NTC CH FLOW / CH RETURN
DHW TOO COOL
SENSOR - NTC - CH FLOW / CH RETURN
SLOW OR WEAK
PUMP
DHW TOO COOL RADS COLD EXCESSIVE DIFFERENTIAL
FILTER PRIMARY CIRCUIT
CALLING UP THE INSTALLER LEVEL
Z DIRECTION CHOICE OR CONTINUE
USING CHECK PROGRAMMES
Z DIRECTION CHOICE OR CONTINUE
FAULT CODE F32
PCB
FAULT CODE F32 2
PCB
FAULT CODE F32 1
PCB
FAULT CODE F32
HARNESS - WIRING X20
FAULT CODE F61
GAS SECTION
FAULT CODE F61
PCB
F49
PCB
FAULT CODE F49
PCB
DHW COOL RADS COOL
SYSTEM PRESSURE
DHW RUNS HOT THEN COLD
SYSTEM PRESSURE
F20
SENSOR - NTC - CH FLOW / CH RETURN
F20
SENSOR - NTC CH FLOW / CH RETURN
F20
CABLE - IGNITION
F20
ELECTRODE
LOW PRESSURE
SYSTEM PRESSURE
FAULT CODE F70
PCB
F13
PCB
F13
SENSOR - NTC - DHW HEAT EXCHANGER
D 071
ADJUSTMENT DIAGNOSTIC CODE
D000
ADJUSTMENT DIAGNOSTIC CODE
DIAGNOSTIC CODE D002
Z DIRECTION CHOICE OR CONTINUE
FUSE FURTHER INVESTIGATION 1
CABLE - PUMP
FUSE FURTHER INVESTIAGTION
CABLE - PUMP
F00 F01 F10 F11 F64 F71 F85
SENSOR FITMENT
FAULT CODES
SENSOR - NTC CH FLOW / CH RETURN
FAULT CODES
SENSOR - NTC - CH FLOW / CH RETURN
TYPE OF DIAGNOSTIC PROCEDURE
Z DIRECTION CHOICE OR CONTINUE
BLANK FOR FAULT CODES 2
Z DIRECTION CHOICE OR CONTINUE
F23 F24 F83 F84
SYSTEM PRESSURE
F23 F24 F83 F84
SENSOR - NTC CH FLOW / CH RETURN
F23 F24 F83 F84
SENSOR - NTC - CH FLOW / CH RETURN
OVERHEAT
CABLE - PUMP
CLOSED TOO MUCH OR BLOCKED
BY-PASS
EXCESSIVE DIFFERENTIAL AND TEMP RISE FAULT CODE
FILTER PRIMARY CIRCUIT
BLANK FOR CASE OFF
Z DIRECTION CHOICE OR CONTINUE
WEAK
PUMP
F23 F24 F83 F84
SENSOR FITMENT
OVERHEAT
SERVICE VALVES (COCK)
DIAGNOSTIC CODE D001
Z DIRECTION CHOICE OR CONTINUE
PUMP RUNS CONTINUOUSLY
SENSOR FITMENT
PUMP RUNS CONTINUOUSLY
SENSOR - NTC CH FLOW / CH RETURN
PUMP RUNS CONTINUOUSLY
SENSOR - NTC - CH FLOW / CH RETURN
TOO LOW
GAS INLET PRESSURE
PERFORMANCE TEST FAIL
PIPE - INLET - AIR
PERFORMANCE TEST FAIL
CONDENSATE SYPHON
PERFORMANCE TEST FAIL
FLUE ASSEMBLY
PERFORMANCE TEST FAIL
COMBUSTION SEALS
PERFORMANCE TEST FAIL
BURNER
PERFORMANCE TEST FAIL
HEAT EXCHANGER
PERFORMANCE TEST FAIL
COMBUSTION ADJUSTMENT
BAFFLING
HEAT EXCHANGER
BAFFLING
BURNER
BAFFLING
CONDENSATE SYPHON
BAFFLING
FLUE ASSEMBLY
DHW RUNS HOT THEN COLD
SENSOR FITMENT
DHW RUNS HOT THEN COLD
SENSOR - NTC CH FLOW / CH RETURN
DHW RUNS HOT THEN COLD
SENSOR - NTC - CH FLOW / CH RETURN
DHW RUNS HOT THEN COLD
FILTER PRIMARY CIRCUIT
SHUT CAUSING CH NOISE
BY-PASS
F76
PCB
F76
HARNESS - WIRING X20
D 093
ADJUSTMENT DIAGNOSTIC CODE
BLOWN STAND BY MODE AT POWER UP
FUSE (MAINS)
HARNESS X20 AND X25
HARNESS - WIRING X20
HARNESS X2
HARNESS - WIRING X2
FUSE F1
FUSE F1
OUT OF CAL STOPPING DHW DEMAND RECOGNITION
SENSOR - NTC - CH FLOW / CH RETURN
BURNER NOT IGNITING
GAS INLET PRESSURE
SPARKING NOT LIGHTING
ELECTRODE
HIGH FAN PRESSURE
PIPE - INLET - AIR
RESTRICTED FAN PRESSURE
CONDENSATE SYPHON
RESTRICTED FAN PRESSURE
BURNER
RESTRICTED FAN PRESSURE
HEAT EXCHANGER
RESTRICTED FAN PRESSURE
FLUE ASSEMBLY
BURNER DOES NOT IGNITE
PCB AND GAS SECTION
SPARKING BUT NOT LIGHTING
GAS SECTION
POOR HOT WATER
EXTERNAL MIXING
NOT SHUTTING BURNER DOWN CH
SENSOR - NTC CH FLOW / CH RETURN
NOT SHUTTING BURNER DOWN CH
SENSOR - NTC - CH FLOW / CH RETURN
NO COMMUNICATION 1
CABLE - DISPLAY
F73 F74
HARNESS - WIRING X2
F73 - F74
SYSTEM PRESSURE
F22
SYSTEM PRESSURE
MEASURING FLOW RATE AND TEMP RISES
Z DIRECTION CHOICE OR CONTINUE
POOR HOT WATER
CONDENSATE SYPHON
POOR HOT WATER
FLUE ASSEMBLY
POOR HOT WATER
HEAT EXCHANGER
POOR HOT WATER
PIPE - INLET - AIR
