4707554 BAXI DUO TEC 2 COMBI 24 GA
GLOBALLY REPLACED
BOILER ENTERS STANDBY MODE
ENSURE THERE ARE NO DEMANDS
OPERATION DHW
DHW TEMPERATURE CONTROL SET TO MAX
OPERATION CH
CH THERMOSTAT SET TO MAX
USER DISPLAY CONTROL SET TO HW AND CH
PUMP RUNS DHW DEMAND
RUN HOT WATER TAP AT FLOW RATE OF 3 L/MIN
ERROR CODE 160 FAN INVESTIGATION
OUTSIDE MODEL
DOES BOILER REACT AND FIRE WITH CH DEMAND
USER DISPLAY CONTROL SET TO HW AND CH
E09 GAS VALVE CABLE
OUTSIDE MODEL
RESET GUIDE
THE ACTUAL METHOD OF
E385 LOW VOLTAGE
HEADER FOR FAULT CODE - NOT USED
VOLTAGE IN
HARNESS - HIGH VOLTAGE - TIMER
SPARKING NOT LIGHTING
CONDENSATE TRAP OR PIPEWORK
NO PRESSURE DROP
FLUE
NO DROP
VENTURI
NO DROP
BURNER
BAFFLES OUT
BURNER
BURNER BAFFLES
FLUE
FAN RUNS OUTSIDE MODEL
SENSOR - THERMODISC - MINIFIT
PREHEAT SATISFACTORY3
HARNESS - 3 WAY VALVE - PUMP - FAN
BLR TO TEMP RADS COLD
HARNESS - 3 WAY VALVE - PUMP - FAN
FALSE FLAME
GAS VALVE
OH INVESTIGATION FAN RUNS DHW
THERMOSTAT 105 DEG C - LIMIT
OVERHEAT INVESTIGATION OH
SENSOR - THERMODISC - MINIFIT
OVERHEAT INVESTIGATION 3
SENSOR - THERMODISC - MINIFIT
NO PUMP OVERRUN
PCB
RESTRICTED
FLUE
RESTRICTED 2
FLUE
RESTRICTED 3
FLUE
NO DROP
HEAT EXCHANGER FLUE WAYS
SERVICE DUE
SERVICE DUE
BLANK FOR BOILER RESET GUIDE
Z DIRECTION CHOICE OR CONTINUE
OVERHEAT INVESTIGATION 2
OVERHEAT FURTHER INVESTIGATION REQUIRED
BURNER DOES NOT IGNITE
BURNER
DIRTY CONFUSING GA SYSTEM
ELECTRODE - SENSING
UNABLE TO CALIBRATE
GAS VALVE
FAN RUNS DHW 1
SENSOR - THERMODISC - MINIFIT
BAFFLES OUT
GAS VALVE
DIRTY CONFUISING GA SYSTEM 2
ELECTRODE - SENSING
DOES NOT IGNITE
HEAT EXCHANGER FLUE WAYS
CALIBBRATION
SENSOR - THERMODISC - MINIFIT
NOT CORRECTLY FITTED
KEY PCB
SHORTED DC SIDE
FAN
SHORTED
SENSOR HALL
SHORTED
VALVE - SENSOR - PRESSURE
SHORTED
HARNESS - FAN (DC)
PRESSURE OR DHW FLOW SENSOR SECTIONS SHORTED
HARNESS - LOW VOLTAGE
STANDBY
HARNESS - FAN (DC)
FAN STANDBY 2
PCB
FAN RUNS
THERMOSTAT 105 DEG C - LIMIT
FAN RUNS DHW
SENSOR - NTC
SOLENOID FAULT
GAS VALVE
BURNER DOES NOT IGNITE
ELECTRODES SPARK AND EARTH AND GAP
BURNER DOES NOT IGNITE
VENTURI
BURNER BAFFLES OUT
CONDENSATE TRAP OR PIPEWORK
DIES AWAY
GAS INLET PRESSURE
BURNER BAFFLES OUT
HEAT EXCHANGER FLUE WAYS
BURNER NON ESTABLISH
CONDENSATE TRAP OR PIPEWORK
BURNER IGNITES BUT DOES NOT ESTABLISH
GAS INLET PRESSURE
BURNER IGNITES
ELECTRODE - SENSING
BURNERIGNITES
CABLE - DETECTION - ELECTRODE
FAN RUNS DHW
THERMOSTAT 105 DEG C - LIMIT
NO SPARK
CABLE - ELECTRODE - IGNITION
NO SPARK
ELECTRODE CONDITION AND SPARK GAP
DHW KETTLING
PUMP
DHW NOISEY KETTLING
CONDENSATE TRAP OR PIPEWORK
PREHEAT SATISFACTORY3
FLOW ASSEMBLY BRASS W/O BYPASS
BLOCKED PREHEAT SAT3
HEAT EXCHANGER - PLATE TO PLATE
DHW DHW COOL RADS COOL
GAS INLET PRESSURE
DHW COOL
PUMP
UNDER PRESSURE
VESSEL - EXPANSION
ANTI CYCLE DELAY
PCB
CPERATION CH OK NO REFIRE FAN RUNS
THERMOSTAT 105 DEG C - LIMIT
BOILER TEMP LOW SYSTEM TEMP LOW
