Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Gain access to PCB (use Insulation Mat as required)
Main On/Off Control in the On position
Heating Control to Heating & Hot Water
CH Temperature Control to Maximum
Main On/Off Control in the On position
Heating Control to Heating & Hot Water
CH Temperature Control to Maximum
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
If a fault code is displayed press boiler 'Reset' button.
Measure DC Voltage on across X49 on Motherboard.
This should lie between 20.0 and 30.0 V DC.
Measure DC Voltage on across X49 on Motherboard.
This should lie between 20.0 and 30.0 V DC.

Isolate as per TOPs P4
and refit as necessary