POOR HOT WATER
BURNER
POOR HOT WATER
FAN ASSEMBLY
S34
SENSOR - NTC CH FLOW / CH RETURN
S34
SENSOR - NTC - CH FLOW / CH RETURN
FROST PROTECTION
SENSOR - NTC CH FLOW / CH RETURN
FROST PROTECTION
SENSOR - NTC - CH FLOW / CH RETURN
NOT RECOGNISING DEMAND
BURNER OFF LINK
FAULT CODE F70
ADJUSTMENT DIAGNOSTIC CODE
D093 ADJUSTMENT
Z DIRECTION CHOICE OR CONTINUE
FAULT CODE F32 1
HARNESS - WIRING X20
F32
HARNESS - WIRING X20
FAULT CODE F75
SYSTEM PRESSURE
PUMP PULSING
SYSTEM PRESSURE
FAULT CODE F75
CABLE - PUMP
FAULT CODE F68
CONDENSATE SYPHON
FAULT CODE F68
FLUE ASSEMBLY
FAULT CODE F68
CABLE - IGNITION
FAULT CODE F68
ELECTRODE
FAULTY
CONDENSATE PUMP
DC HALL SENSOR
HARNESS - WIRING X20
SPARKING
CABLE - IGNITION
SPARKING
ELECTRODE
DC HALL SENSOR CONDENSATE PUMP
HARNESS - WIRING X20
SPARKING CONDENSATE PUMP
CABLE - IGNITION
SPARKING CONDENSATE PUMP
ELECTRODE
FAULT CODE F75
AIR VENT - AUTOMATIC
FAULT CODE F75
EXPANSION VESSEL 10L
DOES NOT RUN
PUMP
FAULT CODE F75
FILTER PRIMARY CIRCUIT
FAULT CODE F75
PUMP
FAULT CODE F75 2
AIR VENT - AUTOMATIC
FAULT CODE F75 2
EXPANSION VESSEL 10L
FAULT CODE F75 2
FILTER PRIMARY CIRCUIT
FAULTY CONDENSE PUMP
CONDENSATE FAULT CODE
CH NOISY
SERVICE VALVES (COCK)
TURNED OFF
SERVICE VALVES (COCK)
CH STAYING TOO COOL
SENSOR - NTC CH FLOW / CH RETURN
CH STAYING TOO COOL
SENSOR - NTC - CH FLOW / CH RETURN
FLAT
EXPANSION VESSEL 10L
BOILER NOT RECOGNISING FACILITY
SENSOR - NTC - DHW HEAT EXCHANGER
WARMSTART ISSUES
SENSOR - NTC CH FLOW / CH RETURN
WARMSTART ISSUES
SENSOR - NTC - CH FLOW / CH RETURN
WARM START NOT HOT ENOUGH
SENSOR - NTC - DHW HEAT EXCHANGER
OPEN TOO MUCH SO BYPASSING RADS
BY-PASS
TO AQUA SENSOR
HARNESS - WIRING X2
OUT OF CAL STOPING DHW DEMAND RECOGNITION
SENSOR - NTC CH FLOW / CH RETURN
FOR USER DISPLAY GUIDE
Z DIRECTION CHOICE OR CONTINUE
NOT OPENING TO RADS POSITION
VALVE - 3 WAY
PASSING SOLENOIDS
GAS SECTION
F27 F62
ELECTRODE
NO COMMUNICATION
DISPLAY
HEAT EXCHANGER - DHW
HEAT EXCHANGER - 13 PLATES - DHW
FLOW LIMITER
LIMITER
PASSING TO RADS
DIVERTER VALVE MOTOR
PASSING TO RADS CH
DIVERTER VALVE MOTOR
FILTER DHW
FILTER DHW
BAFFLING
GAS SECTION
NOT RUNNING WITH CORRECT VOLTAGES
FAN ASSEMBLY
DHW TOO COOL
HEAT EXCHANGER
DHW TOO COOL
HEAT EXCHANGER - 13 PLATES - DHW
NOT RSPONDING TO CH DEMAND
EBUS CONTROL
NOT RSPONDING TO CH DEMAND 3
EBUS CONTROL
F32
FAULT CODE RESET
FAULT CODE F32
FAN ASSEMBLY
FAULT CODE F61
HARNESS - WIRING X20
F61
FAULT CODE RESET
F49
FAULT CODE RESET - F49
FAULT CODE F49
EBUS CONTROL
F20
FAULT CODE RESET
F20 2
HARNESS - WIRING X20
F20
HARNESS - WIRING X20
F20
PCB
SYSTEM PRESSURE FURTHER INVESTIGATION
Z DIRECTION CHOICE OR CONTINUE
DSN NUMBER
FAULT CODE RESET
FAULT CODE F70
FACTORY RESET
F13
FAULT CODE RESET
F13
HARNESS - WIRING X2
RAD TEMP LOW
Z DIRECTION CHOICE OR CONTINUE
RADIATOR TEMP LOW
Z DIRECTION CHOICE OR CONTINUE
BLANK DISPLAY
FUSE FURTHER INVESTIGATION
FUSE INVESTIGATION
PUMP
F00 F01 F10 F11 F64 F71 F85
FAULT CODE RESET
THERMISTOR FAULT CODES FLOW SENSOR
HARNESS - WIRING X20
THERMISTOR FAULT CODES RETURN SENSOR
HARNESS - WIRING X20
BLANK FOR FAULT CODES
Z DIRECTION CHOICE OR CONTINUE
OVERHEAT
PUMP
NOT RESPONDING TO CH DEMAND 4
EBUS CONTROL
F23 F24 F83 F84
HEAT EXCHANGER
F23 F24 F83 F84
HEAT EXCHANGER - 13 PLATES - DHW
NOT REGISTERING PRESSURE
SENSOR - WATER PRESSURE
BLOCKED OR RESTRICTED
SENSOR - WATER PRESSURE
BLOCKED OR RESTRICTED
ADAPTOR
PUMP RUNS CONTINUOUSLY
FROST PROTECTION - NORMAL OPERATION
PERFORMANCE TEST FAIL
