Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
POTTERTON ENVOY 40
GC NUMBER 41 607 61<
DISPLAY SHOWS '0', '1', '2' OR 'H'
SET THE BOILER CONTROL SWITCH TO O POSITION
DISPLAY ILLUMINATES
SET THE BOILER CONTROL SWITCH TO O POSITION
INFORMATION
{ISOLATEMAINSPOWER}
SYSTEM CHECKS
{ISOLATEMAINSPOWER}
ENSURE THE FOLLOWING SYSTEM CHECKS ARE COMPLETED
POTTERTON ENVOY 40
{ISOLATEMAINSPOWER}<
BURNER IGNITES
CONDENSATE PIPE
BURNER IGNITES
GAS VALVE SOLENOID EV1
BURNER IGNITES
SOLENOID OPERATOR
BURNER ESTABLISHED
FLAME DETECTION ELECTRODE LEAD
BOILER NOISY
CONDENSATE PIPE
BOILER NOISY
SYPHON
CENTRAL HEATING OPERATION
CONTROL ASSEMBLY
CENTRAL HEATING OPERATION
SIGHT GLASS
CENTRAL HEATING OPERATION
FLUE HOOD/ELBOW SEALING RING
NEGATIVE PRESSURE ONLY
CONTROL ASSEMBLY
BURNER ESTABLISHED
CONTROL ASSEMBLY
RE-IGNITE DELAY
CONTROL ASSEMBLY
FROST PROTECTION
CONTROL ASSEMBLY
PUMP OVERRUN
CONTROL ASSEMBLY
DISPLAY BOARD SHOWS 'C'
CONDENSATE PIPE
HOT SURFACE IGNITOR
CONTROL ASSEMBLY
CENTRAL HEATING OPERATION
GAS VALVE ARRANGEMENT (GAS RATE)
NEGATIVE ONLY
IMPULSE TUBE
NO GAS
IMPULSE TUBE
MODULATION
THERMISTOR (FLOW SENSOR)
ELECTRICAL SAFETY CHECKS
ELECTRICAL CHECKS
SYSTEM CHECKS
SYSTEM CHECKS
INFORMATION
INCORRECT USE OF 'FAIL'
DISPLAY ILLUMINATES
FUSE T3A
DISPLAY SHOWS '0', '1', '2' OR 'H'
THERMISTOR (FLOW SENSOR)
DISPLAY SHOWS '0', '1', '2' OR 'H'
THERMISTOR (RETURN SENSOR)
DISPLAY SHOWS '0', '1', '2' OR 'H'
THERMISTOR (CASE SENSOR)
DISPLAY SHOWS '0', '1', '2' OR 'H'
THERMISTOR (DRY FIRE SENSOR)
DISPLAY SHOWS '0', '1', '2' OR 'H'
FLAME DETECTION ELECTRODE LEAD
DISPLAY SHOWS '0', '1', '2' OR 'H'
REVERSE POLARITY
DISPLAY SHOWS '0', '1', '2' OR 'H'
BOILER CONTROL SWITCH (3 POSITION)
FAN RUNS (HIGH POSITION)
WIRING LOOM
FAN RUNS (HIGH POSITION)
BOILER CONTROL SWITCH (3 POSITION)
FAN RUNS (HIGH POSITION)
CONTROL ASSEMBLY
FAN RUNS (HIGH POSITION)
SENSOR FIXING AND HEAT SINK COMPOUND
BURNER IGNITES
BURNER INJECTOR
BURNER IGNITES
SYPHON
NEGATIVE PRESSURE ONLY
GAS VALVE ARRANGEMENT
BURNER ESTABLISHED
GAS VALVE ARRANGEMENT
BURNER ESTABLISHED
FLAME DETECTION ELECTRODE
CENTRAL HEATING OPERATION
HEAT EXCHANGER
CENTRAL HEATING OPERATION
PUMP (EXTERNAL)
CENTRAL HEATING OPERATION
GASKETS
DISPLAY BOARD SHOWS 'C'
SYPHON
MODULATION
CONTROL ASSEMBLY
DISPLAY ILLUMINATES
CONTROL ASSEMBLY
DISPLAY BOARD SHOWS '5'
CONTROL ASSEMBLY
DISPLAY BOARD SHOWS '6'
CONTROL ASSEMBLY
