WORCESTER GREENSTAR COMPACT COMBI ERP

GLOBALLY REPLACED

Next: &400, *

OBSERVATION BOILER SELF CHECK

ENSURE CENTRAL HEATING TURNED OFF
ENSURE APPLIANCE IS SET TO ECO MODE

Next: &38, ?411, ?2293, ?2307

OBSERVATION PUMP RUNS

ENSURE APPLIANCE IS SET TO ECO MODE
DHW TEMPERATURE CONTROL TO MAX

Next: &57, f436

OBSERVATION FAN RUNS

ENSURE APPLIANCE IS SET TO ECO MODE
DHW TEMPERATURE CONTROL TO MAX

Next: &176, f508

OBSERVATION BURNER IGNITION

ENSURE APPLIANCE IS SET TO ECO MODE
DHW TEMPERATURE CONTROL TO MAX

Next: &266, ?228, ?1481, ?2061, ?2119, ?2315

OBSERVATION CH DEMAND

Next: &303, f270

OPERATION DHW

DHW TEMPERATURE CONTROL TO MAX

Next: &635, ?278, ?281, ?306, ?364, ?379

OPERATION CH

CH TEMPERATURE CONTROL TO MAX

Next: &277, ?304, ?308, ?326, ?719

OBSERVATION PUMP OVERRUN

ENSURE BOILER IS SET TO ECO MODE

Next: &1844, ?775, ?780, ?3158

FAULT CODES

Next: &nff, !f410

TYPE OF DIAGNOSTIC PROCEDURE

Next: &526, !f524

OPERATION PREHEAT

EXTERNAL AND INTERNA

Next: &342, ?3162, ?3171, ?3173

ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE

BLANK

Next: &nff, ?1489, ?1491, ?1493, ?1515, ?1551, ?1573, ?1618, ?1703, ?1839, ?1866, ?1870, ?2657

FAULT CODE 210 E9

OUTSIDE MODEL

Next: &nff, p885

FAULT CODE 221 E9

OUTSIDE MODEL

Next: &nff, p923

FAULT CODE 231 FD

OUTSIDE MODEL

Next: &nff, f931

FAULT CODE 375 376 E4

Next: &nff, f1293

FAULT CODE 233 9U

OUTSIDE MODEL

Next: &nff, f942

FAULT CODE 240 241 286 D1 285 E9

OUTSIDE MODEL

Next: &nff, f1002

FAULT CODE 223 E2

Next: &nff, f993

FAULT CODE 264 C1

Next: &nff, f1008

FAULT CODE 228 F7

OUTSIDE MODEL

Next: &nff, f1019

FAULT CODE H13

Next: &nff, f1034

FAULT CODE 323 A8

OUTSIDE MODEL

Next: &nff, f1161

FAULT CODE 327

Next: &nff, f1042

FAULT CODE 306 FA

Next: &nff, f1046

FAULT CODE 229 EA 374 8C

Next: &nff, f2530

FAULT CODE 260 345 EF

OUTSIDE MODEL

Next: &nff, f1416

FAULT CODE 271

Next: &nff, f1443

FAULT CODE 278 F0

Next: &nff, f1268

FAULT CODE 380

Next: &nff, f1310

INFORMATION BOILER SETUP PARAMETERS


1. ENTER

Next: &nff, !f1360

FAULT CODE 219 220 277 E9

OUTSIDE MODEL

Next: &nff, f1367

FAULT CODE 218 332 E5 222 E2 276 E9

OUTSIDE MODEL

Next: &nff, f1391

FAULT CODE 237 273 C4 274

Next: &nff, f1424

FAULT CODE 212

OUTSIDE MODEL

Next: &nff, f1434

FAULT CODE 373 8C

OUTSIDE MODEL

Next: &nff, f1462

INFORMATION BOILER TEST MODES


1. ENTER

Next: &nff, !f1488

INFORMATION SETUP PARAMETER LIST

OUTSIDE MODEL, NOT CURRENTLY USED.

Next: &nff, !f1529

FAULT CODE 800 CC

OUTSIDE MODEL

Next: &nff, f1708

COMBUSTION TEST MAX AND MINIMUM

Next: &nff, ?1846, ?1848

FAULT CODE 234 EA

OUTSIDE MODEL

Next: &nff, f2662

FAULT CODE 238 F0

OUTSIDE MODEL

Next: &nff, f2682

OBSERVATION SPARKING HEARD

REMOVE AIR INTAKE FR

Next: &nff, !f2690

INFORMATION USER DISPLAY

Next: &1, !f2954

FAULT CODE 258 356 EH

INTENTIONALLY BLANK

Next: &nff, f3148

LITE DIAGNOSTIC

DIAGNOSIS RELIES ON

Next: &nff, !f3348

QUICK ACCESS DATA AND INFORMATION

THE TABLE BELOW SHOW

Next: &nff, !f3350

HEADER FOR QADAI SENSOR DHW

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3352

HEADER FOR QADAI SENSOR DHW INLET

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3356

HEADER FOR QADAI SENSOR FLOW

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3360

HEADER FOR QADAI SENSOR RETURN

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3364

HEADER FOR QADAI SENSOR SAFETY

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3368

HEADER FOR QADAI SPARK GEN RESISTANCE

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3372

HEADER FOR QADAI SPARK GEN VOLTAGE

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3376

HEADER FOR QADAI PUMP RESISTANCE

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3380

HEADER FOR QADAI PUMP VOLTAGE

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3384

HEADER FOR QADAI FAN RESISTANCE

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3388

HEADER FOR QADAI FAN VOLTAGE

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3392

HEADER FOR QADAI DIVERTER VALVE RESISTANCE

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3396

HEADER FOR QADAI DIVERTER VALVE VOLTAGE

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3400

HEADER FOR QADAI GAS VALVE RESISTANCE

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3404

HEADER FOR QADAI GAS VALVE VOLTAGE

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3408

HEADER FOR QADAI FLOW TURBINE VOLTAGE

INTENTIONALLY BLANK FOR QADAI

Next: &nff, f3412

FAULT CODE 223 E2

SENSOR 18MM (FLOW)

Next: End

FAULT CODE 240 241 286 D1 285 D9

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 264 C1

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FAULT CODE H13

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 306 FA

FLUE

Next: End

FAULT 306 FA

SYPHON - LCS

Next: End

FAULT CODE 306 FA PASSING

GAS VALVE

Next: End

FAULT CODE 327

RESET SWITCH

Next: End

FAULT CODE 228 F7

HARNESS - LOW VOLTAGE

Next: End

FAULT 228 F7

SYPHON - LCS

Next: End

FAULT CODE 228 F7

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 323 A8 FW100 NOT FITTED

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 323 A8 FW100 FITTED

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 278 F0 RETURN SENSOR

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 278 F0

SENSOR - NTC MAX (OVERHEAT)

Next: End

FAULT CODE 278 F0

SENSOR 18MM (FLOW)

Next: End

FAULT CODE 278 F0

SENSOR - TEMPERATURE (DHW)

Next: End

FAULT CODE 375 376 E4 SENSOR NOT FITTED

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 375 376 E4

SENSOR NTC - RIGHT ANGLED (DHW INLET SENSOR)

Next: End

FAULT CODE 380 SENSOR NOT FITTED

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 380

SENSOR NTC - RIGHT ANGLED (DHW INLET SENSOR)

Next: End

FAULT CODE 219 220 277 E9 WILL NOT RESET

SENSOR - NTC MAX (OVERHEAT)

Next: End

FAULT CODE 219 220 227 E9 WILL NOT RESET

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 219 220 277 E9

SYSTEM PRESSURE

Next: End

FAULT CODE 219 220 277 E9

PUMP

Next: End

FAULT CODE 219 220 277 E9

SENSOR 18MM (FLOW)

Next: End

FAULT CODE 218 332 E5 222 E2 267 E9 WILL NOT RESET

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 218 332 E5 222 E2 267 E9

SYSTEM PRESSURE

Next: End

FAULT CODE 218 332 E5 222 E2 267 E9

SENSOR 18MM (FLOW)

Next: End

FAULT CODE 218 332 E5 222 E2 267 E9 WILL NOT RESET

SENSOR - NTC MAX (OVERHEAT)

Next: End

FAULT CODE 260

SYSTEM PRESSURE

Next: End

FAULT CODE 260

SENSOR 18MM (FLOW)

Next: End

FAULT CODE 237 273 C4 274

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 212

SENSOR 18MM (FLOW)

Next: End

FAULT CODE 212

SENSOR - NTC MAX (OVERHEAT)

Next: End

FAULT CODE 212

PUMP

Next: End

FAULT CODE 212

SYSTEM PRESSURE

Next: End

FAULT CODE 271

SYSTEM PRESSURE

Next: End

FAULT CODE 271

PUMP

Next: End

FAULT CODE 271

SENSOR - NTC MAX (OVERHEAT)

Next: End

FAULT CODE 271

SENSOR 18MM (FLOW)

Next: End

FAULT CODE 373 8C

Z REDIRECT

Next: End

FAULT CODE 373 8C

SYSTEM PRESSURE

Next: End

FAULT CODE 373 8C

PUMP

Next: End

FAULT CODE 373 8C WILL NOT RESET

SENSOR - NTC MAX (OVERHEAT)

Next: End

FAULT CODE 373 8C

SENSOR 18MM (FLOW)

Next: End

OBSERVATION BURNER IGNITION IGNITES BUT CUTS OUT

SENSOR - NTC MAX (OVERHEAT)

Next: End

INFORMATION BOILER TEST MODES

Z REDIRECT

Next: End

INFORMATION SETUP PARAMETER LIST

Z REDIRECT

Next: End

OPERATION DHW FLOW RATE NOT OBTAINABLE

ISOLATION VALVES

Next: End

OPERATION DHW DHW COOL RADS COOL

SENSOR - TEMPERATURE (DHW)

Next: End

FAULT CODE 800 CC SENSOR NOT FITTED

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 800 CC SENSOR FITTED

CONTROL BOX - SKIN MID

Next: End

COMBUSTION TEST

ELECTRODE

Next: End

FAULT CODE 278 F0

SENSOR NTC - RIGHT ANGLED (DHW INLET SENSOR)

Next: End

OBSERVATION PUMP RUNS INSUFFICIENT FLOW

WATER SUPPLY (BELOW MINIMUM)

Next: End

OPERATION DHW

WATER SUPPLY (INSUFFICIENT)

Next: End

OPERATION DHW TOO COOL BOILER CUTS OUT

PLATE HEAT EXCHANGER

Next: End

OBSERVATION FAN RUNS

SENSOR 18MM (FLOW)

Next: End

OBSERVATION BURNER IGNITION

CONTROL BOX - SKIN MID AND GAS VALVE

Next: End

OBSERVATION BURNER IGNITION TO GAS VALVE SPARK NO IGNITION

HARNESS ASSEMBLY - HV & IGNITION

Next: End

OBSERVATION BURNER IGNITION NO IGNITION

PIPE - SUCTION (AIR INTAKE)

Next: End

OBSERVATION BURNER IGNITION IGNITION LEAD

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FAULT CODE 278 F0 NO INLET SENSOR

CONTROL BOX - SKIN MID

Next: End

OBSERVATION BURNER IGNITION NO POWER TO SPARK GEN

CONTROL BOX - SKIN MID

Next: End

OBSERVATION BURNER IGNITION HARNESS TO SPARK GENERATOR NO SPARKING

HARNESS ASSEMBLY - HV & IGNITION

Next: End

OBSERVATION BURNER IGNITION DOES NOT ESTABLISH

VALVE - GAS-AIR (BEARING PLATE)

Next: End

OBSERVATION BURNER IGNITION DOES NOT ESTABLISH

PIPE - SUCTION (AIR INTAKE)

Next: End

OBSERVATION BURNER IGNITION RECTIFICATION GROUND

HARNESS - LOW VOLTAGE

Next: End

OBSERVATION BURNER IGNITION RECTIFICATION LEAD

HARNESS - LOW VOLTAGE

Next: End

OBSERVATION BURNER IGNITION IGNITION LEAD NO SPARKING

HARNESS ASSEMBLY - HV & IGNITION

Next: End

OBSERVATION BOILER SELF CHECK FROST PROTECTION

SENSOR 18MM (FLOW)

Next: End

OBSERVATION BURNER IGNITION BAFFLES

SYPHON - LCS

Next: End

OBSERVATION BURNER IGNITION BAFFLES

VALVE - GAS-AIR (BEARING PLATE)

Next: End

OBSERVATION BURNER IGNITION BAFFLES

PIPE - SUCTION (AIR INTAKE)