GAS SECTION
COMBUSTION VALUES
Z DIRECTION CHOICE OR CONTINUE
DHW RUNS HOT THEN COLD
HEAT EXCHANGER
NOT RSPONDING TO CH DEMAND 2
EBUS CONTROL
NOISY
HEAT EXCHANGER - 13 PLATES - DHW
SCALED-NOISY
HEAT EXCHANGER
F76
FAULT CODE RESET
F76
LINK FOR FLUE GAS SAFETY TEMP LIMITER
POOR HW
Z DIRECTION CHOICE OR CONTINUE
FURTHER INVESTIGATION MAINS
Z DIRECTION CHOICE OR CONTINUE
CAUSING BLANK DISPLAY
FAN ASSEMBLY
AQUA SENSOR
SENSOR - FLOW
BLANK DISPLAY
SENSOR - WATER PRESSURE
DISPLAY PCB
DISPLAY
HARNESS DISPLAY PCB
CABLE - DISPLAY
PCB MAIN
PCB
FURTHER INVESTIGATION FUSE F1
Z DIRECTION CHOICE OR CONTINUE
INCORRECT MIX
GAS SECTION
FAN PRESSURE INCORRECT
FAN ASSEMBLY
BURNER DOES NOT IGNITE
PCB AND HARNESS X20
SPARKING BUT NOT LIGHTING
HARNESS - WIRING X20
SOLENOID NOT OPENING
GAS SECTION
DHW TOO COOL
PCB
NO COMMUNICATION 1
DISPLAY
FAULT CODE F73 - F74
SENSOR - WATER PRESSURE
F73 F74
SENSOR - WATER PRESSURE
F73 F74
ADAPTOR
FAULT CODE F73 F74
SENSOR - WATER PRESSURE
FAULT CODE F73 - F74
FAULT CODE RESET
F72
SENSOR - WATER PRESSURE
FAULT CODE F22
ADAPTOR
FAULT CODE F22
SENSOR - WATER PRESSURE
LOW SYSTEM PRESSURE
FAULT CODE RESET
POOR HOT WATER
GAS SECTION
OPERATION CORRECTLY
FROST PROTECTION - NORMAL OPERATION
TAP OPEN OR LEAKING DHW DRAW OFF
TAP OPEN OR LEAKING DHW DRAW OFF
SPANNER ON DISPLAY
MAINTENANCE INTERVAL SURPASSED
FAULT CODE F70
Z DIRECTION CHOICE OR CONTINUE
FAULT CODE F32 1
FAN ASSEMBLY
FAULT CODE F32 3
PCB
SHORTED
CABLE - PUMP
FAULT CODE F75 F75
PUMP
F68
PCB
SPANNER ON DISPLAY 2
MAINTENANCE INTERVAL SURPASSED
HALL SENSOR SIGNAL
FAN ASSEMBLY
NOT SPARKING
PCB
HALL SENSOR SIGNAL CONDENSATE PUMP
FAN ASSEMBLY
FAULTY 2
CONDENSATE PUMP
FAULT CODE F75
SENSOR - WATER PRESSURE
FAULT CODE F75 2
SENSOR - WATER PRESSURE
PASSING TO RADS
VALVE - 3 WAY
BLOCKED
TUBE - EXPANSION VESSEL
WARM START SENSOR
HARNESS - WIRING X2
NOT SENSING DEMAND
SENSOR - FLOW
F27 F62
PCB
LIMITER BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION FLOW LIMITER AND FILTER
FILTER BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION FLOW LIMITER AND FILTER
DIFFERENTIAL EXCESSIVE
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER
BOILER DOES NOT RESPOND TO CENTRAL HEATING
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER
24 VOLT EXTERNAL CONTROLS FITTED
CHARACTERISTIC TEST FROM OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
EBUS CONTROLS FITTED
CHARACTERISTIC TEST FROM OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
24 VOLT EXTERNAL CONTROLS FITTED
CHARACTERISTIC TEST FROM OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
EBUS CONTROLS FITTED
CHARACTERISTIC TEST FROM OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
FAN DOES NOT RUN
CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS - FAULT CODE F32
FAN RUNS AND/OR STOPS AND RESTARTS - FAULT CODE F32 OCCURS
CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS - FAULT CODE F32
BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
BURNER IGNITES BUT DOES NOT ESTABLISH (FLAME SYMBOL DOES NOT APPEAR ON DISPLAY) - RECTIFICATION ISSUE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
BURNER IGNITES BUT BAFFLES OUT/NOISY - COMBUSTION ISSUE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION AND ESTABLISH
PUMP RUNS CONTINUOUSLY
CHARACTERISTIC TEST FROM OBSERVATION SELF CHECK
LOW SYSTEM PRESSURE DISPLAYED
CHARACTERISTIC TEST FROM OBSERVATION SELF CHECK
CON X22 PUMP SPEED CONTROL RESISTANCES NOT AS ABOVE
