Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
FERROLI 77 FF
WARNING - IMPORTA
WATER PRESSURE RISE
SELECTOR SWITCH IN CH CONTINUOUS POSITION
CENTRAL HEATING OPERATION
SELECTOR SWITCH IN CH CONTINUOUS POSITION
DHW OPERATION
SELECTOR SWITCH IN HOT WATER POSITION
CH PUMP OVERRUN
SELECTOR SWITCH IN CH CONTINUOUS POSITION
CH BURNER MODULATION
SELECTOR SWITCH IN C
CH HIGH BURNER
SELECTOR SWITCH IN C
CH FAN RUNS (CH TIMED)
SELECTOR SWITCH IN CH TIMED POSITION
CH FAN RUNS
SELECTOR SWITCH IN CH CONTINUOUS POSITION
CH PUMP RUNS
SELECTOR SWITCH IN CH CONTINUOUS POSITION
DHW BURNER MODULATION
SELECTOR SWITCH IN H
DHW BURNER HIGH FLAME
SELECTOR SWITCH IN H
DHW BURNER IGNITES
SELECTOR SWITCH IN HOT WATER POSITION
FLAME FAILURE DEVICE
SELECTOR SWITCH IN HOT WATER POSITION
DHW PILOT ESTABLISHED
SELECTOR SWITCH IN HOT WATER POSITION
GAS ON
DHW PILOT IGNITES
SELECTOR SWITCH IN HOT WATER POSITION.
GAS ON
DHW SPARKING
SELECTOR SWITCH IN HOT WATER POSITION
COMBUSTION COVER ON
DHW FAN RUNS
SELECTOR SWITCH IN HOT WATER POSITION
SLOW FAN
SELECTOR SWITCH IN HOT WATER POSITION
NO BOILER OPERATION
SELECTOR SWITCH IN HOT WATER POSITION
IMPORTANT INFORMATION
THE COMBUSTION C
FERROLI 77 FF
G.C. NUMBER 47 267 0
DHW SPARKING
FLUE
DHW PILOT IGNITES
PILOT BURNER INJECTOR
DHW PILOT ESTABLISHED
OVERHEAT CUT-OFF THERMOSTAT
DHW PILOT ESTABLISHED
THERMOCOUPLE
DHW PILT ESTABLISHED
THERMOCOUPLE INTERRUPTER
DHW BURNER IGNITES
PRINTED CIRCUIT BOARD
DHW BURNER IGNITES
GAS VALVE
DHW BURNER HIGH FLAME
DHW THERMISTOR
DHW BURNER MODULATION
DHW THERMISTOR
CH PUMP RUNS
ROOM THERMOSTAT
CH PUMP RUNS
PRINTED CIRCUIT BOARD
CH FAN RUNS
CH THERMISTOR
CH FAN RUNS (CH TIMED)
TIMER / CLOCK
CH FAN RUNS
CH POTENTIOMETER
DHW FAN RUNS
FAN ASSEMBLY
CH HIGH BURNER
CH POTENTIOMETER
DHW SPARKING
GAS VALVE
DHW SPARKING
CH LIMIT THERMOSTAT
DHW SPARKING
DHW LIMIT THERMOSTAT
MODULATING BALANCE TUBE
MODULATING BALANCE TUBE
WATER PRESSURE RISE
EXPANSION VESSEL
DHW OPERATION
HEAT EXCHANGER
CH PUMP OVERRUN
PRINTED CIRCUIT BOARD
CH BURNER MODULATION
CH THERMISTOR
CH BURNER MODULATION
CH POTENTIOMETER
CH HIGH BURNER
CH THERMISTOR
ELECTRICAL CHECKS
ELECTRICAL CHECKS
SYSTEM CHECKS
SYSTEM CHECKS
DHW FLOW RATE
DHW INLET FILTER
DHW FLOW RATE
DHW RESTRICTOR
NO BOILER OPERATION
FROST THERMOSTAT
NO BOILER OPERATION
DHW FLOW SWITCH
NO BOILER OPERATION
SELECTOR SWITCH
SLOW FAN
PCB FUSE
SLOW FAN
PRINTED CIRCUIT BOARD
DHW FAN RUNS
PRESSURE SWITCH DAMPER
DHW FAN RUNS
AIR PRESSURE SENSING TUBE
DHW FAN RUNS
DHW FLOW SWITCH
DHW FAN RUNS
DHW THERMISTOR
FLAME FAILURE DEVICE
GAS VALVE
DHW SPARKING
PRESSURE SWITCH DAMPER
DHW SPARKING
AIR PRESSURE SENSING TUBE
DHW SPARKING
ELECTRODE LEAD
DHW SPARKING
SPARK GENERATOR
DHW SPARKING
AIR PRESSURE SWITCH
DHW PILOT IGNITES
GAS VALVE
DHW PILOT IESTABLISHED
GAS VALVE
DHW BURNER IGNITES
BURNER INJECTOR
DHW BURNER HIGH FLAME
GAS VALVE
DHW BURNER HIGH FLAME
PRINTED CIRCUIT BOARD
DHW BURNER MODULATION
GAS VALVE
DHW BURNER MODULATION
PRINTED CIRCUIT BOARD
