Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
VAILLANT COMBICOMPACT ECOMAX VUW 286 EH
GLOBALLY REPLACED
SYSTEM PRESSURE
MAIN ON/OFF CONTROL
CENTRAL HEATING
MAIN ON/OFF CONTROL
PUMP RUNNING
MAIN ON/OFF CONTROL
MULTIFUNCTION DISPLAY CHECK
MAIN ON/OFF CONTROL IN THE ON POSITION
VAILLANT COMBICOMPACT ECOMAX VUW 286 EH
G.C. NUMBER 47 044 2
HOT WATER
MAIN ON/OFF CONTROL
CH DEMAND
MAIN ON/OFF CONTROL
CH DEMAND SATISFIED
MAIN ON/OFF CONTROL
DHW DEMAND
MAIN ON/OFF CONTROL
S1 2
CABLE TREE (FAN CONNECTIONS)
S1
PCB
S1
CABLE TREE (FAN CONNECTIONS)
S1
FAN - COMPLETE - SPECIAL
S1
AIR PRESSURE SENSOR GAS VALVE CONNECTIONS
S1
SIPHON
S1
FLUE
S3 2
PCB - CPU
S3
WIRE - IGNITION
S3
WIRE - IGNITION
S3
CABLE TREE (GV ELECTRICAL CONNECTIONS)
S3
BURNER
SYSTEM PRESSURE
EXPANSION VESSEL
F22/F23
PCB - CPU
F22/F23
PUMP ELECTRICAL CONNECTIONS
ELECTRICAL SAFETY CHECKS
ELECTRICAL SAFETY CHECKS
F60
CABLE TREE (GV ELECTRICAL CONNECTIONS)
F1/F20/F24
CABLE TREE (NTC T1 CONNECTIONS)
F2/F23
CABLE TREE (NTC T2 CONNECTIONS)
F24
CABLE TREE (NTC T0 CONNECTIONS)
F24
CABLE TREE (NTC T1 CONNECTIONS)
INSTRUCTIONS - MULTIFUNCTIONAL DISPLAY
INCORRECT USE OF FAIL
CH DEMAND SATISFIED
GOTO
DHW DEMAND
GOTO
S1
CABLE TREE (APS ELECTRICAL CONNECTIONS)
DHW INLINE FILTER
FILTER
S0/S31 DHW
MICROSWITCH (WATER SECTION)
S0/S31 DHW
DIAPHRAGM (WATER SECTION)
S0/S31 CH
PROGRAMMER
S0/S31 CH
PCB - RELAY
F0/F20/F24
CABLE TREE (NTC T0 CONNECTIONS)
S3
RING PACKING
S3
CABLE TREE (FLAME SENSE ELECTRODE LEAD)
S3
ELECTRODE MONITORING
F31/F34 - NO PERM VOLTAGE SATISFIED
PCB - CPU
F31/F34 SATISFIED
SIPHON
F31/F34 SATISFIED
FLUE
F31/F34 SATISFIED
CABLE TREE (APS ELECTRICAL CONNECTIONS)
F31/F34 SATISFIED
AIR PRESSURE SENSOR GAS VALVE CONNECTIONS
MULTIFUNCTIONAL DISPLAY CHECK
FUSE F1 (2A)
MULTIFUNCTION DISPLAY CHECK
FUSE F2 (2A)
INSTRUCTIONS - RESET
INCORRECT USE OF FAIL
MULTIFUNCTION DISPLAY CHECK
FUSE F5 (1AT)
NO DISPLAY, BOILER NOT FUNCTIONING
PCB - LCD
INSTRUCTIONS - STATUS MODE
INCORRECT USE OF FAIL
PUMP RUNNING
PCB - CPU
PUMP RUNNING
PUMP ELECTRICAL CONNECTIONS
HOT WATER
PCB - CPU
S5 CH DEMAND
PCB - CPU
S7 CH DEMAND
PCB - CPU
S1 3
PCB - CPU
S1 2
PCB - CPU
S1
PCB - CPU
S1
PRESSURE CONTROL
S3
PCB - RELAY
S3
ELECTRODE - IGNITION
S3
TRANSFORMER - IGNITION
S3
NG GAS VALVE
S3
PCB
F20 CH DEMAND
OVERHEAT THERMOSTAT RESET BUTTON
F21/F25/F48/F50 CH DEMAND
FUSE 5A - TEMPORISED
F25 CH DEMAND
FUSE F3 (0.1AF)
F22/F23
PCB - RELAY
F22/F23
PUMP COMPLETE
F60
PCB
F60
NG GAS VALVE
F1/F20/F24
SENSOR - NTC
F2/F23
SENSOR - NTC
F10/F20/F24 CH DEMAND
SENSOR - NTC
F11/F20/F24 CH DEMAND
SENSOR - NTC
F12/F23 SATISFIED
SENSOR - NTC
F24
SENSOR - NTC
SPARKING
GOTO
FAN SPEED
GOTO
S0/S31 DHW
PCB
S0/S31 DHW
CABLE TREE (MICROSWITCH CONNECTIONS)
S0/S31 DHW
UPPER PART COMPLETE - WATER SECTION