DISPLAY BOARD SHOWS '7'
CONTROL ASSEMBLY
DISPLAY BOARD SHOWS '8'
CONTROL ASSEMBLY
DISPLAY BOARD SHOWS 'A'
FLAME DETECTION ELECTRODE
DISPLAY BOARD SHOWS ANY OTHER DISPLAY
CONTROL ASSEMBLY
FAN RUNS (HIGH POSITION)
PUMP (EXTERNAL)
FAN RUNS (LOW POSITION)
BOILER CONTROL SWITCH (3 POSITION)
DISPLAY BOARD SHOWS NON-FLASHING 'F'
GAS VALVE ARRANGEMENT
BURNER IGNITES
BURNER
BURNER IGNITES
HOT SURFACE IGNITER
DISPLAY BOARD SHOWS FLASHING 'F'
CHARACTERISTIC TEST FROM BURNER ESTABLISHED
DISPLAY BOARD SHOWS NON-FLASHING 'F'
CHARACTERISTIC TEST FROM BURNER ESTABLISHED
BOILER NOISY
CHARACTERISTIC TEST FROM CENTRAL HEATING OPERATION
BOILER QUIET
CHARACTERISTIC TEST FROM CENTRAL HEATING OPERATION
DISPLAY BOARD SHOWS '1', '2' OR 'H'
CHARACTERISTIC TEST FROM CENTRAL HEATING OPERATION
DISPLAY BOARD SHOWS '3'
CHARACTERISTIC TEST FROM CENTRAL HEATING OPERATION
DISPLAY BOARD SHOWS 'C'
CHARACTERISTIC TEST FROM CENTRAL HEATING OPERATION
DISPLAY BOARD SHOWS '5'
CHARACTERISTIC TEST FROM DISPLAY SHOWS '0', '1', '2' OR 'H'
DISPLAY BOARD SHOWS '6'
CHARACTERISTIC TEST FROM DISPLAY SHOWS '0', '1', '2' OR 'H'
DISPLAY BOARD SHOWS '7'
CHARACTERISTIC TEST FROM DISPLAY SHOWS '0', '1', '2' OR 'H'
DISPLAY BOARD SHOWS '8'
CHARACTERISTIC TEST FROM DISPLAY SHOWS '0', '1', '2' OR 'H'
DISPLAY BOARD SHOWS 'A'
CHARACTERISTIC TEST FROM DISPLAY SHOWS '0', '1', '2' OR 'H'
DISPLAY BOARD SHOWS ANY OTHER DISPLAY
CHARACTERISTIC TEST FROM DISPLAY SHOWS '0', '1', '2' OR 'H'
DISPLAY BOARD SHOWS '0', '1', '2' OR 'H'
CHARACTERISTIC TEST FROM FAN RUNS (HIGH POSITION)
DISPLAY BOARD SHOWS ANY OTHER DISPLAY
CHARACTERISTIC TEST FROM DISPLAY SHOWS '0', '1', '2' OR 'H'
DISPLAY BOARD SHOWS '9'
CHARACTERISTIC TEST FROM FAN RUNS (LOW POSITION)
FAN DOES NOT RUN
CHARACTERISTIC TEST FROM FAN RUNS (LOW POSITION)
BURNER DOES NOT IGNITE AND DISPLAY BOARD SHOWS FLASHING F
CHARACTERISTIC TEST FROM BURNER IGNITES
BURNER DOES NOT IGNITE AND DISPLAY BOARD SHOWS NON-FLASHING F
CHARACTERISTIC TEST FROM BURNER IGNITES
PRESSURE LESS THAN +11.8 MBAR
CHARACTERISTIC TEST FROM GAS VALVE IGNITION PRESSURE
NEGATIVE PRESSURE ONLY
CHARACTERISTIC TEST FROM GAS VALVE IGNITION PRESSURE
NO PRESSURE, U-GAUGE RECORDS 0 PRESSURE
CHARACTERISTIC TEST FROM GAS VALVE IGNITION PRESSURE
NO NEGATIVE PRESSURE AND ABOVE +16MBAR
CHARACTERISTIC TEST FROM GAS VALVE IGNITION PRESSURE
10/07/2014 09:07:45 1712_1_50_1 09/01/2018 08:43:29