CHARACTERISTIC TEST FROM RESISTANCE PUMP AND HARNESS
CON X18 PUMP MAIN SUPPLY RESISTANCES NOT AS ABOVE
CHARACTERISTIC TEST FROM RESISTANCE PUMP AND HARNESS
DIFFERENTIAL EXCESSIVE
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER
BOILER DOES NOT RESPOND TO CENTRAL HEATING
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER
24 VOLT EXTERNAL CONTROLS FITTED
CHARACTERISTIC TEST FROM OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
EBUS CONTROLS FITTED
CHARACTERISTIC TEST FROM OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
WATER PRESSURE SENSOR RESTRICTED OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION WATER PRESSURE SENSOR AND ADAPTOR
ADAPTOR RESTRICTED OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION WATER PRESSURE SENSOR AND ADAPTOR
STATUS CODE S.34 SHOWN
CHARACTERISTIC TEST FROM OBSERVATION WHICH STATUS CODE IS SHOWN
STATUS CODE S.96 OR S.98 SHOWN
CHARACTERISTIC TEST FROM OBSERVATION WHICH STATUS CODE IS SHOWN
DIFFERENTIAL EXCESSIVE
CHARACTERISTIC TEST FROM RESISTANCE PUMP AND HARNESS
BOILER DOES NOT RESPOND TO CENTRAL HEATING
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER
24 VOLT EXTERNAL CONTROLS FITTED
CHARACTERISTIC TEST FROM OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
EBUS CONTROLS FITTED
CHARACTERISTIC TEST FROM OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
DIFFERENTIAL INCORRECT OR LOCAL NOISE
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER FOR CH NOISE
DIFFERENTIAL OK SYSTEM NOISE
CHARACTERISTIC TEST FROM DIFFERENTIAL PRIMARY HEAT EXCHANGER FOR CH NOISE
DHW TOO HOT
CHARACTERISTIC TEST FROM OPERATION DHW
DISPLAY ILLUMINATES BUT NO INFORMATION/TEXT ON SCREEN
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY ILLUMINATES
TEMPERATURE RISE UNSATISFACTORY, RADIATORS REMAIN COOL
CHARACTERISTIC TEST FROM OPERATION DHW
DISPLAY DOES NOT ILLUMINATE
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY ILLUMINATES
TEMPERATURE RISE UNSATISFACTORY, RADIATORS HEAT WITH NO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION DHW
DHW RUNS HOT THEN COLD
CHARACTERISTIC TEST FROM OPERATION DHW
BOILER COMPLETES SELF CHECK AS DESCRIBED BUT SPANNER ON THE DISPLAY
CHARACTERISTIC TEST FROM OBSERVATION SELF CHECK
ADAPTOR RESTRICTED OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION WATER PRESSURE SENSOR AND ADAPTOR
WATER PRESSURE SENSOR RESTRCITED OR BLOCKED
CHARACTERISTIC TEST FROM RESISTANCE PUMP AND HARNESS
ADAPTOR RESTRICTED OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION WATER PRESSURE SENSOR AND ADAPTOR
WATER PRESSURE SENSOR RESTRICTED OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION WATER PRESSURE SENSOR AND ADAPTOR
PUMP DOES NOT RUN
CHARACTERISTIC TEST FROM OBSERVATION PUMP BEHAVIOUR F75
PUMP RUNS OR F75 OCCURING INTERMITTENTLY
CHARACTERISTIC TEST FROM OBSERVATION PUMP BEHAVIOUR F75
BOILER NOISY
CHARACTERISTIC TEST FROM OPERATION CH
BOILER UP TO TEMP RADS COLD
CHARACTERISTIC TEST FROM OPERATION CH
BOILER AND SYSTEM TEMPERATURE LOW
CHARACTERISTIC TEST FROM OPERATION CH
BOILER DOES NOT GIVE THE OPTION OF ACTIVATING WARMSTART
CHARACTERISTIC TEST FROM OBSERVATION WARMSTART OPERATION
BOILER DOES NOT HEAT SUFFICIENTLY ON WARM START
CHARACTERISTIC TEST FROM OBSERVATION WARMSTART OPERATION
BOILER FIRES WITH NO DEMAND
CHARACTERISTIC TEST FROM OBSERVATION SELF CHECK
FAULT CODE SHOWN
CHARACTERISTIC TEST FROM OBSERVATION SELF CHECK
25/08/2021 08:48:03 2108_1_50_1 23/09/2021 09:29:12
14/09/2021 12:07:54