GAS INLET PRESSURE
BLR TO TEMP RADS NOT
FLOW ASSEMBLY BRASS W/O BYPASS
FAN RUNS DHW
SENSOR - THERMODISC - MINIFIT
PUMP OVERRUN
PCB
CASE REMOVAL
Z DIRECTION CHOICE OR CONTINUE
FOR TYPE DIAG PROCEDURE
Z DIRECTION CHOICE OR CONTINUE
STANDBY
THERMOSTAT 105 DEG C - LIMIT
LOW PRESSURE WARNING
SYSTEM PRESSURE INCORRECT
STANDBY
HARNESS - LOW VOLTAGE
PUMP RUNS HARNESS FLOW SWITCH
HARNESS - LOW VOLTAGE
STOPS PUMP FAN RUNS DHW 1
SENSOR - THERMODISC - MINIFIT
STOPS PUMPFAN RUNS DHW
SENSOR - THERMODISC - MINIFIT
STOPS PUMP FAN RUNS
THERMOSTAT 105 DEG C - LIMIT
STOPS PUMPFAN RUNS DHW
SENSOR - NTC
BLOWN STAND BY MODE AT POWER UP
MAIN FUSE FUSED SPUR F1
BLOWN STANDBY MODE AT POWER UP
FUSE 2A MAIN PCB
BLOWN STANDBY MODE
FUSE 2A MAIN PCB F3
FAN RUNS
SENSOR - NTC
STOPS PUMP FAN RUNS OUTSIDE MODEL
THERMOSTAT 105 DEG C - LIMIT
FROST STOPS PUMP FAN RUNS DHW
SENSOR - NTC
FROSTSTOPS PUMP FAN RUNS DHW
SENSOR - THERMODISC - MINIFIT
FAULT CODES
Z DIRECTION CHOICE OR CONTINUE
FAN RUNS DHW OPERATION DHW TOO HOT
SENSOR - NTC
FAN RUNS 1
SENSOR - THERMODISC - MINIFIT
FAN RUNS
SENSOR - THERMODISC - MINIFIT
FAN RUNS DHW OPERATION DHW COOL
SENSOR - NTC
FAN RUNSDHW COOL
SENSOR - THERMODISC - MINIFIT
FAN RUNS DHW COOL
SENSOR - THERMODISC - MINIFIT
HOT THEN COLD FAN RUNS DHW COOL 1
SENSOR - THERMODISC - MINIFIT
HOT THEN COLD
SENSOR - NTC
HOT THEN COLD FAN RUNS DHW COOL
SENSOR - THERMODISC - MINIFIT
CH OP FAN RUNS
SENSOR - THERMODISC - MINIFIT
CH OPFAN RUNS
SENSOR - THERMODISC - MINIFIT
BLR TEMP LOW SYSTEM LOW FAN RUNS
SENSOR - THERMODISC - MINIFIT
BLR TEMP LOW SYSTEM LOWFAN RUNS
SENSOR - THERMODISC - MINIFIT
POOR FLOW RATE
VALVE - COMPACT - RETURN - DHW
RESTRICTED
BURNER
RESTRICTED
VENTURI
RESTICTED
CONDENSATE PIPE
RESTRICTED
HEAT EXCHANGER PRIMARY
RESTRICTED 2
BURNER
RESTRICTED 2
VENTURI
RESTICTED 2
CONDENSATE PIPE
RESTRICTED 2
HEAT EXCHANGER PRIMARY
STANDBYSYSTEM PRESSURE
HARNESS - LOW VOLTAGE
FAULT CODE
SYSTEM PRESSURE INCORRECT
DC HARNESS
FAN
FUSE BLOWING
MOTOR - 3 WAY VALVE
FAN INVESTIGATION
HARNESS - FAN (DC)
SPARK NOT LIGHT
HARNESS - GAS VALVE
RESTRICTED 3
BURNER
RESTRICTED 3
VENTURI
RESTICTED 3
CONDENSATE PIPE
RESTRICTED 3
HEAT EXCHANGER PRIMARY
FLOW SWITCH ASSEMBLY
FLOW ASSEMBLY BRASS
HARNESS FLOW SWITCH
HARNESS - LOW VOLTAGE
FLOW SWITCH ASSEMBLY 2
FLOW ASSEMBLY BRASS
OVERHEAT INVESTIGATION 1
SENSOR - THERMODISC - MINIFIT
OVERHEAT INVESTIGATION 2
SENSOR - THERMODISC - MINIFIT
NO RECTIFICATION VOLTAGE
HEAT EXCHANGER FLUE WAYS
DHW COOL
HEAT EXCHANGER PRIMARY
DHW HOT THEN COLD
HEAT EXCHANGER PRIMARY
SERVICE VALVES FLOW AND RETURN
SERVICE VALVES FLOW AND RETURN
E09 FAULT CODE
HARNESS - GAS VALVE
MECHANICAL FAULT
GAS VALVE
BURNER IGNITION
FAN
POOR DHW
MOTOR - 3 WAY VALVE
BLR TO TEMP RADS NOT
MOTOR - 3 WAY VALVE
FALSE FLAME
PCB
OH INVESTIGATIONNO SPARK
HARNESS - SAFETY VALVE
OVERHEAT
PUMP
OVERHEAT
HARNESS - 3 WAY VALVE - PUMP - FAN
OVERHEAT INVESTIGATIONOH