Next: End

OPERATION CH SHUTS DOWN BEFORE TEMP

HEAT EXCHANGER ASSEMBLY

Next: End

FURTHER INVESTIGATION FUSE PCB

GAS VALVE

Next: End

FURTHER INVESTIGATION FUSE PCB

TRANSFORMER - IGNITION

Next: End

FURTHER INVESTIGATION FUSE

CONTROL BOX - SKIN MID

Next: End

FURTHER INVESTIGATION MAINS FUSE

GAS VALVE

Next: End

FURTHER INVESTIGATION MAINS FUSE

TRANSFORMER - IGNITION

Next: End

FURTHER INVESTIGATION MAINS FUSE

CONTROL BOX - SKIN MID

Next: End

OBSERVATION DISPLAY ILLUMINATES FAULTY DISPLAY

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 229 EA BAFFLES

SYPHON - LCS

Next: End

FAULT CODE 229 EA BAFFLES

FLUE

Next: End

FAULT CODE 229 EA BAFFLES

VALVE - GAS-AIR (BEARING PLATE)

Next: End

FAULT CODE 229 EA BAFFLES

FLUEWAYS

Next: End

FAULT CODE 229 EA BAFFLES

PIPE - SUCTION (AIR INTAKE)

Next: End

FAULT CODE 229 EA BAFFLES OR NOISY

HOUSING - BURNER

Next: End

FAULT CODE 229 EA DOES NOT ESTABLISH

VALVE - GAS-AIR (BEARING PLATE)

Next: End

FAULT CODE 229 EA DOES NOT ESTABLISH

PIPE - SUCTION (AIR INTAKE)

Next: End

FAULT CODE 229 EA RECTIFICATION GROUND

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 229 EAN RECTIFICATION LEAD

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 229 EADOES NOT IGNITE

SYPHON - LCS

Next: End

FAULT CODE 229 EA DOES NOT IGNITE

VALVE - GAS-AIR (BEARING PLATE)

Next: End

FAULT CODE 229 EA

BURNER

Next: End

FAULT CODE 229 EA

CONTROL BOX - SKIN MID AND GAS VALVE

Next: End

FAULT CODE 229 EA TO GAS VALVE SPARK NO IGNITION

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FAULT CODE 229 EA NO IGNITION

PIPE - SUCTION (AIR INTAKE)

Next: End

FAULT CODE 229 EA IGNITION LEAD

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FAULT CODE 229 EA IGNITES OK

VALVE - GAS-AIR (BEARING PLATE)

Next: End

FAULT CODE 229 EA IGNITES OK

INLET PRESSURE

Next: End

FAULT CODE 229 EA IGNITION OK

ELECTRODE

Next: End

FAULT CODE 234 EA

GAS VALVE

Next: End

FAULT CODE 238 F0 RESETS BUT FAULT REOCCURS

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FAULT CODE 234 EA

Z REDIRECT

Next: End

OBSERVATION SPARKING HEARD

Z REDIRECT

Next: End

OBSERVATION FAN RUNS NO RESPONSE TO DHW

SENSOR NTC - RIGHT ANGLED (DHW INLET SENSOR)

Next: End

FAULT CODE 238 F0

WATER INGRESS

Next: End

FAULT CODE 238 F0 WILL NOT RESET

GAS VALVE

Next: End

FAULT CODE 260 345 EF

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FAULT CODE 260 345 EF NO POWER TO PUMP

CONTROL BOX - SKIN MID

Next: End

OBSERVATION CH DEMAND NOT RESPONDING TO DEMAND

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 271 NO POWER TO PUMP

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 271

HARNESS ASSEMBLY - HV & IGNITION

Next: End

OBSERVATION CH DEMAND NO POWER TO EXT CONTROLS

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 373 8C NO POWER TO PUMP

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 373 8C

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FAULT CODE 218 332 E5 222 E2 267 E9

HEAT EXCHANGER ASSEMBLY

Next: End

FAULT CODE 219 220 277 E9

HEAT EXCHANGER ASSEMBLY

Next: End

FAULT CODE 373 8C

Next: End

FAULT CODE 373 8C

HEAT EXCHANGER ASSEMBLY

Next: End

FAULT CODE 271

HEAT EXCHANGER ASSEMBLY

Next: End

FAULT CODE 271

Next: End

INFORMATION USER DISPLAY

Z REDIRECT

Next: End

OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK FAN PULSES

HARNESS ASSEMBLY - HV & IGNITION

Next: End

OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK FAN DOES NOT RUN

HARNESS ASSEMBLY - HV & IGNITION

Next: End

OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK

HARNESS ASSEMBLY - HV & IGNITION

Next: End

OBSERVATION PUMP RUNS INSUFFICIENT FLOWNO DISPLAY

WATER SUPPLY (BELOW MINIMUM)

Next: End

OBSERVATION PUMP RUNS DHW TURBINENO DISPLAY

HARNESS - LOW VOLTAGE

Next: End

OBSERVATION FAN RUNS RETURN SENSORNO DISPLAY

HARNESS - LOW VOLTAGE

Next: End

OBSERVATION FAN RUNSNO DISPLAY

SENSOR 18MM (FLOW)

Next: End

OBSERVATION FAN RUNS DHW SENSORNO DISPLAY

SENSOR - TEMPERATURE (DHW)

Next: End

OPERATION CH REACHES TEMP RADS DO NOT HEAT

SYSTEM PRESSURE

Next: End

OBSERVATION FAN RUNS NOT FIRING FOR DHWNO DISPLAY

SENSOR - NTC MAX (OVERHEAT)

Next: End

OBSERVATION FAN RUNSNO DISPLAY

LIMITER - TEMPERATURE (FLUE STAT)

Next: End

OBSERVATION FAN RUNS NO RESPONSE TO DHWNO DISPLAY

SENSOR NTC - RIGHT ANGLED (DHW INLET SENSOR)

Next: End

OPERATION DHW TOO COOL BOILER STAYS LIT

VALVE - GAS-AIR (BEARING PLATE)

Next: End

OPERATION DHW TOO COOL STAYS LIT

SENSOR - TEMPERATURE (DHW)

Next: End

OPERATION DHW TOO COOL BOILER STAYS LIT

SENSOR NTC - RIGHT ANGLED (RETURN SENSOR)

Next: End

OPERATION DHW TOO COOL RADS COOL

PLATE HEAT EXCHANGER

Next: End

FAULT CODE 258 356 EH

CONTROL BOX - SKIN MID

Next: End

OPERATION PREHEAT

Next: End

OPERATION PREHEAT NO RESPONDING TO DEMAND

CONTROL BOX - SKIN MID

Next: End

COMBUSTION TEST

PIPE - SUCTION (AIR INTAKE)

Next: End

COMBUSTION TEST

SYPHON - LCS

Next: End

FAULT CODE 229 EA IGNITES OK

PIPE - SUCTION (AIR INTAKE)

Next: End

FAULT CODE 229 EA IGNITES OK

SYPHON - LCS

Next: End

E210 FAULT CODE

SWITCH - AIR PRESSURE

Next: End

FAULT CODE 210 E9

FLUE

Next: End

FAULT CODE 210 E9

SWITCH - AIR PRESSURE

Next: End

NO DISPLAY

SWITCH - AIR PRESSURE

Next: End

OPERATION CH UP TO TEMP RADS DO NOT HEAT

HARNESS - LOW VOLTAGE

Next: End

FAN DOES NOT RUN 1

SWITCH - AIR PRESSURE

Next: End

OPERATION CH INSUFFICIENT HEAT TEMP SETTINGS

BOILER SETUP PARAMETERS

Next: End

OPERATION CH INSUFFICIENT HEAT

INLET PRESSURE

Next: End

OPERATION DHW INSUFFICIENT HEAT

HARNESS - LOW VOLTAGE

Next: End

OPERATION CH INSUFFICIENT HEAT

VALVE - GAS-AIR (BEARING PLATE)

Next: End

OPERATION CH INSUFFICIENT HEAT OUTPUT SETTINGS

BOILER SETUP PARAMETERS

Next: End

OPERATION CH SHUTS DOWN BEFORE TEMP

SYSTEM PRESSURE

Next: End

COMBUSTION TEST MAX AND MINIMUM

HEAT EXCHANGER ASSEMBLY

Next: End

CH BOILER SHUTS DOWN B4 REACH TEMP

SWITCH - AIR PRESSURE

Next: End

FAULT CODE 1001 - 1008 - BATTERIES ETC

COMFORT CONTROLS

Next: End

FAULT CODE 1001 - 1008

CONTROL BOX - SKIN MID

Next: End

EXTERNAL MIXING DILUTING DHW TEMPERATURE

EXTERNAL MIXING

Next: End

BLANK FOR LITE DIAGNOSTIC

Z REDIRECT

Next: End

BLANK FOR QADAI

Z REDIRECT

Next: End

QADAI

SENSOR - TEMPERATURE (DHW)

Next: End

QADAI

SENSOR NTC - RIGHT ANGLED (DHW INLET SENSOR)

Next: End

QADAI

SENSOR 18MM (FLOW)

Next: End

QADAI

SENSOR NTC - RIGHT ANGLED (RETURN SENSOR)

Next: End

QADAI

SENSOR - NTC MAX (OVERHEAT)

Next: End

QADAI

TRANSFORMER - IGNITION

Next: End

SPARK GEN VOLTAGE QADAI

CONTROL BOX - SKIN MID

Next: End

QADAI PUMP RESISTANCE

PUMP

Next: End

PUMP VOLTAGE QADAI

CONTROL BOX - SKIN MID

Next: End

QADAI

FAN

Next: End

FAN VOLTAGE QADAI

CONTROL BOX - SKIN MID

Next: End

QADAI

MOTOR - DIVERTER VALVE

Next: End

DIVERTER VALVE VOLTAGE QADAI

CONTROL BOX - SKIN MID

Next: End

RESISTANCE INCORRECT QADAI

GAS VALVE

Next: End

GAS VALVE VOLTAGE QADAI

CONTROL BOX - SKIN MID

Next: End

QADAI

SENSOR - FLOW (TURBINE)

Next: End

BURNER IGNITES BUT BAFFLES OR NOISY FAULT CODE

MIXING UNIT ASSEMBLY

Next: End

IGNITES BUT DOES NOT ESTABLISH FAULT CODE

MIXING UNIT ASSEMBLY

Next: End

SPARKING HEARD BUT NO IGNITION FAULT CODE

MIXING UNIT ASSEMBLY

Next: End

FAULT CODE 229 EA 374 8C

MIXING UNIT ASSEMBLY

Next: End

DHW COOL RADS COOL

MIXING UNIT ASSEMBLY

Next: End

BOILER REMAINS LIT RADS ONLY GET WARM

MIXING UNIT ASSEMBLY

Next: End

BURNER IGNITES BUT BAFFLES OR IS NOISY

MIXING UNIT ASSEMBLY

Next: End

SPARKING HEARD NO IGNITION

MIXING UNIT ASSEMBLY

Next: End

OBSERVATION BURNER IGNITION DOES NOT IGNITE

VALVE - GAS-AIR (BEARING PLATE)

Next: End

OBSERVATION BURNER IGNITION

BURNER

Next: End

BURNER IGNITES BUT DOES NOT ESTABLISH

MIXING UNIT ASSEMBLY

Next: End

OPERATION DHW DHW COOL RADS HOT

CONTROL BOX - SKIN MID

Next: End

OPERATION DHW DHW COOL RADS HOT

HARNESS - LOW VOLTAGE

Next: End

OPERATION CH SHUTS DOWN BEFORE TEMP

BOILER SETUP PARAMETERS

Next: End

OPERATION DHW TOO HOT

SENSOR - TEMPERATURE (DHW)

Next: End

OPERATION DHW TOO COOL BOILER STAYS LIT

INLET PRESSURE

Next: End

INFORMATION CASE REMOVAL

Z REDIRECT

Next: End

FAULT CODES

Z REDIRECT

Next: End

OBSERVATION FAN RUNS DHW SENSOR

SENSOR - TEMPERATURE (DHW)

Next: End

OBSERVATION FAN RUNS NOT FIRING FOR DHW

SENSOR - NTC MAX (OVERHEAT)

Next: End

OBSERVATION FAN RUNS

LIMITER - TEMPERATURE (FLUE STAT)

Next: End

TYPE OF DIAGNOSTIC PROCEDURE

Z REDIRECT

Next: End

OBSERVATION DISPLAY ILLUMINATES

FUSE (FUSED SPUR)