VOLTAGE TO DISPLAY PCB AT MAIN PCB
REMOVE THE DISPLAY HARNESS CONNECTOR FROM THE MAIN PCB
VOLTAGE DIVERTER VALVE
REMOVE CONNECTOR FROM THE DIVERTER VALVE AND MAKE SAFE
ENSURE NO DEMANDS
VOLTAGE DIVERTER VALVE
REMOVE CONNECTOR FROM THE DIVERTER VALVE AND MAKE SAFE
ENSURE NO DEMANDS
VOLTAGE DC PWM DEMAND AT FAN
{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR FROM FAN ASSEMBLY AND MAKE SAFE
RESISTANCE FLOW SENSOR
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
TEMPERATURE DIFFERENTIAL PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE C
OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
GAIN ACCESS TO THE PCB
RESISTANCE GAS VALVE AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE GAS VALVE
REMOVE THE LEFT HAND
OBSERVATION ARE ANY EBUS CONTROLS FITTED
{GAINPCBACS}
RESISTANCE PUMP AND HARNESS
REMOVE CONNECTOR X22
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESISTANCE FLOW SENSOR AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE FLOW SENSOR
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
OBSERVATION IS THE DSN SET CORRECTLY - D.093
ENSURE NO DEMANDS
RESISTANCE WARM START SENSOR
REMOVE THE CONNECTOR FROM THE WARM START SENSOR
RESISTANCE FLOW SENSOR
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
RESET APPLIANCE - ENSURE APPLIANCE IS COOL
ENSURE NO DEMANDS ARE PRESENT
ENSURE APPLIANCE IS COOL
RESISTANCE FLOW SENSOR
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
VOLTAGE PUMP AT PCB
{GAINPCBACS}
TEMPERATURE DIFFERENTIAL PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE C
INSPECTION WATER PRESSURE SENSOR AND ADAPTOR
DRAIN PRIMARY WATER
INSPECTION AIR INTAKE TUBE
REMOVE AIR INTAKE TUBE
INSPECTION BURNER
REMOVE THE COMBUSTION FRONT ASSEMBLY
TEMPERATURE DIFFERENTIAL PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE C
RESISTANCE HARNESS AND LINK FOR FLUE GAS SAFETY TEMP LIMITER
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE HARNESS FLUE GAS SAFETY TEMP LIMITER
REMOVE CONNECTOR X20 FROM THE PCB
DISCONNECT THE PLUG AT THE INLINE CONNECTOR (AS SHOWN)
DIAGNOSTIC CODE D.093 SET CORRECTLY
THE DEVICE SPECIFIC
RESISTANCE MAINS SUPPLY FUSE
REMOVE THE MAINS 3A FUSE FROM ITS HOLDER
OBSERVATION RE ATTACH X2
REFIT CONNECTOR X2 (BLUE) TO THE PCB
OBSERVATION RE ATTACH X20
REFIT CONNECTOR X20 (RED) TO THE PCB
OBSERVATION RE ATTACH X22 BUT DISCONNECT PUMP SPEED CONTROL
REFIT CONNECTOR X22 TO THE PCB
DISCONNECT PUMP SPEED CONTROL FROM THE PUMP AND MAKE SAFE
OBSERVATION DISCONNECT LOW WATER PRESSURE SENSOR
REMOVE THE CONNECTOR FROM THE LOW WATER
PRESSURE SWITCH AND MAKE SAFE
VOLTAGE TO DISPLAY PCB AT MAIN PCB
REMOVE THE DISPLAY HARNESS CONNECTOR FROM THE MAIN PCB
RESISTANCE FUSE F1
REMOVE FUSE F1 FROM ITS HOLDER ON THE PCB
INSPECTION AIR INTAKE TUBE
REMOVE AIR INTAKE TUBE
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
RESISTANCE GAS VALVE AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE GAS VALVE
REMOVE THE LEFT HAND
RESISTANCE GAS VALVE
REMOVE THE LEFT HAND
INSPECTION AIR INTAKE TUBE
REMOVE AIR INTAKE TUBE
INSPECTION WATER PRESSURE SENSOR AND ADAPTOR
DRAIN PRIMARY WATER
RESISTANCE FLOW SENSOR
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
DIAGNOSTIC CODE D.093 SET CORRECTLY
THE DEVICE SPECIFIC
RESISTANCE FAN HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
REMOVE THE DC FAN CONNECTOR FROM THE FAN ASSEMBLY
OBSERVATION DISCONNECT CONDENSATE PUMP (SPANNER)
REMOVE THE TWO WIRES
OBSERVATION VAILLANT CONDENSATE PUMP FITTED (X40)