HARNESS - LOW VOLTAGE
OVERHEAT INVESTIGATION2OH
HARNESS - LOW VOLTAGE
NO DROP
FAN
OVERHEAT INVESTIGATION
OVERHEAT FURTHER INVESTIGATION REQUIRED
SENSOR PRIMARY FAN RUNS
HARNESS - LOW VOLTAGE
NOT IGNITING
RE CALIBRATION
BAFFLING
RE CALIBRATION
E20 FAULT CODE
HARNESS - LOW VOLTAGE
E40 FAULT CODE
HARNESS - LOW VOLTAGE
OPEN CIRCUIT
HARNESS SUPPLY TO PCB
LED AT POWER UP
PCB
STANDBY
FAN
FLUE SENSOR FAN RUNS
HARNESS - LOW VOLTAGE
FAN RUNS 1
HARNESS - NTC/EXTERNAL SENSOR
FLAME SENSE
PCB
NO SPARK
PCB
DHW NOISY KETTLING
HEAT EXCHANGER - PLATE TO PLATE
DHW NOISY KETTLING
HEAT EXCHANGER PRIMARY
EXTERNAL CONTROL DHW NOISY KETTLING
HARNESS - HIGH VOLTAGE - TIMER
LETBY PREHEAT3
FLOW ASSEMBLY BRASS W/O BYPASS
WATER TOO HOT
PCB
EXPANSION CONNECTION
PIPE - VESSEL - EXPANSION
OPERATION CH OPERATION OK GOES TO OVER HEAT
Z DIRECTION CHOICE OR CONTINUE
CH OPERATION NOISY
HEAT EXCHANGER PRIMARY
SENSOR TEMP RETURN FAN RUNS
HARNESS - LOW VOLTAGE
STANDBY
PCB
PUMP TO PCB
HARNESS - 3 WAY VALVE - PUMP - FAN
STANDBY MODE
VALVE - SENSOR - PRESSURE
STOPS PUMP SENSOR PRIMARY FAN RUNS
HARNESS - LOW VOLTAGE
STOPS PUMP SENSOR TEMP RETURN FAN RUNS
HARNESS - LOW VOLTAGE
STOPS PUMP FLUE SENSOR FAN RUNS
HARNESS - LOW VOLTAGE
STOPS PUMP FAN RUNS
HARNESS - NTC/EXTERNAL SENSOR
FURTHER INVESTIGATION FUSE F1 MAIN SOLENOID
HARNESS - GAS VALVE
FURTHER INVESTIGATION FUSE F1
HARNESS - 3 WAY VALVE - PUMP - FAN
FURTHER INVESTIGATION F1
Z DIRECTION CHOICE OR CONTINUE
FROST PROTECTION
FROST PROTECTION
FURTHER IN VESTIGATION F2
Z DIRECTION CHOICE OR CONTINUE
FURTHER IN VESTIGATION F3
Z DIRECTION CHOICE OR CONTINUE
FAN RUNS
HARNESS - NTC/EXTERNAL SENSOR
STOPS PUMP FLUE SENSOR FAN RUNS OUTSIDE MODEL
HARNESS - LOW VOLTAGE
GAS RATE
GAS VALVE
RESTRICTED
CONDENSATE TRAP OR PIPEWORK
PUMP RUNS
DHW INLET FILTER
GAS RATE LOW
GAS VALVE
RESTRICTED 2
CONDENSATE TRAP OR PIPEWORK
PUMP RUNS
DHW FLOW FLOAT
STANDBY MODE SYSTEM PRESSURE
VALVE - SENSOR - PRESSURE
FUSE BLOWING
PCB
DIVERTER VALVE
HARNESS - 3 WAY VALVE - PUMP - FAN
FUSE INVESTIGATION
HARNESS - FAN (DC)
POOR FLOW RATE
HEAT EXCHANGER - PLATE TO PLATE
NO SPARK
HARNESS - SAFETY VALVE
NOISY CH
GAS VALVE
RESTRICTED 3
CONDENSATE TRAP OR PIPEWORK
VOLTAGE IN
PCB
PUMP RUNS?FAN DOES NOT RUN
SENSOR HALL
FAN DOES NOT RUN
SENSOR HALL
NO REACTION CH
HARNESS - HIGH VOLTAGE - TIMER
OVERHEAT INVESTIGATION
HARNESS - LOW VOLTAGE
OVERHEAT INVESTIGATION2
HARNESS - LOW VOLTAGE
DHW COOL
HEAT EXCHANGER - PLATE TO PLATE
OPERATION DHW DHW RUNS HOT THEN COLD
HEAT EXCHANGER - PLATE TO PLATE
VOLTAGE IN 2
PCB
FAN RUNS CONTINUALLY
CHARACTERISTIC TEST FROM BOILER ENTERS STANDBY MODE
NO SPARK
CHARACTERISTIC TEST FROM BURNER IGNITES AND ESTABLISHES
BURNER IGNITES BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM BURNER IGNITES AND ESTABLISHES
BURNER IGNITES BUT BAFFLES OUT OR DIES AWAY
CHARACTERISTIC TEST FROM BURNER IGNITES AND ESTABLISHES