Next: End

OBSERVATION DISPLAY ILLUMINATES

FUSE INTERNAL 5A

Next: End

OBSERVATION DISPLAY ILLUMINATES ALL OFF

CONTROL BOX - SKIN MID

Next: End

OBSERVATION DISPLAY ILLUMINATES BLANK DISPLAY

HARNESS - LOW VOLTAGE

Next: End

OBSERVATION PUMP RUNS NO POWER TO DHW TURBINE

CONTROL BOX - SKIN MID

Next: End

OBSERVATION PUMP RUNS DHW TURBINE

HARNESS - LOW VOLTAGE

Next: End

OBSERVATION FAN RUNS RETURN SENSOR

HARNESS - LOW VOLTAGE

Next: End

OBSERVATION PUMP RUNS DHW ISOLATION

ISOLATION VALVES

Next: End

OPERATION CH SHUTS DOWN BEFORE TEMP

SENSOR 18MM (FLOW)

Next: End

OPERATION CH SHUTS DOWN BEFORE TEMP

SENSOR - NTC MAX (OVERHEAT)

Next: End

OPERATION CH SHUTS DOWN BEFORE TEMP

SENSOR NTC - RIGHT ANGLED (RETURN SENSOR)

Next: End

OPERATION DHW DHW COOL RADS COLD

SYSTEM PRESSURE

Next: End

OBSERVATION PUMP OVERRUN

BOILER SETUP PARAMETERS

Next: End

FAULT CODE H11

SENSOR - TEMPERATURE (DHW)

Next: End

FAULT CODE 210 E9

LIMITER - TEMPERATURE (FLUE STAT)

Next: End

FAULT CODE 221 E9

SENSOR - NTC MAX (OVERHEAT)

Next: End

FAULT CODE 221 E9

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 233 9U

CODE PLUG

Next: End

OBSERVATION BOILER SELF CHECK NO VOLTAGE TO PUMP

CONTROL BOX - SKIN MID

Next: End

OBSERVATION BOILER SELF CHECK

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FAULT CODE 233 9U

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 231 FD

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 223 E2

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 240 241 286 D1 285 D9

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 240 241 286 D1 285 D9

SENSOR NTC - RIGHT ANGLED (RETURN SENSOR)

Next: End

FAULT CODE 264 C1

FAN

Next: End

FAULT CODE 228 F7

Z REDIRECT

Next: End

FAULT CODE H13

Z REDIRECT

Next: End

FAULT CODE 327

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 306 FA

CONTROL BOX - SKIN MID

Next: End

FAULT 228 F7

ELECTRODE

Next: End

FAULT CODE 323 A8

Next: End

FAULT CODE 278 F0

Z REDIRECT

Next: End

FAULT CODE 278 F0

SENSOR NTC - RIGHT ANGLED (RETURN SENSOR)

Next: End

FAULT CODE 278 F0 SAFETY SENSOR

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 278 F0 FLOW SENSOR

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 278 F0 DHW SENSOR

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 375 376 E4 SENSOR NOT FITTED

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 375 376 F4

Z REDIRECT

Next: End

FAULT CODE 375 376 E4 SENSOR FITTED

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 375 376 E4 SENSOR FITTED

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 380

EXTERNAL HEAT SOURCE

Next: End

FAULT CODE 380 SENSOR FITTED

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 219 220 277 E9

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 218 332 E5 222 E2 267 E9

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 260 STUCK IN FAULT CODE

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 237 273 C4 274

Z REDIRECT

Next: End

FAULT CODE 212

CONTROL BOX - SKIN MID

Next: End

OBSERVATION BURNER IGNITION IGNITES BUT CUTS OUT

CONTROL BOX - SKIN MID

Next: End

OPERATION DHW FLOW RATE NOT OBTAINABLE

PLATE HEAT EXCHANGER

Next: End

OPERATION DHW FLOW RATE NOT OBTAINABLE

SENSOR - FLOW (TURBINE)

Next: End

OPERATION DHW FLOW RATE NOT OBTAINABLE

BODY BRASS - SILENCER (NOZZLES)

Next: End

OPERATION DHW FLOW RATE NOT OBTAINABLE

ADAPTOR - FLOW - LIMITER

Next: End

FAULT CODE 800 CC

Z REDIRECT

Next: End

FAULT CODE 800 CC

Next: End

COMBUSTION TEST DROPS ON MINIMUM

GAS VALVE

Next: End

FAULT CODE 278 F0

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 278 F0 DHW INLET SENSOR

HARNESS - LOW VOLTAGE

Next: End

OPERATION DHW DHW COOL RADS COLD LOW FAN SPEED

CONTROL BOX - SKIN MID

Next: End

OBSERVATION BURNER IGNITION NO IGNITION

INLET PRESSURE

Next: End

OBSERVATION BURNER IGNITION NO POWER TO GAS VALVE

CONTROL BOX - SKIN MID

Next: End

OBSERVATION BURNER IGNITION

CONTROL BOX - SKIN MID AND HARNESS ASSEMBLY HV

Next: End

OBSERVATION BURNER IGNITION NO IGNITION

TRANSFORMER - IGNITION

Next: End

OBSERVATION BURNER IGNITION TO GAS VALVE NO SPARKING

HARNESS ASSEMBLY - HV & IGNITION

Next: End

OPERATION DHW TOO HOT

CONTROL BOX - SKIN MID

Next: End

OBSERVATION BURNER IGNITION NO SPARKING

TRANSFORMER - IGNITION

Next: End

OBSERVATION BURNER IGNITION RECTIFICATION SHORTING

HARNESS - LOW VOLTAGE

Next: End

OBSERVATION BOILER SELF CHECK FROST PROTECTION

CONTROL BOX - SKIN MID

Next: End

OBSERVATION BURNER IGNITION BURNER BAFFLES

NOZZLE (INJECTOR)

Next: End

OPERATION CH SHUTS DOWN BEFORE TEMP STUCK LOW TEMP

CONTROL BOX - SKIN MID

Next: End

FURTHER INVESTIGATION FUSE PCB PUMP

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FURTHER INVESTIGATION FUSE PCB GAS VALVE

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FURTHER INVESTIGATION FUSE PCB FAN

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FURTHER INVESTIGATION

FUSE INTERNAL 5A FURTHER INVESTIGATION

Next: End

FURTHER INVESTIGATION FUSE PCB SPARK GENERATOR

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FURTHER INVESTIGATION MAINS FUSE PUMP

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FURTHER INVESTIGATION MAINS FUSE GAS VALVE

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FURTHER INVESTIGATION MAINS FUSE FAN

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FURTHER INVESTIGATION

FUSE (FUSED SPUR) FURTHER INVESTIGATION

Next: End

FURTHER INVESTIGATION MAINS FUSE SPARK GENERATOR

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FAULT CODE 229 EA BURNER BAFFLES

NOZZLE (INJECTOR)

Next: End

FAULT CODE 229 EA BAFFLES

GAS VALVE

Next: End

FAULT CODE 229 EA RECTIFICATION SHORTING

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 229 EA NOT ESTABLISHING LOW VOLTAGE

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 229 EA NO IGNITION

INLET PRESSURE

Next: End

FAULT CODE 229 EA NO IGNITION NO DROP

NOZZLE (INJECTOR)

Next: End

FAULT CODE 229 EA NO POWER TO GAS VALVE

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 229 EA

CONTROL BOX - SKIN MID AND HARNESS ASSEMBLY HV

Next: End

FAULT CODE 229 EA SPARKING NO IGNITION

NOZZLE (INJECTOR)

Next: End

FAULT CODE 229 EA NO IGNITION

TRANSFORMER - IGNITION

Next: End

FAULT CODE 299 EA IGNITES OK

FLUEWAYS

Next: End

FAULT CODE 229 EA

NO FAULT FOUND

Next: End

FAULT CODE 234 EA

HARNESS ASSEMBLY - HV & IGNITION

Next: End

FAULT CODE 234 EA

CONTROL BOX - SKIN MID

Next: End

OBSERVATION FAN RUNS DHW INLET SENSOR

HARNESS - LOW VOLTAGE

Next: End

OBSERVATION FAN RUNS

EXTERNAL HEAT SOURCE

Next: End

FAULT CODE 238 F0

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 238 F0 WILL NOT RESET

HARNESS ASSEMBLY - HV & IGNITION

Next: End

OBSERVATION CH DEMAND

INTERNAL TIMER

Next: End

FAULT CODE 271 STUCK

PUMP

Next: End

FAULT CODE 218 332 E5 222 E2 267 E9

PLATE HEAT EXCHANGER

Next: End

FAULT CODE 219 220 277 E9

PLATE HEAT EXCHANGER

Next: End

FAULT CODE 219 220 277 E9 NOT SHUTTING DOWN

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 373 8C

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 373 8C

PLATE HEAT EXCHANGER

Next: End

FAULT CODE 271

PLATE HEAT EXCHANGER

Next: End

FAULT CODE 271

CONTROL BOX - SKIN MID

Next: End

OPERATION CH

EXPANSION VESSEL

Next: End

OBSERVATION DISPLAY ILLUMINATES SELF CHECK FAN RUNS CONSTANT SPEED

HARNESS ASSEMBLY - HV & IGNITION

Next: End

OBSERVATION PUMP RUNS INSUFFICIENT FLOW RATENO DISPLAY

SENSOR - FLOW (TURBINE)

Next: End

OBSERVATION PUMP RUNSNO DISPLAY

FILTER - DCW

Next: End

OBSERVATION PUMP RUNSNO DISPLAY

REGULATOR

Next: End

OBSERVATION PUMP RUNSNO DISPLAY

BODY BRASS - SILENCER (NOZZLES)

Next: End

OBSERVATION PUMP RUNSNO DISPLAY

ADAPTOR - FLOW - LIMITER

Next: End

OBSERVATION PUMP RUNS IGNORING DEMANDNO DISPLAY

CONTROL BOX - SKIN MID

Next: End

OBSERVATION PUMP RUNS TURBINE FAULTYNO DISPLAY

SENSOR - FLOW (TURBINE)

Next: End

NO DISPLAY

CONTROL BOX - SKIN MID (NO DISPLAY)

Next: End

OBSERVATION FAN RUNSNO DISPLAY

SENSOR NTC - RIGHT ANGLED (RETURN SENSOR)

Next: End

OBSERVATION FAN RUNSNO DISPLAY

EXTERNAL HEAT SOURCE

Next: End

OBSERVATION FAN RUNS DHW INLET SENSORNO DISPLAY

HARNESS - LOW VOLTAGE

Next: End

OPERATION DHW TOO COOL BOILER STAYS LIT

NOZZLE (INJECTOR)

Next: End

FAULT CODE 258 356 EH

Z REDIRECT

Next: End

OBSERVATION PUMP OVERRUN DHW

CONTROL BOX - SKIN MID

Next: End

OPERATION PREHEAT

INTERNAL TIMER

Next: End

OPERATION PREHEAT STUCK IN ECO

CONTROL BOX - SKIN MID

Next: End

OPERATION PREHEAT NOT FIRING WITH PREHEAT DISPLAYED

CONTROL BOX - SKIN MID

Next: End

OPERATION CH REACHES TEMP RADS DO NOT HEAT

DIVERTER VALVE ASSEMBLY

Next: End

FAULT CODE 210 E9

HARNESS - LOW VOLTAGE

Next: End

OPERATION CH UP TO TEMP RADS DO NOT HEAT

MOTOR - DIVERTER VALVE

Next: End

FAULT CODE 210 E9

OVERHEAT - FLUE

Next: End

FAULT CODE 210 E9

FLUEWAYS

Next: End

FAULT 210 E9

LIMITER - TEMPERATURE (FLUE STAT)

Next: End

OBSERVATION FAN RUNS FLUE SENSORNO DISPLAY

HARNESS - LOW VOLTAGE

Next: End

OBSERVATION FAN RUNS FLUE SENSOR

HARNESS - LOW VOLTAGE

Next: End

OPERATION DHW INSUFFICIENT HEAT

DIVERTER VALVE ASSEMBLY

Next: End

OPERATION DHW INSUFFICIENT HEAT

MOTOR - DIVERTER VALVE

Next: End

OPERATION CH INSUFFICIENT HEAT

FLUEWAYS

Next: End

OPERATION CH INSUFFICIENT HEAT

CONTROL BOX - SKIN MID

Next: End

OPERATION CH INSUFFICIENT HEAT

NOZZLE (INJECTOR)

Next: End

OPERATION CH INSUFFICIENT HEAT

HOSE - GAS

Next: End

RETEST BOILER CH RADS COOL

Z REDIRECT

Next: End

COMBUSTION TEST

NOZZLE (INJECTOR)