GAIN ACCESS TO THE PCB
RESISTANCE FAN HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
REMOVE THE DC FAN CONNECTOR FROM THE FAN ASSEMBLY
OBSERVATION DISCONNECT CONDENSATE PUMP (SPARKING)
REMOVE IGNITION ELEC
VOLTAGE HALL SENSOR
{GAINPCBACS}
RESISTANCE FAN HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
REMOVE THE DC FAN CONNECTOR FROM THE FAN ASSEMBLY
PRESSURE EXPANSION VESSEL
APPLIANCE PRIMARY CIRCUIT DRAINED AND DISCHARGED
RESISTANCE WARM START SENSOR
REMOVE THE CONNECTOR FROM THE WARM START SENSOR
VOLTAGE DEMAND FROM AQUA SENSOR
{GAINPCBACS}
ENSURE A FLOW RATE ABOVE 3 LITRES PER MINUTE
RESISTANCE WARM START SENSOR AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESISTANCE HARNESS DISPLAY PCB
REMOVE DISPLAY HARNESS FROM X51 CONNECTIONS
INSPECTION AIR INTAKE TUBE
REMOVE AIR INTAKE TUBE
PRESSURE GAS INLET
ATTACH PRESSURE GAUG
INSPECTION FLOW LIMITER AND FILTER
DHW SUPPLY ISOLATED
RESISTANCE DIVERTER VALVE HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
REMOVE THE CONNECTOR FROM THE DIVERTER VALVE MOTOR
RESISTANCE DIVERTER VALVE HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
REMOVE THE CONNECTOR FROM THE DIVERTER VALVE MOTOR
INSPECTION AIR INTAKE TUBE
REMOVE AIR INTAKE TUBE
PRESSURE GAS INLET
ATTACH PRESSURE GAUG
RESISTANCE IGNITION LEAD
REMOVE THE IGNITION LEAD FROM THE PCB
REMOVE THE IGNITION LEAD FROM THE SPARK ELECTRODE
INSPECTION SPARK ELECTRODE
REMOVE THE SPARK ELECTRODE ASSEMBLY
INSPECTION BURNER
REMOVE THE COMBUSTION FRONT ASSEMBLY
INSPECTION BURNER
REMOVE THE COMBUSTION FRONT ASSEMBLY
INSPECTION PRIMARY HEAT EXCHANGER FLUEWAYS
REMOVE THE BURNER DOOR ASSEMBLY
VOLTAGE FAN 22VDC AT PCB
{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR FROM FAN ASSEMBLY AND MAKE SAFE
RESISTANCE RETURN SENSOR
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
RESISTANCE FAN HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
REMOVE THE DC FAN CONNECTOR FROM THE FAN ASSEMBLY
RESISTANCE FLOW SENSOR
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
RESISTANCE FLOW SENSOR
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
TEMPERATURE DIFFERENTIAL DHW HEAT EXCHANGER
ATTACH TEMPERATURE C
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE DRAINED AND DISCHARGED
DISCONNECT EBUS CONTROLS - CH DEMAND
DISCONNECT EBUS WIRING FROM CONNECTOR X100 AND MAKE SAFE
VOLTAGE FROM 240V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE FROM 24V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
OBSERVATION D.000 - ADJUSTABLE HEATING PARTIAL LOAD
ENSURE NO DEMANDS
OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
GAIN ACCESS TO THE PCB
VOLTAGE FROM 240V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE FROM 24V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
DISCONNECT EBUS CONTROLS - CH DEMAND
DISCONNECT EBUS WIRING FROM CONNECTOR X100 AND MAKE SAFE
VOLTAGE DC PWM DEMAND AT FAN
{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR FROM FAN ASSEMBLY AND MAKE SAFE
VOLTAGE HALL SENSOR
{GAINPCBACS}
VOLTAGE FAN 22VDC AT PCB
{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR FROM FAN ASSEMBLY AND MAKE SAFE
RESISTANCE FAN HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
REMOVE THE DC FAN CONNECTOR FROM THE FAN ASSEMBLY
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
DISCONNECT EBUS CONTROLS
DISCONNECT EBUS WIRING FROM CONNECTOR X100 AND MAKE SAFE
RESISTANCE RETURN SENSOR AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE IGNITION LEAD