SPARKING OCCURS BUT BURNER DOES NOT LIGHT
CHARACTERISTIC TEST FROM BURNER IGNITES AND ESTABLISHES
DHW TOO HOT
CHARACTERISTIC TEST FROM OPERATION DHW
DHW COOL RADS COLD NO HEAT DEMAND
CHARACTERISTIC TEST FROM OPERATION DHW
DHW COOL RADS HOT WITH NO CH DEMAND
CHARACTERISTIC TEST FROM OPERATION DHW
DHW NOISY KETTLING
CHARACTERISTIC TEST FROM OPERATION DHW
DHW RUNS HOT THEN COLD
CHARACTERISTIC TEST FROM OPERATION DHW
BOILER DOES NOT REACT TO CH DEMAND
CHARACTERISTIC TEST FROM CH OPERATION (FOR HEAT EX DIAG)
BOILER KETTLES
CHARACTERISTIC TEST FROM CH OPERATION (FOR HEAT EX DIAG)
BOILER NOISY
CHARACTERISTIC TEST FROM OPERATION CH
BOILER UP TO TEMP RADS COLD
CHARACTERISTIC TEST FROM OPERATION CH
BOILER TEMP LOW SYSTEM TEMP LOW
CHARACTERISTIC TEST FROM OPERATION CH
OPERATION SATISFACTORY BUT BOILER GOES TO OVER HEAT
CHARACTERISTIC TEST FROM OPERATION CH
OPERATES CORRECTLY BUT SYSTEM GETS TOO COOL BEFORE REFIRING
CHARACTERISTIC TEST FROM OPERATION CH
SYSTEM PRESSURE RISE EXCESSIVE
CHARACTERISTIC TEST FROM OPERATION CH
PUMP RUNS CONTINUALLY
CHARACTERISTIC TEST FROM BOILER ENTERS STANDBY MODE
TEMP DIFF CORRECT LOCAL BOILING
CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL FLOW RETURN (P=DIF NOK NOISY NSD)
DIFFERENTIAL OK
CHARACTERISTIC TEST FROM TEMPERATURE DIFFERENTIAL FLOW RETURN (P=DIF NOK NOISY NSD)
BOILER FIRES WITH NO DEMAND
CHARACTERISTIC TEST FROM BOILER ENTERS STANDBY MODE
FLOAT DAMAGED,RESTRICTED OR JAMMED
CHARACTERISTIC TEST FROM FLOW SWITCH ASSEMBLY
FLOW SWITCH ASSEMBLY CLEAR
CHARACTERISTIC TEST FROM FLOW SWITCH ASSEMBLY
30/06/2021 14:52:52 2107_1_50_1 31/08/2021 11:18:14
29/07/2021 09:48:48
VOLTAGE PERMANENT TO FAN
REMOVE CONTROL BOX COVER IF NECESSARY
VOLTAGE DIVERTER VALVE PCB (DHW)
REMOVE CONTROL BOX COVER IF NECESSARY
VOLTAGE DIVERTER VALVE PCB CH
USER DISPLAY CONTROL SET TO HW AND CH
REMOVE CONTROL BOX COVER IF NECESSARY
VOLTAGE DEMAND FROM FLOW SENSOR
REMOVE CONTROL BOX COVER IF NECESSARY
RUN HOT WATER TAP AT FLOW RATE OF 3 L/MIN
PRESSURE STANDING_RETURN
ATTACH U GAUGE TO INLET TEST POINT
USER DISPLAY CONTROL SET TO HW MODE ONLY
OBSERVATION RESET BOILER
ALLOW THE APPLIANCE TO COOL
RESISTANCE OVERHEAT STAT AND HARNESS
DISCONNECT CONNECTOR X37 FROM ON THE PCB
RESISTANCE SENSOR OVERHEAT STAT NO SPARK
DISCONNECT THE BLUE WIRES FROM THE OVERHEAT
VOLTAGE PUMP AT PUMP
REMOVE THE COVER FROM THE PUMP
RUN HOT WATER TAP AT FLOW RATE OF 3 L/MIN
VOLTAGE PUMP AT PCB
RUN HOT WATER TAP AT FLOW RATE OF 3 L/MIN
RESISTANCE SENSOR TEMP PRIMARY
DISCONNECT PLUG (RED LEADS) FROM PRIMARY SENSOR
RESISTANCE SENSOR TEMP RETURN
REMOVE THE TWO LEADS (BLUE) FROM THE RETURN SENSOR
RESISTANCE SENSOR TEMP PRIMARY
DISCONNECT PLUG (RED LEADS) FROM PRIMARY SENSOR
RESISTANCE SENSOR TEMP RETURN
REMOVE THE TWO LEADS (BLUE) FROM THE RETURN SENSOR
SOCKET AND SEE CHECK (LOW VOLTAGE)
REMOVE CONTROL BOX COVER IF NECESSARY
VOLTAGE DC TO FAN (FAN DISCONNECTED)