Next: End

COMBUSTION TEST

HOSE - GAS

Next: End

COMBUSTION TEST FAILED AIR INTEGRITY OK

SEAL - CONDENSATE COLLECTOR

Next: End

COMBUSTION TEST FAILS COMBUSTION

GAS VALVE

Next: End

FAULT CODE 229 EA IGNITES OK

NOZZLE (INJECTOR)

Next: End

FAULT CODE 229 EA IGNITES OK

HOSE - GAS

Next: End

FAULT CODE 229 EA COMBUSTION TEST FAILED AIR INTEGRITY OK

SEAL - CONDENSATE COLLECTOR

Next: End

OPERATION CH SHUTS DOWN BEFORE TEMP

LIMITER - TEMPERATURE (FLUE STAT)

Next: End

FAULT CODE 1001 - 1008 STUCK FAULTY

COMFORT CONTROLS

Next: End

OPERATION DHW TOO COOL BOILER STAYS LIT

CONTROL BOX - SKIN MID

Next: End

SENSOR DHW

RESULT AS EXPECTED

Next: End

SENSOR DHW INLET

RESULT AS EXPECTED

Next: End

SENSOR FLOW

RESULT AS EXPECTED

Next: End

SENSOR RETURN

RESULT AS EXPECTED

Next: End

SENSOR SAFETY

RESULT AS EXPECTED

Next: End

SPARK GEN RESISTANCE

RESULT AS EXPECTED

Next: End

SPARK GEN VOLTAGE

RESULT AS EXPECTED

Next: End

PUMP RESISTANCE

RESULT AS EXPECTED

Next: End

PUMP VOLTAGE

RESULT AS EXPECTED

Next: End

FAN RESISTANCE

RESULT AS EXPECTED

Next: End

FAN VOLTAGE

RESULT AS EXPECTED

Next: End

DIVERTER VALVE RESISTANCE

RESULT AS EXPECTED

Next: End

DIVERTER VALVE VOLTAGE

RESULT AS EXPECTED

Next: End

GAS VALVE RESISTANCE

RESULT AS EXPECTED

Next: End

GAS VALVE VOLTAGE

RESULT AS EXPECTED

Next: End

FLOW TURBINE VOLTAGE

RESULT AS EXPECTED

Next: End

OPERATION DHW DHW COOL RADS HOT

DIVERTER VALVE ASSEMBLY

Next: End

OPERATION DHW DHW COOL RADS HOT

MOTOR - DIVERTER VALVE

Next: End

OBSERVATION DISPLAY ILLUMINATES BLANK DISPLAY

SENSOR - FLOW (TURBINE)

Next: End

OBSERVATION PUMP RUNS INSUFFICIENT FLOW RATE

PLATE HEAT EXCHANGER

Next: End

OBSERVATION PUMP RUNS INSUFFICIENT FLOW RATE

SENSOR - FLOW (TURBINE)

Next: End

OBSERVATION PUMP RUNS

FILTER - DCW

Next: End

OBSERVATION PUMP RUNS

REGULATOR

Next: End

OBSERVATION PUMP RUNS

BODY BRASS - SILENCER (NOZZLES)

Next: End

OBSERVATION PUMP RUNS

ADAPTOR - FLOW - LIMITER

Next: End

OBSERVATION PUMP RUNS DOES NOT RECOGNISING DEMAND

CONTROL BOX - SKIN MID

Next: End

OBSERVATION PUMP RUNS IGNORING DEMAND

CONTROL BOX - SKIN MID

Next: End

OBSERVATION PUMP RUNS TURBINE FAULTY

SENSOR - FLOW (TURBINE)

Next: End

OBSERVATION FAN RUNS

SENSOR NTC - RIGHT ANGLED (RETURN SENSOR)

Next: End

OBSERVATION PUMP OVERRUN CH

CONTROL BOX - SKIN MID

Next: End

OBSERVATION PUMP OVERRUN DOES NOT OVERRUN

CONTROL BOX - SKIN MID

Next: End

FAULT CODE H11

CONTROL BOX - SKIN MID

Next: End

FAULT CODE H11

HARNESS - LOW VOLTAGE

Next: End

FAULT CODE 210 E9

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 221 E9

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 231 FD

Z REDIRECT

Next: End

FAULT CODE 233 9U

CONTROL BOX - SKIN MID

Next: End

FAULT CODE 223 E2

CONTROL BOX - SKIN MID

Next: End

FAULT CODE D4 (STATUS 271) DISPLAYED SHORTLY AFTER IGNITION

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION

Next: p1482

ALTERNATIVE TO VOLTAGE SPARK GENERATOR AT PCB

CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE

Next: p1495

ALTERNATIVE TO OBSERVATION FAULT CODE AT SHUTDOWN

CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE

Next: p1498

ALTERNATIVE TO TEMPERATURE DIFFERENTIAL SAFETY AND FLOW

CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE

Next: p1510

ALTERNATIVE TO OBSERVATION RECTIFICATION CURRENT

CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE

Next: p1516

ALTERNATIVE TO OBSERVATION SPARK GENERATOR OUTPUT

CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE

Next: p1552

ALTERNATIVE TO OPERATION PREHEAT

CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE

Next: p1574

ALTERNATIVE TO TEMPERATURE DIFFERENTIAL SAFETY AND FLOW DHW

CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE

Next: p1619

FLOW SENSOR BLOCKED AND/OR POOR CONDITION

CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS

Next: !p1677

FILTER BLOCKED AND/OR POOR CONDITION

CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS

Next: !p1679

FLOW REGULATOR BLOCKED AND/OR POOR CONDITION

CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS

Next: !p1681

NOZZLES BLOCKED AND/OR POOR CONDITION

CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS

Next: !p1683

ADAPTOR BLOCKED AND/OR POOR CONDITION

CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS

Next: !p1685

ALTERNATIVE TO VOLTAGE DIVERTER VALVE AT PCB

CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE

Next: p1704

ALTERNATIVE TO OBSERVATION DIVERTER MOVEMENT IN OP CH RADS DO NOT HEAT

CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE

Next: p1840

COMBUSTION TEST FAILED

CHARACTERISTIC TEST FROM COMBUSTION TEST MAX AND MINIMUM

Next: p3175

BOILER DROPS OUT ON MINIMUM RATE

CHARACTERISTIC TEST FROM COMBUSTION TEST MAX AND MINIMUM

Next: p1849

ALTERNATIVE TO OBSERVATION DIVERTER MOVEMENT

CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE

Next: p1867

ALTERNATIVE TO OBSERVATION DIVERTER MOVEMENT IN OP CH INSUFF HEAT

CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE

Next: p1871

SPARKING HEARD BUT NO IGNITION

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION

Next: p2063

NO PRESSURE DROP OBSERVED

CHARACTERISTIC TEST FROM PRESSURE GAS INLET AND DROP

Next: p2079

PRESSURE DROPS BELOW 16 5MB (28MB FOR LPG)

CHARACTERISTIC TEST FROM PRESSURE GAS INLET AND DROP

Next: !p2081

INJECTOR BLOCKED OR RESTRICTED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p2084

GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p2086

INJECTOR BLOCKED OR RESTRICTED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p2100

GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p2102

NO SPARKING HEARD

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION

Next: p2120

APPROX 90V AC MEASURED

CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT

Next: p2186

VOLTAGE LESS THAN 30V AC MEASURED

CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT

Next: p2188

BURNER IGNITES SMOOTHLY BUT DOES NOT ESTABLISH (SPARKING CONTINUES)

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION

Next: p2172

BOILER ATTEMPTS TO FIRE AFTER SELF CHECK

CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK

Next: p2294

PUMP RUNS CONTINUOUSLY AFTER SELF CHECK

CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK

Next: p2308

BURNER IGNITES BUT BAFFLES OUT OR IS NOISY

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION

Next: p2316

INJECTOR BLOCKED OR RESTRICTED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p2332

GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p2334

SPARKING HEARD BUT NO IGNITION OR IGNITION INTERMITTENT

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION FAULT CODE 229

Next: p2533

BURNER IGNITES SMOOTHLY BUT DOES NOT ESTABLISH OR ESTABLISHES INTERMITTENTLY

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION FAULT CODE 229

Next: p2535

BURNER IGNITES BUT BAFFLES OUT OR IS NOISY

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION

Next: p2537

INJECTOR BLOCKED OR RESTRICTED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p2553

GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p2555

APPROX 90V AC MEASURED

CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT

Next: p2573

VOLTAGE LESS THAN 30V AC MEASURED

CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT

Next: p2575

NO PRESSURE DROP OBSERVED

CHARACTERISTIC TEST FROM PRESSURE GAS INLET AND DROP

Next: p2601

PRESSURE DROPS BELOW 16 5MB (28MB FOR LPG)

CHARACTERISTIC TEST FROM PRESSURE GAS INLET AND DROP

Next: !p2603

INJECTOR BLOCKED OR RESTRICTED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p2606

GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p2608

INJECTOR BLOCKED OR RESTRICTED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p2622

GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p2624

COMBUSTION TEST FAILED

CHARACTERISTIC TEST FROM COMBUSTION TEST MAX AND MINIMUM

Next: p3206

BOILER DROPS OUT ON MINIMUM RATE

CHARACTERISTIC TEST FROM COMBUSTION TEST MAX AND MINIMUM

Next: p2644

ALTERNATIVE TO TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH

CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE

Next: p2658

FLOW RATE NOT OBTAINABLE

CHARACTERISTIC TEST FROM OPERATION DHW

Next: p1671

BOILER CUTS OUT OR HOT WATER RUNS HOT COLD

CHARACTERISTIC TEST FROM OPERATION DHW

Next: p740

PUMP DOES NOT RUN

CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK

Next: p3012

FAN DOES NOT RUN

CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK NO DISPLAY

Next: p3014

FAN PULSES 3 TIMES AT INCREASING SPEEDS THEN RUNS FOR 2 MINUTES

CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK NO DISPLAY

Next: p3016

FAN RUNS AT A CONSTANT SPEED FOR 2 MINUTES

CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK NO DISPLAY

Next: p3018

BOILER ATTEMPTS TO FIRE AFTER SELF CHECK

CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK

Next: p3020

PUMP RUNS CONTINUOUSLY AFTER SELF CHECK

CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK

Next: p3022

EXCESSIVE SYSTEM PRESSURE RISE

CHARACTERISTIC TEST FROM OPERATION CH

Next: !p305

DHW TOO COOL, RADIATORS HOT

CHARACTERISTIC TEST FROM OPERATION DHW

Next: p307

BOILER REACHES TEMPERATURE, RADIATORS DO NOT HEAT OR ONLY GET WARM

CHARACTERISTIC TEST FROM OPERATION CH

Next: p309

FLOW SENSOR BLOCKED AND/OR POOR CONDITION

CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS

Next: !p3084

FILTER BLOCKED AND/OR POOR CONDITION

CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS

Next: !p3086

FLOW REGULATOR BLOCKED AND/OR POOR CONDITION

CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS

Next: !p3088

NOZZLES BLOCKED AND/OR POOR CONDITION

CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS

Next: !p3090

ADAPTOR BLOCKED AND/OR POOR CONDITION

CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS

Next: !p3092

INJECTOR BLOCKED OR RESTRICTED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p3139

GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p3141

PUMP DOES NOT OVERRUN ON DHW

CHARACTERISTIC TEST FROM OBSERVATION PUMP OVERRUN

Next: !p3159

DIVERTER DOES NOT MOVE ON EITHER TEST

CHARACTERISTIC TEST FROM OBSERVATION DIVERTER MOTOR MOVEMENT

Next: p317

DISPLAY CHANGES TO ECO MODE WITH CLOCK SYMBOL

CHARACTERISTIC TEST FROM OPERATION PREHEAT

Next: p3164

APPLIANCE WILL NOT LEAVE ECO MODE

CHARACTERISTIC TEST FROM OPERATION PREHEAT

Next: !p3172

DISPLAY SHOWS PREHEAT BUT DOES NOT FIRE

CHARACTERISTIC TEST FROM OPERATION PREHEAT

Next: !p3174

DIVERTER ONLY MOVES WHEN REMOVED FROM HOUSING

CHARACTERISTIC TEST FROM OBSERVATION DIVERTER MOTOR MOVEMENT

Next: !p319

FLUE TEMPERATURE REACHES APPROX 95°C OR HIGHER

CHARACTERISTIC TEST FROM TEMPERATURE EXHAUST GAS (FAULT CODE)