S0/S31 DHW
HEAT EXCHANGER - SECONDARY - DHW (SCALED)
S0/S31 CH
PCB - CPU
F0/F20/F24
SENSOR - NTC
S3
PCB - CPU
F31/F34 - STUCK IN FAULT SATISFIED
PCB - CPU
F31/F34 - STUCK MADE SATISFIED
PRESSURE CONTROL
F31/F34 - NO VOLTAGE SATISFIED
PRESSURE CONTROL
F80
PCB - CPU
MULTIFUNCTION DISPLAY CHECK
TRANSFORMER
MULTIFUNCTION DISPLAY CHECK
PCB (RECTIFIER BOARD)
MULTIFUNCTIONAL DISPLAY CHECK
PCB - CPU
PUMP RUNNING
PCB - RELAY
PUMP RUNNING
PUMP COMPLETE
HOT WATER 4
HEAT EXCHANGER - SECONDARY - DHW
HOT WATER
HEAT EXCHANGER - SECONDARY - DHW
HOT WATER
PRIMARY HEAT EXCHANGER
HOT WATER 2
HEAT EXCHANGER - SECONDARY - DHW
HOT WATER 3
HEAT EXCHANGER - SECONDARY - DHW
HOT WATER
DIVERTER VALVE
HOT WATER
PCB
CENTRAL HEATING
PCB - CPU
CODE REMAINS ON S1
CHARACTERISTIC TEST FROM DISPLAY SHOW A STATUS CODE
CODE REMAINS ON S3
CHARACTERISTIC TEST FROM DISPLAY SHOW A STATUS CODE
CODE REMAINS ON S5
CHARACTERISTIC TEST FROM DISPLAY SHOW A STATUS CODE
CODE REMAINS ON S7
CHARACTERISTIC TEST FROM DISPLAY SHOW A STATUS CODE
FAULT CODE F20 DISPLAYED
CHARACTERISTIC TEST FROM DISPLAY SHOW A FAULT CODE
FAULT CODE F21 DISPLAYED
CHARACTERISTIC TEST FROM DISPLAY SHOW A FAULT CODE
FAULT CODE F21/F25/F48/F50 DISPLAYED
CHARACTERISTIC TEST FROM DISPLAY SHOW A FAULT CODE
FAULT CODE F22/F23 DISPLAYED
CHARACTERISTIC TEST FROM DISPLAY SHOW A FAULT CODE
FAULT CODE F25 DISPLAYED
CHARACTERISTIC TEST FROM DISPLAY SHOW A FAULT CODE
FAULT CODE F30/F32/F33 DISPLAYED
CHARACTERISTIC TEST FROM DISPLAY SHOW A FAULT CODE
FAULT CODE F60 DISPLAYED
CHARACTERISTIC TEST FROM DISPLAY SHOW A FAULT CODE
FAULT CODE F1/F20 DISPLAYED AND MAYBE F24
CHARACTERISTIC TEST FROM NTC FAULT
FAULT CODE F2/F23 DISPLAYED
CHARACTERISTIC TEST FROM NTC FAULT
FAULT CODE F10/F20 DISPLAYED AND MAYBE F24
CHARACTERISTIC TEST FROM NTC FAULT
FAULT CODE F11/F20 DISPLAYED AND MAYBE F24
CHARACTERISTIC TEST FROM NTC FAULT
FAULT CODE F12/F23 DISPLAYED
CHARACTERISTIC TEST FROM NTC FAULT
FAULT CODE F24 DISPLAYED
CHARACTERISTIC TEST FROM NTC FAULT
NO DISPLAY, BUT BOILER OPERATION APPEARS OKAY
CHARACTERISTIC TEST FROM MULTIFUNCTION DISPLAY CHECK
NO DISPLAY, BOILER NOT FUNCTIONING
CHARACTERISTIC TEST FROM MULTIFUNCTION DISPLAY CHECK
CODE REMAINS ON S0 OR S31 FOR DHW
CHARACTERISTIC TEST FROM DISPLAY SHOW A STATUS CODE
CODE REMAINS ON S10
CHARACTERISTIC TEST FROM DISPLAY SHOW A STATUS CODE
FAULT CODE F31/F34 DISPLAYED
CHARACTERISTIC TEST FROM DISPLAY SHOW A FAULT CODE
ZERO VOLTS MESAURED
CHARACTERISTIC TEST FROM VOLTAGE AIR PRESSURE SENSOR (PRESSURE)
VOLTAGE GREATER THAN EXPECTED
CHARACTERISTIC TEST FROM VOLTAGE AIR PRESSURE SENSOR (PRESSURE)
FAULT CODE F80 DISPLAYED
CHARACTERISTIC TEST FROM DISPLAY SHOW A FAULT CODE
CH NOISY, DHW PREVIOUSLY NOISY
CHARACTERISTIC TEST FROM CENTRAL HEATING