CH PUMP RUNS
SELECTOR SWITCH
CH PUMP RUNS
PUMP
CH FAN RUNS (CH TIMED)
SELECTOR SWITCH
CH FAN RUNS
PRINTED CIRCUIT BOARD
DHW FAN RUNS
AIR PRESSURE SWITCH
CH HIGH BURNER
PRINTED CIRCUIT BOARD
DHW SPARKING
IGNITION MICROSWITCH
DHW SPARKING
PRINTED CIRCUIT BOARD
CENTRAL HEATING OPERATION
HEAT EXCHANGER
CH BURNER MODULATION
PRINTED CIRCUIT BOARD
DHW FLOW RATE
HEAT EXCHANGER
NO BOILER OPERATION
PRINTED CIRCUIT BOARD
SLOW FAN
FAN ASSEMBLY
DHW FAN RUNS
PRINTED CIRCUIT BOARD
DHW SPARKING
ELECTRODE
HEAT EXCHANGER NOISY OPERATION, WATER CIRCULATING
CHARACTERISTIC TEST FROM CENTRAL HEATING OPERATION
HEAT EXCHANGER QUIET OPERATION, RADIATORS NOT HEATING
CHARACTERISTIC TEST FROM CENTRAL HEATING OPERATION
11/07/2018 09:57:05 1807_1_50_1 20/07/2018 14:02:22
11/07/2018 10:39:52
OVERHEAT THERMOSTAT RESISTANCE
ENSURE THAT THE BOILER IS NOT IN AN OVERHEAT CONDITION
DHW GAS VALVE VOLTAGE
SELECTOR SWITCH IN HOT WATER POSITION
DHW FULL MODUREG VOLTAGE
SELECTOR SWITCH IN HOT WATER POSITION
DHW SENSOR RESISTANCE
REMOVE THE BROWN WIRE AND THE BLUE WIRE FROM THE HW SENSOR
DHW MODUREG MODULATION VOLTAGE
SELECTOR SWITCH IN HOT WATER POSITION
DHW SENSOR RESISTANCE
REMOVE THE BROWN WIRE AND THE BLUE WIRE FROM THE HW SENSOR
SELECTOR SWITCH RESISTANCE (CH 24HRS)
SELECTOR SWITCH IN CH CONTINUOUS POSITION
REMOVE CONNECTOR PLUG FROM X2 ON PCB
CH THERMISTOR RESISTANCE
REMOVE THE BROWN WIRE AND THE BLACK WIRE FROM THE CH THERMISTOR
CH TIMER RESISTANCE
SELECTOR SWITCH IN CH TIMED POSITION
ENSURE THAT THE CH TIMER IS IN ITS CH ON CONDITION
CH THERMISTOR RESISTANCE
REMOVE THE BROWN WIRE AND THE BLACK WIRE FROM THE CH THERMISTOR
CH THERMISTOR RESISTANCE
REMOVE THE BROWN WIRE AND THE BLACK WIRE FROM THE CH THERMISTOR
DHW INLET FILTER
WATER OFF
AIR PRESSURE SWITCH NO AIR RESISTANCE
REMOVE CONNECTOR PLUG FROM R ON PCB
DHW AIR PRESSURE SWITCH AIR DETECT
{GAINPCBACS}
SELECTOR SWITCH IN HOT WATER POSITION
THERMOCOUPLE MILLIVOLTAGE
SELECTOR SWITCH IN HOT WATER POSITION
DHW BURNER GAS PRESSURE
SELECTOR SWITCH IN H
CH PUMP VOLTAGE
SELECTOR SWITCH IN CH CONTINUOUS POSITION
CH POTENTIOMETER RESISTANCE
REMOVE THE CONNECTOR PLUG MARKED X1 FROM THE PCB
INSPECTION FAN ASSEMBLY
REMOVE FAN ASSEMBLY
CH POTENTIOMETER RESISTANCE
REMOVE THE CONNECTOR PLUG MARKED X1 FROM THE PCB
CH LIMIT THERMOSTAT RESISTANCE
ENSURE THAT THE BOILER IS NOT IN AN OVERHEAT CONDITION
DHW LIMIT THERMOSTAT RESISTANCE
ENSURE THE BOILER IS NOT IN AN OVERHEATED STATE
CH POTENTIOMETER RESISTANCE
REMOVE THE CONNECTOR PLUG MARKED X1 FROM THE PCB
DHW RESTRICTOR
WATER OFF
DHW FLOW SWITCH RESISTANCE (OPEN CIRCUIT)
DHW TAPS OFF
SELECTOR SWITCH RESISTANCE (DHW)
SELECTOR SWITCH IN HOT WATER POSITION
REMOVE CONNECTOR PLUG FROM X2 ON PCB
MAINS POWER SUPPLY
{GAINPCBACS}
DHW SENSOR RESISTANCE
REMOVE THE BROWN WIRE AND THE BLUE WIRE FROM THE HW SENSOR
SPARK GENERATOR INPUT VOLTAGE
SELECTOR SWITCH IN HOT WATER POSITION
System Information
- Total Tests: 142
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control