Next: !p3242

RETURNS TO FAULT CODE, FLUE TEMPERATURE BELOW 95°C

CHARACTERISTIC TEST FROM TEMPERATURE EXHAUST GAS (FAULT CODE)

Next: !p3244

BOILER SHUTS DOWN BEFORE REACHING TEMPERATURE

CHARACTERISTIC TEST FROM OPERATION CH

Next: p327

DIVERTER DOES NOT MOVE ON EITHER TEST

CHARACTERISTIC TEST FROM OBSERVATION DIVERTER MOTOR MOVEMENT

Next: p3261

DIVERTER ONLY MOVES WHEN REMOVED FROM HOUSING

CHARACTERISTIC TEST FROM OBSERVATION DIVERTER MOTOR MOVEMENT

Next: !p3263

INJECTOR BLOCKED OR RESTRICTED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p3279

GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p3281

INJECTOR BLOCKED OR RESTRICTED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p3291

GAS SUPPLY TUBE BLOCKED RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM TEMPERATURE EXHAUST GAS (FAULT CODE)

Next: !p3293

FLUEWAY SUMP SEAL DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS

Next: !p3302

UPPER CONDENSATE SEAL DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS

Next: !p3304

INNER FLUE SEAL DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS

Next: !p3306

INJECTOR BLOCKED OR RESTRICTED

CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE

Next: !p3319

GAS SUPPLY TUBE BLOCKED RESTRICTED OR DAMAGED

CHARACTERISTIC TEST FROM TEMPERATURE EXHAUST GAS (FAULT CODE)

Next: !p3321

FLUEWAY SUMP SEAL DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS

Next: !p3326

UPPER CONDENSATE SEAL DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS

Next: !p3328

INNER FLUE SEAL DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS

Next: !p3330

DHW TOO COOL, RADS COOL, BOILER STAYS LIT

CHARACTERISTIC TEST FROM OPERATION DHW

Next: p390

DHW TOO HOT

CHARACTERISTIC TEST FROM OPERATION DHW

Next: p380

PUMP DOES NOT RUN

CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK

Next: p951

DISPLAY SHOWS ZERO FLOW RATE

CHARACTERISTIC TEST FROM OBSERVATION DHW MIN FLOW RATE

Next: p596

DISPLAY SHOWS FLOW RATE LESS THAN 2 LITRES A MINTUE

CHARACTERISTIC TEST FROM OBSERVATION DHW MIN FLOW RATE

Next: p673

FLOW SENSOR BLOCKED AND/OR POOR CONDITION

CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS

Next: !p586

FILTER BLOCKED AND/OR POOR CONDITION

CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS

Next: !p588

FLOW REGULATOR BLOCKED AND/OR POOR CONDITION

CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS

Next: !p590

NOZZLES BLOCKED AND/OR POOR CONDITION

CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS

Next: !p592

ADAPTOR BLOCKED AND/OR POOR CONDITION

CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS

Next: !p594

BOILER REMAINS LIT BUT BOILER AND RADIATORS ONLY GET WARM

CHARACTERISTIC TEST FROM OPERATION CH

Next: p3252

PUMP OVERRUNS EXCESSIVELY

CHARACTERISTIC TEST FROM OBSERVATION PUMP OVERRUN

Next: p777

PUMP OVERRUNS FOR LESS THAN 3 MINUTES ON CH OR DOES NOT OVERRUN

CHARACTERISTIC TEST FROM OBSERVATION PUMP OVERRUN

Next: !p781

RESISTANCE SENSOR RETURN AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: !p1003, f1004

RESISTANCE HARNESS RETURN SENSOR

DISCONNECT PLUG FROM

Next: !p1005, !f1006

RESISTANCE HARNESS FAN

DISCONNECT FAN CONNECTOR FROM FAN

Next: !p1010, !f1009

INFORMATION SERVICE REMINDER

H13 IS THE CODE TO I

Next: !p1035, !f1036

INSPECTION RESET SWITCH

Next: !p1043, !f1055

INSPECTION FLUE

Next: p1047, !f1048

INSPECTION RECTIFICATION LEADS

{GAINPCBACS}
REMOVE BOILER CASING
DISCONNECT THE AIR INTAKE

Next: p1061, !f1058

OBSERVATION BOILER RESET FAULT 278 F0

ENSURE APPLIANCE IS COOL

Next: !p1269, f1270

RESISTANCE SENSOR FLOW AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p1271, f1274

RESISTANCE SENSOR FLOW

REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR

Next: !p1282, !f1283

RESISTANCE SENSOR SAFETY

DISCONNECT WIRES FROM SAFETY SENSOR

Next: !p1280, !f1281

RESISTANCE HARNESS RETURN SENSOR

DISCONNECT PLUG FROM

Next: !p1278, !f1279

RESISTANCE SENSOR DHW

DISCONNECT WIRES FROM DHW SENSOR

Next: !p1285, !f1286

RESISTANCE HARNESS DHW INLET SENSOR

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: !p1298, !f1289

OBSERVATION BOILER RESET 375 376 F4

ENSURE APPLIANCE IS COOL

Next: !p1304, f1287

RESISTANCE SENSOR DHW INLET

DISCONNECT PLUG FROM DHW INLET SENSOR

Next: !p1307, !f1308

RESISTANCE SENSOR DHW INLET

DISCONNECT PLUG FROM DHW INLET SENSOR

Next: !p1318, !f1319

RESISTANCE SENSOR SAFETY AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p1368, f1369

RESISTANCE SENSOR SAFETY

DISCONNECT WIRES FROM SAFETY SENSOR

Next: !p1370, !f1371

RESISTANCE SENSOR FLOW AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p1392, f1393

RESISTANCE SENSOR FLOW

REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR

Next: !p1394, !f1414

INSPECTION PRESSURE SYSTEM

Next: p2715, !f1418

INSPECTION PRESSURE SYSTEM

Next: p1435, !f1442

INSPECTION PRESSURE SYSTEM

Next: p2726, !f1448

INFORMATION APPLIANCE OVERHEAT

DUE TO THE DESIGN OF

Next: p1463, !f1464

OBSERVATION IS OUTDOOR TEMPERATURE SENSOR FITTED

GAIN ACCESS TO LOWER PCB PANEL

Next: p1711, !f1718

RESISTANCE SENSOR DHW INLET

DISCONNECT PLUG FROM DHW INLET SENSOR

Next: !p1864, !f1865

INSPECTION CONDENSATE PIPE

Next: p3485, !f2067

RESISTANCE GAS VALVE AND HARNESS

DISCONNECT CONNECTOR X4 FROM THE PCB

Next: !p2089, f2090

RESISTANCE GAS VALVE

DISCONNECT PLUG FROM GAS VALVE

Next: !p2091, !f2092

RESISTANCE IGNITION LEAD

DISCONNECT THE IGNIT

Next: !p2105, !f2106

RESISTANCE GAS VALVE

DISCONNECT PLUG FROM GAS VALVE

Next: !p2123, !f2124

VOLTAGE SPARK GENERATOR AT PCB

{GAINPCBACS}

Next: p2165, !f2166

INSPECTION FLUE

Next: p3496, !f2176

RESISTANCE RECTIFICATION ELECTRODE TO EARTH

DISCONNECT LEAD FROM RECTIFICATION ELECTRODE

Next: !p2191, !f2192

OBSERVATION DISCONNECT CH LINK

REMOVE THE LINK BETWEEN L AND LR FOR CH
ENSURE CENTRAL HEATING TURNED OFF

Next: !p2303, !f2304

INSPECTION FLUE

Next: p3457, !f2322

RESISTANCE MAINS IN FURTHER INVESTIGATION

GAIN ACCESS TO THE LOWER PANEL OF THE PCB

Next: p2389, !f2406

RESISTANCE PUMP FURTHER INVESTIGATION

DISCONNECT CONNECTOR FROM PUMP

Next: !p2392, !f2393

RESISTANCE GAS VALVE FURTHER INVESTIGATION

DISCONNECT PLUG FROM GAS VALVE

Next: !p2396, !f2397

RESISTANCE FAN FURTHER INVESTIGATION

DISCONNECT CONNECTOR FROM FAN

Next: !p2400, !f2401

RESISTANCE SPARK GENERATOR FURTHER INVESTIGATION

DISCONNECT CONNECTOR FROM SPARK GENERATOR

Next: !p2404, !f2405

RESISTANCE MAINS IN FURTHER INVESTIGATION

GAIN ACCESS TO THE LOWER PANEL OF THE PCB

Next: p2408, !f2425

RESISTANCE PUMP FURTHER INVESTIGATION

DISCONNECT CONNECTOR FROM PUMP

Next: !p2411, !f2412

RESISTANCE GAS VALVE FURTHER INVESTIGATION

DISCONNECT PLUG FROM GAS VALVE

Next: !p2415, !f2416

RESISTANCE FAN FURTHER INVESTIGATION

DISCONNECT CONNECTOR FROM FAN

Next: !p2419, !f2420

RESISTANCE SPARK GENERATOR FURTHER INVESTIGATION

DISCONNECT CONNECTOR FROM SPARK GENERATOR

Next: !p2423, !f2424

OBSERVATION BURNER IGNITION FAULT CODE 229

ENSURE APPLIANCE IS SET TO ECO MODE

Next: p2531, ?2532, ?2534, ?2536

INSPECTION FLUE

Next: p3415, !f2543

INSPECTION FLUE

Next: p3422, !f2563

RESISTANCE RECTIFICATION ELECTRODE TO EARTH

DISCONNECT LEAD FROM RECTIFICATION ELECTRODE

Next: !p2578, !f2579

INSPECTION CONDENSATE PIPE

Next: p2588, !f2589

RESISTANCE GAS VALVE AND HARNESS

DISCONNECT CONNECTOR X4 FROM THE PCB

Next: !p2611, f2612

RESISTANCE GAS VALVE

DISCONNECT PLUG FROM GAS VALVE

Next: !p2613, !f2614

RESISTANCE IGNITION LEAD

DISCONNECT THE IGNIT

Next: !p2627, !f2628

INSPECTION FLUE

Next: p3438, !f2634

RESISTANCE GAS VALVE

DISCONNECT PLUG FROM GAS VALVE

Next: !p2670, !f2671

INSPECTION HARNESS GAS VALVE

Next: !p2685, !f2686

RESISTANCE SENSOR DHW INLET AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: !p2693, f2694

RESISTANCE SENSOR DHW INLET

DISCONNECT PLUG FROM DHW INLET SENSOR

Next: !p2695, !f2696

VOLTAGE CH DEMAND INTO BOILER

GAIN ACCESS TO LOWER PCB PANEL

Next: p646, f271

VOLTAGE CH DEMAND OUT OF BOILER

Next: !p275, !f276

RESISTANCE GAS VALVE TO EARTH

DISCONNECT PLUG FROM GAS VALVE

Next: !p2713, !f2714

VOLTAGE PUMP AT PCB

{GAINPCBACS}

Next: p2722, !f2725

VOLTAGE PUMP AT PCB

{GAINPCBACS}

Next: p2744, !f2745

VOLTAGE PUMP AT PCB

{GAINPCBACS}

Next: p2765, !f2766

TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH

CH TEMPERATURE CONTROL TO MAX

Next: !p2840, !f2841

TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH

CH TEMPERATURE CONTROL TO MAX

Next: !p2854, !f2855

TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH

CH TEMPERATURE CONTROL TO MAX

Next: !p2865, !f2866

TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH

CH TEMPERATURE CONTROL TO MAX

Next: !p2870, !f2871

OBSERVATION DISCONNECT CH LINK

REMOVE THE LINK BETWEEN L AND LR FOR CH
ENSURE CENTRAL HEATING TURNED OFF

Next: !p3037, !f3038

RESISTANCE SENSOR FLOW

REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR

Next: !p3160, !f3161

RESISTANCE SENSOR SAFETY

DISCONNECT WIRES FROM SAFETY SENSOR

Next: !p3047, !f3048

RESISTANCE GAS VALVE TO EARTH

DISCONNECT PLUG FROM GAS VALVE

Next: !p3053, !f3054

INSPECTION ISOLATION VALVE DHW

Next: p3077, !f3078

RESISTANCE SENSOR RETURN AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p3101, f3102

RESISTANCE HARNESS RETURN SENSOR

DISCONNECT PLUG FROM

Next: !p3103, !f3104

RESISTANCE SENSOR FLUE

DISCONNECT WIRES FROM FLUE SENSOR

Next: p3246, !f3114

RESISTANCE SENSOR DHW INLET AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: !p3119, f3120