15/12/2017 09:28:36
VOLTAGE TO PUMP
{ISOLATEMAINSPOWER}<
FLOW SENSOR RESISTANCE (CALLING OR MODULATION)
{ISOLATEMAINSPOWER}
REMOVE FUNCTIONAL CASE DOOR
REMOVE THE RED WIRES FROM THE FLOW SENSOR
MAINS POWER SUPPLY
{ISOLATEMAINSPOWER}<
EXTERNAL CONTROLS/ROOM THERMOSTAT VOLTAGE
{ISOLATEMAINSPOWER}<
IGNITER VOLTAGE
{ISOLATEMAINSPOWER}<
GAS VALVE 1 SOLENOID RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE BLACK PLUG FROM THE LOWER SOLENOID ON GAS VALVE
GAS VALVE 2 SOLENOID RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE BLACK PLUG FROM THE UPPER SOLENOID ON THE GAS VALVE
FLAME DETECT VOLTAGE
{ISOLATEMAINSPOWER}<
FLAME DETECT LEAD RESISTANCE
{ISOLATEMAINSPOWER}<
EXTERNAL PUMP RUNS
SET BOILER CONTROL SWITCH TO H POSITION
SIGHT GLASS
{ISOLATEMAINSPOWER}
REMOVE THE FUNCTIONAL CASE DOOR
SYPHON
{ISOLATEMAINSPOWER}
REMOVE THE FUNCTIONAL CASE DOOR
FLUE HOOD/ELBOW SEALING RING
{ISOLATEMAINSPOWER}
REMOVE THE FUNCTIONAL CASE DOOR
INSPECTION IMPULSE TUBE
{ISOLATEMAINSPOWER}
REMOVE IMPULSE TUBE FROM GAS VALVE TO FAN
INSPECTION IMPULSE TUBE
{ISOLATEMAINSPOWER}
REMOVE IMPULSE TUBE FROM GAS VALVE TO FAN
FUSE (T3) RESISTANCE
{ISOLATEMAINSPOWER}<
FLOW SENSOR RESISTANCE (CALLING OR MODULATION)
{ISOLATEMAINSPOWER}
REMOVE FUNCTIONAL CASE DOOR
REMOVE THE RED WIRES FROM THE FLOW SENSOR
RETURN SENSOR RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE FUNCTIONAL CASE DOOR
REMOVE THE ORANGE LEADS FROM THE SENSOR
CASE SENSOR RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE FUNCTIONAL CASE DOOR
REMOVE THE YELLOW WIRES FROM THE CASE SENSOR
DRY FIRE SENSOR RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE FUNCTIONAL CASE DOOR
REMOVE THE GREY WIRES FROM THE DRY FIRE SENSOR
FLAME DETECT LEAD SHORT TO EARTH
{ISOLATEMAINSPOWER}<
POLARITY CHECK
{ISOLATEMAINSPOWER}<
BOILER CONTROL SWITCH RESISTANCE
{ISOLATEMAINSPOWER}<
EXTERNAL PUMP RUNS
SET BOILER CONTROL SWITCH TO H POSITION
WIRING LOOM
{ISOLATEMAINSPOWER}<
SENSOR FITTING AND HEAT SINK COMPOUND
{ISOLATEMAINSPOWER}
REMOVE FUNCTIONAL CASE DOOR
BOILER CONTROL SWITCH RESISTANCE
{ISOLATEMAINSPOWER}<
VOLTAGE TO PUMP
{ISOLATEMAINSPOWER}<
GAS VALVE IGNITION PRESSURE
{ISOLATEMAINSPOWER}<
HOT SURFACE IGNITER
SET BOILER CONTROL SWITCH TO H POSITION
GAS VALVE VOLTAGE
{ISOLATEMAINSPOWER}<
System Information
- Total Tests: 144
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control