REMOVE 4 WIRE CONNECTOR FROM FAN AND MAKE SAFE
VOLTAGE DC TO FAN (FAN DISCONNECTED)
REMOVE 4 WIRE CONNECTOR FROM FAN AND MAKE SAFE
RESISTANCE HEAT EX OVERHEAT SENSOR
DISCONNECT THE WIRING FROM THE FLUE OVERHEAT STAT
VOLTAGE TO FLOW SENSOR
REMOVE CONTROL BOX COVER IF NECESSARY
RESISTANCE SENSOR TEMP DHW
REMOVE THE GREEN LEADS FROM DHW SENSOR
VOLTAGES DC TO GAS VALVE
REMOVE CONTROL BOX COVER IF NECESSARY
ELECTRODE SENSE
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
RESISTANCE SENSOR OVERHEAT STAT NO SPARK
DISCONNECT THE BLUE WIRES FROM THE OVERHEAT
VOLTAGE EXTERNAL CONTROLS (IN)
USER DISPLAY CONTROL TO HW AND CH
REMOVE CONTROL BOX COVER IF NECESSARY
VOLTAGE PUMP AT PUMP
REMOVE THE COVER FROM THE PUMP
RUN HOT WATER TAP AT FLOW RATE OF 3 L/MIN
VOLTAGE PUMP AT PCB
RUN HOT WATER TAP AT FLOW RATE OF 3 L/MIN
VOLTAGE TO LOW PRESSURE SWITCH
REMOVE CONTROL BOX COVER IF NECESSARY
VOLTAGE TO FLOW SENSOR
REMOVE CONTROL BOX COVER IF NECESSARY
RESISTANCE SENSOR TEMP PRIMARY
DISCONNECT PLUG (RED LEADS) FROM PRIMARY SENSOR
RESISTANCE SENSOR TEMP RETURN
REMOVE THE TWO LEADS (BLUE) FROM THE RETURN SENSOR
RESISTANCE HEAT EX OVERHEAT SENSOR
DISCONNECT THE WIRING FROM THE FLUE OVERHEAT STAT
VOLTAGE MAINS POWER INPUT TO APPLIANCE
REMOVE CONTROL BOX COVER IF NECESSARY
RESISTANCE SENSOR TEMP DHW
REMOVE THE GREEN LEADS FROM DHW SENSOR
RESISTANCE FUSE F1 (FUSED SPUR)
REMOVE FUSE FROM HOLDER
RESISTANCE GAS VALVE SOLENOID MAIN AND HARNESS
DISCONNECT CONNECTOR MARKED X36
RESISTANCE GAS VALVE SOLENOID MAIN
DISCONNECT THE LEAD FROM THE GAS VALVE
RESISTANCE PUMP
REMOVE THE COVER FROM THE PUMP AND DISCONNECT THE
LEAD FROM THE PUMP HOUSING
RESISTANCE FAN HARNESS
DISCONNECT THE 4 WAY CONNECTOR FROM THE PCB AND FAN
RESISTANCE FUSE F2 ( APPLIANCE)
REMOVE FUSE FROM HOLDER AND CONNECTOR BLOCK
EXTERNAL CONTROLS CALLING
ENSURE THERE ARE NO
RESISTANCE SENSOR TEMP DHW
REMOVE THE GREEN LEADS FROM DHW SENSOR
RESISTANCE SENSOR TEMP FLOW AND HARNESS
DISCONNECT CONNECTOR FROM X22 ON THE PCB
RESISTANCE SENSOR TEMP PRIMARY
DISCONNECT PLUG (RED LEADS) FROM PRIMARY SENSOR
RESISTANCE SENSOR TEMP RETURN AND HARNESS
DISCONNECT CONNECTOR FROM X22 ON THE PCB
RESISTANCE SENSOR TEMP RETURN
REMOVE THE TWO LEADS (BLUE) FROM THE RETURN SENSOR
RESISTANCE SENSOR TEMP DHW AND HARNESS
DISCONNECT CONNECTOR FROM X20 ON THE PCB
RESISTANCE SENSOR TEMP DHW
REMOVE THE GREEN LEADS FROM DHW SENSOR
RESISTANCE HEAT EX OVERHEAT AND HARNESS
DISCONNECT CONNECTOR FROM X22 ON THE PCB
RESISTANCE HEAT EX OVERHEAT SENSOR
DISCONNECT THE WIRING FROM THE FLUE OVERHEAT STAT
PRESSURE FAN
ATTACH U GAUGE TO GAS VALVE OUTLET TEST POINT
REMOVE 4 WIRE HARNESS FROM FAN
INSPECTION BURNER
REMOVE THE FRONT OF THE COMBUSTION CHAMBER
PRESSURE FAN
ATTACH U GAUGE TO GAS VALVE OUTLET TEST POINT
REMOVE 4 WIRE HARNESS FROM FAN
INSPECTION BURNER
REMOVE THE FRONT OF THE COMBUSTION CHAMBER
VOLTAGE TO LOW PRESSURE SWITCH