RESISTANCE SENSOR DHW INLET

DISCONNECT PLUG FROM DHW INLET SENSOR

Next: !p3121, !f3122

INSPECTION FLUE

Next: p3443, !f3127

VOLTAGE MAINS POWER IN FAULT CODE

GAIN ACCESS TO THE LOWER PANEL OF THE PCB

Next: p3153, !f3145

INSPECTION FLUE

Next: p3450, !f3271

ADJUSTMENT CH OUTPUT SETTINGS

Next: !p3284, !f3283

INSPECTION FLUE

Next: p3332, !f3333

INFORMATION COMFORT CONTROLS

Next: p3340, !f3341

RESISTANCE SENSOR DHW

DISCONNECT WIRES FROM DHW SENSOR

Next: !p3353, !f3354

RESISTANCE SENSOR DHW INLET

DISCONNECT PLUG FROM DHW INLET SENSOR

Next: !p3357, !f3358

RESISTANCE SENSOR FLOW

REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR

Next: !p3361, !f3362

RESISTANCE SENSOR RETURN AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: !p3365, !f3366

RESISTANCE SENSOR SAFETY

DISCONNECT WIRES FROM SAFETY SENSOR

Next: !p3369, !f3370

RESISTANCE SPARK GENERATOR (QADAI)

REMOVE AIR INTAKE
DISCONNECT CONNECTOR FROM SPARK GENERATOR

Next: !p3373, !f3374

VOLTAGE SPARK GENERATOR AT PCB

{GAINPCBACS}

Next: !p3377, !f3378

RESISTANCE PUMP (QADAI)

DISCONNECT CONNECTOR FROM PUMP

Next: !p3381, !f3382

VOLTAGE PUMP AT PCB

{GAINPCBACS}

Next: !p3385, !f3386

RESISTANCE FAN (QADAI)

DISCONNECT CONNECTOR FROM FAN

Next: !p3389, !f3390

VOLTAGE FAN SELF CHECK

{GAINPCBACS}

Next: !p3393, !f3394

RESISTANCE DIVERTER VALVE AND HARNESS (QADAI)

{GAINPCBACS}
DISCONNECT CONNECTOR X7 FROM THE PCB

Next: !p3397, !f3398

VOLTAGE DIVERTER VALVE AT PCB

{GAINPCBACS}
DISCONNECT PLUG FROM DIVERTER VALVE AND MAKE SAFE

Next: !p3401, !f3402

RESISTANCE GAS VALVE

DISCONNECT PLUG FROM GAS VALVE

Next: !p3405, !f3406

VOLTAGE GAS VALVE AT PCB

{GAINPCBACS}

Next: !p3409, !f3410

VOLTAGE FLOW TURBINE INTO BOILER

{GAINPCBACS}

Next: !p3413, !f3414

VOLTAGE DIVERTER VALVE AT PCB

{GAINPCBACS}
DISCONNECT PLUG FROM DIVERTER VALVE AND MAKE SAFE

Next: p360, !f361

OBSERVATION DHW MIN FLOW RATE

Next: !p595, ?579, ?581

RESISTANCE SENSOR RETURN AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p2042, f603

RESISTANCE SENSOR FLUE

DISCONNECT WIRES FROM FLUE SENSOR

Next: p3249, !f522

OBSERVATION DOES APPLIANCE RUN SELF CHECK

REMOVE THE OUTER CASING

Next: p549, f550

VOLTAGE MAINS POWER IN

GAIN ACCESS TO THE LOWER PANEL OF THE PCB

Next: p551, f552

RESISTANCE FUSE (MAINS FUSE)

REMOVE THE FUSE FROM THE FUSED SPUR

Next: !p553, f554

FURTHER INVESTIGATION FUSE PCB

Next: !p559, !f560

RESISTANCE HARNESS RETURN SENSOR

DISCONNECT PLUG FROM

Next: !p606, !f607

RESISTANCE SENSOR DHW

DISCONNECT WIRES FROM DHW SENSOR

Next: !p882, !f883

RESISTANCE SENSOR FLUE - AIR PRESSURE SWITCH AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X7 FROM THE PCB

Next: !p888, f889

RESISTANCE SENSOR FLUE

DISCONNECT WIRES FROM FLUE SENSOR

Next: p3233, !f891

INSPECTION CODE PLUG

{GAINPCBACS}

Next: p943, !f944

RESISTANCE SENSOR FLOW AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: !p994, f997

RESISTANCE SENSOR FLOW

REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR

Next: !p1000, !f1001

INSPECTION CONDENSATE PIPE

Next: p1049, !f1050

PRESSURE TIGHTNESS TEST

Next: p1052, !f1051

PRESSURE STANDING RETURN

ATTACH U-GAUGE TO INLET PRESSURE TEST POINT

Next: !p1054, !f1053

OBSERVATION DISCONNECT RECTIFICATION LEADS

DISCONNECT THE RECTI

Next: p1063, !f1066

INSPECTION CONDENSATE PIPE

Next: !p1064, !f1065

DISCONNECT FW100 CONTROLS

DISCONNECT FW100 OR

Next: !p1164, !f1165

RESISTANCE SENSOR SAFETY AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p1272, f1275

RESISTANCE SENSOR RETURN AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p1273, f1276

RESISTANCE SENSOR DHW AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p2150, f1277

RESISTANCE SENSOR DHW INLET AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: !p1305, f1306

TEMPERATURE DHW INLET

ATTACH TEMPERATURE CLAMP TO DHW INLET PIPE

Next: !p1316, f1317

OBSERVATION BOILER RESET

ENSURE APPLIANCE IS COOL

Next: p1372, !f1373

INFORMATION APPLIANCE OVERHEAT

DUE TO THE DESIGN OF

Next: p1374, !f1375

INSPECTION PRESSURE SYSTEM

Next: p1376, !f1377

PUMP LIMPET TEST

Next: p1378, !f1379

RESISTANCE SENSOR FLOW AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p2851, !f1381

OBSERVATION BOILER RESET

ENSURE APPLIANCE IS COOL

Next: p1396, !f1397

INFORMATION APPLIANCE OVERHEAT

DUE TO THE DESIGN OF

Next: p1398, !f1399

INSPECTION PRESSURE SYSTEM

Next: p1400, !f1401

PUMP LIMPET TEST

Next: p1402, !f1403

RESISTANCE SENSOR SAFETY

DISCONNECT WIRES FROM SAFETY SENSOR

Next: p1404, !f1415

TEMPERATURE DIFFERENTIAL SAFETY AND FLOW DHW

DHW TEMPERATURE CONTROL TO MAX

Next: p2835, f2839

PUMP LIMPET TEST

Next: p1419, !f1420

RESISTANCE SENSOR FLOW

REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR

Next: !p1421, !f1422

PUMP LIMPET TEST

Next: p1436, !f1441

RESISTANCE SENSOR FLOW

REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR

Next: p1437, !f1438

RESISTANCE SENSOR SAFETY

DISCONNECT WIRES FROM SAFETY SENSOR

Next: !p1439, !f1440

PUMP LIMPET TEST

Next: p1445, !f1449

RESISTANCE SENSOR SAFETY

DISCONNECT WIRES FROM SAFETY SENSOR

Next: p1446, !f1450

RESISTANCE SENSOR FLOW

REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR

Next: p2867, !f1451

INSPECTION PRESSURE SYSTEM

Next: p2748, !f1466

PUMP LIMPET TEST

Next: p1467, !f1468

RESISTANCE SENSOR SAFETY

DISCONNECT WIRES FROM SAFETY SENSOR

Next: p1469, !f1470

RESISTANCE SENSOR FLOW

REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR

Next: p1471, !f1472

TEMPERATURE DIFFERENTIAL SAFETY AND FLOW DHW

DHW TEMPERATURE CONTROL TO MAX

Next: p2861, f2862

RESISTANCE SENSOR SAFETY

DISCONNECT WIRES FROM SAFETY SENSOR

Next: p1483, !f1486

RESISTANCE SENSOR FLOW

REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR

Next: !p1484, !f1485

VOLTAGE SPARK GENERATOR AT PCB (NO DISPLAY)

{GAINPCBACS}

Next: !p1497, !f1496

VOLTAGE RECTIFICATION CIRCUIT (NO DISPLAY)

{GAINPCBACS}

Next: p1559, !f1518

RESISTANCE RECTIFICATION LEAD (NO DISPLAY)

{GAINPCBACS}

Next: !p1563, !f1561

OPERATION PREHEAT (NO DISPLAY)

<

Next: !p1575, !f1576

INSPECTION ISOLATION VALVE DHW

Next: p1890, !f1673

INSPECTION FLOW COMPONENTS

HOT WATER CIRCUIT ISOLATED AND DRAINED

Next: !p1674, ?1676, ?1678, ?1680, ?1682, ?1684

RESISTANCE SENSOR DHW

DISCONNECT WIRES FROM DHW SENSOR

Next: p1932, !f1695

VOLTAGE DIVERTER VALVE AT PCB (DISTANT FUSE SPUR)

{GAINPCBACS}
DISC

Next: !p1715, !f1716

DISCONNECT OUTDOOR SENSOR

DISCONNECT THE PLUG FOR THE OUTDOOR TEMPERATURE SENSOR (BLUE CONNECTOR) AND MAKE SAFE

Next: !p1719, !f1720

OBSERVATION DIVERTER MOVEMENT (DISTANT FUSE SPUR) NO CH

DISCONNECT THE CONNECTOR TO THE GAS VALVE AND MAKE SAFE

Next: !p1841, !f1842

INSPECTION RECTIFICATION ELECTRODE

SLIDE THE SPARK GENE

Next: !p1850, !f1851

RESISTANCE SENSOR DHW INLET AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: !p1863, f1862

OBSERVATION DIVERTER MOVEMENT OFF ONLY (DISTANT FUSE SPUR)

DISCONNECT THE CONNE

Next: !p1889, !f1888

OBSERVATION DIVERTER MOVEMENT (DISTANT FUSE SPUR) POOR CH

DISCONNECT THE CONNECTOR TO THE GAS VALVE AND MAKE SAFE

Next: !p1872, !f1873

OBSERVATION FLOW RATE INTO BOILER

Next: p1672, !f1904

TEMPERATURE DHW INLET

ATTACH TEMPERATURE CLAMP TO DHW INLET PIPE

Next: !p2697, f2692

TEMPERATURE DIFFERENTIAL SAFETY AND FLOW DHW

DHW TEMPERATURE CONTROL TO MAX

Next: !p1933, !f1934

TEMPERATURE INTEGRAL BYPASS

ATTACH TEMPERATURE PROBE TO CH FLOW PIPE

Next: !p2040, !f2041

RESISTANCE SENSOR FLOW AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p509, !f2060

PRESSURE FAN LOCKOUT

1. ATTACH FGA

Next: p2064, f2065

PRESSURE GAS INLET AND DROP

ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT

Next: p2076, ?2078, ?2080

INSPECTION AIR INTAKE FAN

REMOVE THE FAN AIR INTAKE FROM THE FAN

Next: p2095, !f2096

INSPECTION GAS SUPPLY TUBE

UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE

Next: p2082, ?2083, ?2085

VOLTAGE GAS VALVE AT PCB

{GAINPCBACS}

Next: p2087, f2088

RESISTANCE HARNESS GAS VALVE

DISCONNECT THE PLUG FROM THE GAS VALVE

Next: !p2093, !f2094

INSPECTION GAS SUPPLY TUBE

UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE

Next: p2097, ?2099, ?2101

OBSERVATION SPARK GENERATOR OUTPUT

REMOVE THE AIR INTAK

Next: p2103, f2104

INSPECTION ELECTRODE ASSEMBLY

SLIDE THE SPARK GENE

Next: !p2107, !f2108

RESISTANCE GAS VALVE AND HARNESS

DISCONNECT CONNECTOR X4 FROM THE PCB

Next: p2157, f2122

OBSERVATION DISCONNECT SPARK ELECTRODE LEAD

REMOVE THE AIR INTAK

Next: p2169, f2164

RESISTANCE HARNESS PCB TO SPARK GENERATOR

DISCONNECT PLUG FROM THE SPARK GENERATOR

Next: !p2167, !f2168

RESISTANCE IGNITION LEAD (OPEN CIRCUIT CHECK)