CH NOISY, DHW PREVIOUSLY OK
CHARACTERISTIC TEST FROM CENTRAL HEATING
DHW NOISY OPERATION
CHARACTERISTIC TEST FROM HOT WATER
DHW QUIET OPERATION, RADIATORS COLD
CHARACTERISTIC TEST FROM HOT WATER
DHW QUIET OPERATION, RADIATORS WARM
CHARACTERISTIC TEST FROM HOT WATER
CH NOISY, DHW PREVIOUSLY NOISY
CHARACTERISTIC TEST FROM CENTRAL HEATING
CH NOISY, DHW PREVIOUSLY OK
CHARACTERISTIC TEST FROM CENTRAL HEATING
CH QUIET OPERATION
CHARACTERISTIC TEST FROM CENTRAL HEATING
CH QUIET OPERATION
CHARACTERISTIC TEST FROM CENTRAL HEATING
11/07/2018 15:13:53 1807_1_50_1 20/07/2018 13:55:11
11/07/2018 15:20:27
CPU: FAN CONTROL
HEATING CONTROL TO HEATING & HOT WATER
CH TEMPERATURE CONTROL TO MAXIMUM
RELAY BOARD: IGNITION
MAIN ON/OFF CONTROL
CPU: RELAY CONTROL
MAIN ON/OFF CONTROL
CPU: PUMP CONTROL
MAIN ON/OFF CONTROL
WATER SECTION MICROSWITCH
LIFT OFF WATER SECTION COVER
REMOVE ONE WIRE
EXTERNAL CONTROLS LIVE IN
MAIN ON/OFF CONTROL
PUMP DRIVER VOLTAGE
{GAINPCBACS}
MAIN
CPU: PUMP CONTROL
MAIN ON/OFF CONTROL
CPU: DIVERTER VALVE
MAIN ON/OFF CONTROL
FAN SPEED
MAIN ON/OFF CONTROL
AIR PRESSURE SENSOR
{GAINPCBACS}
MAIN
MOTHERBOARD FAN DRIVER
MAIN ON/OFF CONTROL
FAN SENSE VOLTAGE
MAIN ON/OFF CONTROL
AIR PRESSURE SENSOR: GAS VALVE CONNECTIONS
REMOVE THE SENSOR BY PULLING DOWN AT THE FRONT AND PUSHING GENTLY BACK
SPARKING
MAIN ON/OFF CONTROL
CH BURNER IGNITES
MAIN ON/OFF CONTROL
IGNITION LEAD SPARKING
MAIN ON/OFF CONTROL
PUMP DRIVER VOLTAGE
{GAINPCBACS}
MAIN
PUMP LEAD VOLTAGE
MAIN ON/OFF CONTROL
NTC T1 CONNECTION
REMOVE X1 FROM CPU BOARD
REMOVE LEAD FROM NTC T1
NTC T2 CONNECTION
REMOVE X1 FROM CPU BOARD
REMOVE LEAD FROM NTC T2
NTC T0 CONNECTION
REMOVE X1 FROM CPU BOARD
REMOVE LEAD FROM NTC T0
NTC T1 CONNECTION
REMOVE X1 FROM CPU BOARD
REMOVE LEAD FROM NTC T1
WATER SECTION MICROSWITCH LEADS
REMOVE PLUG X13 FROM MOTHERBOARD
EXTERNAL CONTROLS LIVE OUT
MAIN ON/OFF CONTROL
NTC T0 CONNECTION
REMOVE X1 FROM CPU BOARD
REMOVE LEAD FROM NTC T0
INTERNAL PROGRAMMER
MAIN ON/OFF CONTROL
VOLTAGE AIR PRESSURE SENSOR (PERMANENT)
{GAINPCBACS}
MAIN ON/OFF CONTROL IN THE ON POSITION
VOLTAGE AIR PRESSURE SENSOR (PRESSURE)
MAIN ON/OFF CONTROL IN THE ON POSITION
ENSURE NO DEMANDS
AIR PRESSURE SENSOR: GAS VALVE CONNECTIONS
REMOVE THE SENSOR BY PULLING DOWN AT THE FRONT AND PUSHING GENTLY BACK
MAINS TRANSFORMER SECONDARY
{GAINPCBACS}
MAIN ON/OFF CONTROL IN THE ON POSITION
DISCONNECT CONNECTOR X10
DISPLAY BOARD 5V
MAIN ON/OFF CONTROL
MAINS SUPPLY
GAIN ACCESS TO INSTALLER TERMINAL BLOCK
(USE INSULATION MAT AS NECESSARY)
PUMP LEAD VOLTAGE
MAIN ON/OFF CONTROL
CENTRAL HEATING
MAIN ON/OFF CONTROL
MOTHERBOARD DIVERTER VALVE DRIVER
{GAINPCBACS}
MAIN
System Information
- Total Tests: 219
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control