REMOVE CONTROL BOX COVER IF NECESSARY
RESISTANCE FAN (DC)
REMOVE THE 4 WIRE CONNECTOR FROM THE FAN
RESISTANCE DIVERTER VALVE HEAD
REMOVE DIVERTER VALVE HEAD FROM BODY
PRESSURE FAN
ATTACH U GAUGE TO GAS VALVE OUTLET TEST POINT
REMOVE 4 WIRE HARNESS FROM FAN
INSPECTION BURNER
REMOVE THE FRONT OF THE COMBUSTION CHAMBER
VOLTAGE EXTERNAL CONTROLS (OUT PCB)
REMOVE CONTROLS COVER AS NECESSARY
USER DISPLAY CONTROL TO CH AND HW
VOLTAGE EXTERNAL CONTROLS (IN)
USER DISPLAY CONTROL TO HW AND CH
REMOVE CONTROL BOX COVER IF NECESSARY
RESISTANCE SENSOR TEMP PRIMARY
DISCONNECT PLUG (RED LEADS) FROM PRIMARY SENSOR
RESISTANCE SENSOR TEMP RETURN
REMOVE THE TWO LEADS (BLUE) FROM THE RETURN SENSOR
TEMPERATURE DIFFERENTIAL PRIMARY HEAT EX_CH
USER DISPLAY CONTROL SET TO DHW AND CH
ATTACH TEMPERATURE PROBES AS INDICATED BY THE RED ARROWS
TEMPERATURE DIFFERENTIAL PRIMARY HEAT EX_CH
USER DISPLAY CONTROL SET TO DHW AND CH
ATTACH TEMPERATURE PROBES AS INDICATED BY THE RED ARROWS
RESISTANCE GAS VALVE HARNESS
DISCONNECT THE 4 WAY CONNECTOR ( X36) FROM THE PCB
ALSO DISCONNECT THE LEAD FROM THE GAS VALVE
PRESSURE FAN
ATTACH U GAUGE TO GAS VALVE OUTLET TEST POINT
REMOVE 4 WIRE HARNESS FROM FAN
VOLTAGE FAN
REMOVE CONTROL BOX COVER IF NECESSARY
INSPECTION BURNER
REMOVE THE FRONT OF THE COMBUSTION CHAMBER
INSPECTION BURNER
REMOVE THE FRONT OF THE COMBUSTION CHAMBER
RESISTANCE DIVERTER VALVE HARNESS
DISCONNECT X13 FROM THE PCB
DISCONNECT THE LEAD FROM THE DIVERTER VALVE MOTOR
RESISTANCE DIVERTER VALVE HARNESS
DISCONNECT X13 FROM THE PCB
DISCONNECT THE LEAD FROM THE DIVERTER VALVE MOTOR
RESISTANCE SENSOR TEMP FLOW AND HARNESS
DISCONNECT CONNECTOR FROM X22 ON THE PCB
INSPECTION AIR IN SYSTEM AND BOILER
ENSURE BOILER SYSTEM PRESSURE IS CORRECT
ENSURE AUTO AIR VENT CAP IS OPEN
RESISTANCE SENSOR TEMP FLOW AND HARNESS
DISCONNECT CONNECTOR FROM X22 ON THE PCB
RESISTANCE SENSOR TEMP RETURN AND HARNESS
DISCONNECT CONNECTOR FROM X22 ON THE PCB
OBSERVATION PUMP OVERRUN
USER DISPLAY CONTROL SET TO HW AND CH
OBSERVATION DOES E110 RE APPEAR
DHW TEMPERATURE SET TO MAX
CH TEMPERATURE SET TO MAX
RESISTANCE SENSOR TEMP RETURN AND HARNESS
DISCONNECT CONNECTOR FROM X22 ON THE PCB
INSPECTION BURNER
REMOVE THE FRONT OF THE COMBUSTION CHAMBER
ELECTRODE SENSE
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
ELECTRODE SENSE
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
RESISTANCE HEAT EX OVERHEAT AND HARNESS
DISCONNECT CONNECTOR FROM X22 ON THE PCB
HEAT EXCHANGER FLUE WAYS
REMOVE THE COMBUSTION CHAMBER FRONT
OBSERVATION DISPLAY OPERATES WITH FAN DISCONNECTED
REMOVE THE 4 WIRE CONNECTOR FROM THE FAN AND MAKE SAFE
OBSERVATION DISPLAY OPERATES WITH DHW FLOW SENSOR DISCONNECTED
REMOVE THE CONNECTOR FOR THE DHW FLOW SENSOR AND MAKE SAFE
OBSERVATION DISPLAY OPERATES WITH PRESSURE SENSOR DISCONNECTED
REMOVE THE CONNECTOR FROM THE PRESSURE SENSOR AND MAKE SAFE