DISCONNECT THE IGNIT

Next: !p2170, !f2199

PRESSURE FAN LOCKOUT

1. ATTACH FGA

Next: p2173, f2174

INSPECTION AIR INTAKE FAN

REMOVE THE FAN AIR INTAKE FROM THE FAN

Next: p2181, !f2182

INSPECTION FAN BEARING PLATE

Next: p2177, !f2178

INSPECTION BURNER ASSEMBLY

REMOVE THE FAN HOOD ASSEMBLY

Next: !p2179, !f2180

VOLTAGE RECTIFICATION CIRCUIT

{GAINPCBACS}
ATTACH A CROCODILE CLIP TO THE RECTIFICATION LEAD

Next: p2183, ?2185, ?2187

RESISTANCE RECTIFICATION LEAD

{GAINPCBACS}
DISC

Next: p2195, !f2196

RESISTANCE HARNESS RECTIFICATION GROUND

DISCONNECT X5 FROM THE PCB
DISCONNECT THE FLAME SENSE LEAD FROM THE SAFETY SENSOR

Next: !p2193, !f2194

RESISTANCE RECTIFICATION CIRCUIT TO EARTH

{GAINPCBACS}
DISCONNECT CONNECTOR X5 FROM THE PCB

Next: !p2189, f2190

INSPECTION RECTIFICATION ELECTRODE

SLIDE THE SPARK GENE

Next: !p2197, !f2198

TEMPERATURE FLOW (BOILER FIRING)

REMOVE AIR INTAKE FROM APPLIANCE

Next: p2295, !f2296

RESISTANCE SENSOR FLOW

REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR

Next: p2297, !f2298

OBSERVATION DISCONNECT FLOW TURBINE (DEMAND CHECK)

DISCONNECT FLOW TURBINE FROM ITS INLINE CONNECTOR AND MAKE SAFE
ENSURE CENTRAL HEATING TURNED OFF

Next: p2299, !f2300

VOLTAGE CH DEMAND INTO BOARD (NO DEMAND)

GAIN ACCESS TO LOWER PCB PANEL
ENSURE CENTRAL HEATING TURNED OFF

Next: !p2305, !f2306

TEMPERATURE FLOW (PUMP RUNNING)

REMOVE AIR INTAKE FROM APPLIANCE

Next: p2309, !f2310

RESISTANCE SENSOR FLOW

REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR

Next: p2311, !f2312

RESISTANCE FROST PROTECTION

GAIN ACCESS TO LOWER PCB PANEL

Next: !p2313, !f2314

INSPECTION CONDENSATE PIPE

Next: p2317, !f2318

PRESSURE FAN LOCKOUT

1. ATTACH FGA

Next: p2319, f2320

INSPECTION FLUE

Next: p2327, !f2328

INSPECTION FAN BEARING PLATE

Next: p2770, !f2324

INSPECTION GAS SUPPLY TUBE

UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE

Next: p2777, ?2331, ?2333

TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH

CH TEMPERATURE CONTROL TO MAX

Next: !p2340, !f2341

RESISTANCE PUMP AND HARNESS FURTHER INVESTIGATION

{GAINPCBACS}
DISCONNECT CONNECTOR X11 FROM THE PCB

Next: p2390, f2391

RESISTANCE GAS VALVE AND HARNESS FURTHER INVESTIGATION

DISCONNECT CONNECTOR X4 FROM THE PCB

Next: p2394, f2395

RESISTANCE FAN AND HARNESS FURTHER INVESTIGATION

DISCONNECT CONNECTOR X3 FROM THE PCB

Next: p2398, f2399

RESISTANCE SPARK GENERATOR AND HARNESS FURTHER INVESTIGATION

DISCONNECT CONNECTOR X3 AND FROM THE PCB

Next: !p2402, f2403

RESISTANCE PUMP AND HARNESS FURTHER INVESTIGATION

{GAINPCBACS}
DISCONNECT CONNECTOR X11 FROM THE PCB

Next: p2409, f2410

RESISTANCE GAS VALVE AND HARNESS FURTHER INVESTIGATION

DISCONNECT CONNECTOR X4 FROM THE PCB

Next: p2413, f2414

RESISTANCE FAN AND HARNESS FURTHER INVESTIGATION

DISCONNECT CONNECTOR X3 FROM THE PCB

Next: p2417, f2418

RESISTANCE SPARK GENERATOR AND HARNESS FURTHER INVESTIGATION

DISCONNECT CONNECTOR X3 AND FROM THE PCB

Next: !p2421, f2422

PRESSURE FAN MAX RATE

ATTACH FGA TO FAN PR

Next: p2631, f2632

PRESSURE FAN LOCKOUT

1. ATTACH FGA

Next: p2586, f2587

PRESSURE FAN LOCKOUT

1. ATTACH FGA

Next: p2560, f2561

INSPECTION CONDENSATE PIPE

Next: p2538, !f2539

PRESSURE FAN LOCKOUT

1. ATTACH FGA

Next: p2540, f2541

INSPECTION AIR INTAKE FAN

REMOVE THE FAN AIR INTAKE FROM THE FAN

Next: p2548, !f2549

INSPECTION FAN BEARING PLATE

Next: p2544, !f2545

INSPECTION GAS SUPPLY TUBE

UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE

Next: p2550, ?2552, ?2554

INSPECTION FLUE

Next: p2556, !f2557

INSPECTION HOUSING BURNER

REMOVE THE BURNER HOUSING FROM THE BOILER ASSEMBLY
REMOVE THE SILENCER FROM THE BURNER HOUSING

Next: !p2558, !f2559

INSPECTION AIR INTAKE FAN

REMOVE THE FAN AIR INTAKE FROM THE FAN

Next: p2568, !f2569

INSPECTION FAN BEARING PLATE

Next: p2564, !f2565

INSPECTION BURNER ASSEMBLY

REMOVE THE FAN HOOD ASSEMBLY

Next: !p2566, !f2567

VOLTAGE RECTIFICATION CIRCUIT

{GAINPCBACS}
ATTACH A CROCODILE CLIP TO THE RECTIFICATION LEAD

Next: p2570, ?2572, ?2574

RESISTANCE RECTIFICATION LEAD

{GAINPCBACS}
DISC

Next: p2582, !f2583

RESISTANCE HARNESS RECTIFICATION GROUND

DISCONNECT X5 FROM THE PCB
DISCONNECT THE FLAME SENSE LEAD FROM THE SAFETY SENSOR

Next: !p2580, !f2581

RESISTANCE RECTIFICATION CIRCUIT TO EARTH

{GAINPCBACS}
DISCONNECT CONNECTOR X5 FROM THE PCB

Next: !p2576, f2577

INSPECTION RECTIFICATION ELECTRODE

SLIDE THE SPARK GENE

Next: !p2584, !f2585

PRESSURE GAS INLET AND DROP

ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT

Next: p2598, ?2600, ?2602

INSPECTION FLUE

Next: p3429, !f2591

INSPECTION FAN BEARING PLATE

Next: p2592, !f2593

INSPECTION BURNER ASSEMBLY

REMOVE THE FAN HOOD ASSEMBLY

Next: p2594, !f2595

INSPECTION AIR INTAKE FAN

REMOVE THE FAN AIR INTAKE FROM THE FAN

Next: p2617, !f2618

INSPECTION GAS SUPPLY TUBE

UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE

Next: p2604, ?2605, ?2607

VOLTAGE GAS VALVE AT PCB

{GAINPCBACS}

Next: p2609, f2610

RESISTANCE HARNESS GAS VALVE

DISCONNECT THE PLUG FROM THE GAS VALVE

Next: !p2615, !f2616

INSPECTION GAS SUPPLY TUBE

UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE

Next: p2619, ?2621, ?2623

OBSERVATION SPARK GENERATOR OUTPUT

REMOVE THE AIR INTAK

Next: p2625, f2626

INSPECTION ELECTRODE ASSEMBLY

SLIDE THE SPARK GENE

Next: !p2629, !f2630

PRESSURE GAS INLET

ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT

Next: p2637, !f2638

INSPECTION FAN BEARING PLATE

Next: !p2635, !f2636

COMBUSTION TEST MAX AND MINIMUM

Next: !p2639, ?2641, ?2643

INSPECTION RECTIFICATION ELECTRODE

SLIDE THE SPARK GENE

Next: !p2645, !f2646

RESISTANCE GAS VALVE AND HARNESS

DISCONNECT CONNECTOR X4 FROM THE PCB

Next: !p2688, f2669

RESISTANCE GAS VALVE AND HARNESS TO EARTH

DISCONNECT CONNECTOR X4 FROM THE PCB

Next: !p2711, f2712

DISCONNECT INTERNAL CONTROLS CH

DISCONNECT THE INTEG

Next: !p273, !f274

RESISTANCE HARNESS PUMP

DISCONNECT THE PLUG FROM THE PUMP

Next: !p2723, !f2724

RESISTANCE HARNESS PUMP

DISCONNECT THE PLUG FROM THE PUMP

Next: !p2746, !f2747

OBSERVATION PUMP RUNS

ENSURE APPLIANCE IS SET TO ECO MODE
DHW TEMPERATURE CONTROL TO MAX

Next: p1465, f2764

RESISTANCE HARNESS PUMP

DISCONNECT THE PLUG FROM THE PUMP

Next: !p2767, !f2768

INSPECTION BURNER ASSEMBLY

REMOVE THE FAN HOOD ASSEMBLY

Next: p2323, !f2774

INSPECTION HOUSING BURNER

REMOVE THE BURNER HOUSING FROM THE BOILER ASSEMBLY
REMOVE THE SILENCER FROM THE BURNER HOUSING

Next: p2778, !f2779

INSPECTION BURNER ASSEMBLY

REMOVE THE FAN HOOD ASSEMBLY

Next: !p2780, !f2781

PUMP LIMPET TEST

Next: p3123, !f2834

TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH

CH TEMPERATURE CONTROL TO MAX

Next: !p2842, !f2843

TEMPERATURE DIFFERENTIAL SAFETY AND FLOW DHW

DHW TEMPERATURE CONTROL TO MAX

Next: p2852, f2853

TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH

CH TEMPERATURE CONTROL TO MAX

Next: !p2856, !f2857

TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH

CH TEMPERATURE CONTROL TO MAX

Next: !p2863, !f2864

TEMPERATURE DIFFERENTIAL SAFETY AND FLOW DHW

DHW TEMPERATURE CONTROL TO MAX

Next: p2868, f2869

TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH

CH TEMPERATURE CONTROL TO MAX

Next: !p2872, !f2873

OBSERVATION BOILER SELF CHECK NO DISPLAY

ENSURE CENTRAL HEATING TURNED OFF

Next: p3010, ?3011, ?3013, ?3015, ?3017, ?3019, ?3021

INFORMATION SET BOILER TO ECO

BECAUSE IT IS NOT PO

Next: p3071, !f3072

VOLTAGE PUMP AT PCB

{GAINPCBACS}

Next: p3067, !f3068

INSPECTION CODE PLUG

{GAINPCBACS}

Next: p3059, !f3060

VOLTAGE FAN SELF CHECK

{GAINPCBACS}

Next: p3055, !f3056

RESISTANCE SENSOR FLOW AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p3041, f3042

TEMPERATURE FLOW (BOILER FIRING)

REMOVE AIR INTAKE FROM APPLIANCE

Next: p3029, !f3030

TEMPERATURE FLOW (PUMP RUNNING)

REMOVE AIR INTAKE FROM APPLIANCE

Next: p3023, !f3024

RESISTANCE SENSOR FLOW

REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR

Next: p3025, !f3026

RESISTANCE FROST PROTECTION

GAIN ACCESS TO LOWER PCB PANEL

Next: !p3027, !f3028

RESISTANCE SENSOR FLOW

REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR

Next: p3031, !f3032

OBSERVATION DISCONNECT FLOW TURBINE (DEMAND CHECK)

DISCONNECT FLOW TURBINE FROM ITS INLINE CONNECTOR AND MAKE SAFE
ENSURE CENTRAL HEATING TURNED OFF

Next: p3033, !f3034

VOLTAGE CH DEMAND INTO BOARD (NO DEMAND)

GAIN ACCESS TO LOWER PCB PANEL
ENSURE CENTRAL HEATING TURNED OFF

Next: !p3039, !f3040

RESISTANCE SENSOR SAFETY AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p3045, f3046