REMOVE THE IGNITION LEAD FROM THE PCB
REMOVE THE IGNITION LEAD FROM THE SPARK ELECTRODE
INSPECTION SPARK ELECTRODE
REMOVE THE SPARK ELECTRODE ASSEMBLY
OBSERVATION IS THE DSN SET CORRECTLY - D.093
ENSURE NO DEMANDS
SYSTEM PRESSURE FURTHER INVESTIGATION
THE SYSTEM PRESSURE
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
OBSERVATION D.071 - TARGET VALUE MAXIMUM HEATING FLOW TEMPERATURE
ENSURE NO DEMANDS
DIAGNOSTIC CODE D.000 SET CORRECTLY
THE HEATING PARTIAL
DIAGNOSTIC CODE D.071 SET CORRECTLY
THE TARGET VALUE MAX
RESISTANCE PUMP SPEED CONTROL HARNESS
REMOVE CONNECTOR X22
RESISTANCE PUMP MAIN SUPPLY HARNESS
REMOVE CONNECTOR X18
RESISTANCE FLOW SENSOR AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE RETURN SENSOR AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE RETURN SENSOR
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
RESISTANCE PUMP MAIN SUPPLY HARNESS
REMOVE CONNECTOR X18
TEMPERATURE DIFFERENTIAL DHW HEAT EXCHANGER
ATTACH TEMPERATURE C
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE DRAINED AND DISCHARGED
OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
GAIN ACCESS TO THE PCB
VOLTAGE FROM 240V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE FROM 24V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
DISCONNECT EBUS CONTROLS - CH DEMAND
DISCONNECT EBUS WIRING FROM CONNECTOR X100 AND MAKE SAFE
INSPECTION INTEGRAL BYPASS
APPLIANCE DRAINED AND DISCHARGED
OBSERVATION PUMP OVERRUN
ENSURE CH CONTROLS ARE CALLING FOR HEAT
RESISTANCE FLOW SENSOR
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
OBSERVATION CAN COMBUSTION BE ADJUSTED
CONNECT FGA TO THE C
COMBUSTION VALUES CORRECTLY ADJUSTED
THE COMBUSTION READI
INSPECTION PRIMARY HEAT EXCHANGER FLUEWAYS
REMOVE THE BURNER DOOR ASSEMBLY
RESISTANCE FLOW SENSOR
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE DRAINED AND DISCHARGED
OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED ?
GAIN ACCESS TO THE PCB
VOLTAGE FROM 240V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
VOLTAGE FROM 24V EXTERNAL CONTROLS
{GAINPCBACS}
ENSURE ALL EXTERNAL CONTROLS ARE CALLING
DISCONNECT EBUS CONTROLS - CH DEMAND
DISCONNECT EBUS WIRING FROM CONNECTOR X100 AND MAKE SAFE
TEMPERATURE DIFFERENTIAL PRIMARY HEAT EXCHANGER FOR CH NOISE
ATTACH TEMPERATURE C
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
VOLTAGE MAINS POWER INPUT TO APPLIANCE
{GAINPCBACS}
OBSERVATION REMOVE CONNECTORS FROM PCB
REMOVE CONNECTORS X20 (RED) X2 (BLUE) AND X22 FROM
THE PCB AND MAKE SAFE
OBSERVATION DISCONNECT AQUA SENSOR
REMOVE THE CONNECTOR FROM THE AQUA SENSOR AND MAKE SAFE
INSPECTION DIVERTER VALVE MOTOR OPERATION
REMOVE THE DIVERTER
RESISTANCE FAN HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
REMOVE THE DC FAN CONNECTOR FROM THE FAN ASSEMBLY
TEMPERATURE DIFFERENTIAL DHW HEAT EXCHANGER
ATTACH TEMPERATURE C
PRESSURE GAS INLET
ATTACH PRESSURE GAUG
OBSERVATION IS SPARKING PRESENT
REMOVE IGNITION ELEC
INSPECTION SPARK ELECTRODE
REMOVE THE SPARK ELECTRODE ASSEMBLY
PRESSURE FAN
ATTACH PRESSURE TUBE
PRESSURE FAN - EQUALISATION
ATTACH PRESSURE TUBE
INSPECTION BURNER
REMOVE THE COMBUSTION FRONT ASSEMBLY
INSPECTION PRIMARY HEAT EXCHANGER FLUEWAYS
REMOVE THE BURNER DOOR ASSEMBLY
RESISTANCE GAS VALVE AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE FLOW SENSOR
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
VOLTAGE TO DISPLAY PCB AT MAIN PCB