OBSERVATION DISPLAY OPERATES WITH X23 DISCONNECTED
REMOVE CONNECTOR X23 FROM THE PCB AND MAKE SAFE
OBSERVATION DISPLAY OPERATES WITH X22 DISCONECTED
REMOVE CONNECTOR X22 FROM THE PCB AND MAKE SAFE
RESISTANCE FAN HARNESS
DISCONNECT THE 4 WAY CONNECTOR FROM THE PCB AND FAN
VOLTAGE DC TO FAN
REMOVE CONTROL BOX COVER IF NECESSARY
VOLTAGES DC FROM FAN
REMOVE CONTROL BOX COVER IF NECESSARY
RESISTANCE SENSOR TEMP DHW AND HARNESS
DISCONNECT CONNECTOR FROM X20 ON THE PCB
RESISTANCE OVERHEAT STAT AND HARNESS
DISCONNECT CONNECTOR X37 FROM ON THE PCB
INLET PRESSURE DROP
ATTACH PRESSURE GAU
RESISTANCE GAS VALVE
DISCONNECT THE LEAD FROM THE GAS VALVE
RESISTANCE GAS VALVE HARNESS
DISCONNECT THE 4 WAY CONNECTOR ( X36) FROM THE PCB
ALSO DISCONNECT THE LEAD FROM THE GAS VALVE
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
HEAT EXCHANGER FLUE WAYS
REMOVE THE COMBUSTION CHAMBER FRONT
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
VOLTAGE RECTIFICATION
DISCONNECT FLAME SEN
RESISTANCE ELECTRODE SENSE HARNESS
REMOVE LEAD FROM ELECTRODE AND PCB
INSPECTION BURNER
REMOVE THE FRONT OF THE COMBUSTION CHAMBER
RESISTANCE CHECK IGNITION LEAD
REMOVE THE SPARK LEAD FROM THE SPARK ELECTRODE AND PCB
RESISTANCE SENSOR TEMP DHW
REMOVE THE GREEN LEADS FROM DHW SENSOR
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
INSPECTION DIVERTER VALVE DHW POSITION
REMOVE DIVERTER VALVE MOTOR FROM THE BODY
CH OPERATION
FLOW AND RETURN VALV
VOLTAGE EXTERNAL CONTROLS (OUT PCB)
REMOVE CONTROLS COVER AS NECESSARY
USER DISPLAY CONTROL TO CH AND HW
VOLTAGE EXTERNAL CONTROLS (OUT)
REMOVE CONTROLS COVER AS NECESSARY
USER DISPLAY CONTROL SET TO HW AND CH
INSPECTION DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER VALVE ACTUATOR FROM THE DIVERTER VALVE BODY
DIFFERENTIAL PLATE HEAT EX
USER CONTROL SETTING
RESISTANCE SENSOR TEMP DHW
REMOVE THE GREEN LEADS FROM DHW SENSOR
RESISTANCE SENSOR TEMP FLOW
DISCONNECT PLUG (RED LEADS) FROM PRIMARY SENSOR.
RESISTANCE SENSOR TEMP RETURN
REMOVE THE TWO LEADS (BLUE) FROM THE RETURN SENSOR
DIFFERENTIAL PLATE HEAT EX
USER CONTROL SETTING
RESISTANCE SENSOR TEMP FLOW
DISCONNECT PLUG (RED LEADS) FROM PRIMARY SENSOR.
RESISTANCE SENSOR TEMP RETURN
REMOVE THE TWO LEADS (BLUE) FROM THE RETURN SENSOR
INSPECTION DIVERTER VALVE CH POSITION
REMOVE DIVERTER VALVE MOTOR FROM DIVERTER BODY
GAS INLET PRESSURE
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
VOLTAGE BOILER SWITCHED LIVE OPERATION REFIRE
ENSURE EXTERNAL TIME
EXPANSION VESSEL PRESSURE
SYSTEM DISCHARGED
OBSERVATION ANTI CYCLE DELAY
ALLOW THE HEATING SY
RESISTANCE SENSOR TEMP FLOW
DISCONNECT PLUG (RED LEADS) FROM PRIMARY SENSOR.
RESISTANCE SENSOR TEMP RETURN
REMOVE THE TWO LEADS (BLUE) FROM THE RETURN SENSOR
INSPECTION DIVERTER SPINDLE CH
REMOVE THE DIVERTER VALVE ACTUATOR FROM THE DIVERTER VALVE BODY
RESISTANCE SENSOR TEMP FLOW
DISCONNECT PLUG (RED LEADS) FROM PRIMARY SENSOR.