RESISTANCE GAS VALVE AND HARNESS TO EARTH

DISCONNECT CONNECTOR X4 FROM THE PCB

Next: !p3051, f3052

RESISTANCE HARNESS FAN

DISCONNECT FAN CONNECTOR FROM FAN

Next: !p3057, !f3058

RESISTANCE HARNESS CODE PLUG

DISCONNECT THE CONNECTOR FROM THE CODE PLUG

Next: p3061, !f3062

VOLTAGE FAN SELF CHECK

{GAINPCBACS}

Next: p3063, !f3064

RESISTANCE HARNESS FAN

DISCONNECT FAN CONNECTOR FROM FAN

Next: !p3065, !f3066

RESISTANCE HARNESS PUMP

DISCONNECT THE PLUG FROM THE PUMP

Next: !p3069, !f3070

OBSERVATION DIVERTER MOTOR MOVEMENT (REMOVED)

REMOVE DIVERTER MOTOR FROM ITS HOUSING AND PLACE IN A SAFE LOCATION TO OBSERVE ITS MOVEMENT

Next: !p352, f359

OBSERVATION PUMP RUNS

ENSURE APPLIANCE IS SET TO ECO MODE
DHW TEMPERATURE CONTROL TO MAX

Next: p3073, f3074

OBSERVATION FAN RUNS

ENSURE APPLIANCE IS SET TO ECO MODE
DHW TEMPERATURE CONTROL TO MAX

Next: !p3099, f3100

VOLTAGE FLOW TURBINE INTO BOILER

{GAINPCBACS}

Next: !p3093, f3094

OBSERVATION FLOW RATE INTO BOILER

Next: p3079, !f3080

INSPECTION FLOW COMPONENTS

HOT WATER CIRCUIT ISOLATED AND DRAINED

Next: !p3081, ?3083, ?3085, ?3087, ?3089, ?3091

INSPECTION PRESSURE SYSTEM

Next: p656, !f311

RESISTANCE HARNESS FLOW TURBINE

DISCONNECT THE INLINE PLUG FROM THE FLOW SENSOR

Next: !p3097, !f3098

RESISTANCE SENSOR FLOW AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p3105, !f3106

RESISTANCE SENSOR DHW

DISCONNECT WIRES FROM DHW SENSOR

Next: p3107, !f3108

RESISTANCE SENSOR SAFETY

DISCONNECT WIRES FROM SAFETY SENSOR

Next: p3109, !f3110

RESISTANCE SENSOR FLUE - AIR PRESSURE SWITCH AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X7 FROM THE PCB

Next: p3111, f3112

TEMPERATURE DHW INLET

ATTACH TEMPERATURE CLAMP TO DHW INLET PIPE

Next: !p3117, f3118

PRESSURE FAN MAX RATE

ATTACH FGA TO FAN PR

Next: p3124, f3125

RESISTANCE SENSOR DHW

DISCONNECT WIRES FROM DHW SENSOR

Next: p3132, !f3133

INSPECTION FAN BEARING PLATE

Next: p3128, !f3129

INSPECTION BURNER ASSEMBLY

REMOVE THE FAN HOOD ASSEMBLY

Next: !p3130, !f3131

OBSERVATION DIVERTER MOTOR MOVEMENT

Next: p315, ?316, ?318

RESISTANCE SENSOR RETURN AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p3134, !f3135

INSPECTION GAS SUPPLY TUBE

UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE

Next: p3136, ?3138, ?3140

TEMPERATURE DIFFERENTIAL SAFETY AND FLOW DHW

DHW TEMPERATURE CONTROL TO MAX

Next: p3344, !f3143

INSPECTION EXTERNAL BYPASS

Next: p2039, !f321

VOLTAGE PREHEAT DEMAND INTO BOILER

GAIN ACCESS TO LOWER PCB PANEL
EXTERNAL CONTROLS (IF FITTED) CALLING FOR PREHEAT

Next: p3165, !f3166

DISCONNECT INTERNAL CONTROLS PREHEAT

DISCONNECT THE INTEG

Next: !p3169, !f3170

VOLTAGE DIVERTER VALVE AT PCB

{GAINPCBACS}
DISCONNECT PLUG FROM DIVERTER VALVE AND MAKE SAFE

Next: p323, !f389

INSPECTION AIR INLET INTEGRITY

DHW TEMPERATURE CONT

Next: p3176, !f3286

INSPECTION AIR INTAKE FAN

REMOVE THE FAN AIR INTAKE FROM THE FAN

Next: p3185, !f3186

INSPECTION CONDENSATE PIPE

Next: p3288, !f3188

INSPECTION AIR INLET INTEGRITY

DHW TEMPERATURE CONT

Next: p3207, !f3314

INSPECTION AIR INTAKE FAN

REMOVE THE FAN AIR INTAKE FROM THE FAN

Next: p3216, !f3217

INSPECTION CONDENSATE PIPE

Next: p3316, !f3219

RESISTANCE HARNESS DIVERTER VALVE

DISCONNECT THE PLUG FROM THE DIVERTER MOTOR

Next: !p324, !f325

RESISTANCE SWITCH AIR PRESSURE

REMOVE ELECTRICAL LEADS FROM AIR PRESSURE SWITCH

Next: !p3234, !f3235

INSPECTION FLUE

Next: p3237, !f3238

TEMPERATURE EXHAUST GAS (FAULT CODE)

CH TEMPERATURE CONTR

Next: !p3240, ?3241, ?3243

RESISTANCE SWITCH AIR PRESSURE

REMOVE ELECTRICAL LEADS FROM AIR PRESSURE SWITCH

Next: !p3247, !f3248

RESISTANCE SWITCH AIR PRESSURE

REMOVE ELECTRICAL LEADS FROM AIR PRESSURE SWITCH

Next: !p3250, !f3251

INSPECTION CH OUTPUT SETTING

CH TEMPERATURE CONTROL KNOB SET TO MAX

Next: p3253, f3282

INSPECTION CH TEMP SETTING

CH TEMPERATURE CONTROL KNOB SET TO MAX

Next: p3254, !f3255

PRESSURE GAS INLET

ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT

Next: p3256, !f3257

OBSERVATION DIVERTER MOTOR MOVEMENT

Next: p3258, ?3260, ?3262

PRESSURE FAN MAX RATE

ATTACH FGA TO FAN PR

Next: p3268, f3269

VOLTAGE DIVERTER VALVE AT PCB

{GAINPCBACS}
DISCONNECT PLUG FROM DIVERTER VALVE AND MAKE SAFE

Next: p3264, !f3265

RESISTANCE HARNESS DIVERTER VALVE

DISCONNECT THE PLUG FROM THE DIVERTER MOTOR

Next: !p3266, !f3267

INSPECTION GAS SUPPLY TUBE

UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE

Next: !p3276, ?3278, ?3280

INSPECTION PRESSURE SYSTEM

Next: p328, !f329

INSPECTION FAN BEARING PLATE

Next: p3272, !f3273

INSPECTION BURNER ASSEMBLY

REMOVE THE FAN HOOD ASSEMBLY

Next: !p3274, !f3275

PUMP LIMPET TEST

Next: p366, !f330

INSPECTION GAS SUPPLY TUBE

UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE

Next: p3299, ?3290, ?3292

INSPECTION FLUE SEALS

Next: p3308, ?3301, ?3303, ?3305

INSPECTION BURNER ASSEMBLY

REMOVE THE FAN HOOD ASSEMBLY

Next: p3309, !f3310

INSPECTION GAS SUPPLY TUBE

UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE

Next: p3323, ?3318, ?3320

INSPECTION FLUE SEALS

Next: !p3324, ?3325, ?3327, ?3329

TEMPERATURE EXHAUST GAS

CH TEMPERATURE CONTR

Next: !p3335, !f3336

DISCONNECT COMFORT CONTROLS

{GAINPCBACS}
DISCONNECT PLUG MARKED "EMS" ON LEFT HAND SIDE OF BOILER WIRING AND MAKE SAFE

Next: !p3342, !f3343

INSPECTION MIXING UNIT ASSEMBLY

DISCONNECT THE FAN C

Next: p2542, !f3421

INSPECTION MIXING UNIT ASSEMBLY

DISCONNECT THE FAN C

Next: p2562, !f3428

INSPECTION MIXING UNIT ASSEMBLY

DISCONNECT THE FAN C

Next: p2590, !f3437

INSPECTION MIXING UNIT ASSEMBLY

DISCONNECT THE FAN C

Next: p2633, !f3442

INSPECTION MIXING UNIT ASSEMBLY

DISCONNECT THE FAN C

Next: p3126, !f3449

INSPECTION MIXING UNIT ASSEMBLY

DISCONNECT THE FAN C

Next: p3270, !f3456

INSPECTION MIXING UNIT ASSEMBLY

DISCONNECT THE FAN C

Next: p2321, !f3465

INSPECTION FLUE

Next: p3486, !f3487

INSPECTION MIXING UNIT ASSEMBLY

DISCONNECT THE FAN C

Next: p3488, !f3489

INSPECTION FAN BEARING PLATE

Next: p3490, !f3491

INSPECTION BURNER ASSEMBLY

REMOVE THE FAN HOOD ASSEMBLY

Next: p3492, !f3493

INSPECTION MIXING UNIT ASSEMBLY

DISCONNECT THE FAN C

Next: p2175, !f3502

RESISTANCE HARNESS DIVERTER VALVE

DISCONNECT THE PLUG FROM THE DIVERTER MOTOR

Next: !p385, !f363

INSPECTION CH TEMP SETTING

CH TEMPERATURE CONTROL KNOB SET TO MAX

Next: p702, !f378

RESISTANCE SENSOR DHW

DISCONNECT WIRES FROM DHW SENSOR

Next: !p2141, !f382

PRESSURE GAS INLET

ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT

Next: p2814, !f394

RESISTANCE SENSOR DHW

DISCONNECT WIRES FROM DHW SENSOR

Next: p513, !f514

RESISTANCE SENSOR SAFETY

DISCONNECT WIRES FROM SAFETY SENSOR

Next: p517, !f518

RESISTANCE SENSOR FLUE - AIR PRESSURE SWITCH AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X7 FROM THE PCB

Next: p1918, f520

INFORMATION BLANK DISPLAY

THE DISPLAY FOR THIS

Next: p3009, !f2489

RESISTANCE FUSE (PCB)

REMOVE THE FUSE FROM ITS HOUSING

Next: p557, f558

OBSERVATION DISCONNECT X5 AT PCB

{GAINPCBACS}
DISCONNECT CONNECTOR X5 AT THE PCB AND MAKE SAFE
(THIRD CONNECTOR FROM THE LEFT)

Next: p561, !f562

OBSERVATION DISCONNECT FLOW TURBINE

DISCONNECT FLOW TURB

Next: !p563, !f564

INSPECTION FLOW COMPONENTS

HOT WATER CIRCUIT ISOLATED AND DRAINED

Next: !p584, ?585, ?587, ?589, ?591, ?593

VOLTAGE FLOW TURBINE INTO BOILER

{GAINPCBACS}

Next: !p597, f598

RESISTANCE HARNESS FLOW TURBINE

DISCONNECT THE INLINE PLUG FROM THE FLOW SENSOR

Next: !p601, !f602

PUMP LIMPET TEST

Next: p310, !f672

INSPECTION ISOLATION VALVE DHW

Next: p1874, !f686

OBSERVATION FAULT CODE AT SHUTDOWN

CH TEMPERATURE CONTROL KNOB TO MAX

Next: p708, f3331

RESISTANCE SENSOR FLOW

REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR

Next: p709, !f710

RESISTANCE SENSOR SAFETY

DISCONNECT WIRES FROM SAFETY SENSOR

Next: p711, !f712

RESISTANCE SENSOR RETURN AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: p2339, !f713

INSPECTION PRESSURE SYSTEM

Next: p741, !f742

PUMP LIMPET TEST

Next: p1693, !f744

INSPECTION PUMP SETTINGS

Next: !p778, !f779

RESISTANCE SENSOR DHW AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: !p880, f881

OBSERVATION BOILER RESET

ENSURE APPLIANCE IS COOL

Next: p3236, f887

RESISTANCE SENSOR SAFETY

DISCONNECT WIRES FROM SAFETY SENSOR

Next: p924, !f925

RESISTANCE SENSOR SAFETY AND HARNESS

{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB

Next: !p926, !f927

RESISTANCE HARNESS CODE PLUG

DISCONNECT THE CONNECTOR FROM THE CODE PLUG

Next: !p983, !f984

VOLTAGE PUMP AT PCB

{GAINPCBACS}

Next: p952, !f953

RESISTANCE HARNESS PUMP

DISCONNECT THE PLUG FROM THE PUMP

Next: !p954, !f955

System Information

  • Total Tests: 1169
  • Sequence Logic: Decoded from encrypted .seq file
  • Navigation: Dynamic based on pass/fail results
  • Source: 4731307 GW SWIFTFLOW 100 SIT Control