REMOVE THE DISPLAY HARNESS CONNECTOR FROM THE MAIN PCB
RESISTANCE HARNESS DISPLAY PCB
REMOVE DISPLAY HARNESS FROM X51 CONNECTIONS
VOLTAGE FROM WATER PRESSURE SENSOR
{GAINPCBACS}
OBSERVATION ADJUST PRIMARY SYSTEM PRESSURE
LOCATE SYSTEM FILING LOOP
RESISTANCE WATER PRESSURE SENSOR HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
REMOVE CONNECTOR FROM THE LOW WATER PRESSURE SWITCH
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
OBSERVATION ADJUST SYSTEM PRESSURE
{GAINPCBACS}
LOCATE THE SYSTEM FILLING LOOP
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
INSPECTION WATER PRESSURE SENSOR AND ADAPTOR
DRAIN PRIMARY WATER
INSPECTION BURNER
REMOVE THE COMBUSTION FRONT ASSEMBLY
INSPECTION PRIMARY HEAT EXCHANGER FLUEWAYS
REMOVE THE BURNER DOOR ASSEMBLY
RESISTANCE FLOW SENSOR
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
RESISTANCE RETURN SENSOR
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
OBSERVATION DHW DEMAND INCORRECTLY RECOGNISED
HOT WATER TAPS OFF
OBSERVATION ISOLATE MAINS WATER - DOES DEMAND STOP ?
TURN OFF THE DHW ISOLATION VALVE
RESISTANCE FAN HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
REMOVE THE DC FAN CONNECTOR FROM THE FAN ASSEMBLY
VOLTAGE PUMP AT PCB
{GAINPCBACS}
RESISTANCE PUMP MAIN SUPPLY HARNESS
REMOVE CONNECTOR X18
RESISTANCE IGNITION LEAD
REMOVE THE IGNITION LEAD FROM THE PCB
REMOVE THE IGNITION LEAD FROM THE SPARK ELECTRODE
INSPECTION SPARK ELECTRODE
REMOVE THE SPARK ELECTRODE ASSEMBLY
OBSERVATION VAILLANT CONDENSATE PUMP FITTED (BURNER OFF)
GAIN ACCESS TO THE PCB
VOLTAGE HALL SENSOR
{GAINPCBACS}
RESISTANCE IGNITION LEAD
REMOVE THE IGNITION LEAD FROM THE PCB
REMOVE THE IGNITION LEAD FROM THE SPARK ELECTRODE
INSPECTION SPARK ELECTRODE
REMOVE THE SPARK ELECTRODE ASSEMBLY
RESISTANCE IGNITION LEAD
REMOVE THE IGNITION LEAD FROM THE PCB
REMOVE THE IGNITION LEAD FROM THE SPARK ELECTRODE
INSPECTION SPARK ELECTRODE
REMOVE THE SPARK ELECTRODE ASSEMBLY
PRESSURE EXPANSION VESSEL
APPLIANCE PRIMARY CIRCUIT DRAINED AND DISCHARGED
INSPECTION PUMP IMPELLER
BOILER PRIMARY CIRCUIT DRAINED AS NECESSARY
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE DRAINED AND DISCHARGED
PRESSURE EXPANSION VESSEL
APPLIANCE PRIMARY CIRCUIT DRAINED AND DISCHARGED
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE DRAINED AND DISCHARGED
RESISTANCE FLOW SENSOR
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
INSPECTION INTEGRAL BYPASS
APPLIANCE DRAINED AND DISCHARGED
RESISTANCE RETURN SENSOR
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
RESISTANCE WARM START SENSOR AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
RESISTANCE FLOW SENSOR
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE RETURN SENSOR
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
RESISTANCE WARM START SENSOR
REMOVE THE CONNECTOR FROM THE WARM START SENSOR
INSPECTION DIVERTER VALVE MOTOR OPERATION
REMOVE THE DIVERTER
OBSERVATION CLOSE INTEGRAL BYPASS
CLOSE THE INTEGRAL B
RESISTANCE FLOW SENSOR
REMOVE THE CONNECTOR FROM THE FLOW SENSOR (RED)
RESISTANCE CHECK AQUA SENSOR HARNESS
REMOVE THE CONNECTOR FROM THE AQUA SENSOR
REMOVE CONNECTOR X2 FROM THE PCB
RESISTANCE RETURN SENSOR
REMOVE THE CONNECTOR FROM THE RETURN SENSOR (BLUE)
INSPECTION DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER VALVE MOTOR FROM THE BODY
INSPECTION SPARK ELECTRODE
REMOVE THE SPARK ELECTRODE ASSEMBLY
System Information
- Total Tests: 689
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control