RESISTANCE SENSOR TEMP RETURN
REMOVE THE TWO LEADS (BLUE) FROM THE RETURN SENSOR
TEMPERATURE DIFFERENTIAL FLOW RETURN FROM BOILER
ATTACH TEMPERATURE PROBES AS INDICATED BY THE RED ARROWS
RESISTANCE OVERHEAT STAT
DISCONNECT THE CONNECTOR FROM THE PCB
ENSURE THE APPLIANCE IS NOT TOO HOT
OBSERVATION PUMP OVERRUN
USER DISPLAY CONTROL SET TO HW AND CH
VOLTAGE LOW PRESSURE SWITCH
ENSURE SYSTEM PRESSURE IS SET BETWEEN 0.6 AND 1.5BAR
REMOVE CONTROL BOX COVER IF NECESSARY
VOLTAGE DEMAND FROM FLOW SENSOR
REMOVE CONTROL BOX COVER IF NECESSARY
RUN HOT WATER TAP AT FLOW RATE OF 3 L/MIN
RESISTANCE LOW PRESSURE SWITCH HARNESS
REMOVE THE CONNECTOR X22 FROM THE PCB AND THE LOW PRESSURE SWITCH.
RESISTANCE SENSOR TEMP FLOW AND HARNESS
DISCONNECT CONNECTOR FROM X22 ON THE PCB
RESISTANCE HARNESS FLOW SENSOR
DISCONNECT TERMINAL X22 FROM THE PCB AND THE LEAD FROM THE HALL SENSOR
RESISTANCE SENSOR TEMP RETURN AND HARNESS
DISCONNECT CONNECTOR FROM X22 ON THE PCB
RESISTANCE HEAT EX OVERHEAT AND HARNESS
DISCONNECT CONNECTOR FROM X22 ON THE PCB
RESISTANCE SENSOR TEMP DHW AND HARNESS
DISCONNECT CONNECTOR FROM X20 ON THE PCB
RESISTANCE PUMP AND HARNESS
REMOVE CONNECTORS X13 AND X11 FROM THE PCB
VOLTAGE PERMANENT TO FAN
REMOVE CONTROL BOX COVER IF NECESSARY
VOLTAGE DC TO FAN
REMOVE CONTROL BOX COVER IF NECESSARY
VOLTAGE FAN
REMOVE CONTROL BOX COVER IF NECESSARY
VOLTAGES DC FROM FAN
REMOVE CONTROL BOX COVER IF NECESSARY
RESISTANCE FUSE F3 ( APPLIANCE)
REMOVE FUSE FROM HOLDER AND THE CONNECTOR BLOCK.
RESISTANCE SENSOR TEMP PRIMARY
DISCONNECT PLUG (RED LEADS) FROM PRIMARY SENSOR
RESISTANCE SENSOR TEMP DHW
REMOVE THE GREEN LEADS FROM DHW SENSOR
RESISTANCE SENSOR TEMP FLOW
DISCONNECT PLUG (RED LEADS) FROM PRIMARY SENSOR.
RESISTANCE SENSOR TEMP RETURN
REMOVE THE TWO LEADS (BLUE) FROM THE RETURN SENSOR
DIFFERENTIAL PLATE HEAT EX
USER CONTROL SETTING
FLOW SWITCH ASSEMBLY
DHW DISCHARGED AND D
VOLTAGE LOW PRESSURE SWITCH
ENSURE SYSTEM PRESSURE IS SET BETWEEN 0.6 AND 1.5BAR
REMOVE CONTROL BOX COVER IF NECESSARY
RESISTANCE LOW PRESSURE SWITCH HARNESS
REMOVE THE CONNECTOR X22 FROM THE PCB AND THE LOW PRESSURE SWITCH.
RESISTANCE FAN AND HARNESS (DC)
DISCONNECT CONNECTOR X23 FROM THE PCB
RESISTANCE DIVERTER VALVE AND HARNESS
REMOVE CONNECTOR X13 FROM THE PCB
REMOVE DIVERTER VALVE HEAD FROM BODY
INSPECTION FLOW ASSEMBLY
ISOLATE MAINS WATER
DRAIN DOMESTIC WATER CIRCUITS
RESISTANCE HARNESS FLOW SENSOR
DISCONNECT TERMINAL X22 FROM THE PCB AND THE LEAD FROM THE HALL SENSOR
INSPECTION FLOW ASSEMBLY
ISOLATE MAINS WATER
DRAIN DOMESTIC WATER CIRCUITS
VOLTAGE EXTERNAL CONTROLS (OUT)
REMOVE CONTROLS COVER AS NECESSARY
USER DISPLAY CONTROL SET TO HW AND CH
INSPECTION AIR IN SYSTEM AND BOILER
ENSURE BOILER SYSTEM PRESSURE IS CORRECT
ENSURE AUTO AIR VENT CAP IS OPEN
RESISTANCE SENSOR TEMP FLOW AND HARNESS
DISCONNECT CONNECTOR FROM X22 ON THE PCB
RESISTANCE SENSOR TEMP RETURN AND HARNESS
DISCONNECT CONNECTOR FROM X22 ON THE PCB
HEAT EXCHANGER FLUE WAYS
REMOVE THE COMBUSTION CHAMBER FRONT
VOLTAGE EXTERNAL CONTROLS IN PCB
REMOVE CONTROLS COVER AS NECESSARY
USER DISPLAY CONTROL SET TO HW AND CH
System Information
- Total Tests: 540
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control